X20TB06/X20TB12: 1 General Information

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

X20TB06/X20TB12

X20TB06/X20TB12

1 General information
The X20 24 VDC modules are wired using the X20TB06 and X20TB12 terminal blocks.
• Tool-free wiring with push-in technology
• Simple wire release using lever
• Ability to label each terminal
• Plain text labeling also possible
• Test access for standard probes
• Can be customer-coded

2 Order data

X20TB06 X20TB12

Model number Short description


Terminal blocks
X20TB06 X20 terminal block, 6-pin, 24 VDC keyed
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed

Table 1: X20TB06, X20TB12 - Order data

Data sheet V2.60 1


X20TB06/X20TB12

3 Technical data
Model number X20TB06 X20TB12
General information
Certifications
CE Yes
UL cULus E115267
Industrial control equipment
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see user's manual)
FTZÚ 09 ATEX 0083X
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (Bridge and open deck)
LR ENV1
GOST-R Yes
Terminal block
Number of pins 6 12
Type of terminal block Push-in terminal
Push-in force per contact Typ. 10 N
Cable type Only copper wires (no aluminum wires!)
Wire stripping length 7 to 9 mm
Connection cross section
Solid wires 0.08 to 2.50 mm² / 28 to 14 AWG
Fine strand wires 0.25 to 2.50 mm² / 24 to 14 AWG
With wire end sleeves 0.25 to 1.50 mm² / 24 to 16 AWG
With double wire end sleeves Up to 2x 0.75 mm²
Distance between contacts
Left - Right 4.2 mm
Above - Below 10.96 mm
Electrical characteristics
Nominal voltage 240 VAC
Max. voltage 300 VAC
Nominal current 1) 10 A / contact
Contact resistance ≤5 mΩ
Environmental conditions 2)
Temperature
Operation Corresponds to the X20 module used
Relative humidity
Operation Corresponds to the X20 module used

Table 2: X20TB06, X20TB12 - Technical data


1) Take the respective limit data for the I/O modules into consideration!
2) Identical for operation, storage and transport.

Warning!
It is possible to come into contact with parts that carry voltage when the clamping block is discon-
nected. For this reason, working on a disconnected clamping block is not permitted at voltages of 50
V or higher.

4 Wiring
In order to achieve a secure connection in the terminal blocks, wires must be stripped accordingly.

7 to 9 mm

Figure 1: Wire stripping for a secure connection

Information:
The wire stripping length must not be more or less than 7 to 9 mm.

2 Data sheet V2.60


X20TB06/X20TB12

5 Contact holding force


To ensure that cables maintain a secure contact with the terminal block, they must not be under too much stress.
If the holding force is exceeded, the cable will come loose from the terminal block and cause a malfunction.
Fine strand wires Solid wires With wire
end sleeves
Cables in mm2 0.25 1.5 2.5 0.08 0.25 1.5 2.5 0.25 1.5
Standard spec. (min. value in Newton) 12.5 40 50 4 12.5 40 50 12.5 40

Information:
Fine strand wires must be twisted to provide sufficient holding force.
Use of wire end sleeves
In order to achieve an optimal cable retention force, the following points must be observed:
• Square crimping with the roughest possible surface should be carried out.
• The end of the wire end sleeve should not be cut in order to avoid a reduction of the cross section.
• No wires should protrude at the end of the sleeve.
• The wire end sleeve must be inserted completely to the end.
• The length of the wire end sleeve corresponds to the wire stripping length.

6 Access for test probes


Each contact is equipped with an additional opening for using a test probe.

ø 2 mm