X20TB06/X20TB12
1 General information
The X20 24 VDC modules are wired using the X20TB06 and X20TB12 terminal blocks.
• Tool-free wiring with push-in technology
• Simple wire release using lever
• Ability to label each terminal
• Plain text labeling also possible
• Test access for standard probes
• Can be customer-coded
2 Order data
X20TB06 X20TB12
3 Technical data
Model number X20TB06 X20TB12
General information
Certifications
CE Yes
UL cULus E115267
Industrial control equipment
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see user's manual)
FTZÚ 09 ATEX 0083X
DNV GL Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (Bridge and open deck)
LR ENV1
GOST-R Yes
Terminal block
Number of pins 6 12
Type of terminal block Push-in terminal
Push-in force per contact Typ. 10 N
Cable type Only copper wires (no aluminum wires!)
Wire stripping length 7 to 9 mm
Connection cross section
Solid wires 0.08 to 2.50 mm² / 28 to 14 AWG
Fine strand wires 0.25 to 2.50 mm² / 24 to 14 AWG
With wire end sleeves 0.25 to 1.50 mm² / 24 to 16 AWG
With double wire end sleeves Up to 2x 0.75 mm²
Distance between contacts
Left - Right 4.2 mm
Above - Below 10.96 mm
Electrical characteristics
Nominal voltage 240 VAC
Max. voltage 300 VAC
Nominal current 1) 10 A / contact
Contact resistance ≤5 mΩ
Environmental conditions 2)
Temperature
Operation Corresponds to the X20 module used
Relative humidity
Operation Corresponds to the X20 module used
Warning!
It is possible to come into contact with parts that carry voltage when the clamping block is discon-
nected. For this reason, working on a disconnected clamping block is not permitted at voltages of 50
V or higher.
4 Wiring
In order to achieve a secure connection in the terminal blocks, wires must be stripped accordingly.
7 to 9 mm
Information:
The wire stripping length must not be more or less than 7 to 9 mm.
Information:
Fine strand wires must be twisted to provide sufficient holding force.
Use of wire end sleeves
In order to achieve an optimal cable retention force, the following points must be observed:
• Square crimping with the roughest possible surface should be carried out.
• The end of the wire end sleeve should not be cut in order to avoid a reduction of the cross section.
• No wires should protrude at the end of the sleeve.
• The wire end sleeve must be inserted completely to the end.
• The length of the wire end sleeve corresponds to the wire stripping length.
ø 2 mm