Motor Protection, Control & Maintenance
Motor Protection, Control & Maintenance
Electric Motors
Figure 1.1
Magnetic field lines around a current carrying conductor
x A time varying magnetic field crossing a coil of wire induces a voltage in the
coil. This is the basic guiding principle for a transformer.
x A magnetic field crossing a current carrying conductor develops a force on the
conductor. This is because the current carrying conductor produces a magnetic
field that interacts with the external magnetic field to develop the mechanical
force. This is the basic guiding principle for a motor.
x Voltage gets induced in a conductor moving in a magnetic field. This is the
basic guiding principle for a generator.
x All these principles put together, generate the motoring action, as shown in
Figure 1.2. The process can be summed up as follows:
As a voltage is applied to the stationary conductors, a magnetic field
is produced.
This magnetic field, in turn, induces a voltage in the rotor conductors
in case of some motors (induction motors) or a voltage is externally
applied to the rotor conductors.
This voltage also produces a magnetic field.
The magnetic field of the stator and rotor, together, put the rotor in
running condition.
Electric Motors 3
Figure 1.2
A motor action
Figure 1.3
Simple depiction of a motor
4 Motor Protection, Control & Maintenance
For the sake of clarity, it is more appropriate to study the details of a DC machine, as
the underlying principle of operation is simpler to comprehend. A simple DC machine, as
shown in Figure 1.4, has a current carrying coil supported in between two permanent
magnets (opposite poles facing each other) so the coil can rotate freely inside.
Figure 1.4
A simple DC machine with two pairs of poles
When the coil ends are connected to a DC source then current flows through it and it
behaves like a bar magnet. As the current starts flowing, the magnetic flux lines of the
coil, as shown in Figure 1.5, interact with the flux lines of the permanent magnet. This
causes motion of coil due to forces of attraction / repulsion between two fields. The coil
rotates in order to achieve a position where there is no force of attraction or repulsion.
Figure 1.5
Electromagnetic circuit of a DC machine
Electric Motors 5
As the commutator segments are mounted on the same shaft, the commutator-to-
brushes contact changes and the polarity of DC supply connected to the coil is reversed.
This causes change in the direction of current, thereby changing the direction of the
resultant mechanical force. Hence the coil rotates by another 180 degrees and the process
continues forever. The mechanical features and electrical connection diagram of such a
machine is as shown in Figure 1.6.
Figure 1.6
Electromechanical features of DC machines
The brush contacting positions will keep on changing like this and a continuous
rotation of the coil (on the rotor) is achieved. The changes in the contact making
combinations - of the brush and commutator segments - make the coil supply (even
though DC) to alternate continuously. It is, therefore, apt to say that a commutator is the
heart of a DC machine. A commutator looks as shown in Figure 1.7.
6 Motor Protection, Control & Maintenance
Figure 1.7
Commutator of a DC machine
The resulting alternating electric current flows through the coil and produces necessary
rotation.
The cross sectional view of a DC machine is as shown in Figure 1.8.
Figure 1.8
Simple cross sectional view of a DC machine
Electric Motors 7
In the case of an AC machine, as shown in Figure 1.9, the magnetic field itself revolves
at a speed corresponding to the supply frequency. The electric current in the rotor coils is
either induced (in case of asynchronous machines) or supplied through an external source
(synchronous machines). In either case, the current in the coil is alternating thereby
producing the rotating motion.
Figure 1.9
Simple cross sectional view of an Alternator / Synchronous motor
1.3.1. DC Motors
The speed of a shunt motor is proportional to the armature voltage and is inversely
proportional to the field current (excitation) of the motor. An overview of the different
types of DC motors has been given below:
Shunt motor has field winding mounted on a yoke and the armature winding is
mounted on the rotor. The shunt motor is used where speed regulation is important.
Self-excited motor has the field winding connected in parallel (shunt) with
the armature winding and hence draws current from the same supply.
The speed control can be achieved by only adjusting the terminal
voltage. The series resistance in the field circuit can be adjusted, but
can naturally be done off-line.
Separately excited shunt motor has the field winding connected to a
separate constant voltage power supply.
The speed control can be achieved by only adjusting the armature
voltage as well as the field (excitation) current separately. The
armature voltage control mode is the constant torque operation zone
and the field current control mode is called as constant power
operation. This is also known as field weakening mode.
Series motor has the field winding connected in series with the armature winding.
Naturally, heavy current will pass through it, so field winding is of a thicker gauge. Series
motor is used where speed regulation is not important and the torque requirement is very
high.
In case of series motor, the field current cannot be controlled separately and is equal to
the armature current. Hence under no load condition the excitation becomes very weak.
The most important precaution required to be taken while using a series motor is that the
motor cannot be run in no-load as it can speed up to very dangerous levels and can cause
serious damage to itself.
Compound motor combines both series and shunt motor features. This combines the
good features of both types such as high torque characteristics of series motor and the
speed regulation of shunt motor. The level of compounding can be decided based on the
particular application. These motors are generally used where severe starting conditions
are met and constant speed is required at the same time.
The speed versus load current of various types of DC motors can be summarized as
shown in Figure 1.10.
Electric Motors 9
Figure 1.10
Speed characteristics of various types of DC Motors
1.3.2. AC Motors
The synchronous speed of an AC motor is given by the following relation:
60 X Frequency
Synchronous Speed (rpm) =
No. of Pole pairs
For example, if the motor has two poles, then at 50 Hz frequency motor rpm will be
3000 rpm.
However, all AC motors do not run at synchronous speeds. Only synchronous motors
run at these speeds. Induction motors run at speeds slightly lower than the synchronous
speed and hence are known as asynchronous motors. By varying the frequency of the
supply, synchronous speed of these AC motors can be varied.
A simple definition for an AC induction motor is that it is essentially a rotating
transformer. Each of these different types of motors has specific benefits to offer over the
other. Even though they have different performance characteristics to offer, the AC
motors are virtually taking over the domain of DC motors for various reasons like ease of
maintenance and recent developments in the manufacturing of reliable power components
& controllers.
10 Motor Protection, Control & Maintenance
Rotor Output
Efficiency =
Stator Input
The stator input can be directly measured, but the rotor output needs to be measured by
some indirect methods. However it is more accurate to determine the efficiency of a
rotating machine by determination of its losses rather than by the direct load test, in
which the input and output are to be measured. Furthermore, in large and even medium
size machines, it is not practically possible to arrange for the actual loading of the
machine. Once the losses are determined,
As the voltage can be assumed to be constant, the core loss can also be approximated
as a constant. The stator resistance can be measured by DC methods. However, hysteresis
and eddy current loss in the conductors increase the resistance, and hence the effective
resistance is normally taken as 1.2 times the DC resistance. The rotor copper loss is
calculated by subtracting stator copper loss from the total measured loss or the rotor I2R
loss. Friction and windage loss may be assumed constant irrespective of the load.
Because of the fixed and variable losses, the motor efficiency continuously increases
with the load. The efficiency is maximum at a particular designed load. This full load
efficiency also varies with the rating of a motor and is higher for large size machines
varying between 75 % (typically for a 1 kW motor) and as high as 97 % (for a 3500 kW
motor). Similarly efficiency of a low speed motor is usually lower than that of a high
speed motor, the difference being as high as 3 to 4 %.
1.4.2. Torque
The torque on an object is defined as the product of the force applied to the object and
the smallest distance between the line of action of the force and the object’s axis of
rotation.
Torque is a force applied in a manner that tends to produce rotation, such as a pipe
wrench on a shaft. Torque without rotation is termed static torque, since no motion is
produced. Torque is measured in kg-m or lb-ft which is the product of the force in kgs or
in pounds (lb) x the distance in meters (m) or in feet (ft) from the center of the point of
apparent rotation. Because most power transmission is based upon rotating elements,
torque is important as a measurement of the effort required to do work (horsepower).
When the stator and rotor windings of an AC motor both carry currents, they produce
their own magnetic fields along their respective axes which are sinusoidally distributed
along the air gap. A torque results from the tendency of these two fields to align
themselves.
12 Motor Protection, Control & Maintenance
1.4.3. Inertia
Inertia in a rotational motion, as in case of a motor, is analogous to mass in a linear
motion.
Newtonian physics teaches us that F (force) = M (mass) x A (acceleration). In rotary
terms, the same is expressed as T (torque) = J (inertia) x A (acceleration). This
fundamental equation shows us that the less inertia a system has the less torque it will
take to meet a desired acceleration rate. For this reason it is advantageous to minimize
inertia to the greatest extent to maximize acceleration. For a fixed amount of load inertia
this means minimizing motor inertia. Stated another way, minimizing motor inertia would
allow most of the motor’s torque to accelerate the load not ‘wasting’ much of the motor’s
torque accelerating its own inertia. This is one of the main reasons for preferring AC
motors over DC motors, to the possible extent, as “inertia of AC motor is lower compared
to DC motor of similar rating”. Minimizing motor inertia for a given rating of torque will
theoretically maximize acceleration, increase system bandwidth, but at the same time,
increases load to motor inertia mismatch and needs to a careful evaluation.
Torque (N-m)
2
Moment of Inertia, J (kg-m ) =
Angular acceleration (rad / m2)
1.4.4. Horsepower
Power (Horsepower) is the rate of doing work and is a force applied in a manner that
produces motion and, therefore, is work over a specified time period. A common unit of
power is horsepower. One horsepower (HP) is defined as the force required to lift 33,000
lbs, one foot in one minute and is approximately 0.75 kW. Torque is constant at any
speed while there is a directly proportional relationship between power and speed.
Therefore, power is motion dependent but torque is not.
The sum (not algebraic) of these two components is the input power to the motor and is
called as the apparent power. The ratio between active power (W) and apparent power
(VA) is power factor.
True or Real Power is measured in watts (W). It is the power drawn by the electrical
resistance of a system that does useful work. Reactive Power is measured in volt-amperes
reactive (VAR) and is the power stored in and discharged by the inductive motors,
transformers or solenoids. Reactive power required by inductive loads increases the
amount of apparent power - measured in kilovolt amps (kVA) - in the distribution system.
Increasing the reactive and apparent power causes the power factor, PF, to
decrease. Apparent Power is measured in volt-amperes (VA) and is the voltage on an AC
system multiplied by all the current that flows in it. It is the vector sum of the true and the
reactive power and can be represented as shown in Figure 1.11
14 Motor Protection, Control & Maintenance
Figure 1.11
Representation of apparent power and real power
Power factor is the cosine of angle between the Resultant power and Real power. In the
above triangle, power factor is a fraction obtained by dividing the real power in the
system by (real power + apparent power). So it implies that Real power is equal to
product of resultant power and PF. Hence if we increase the PF we will get more real
power. But that is not so. We can not change the PF of individual equipment but we can
change the PF of the system.
Consider a 750 kVA load operating at 80% lagging PF. Construct a power triangle to
help determine the kW and kVAR components of the power
Solving for the real and reactive power values yields 600 kW and 450 kVAR,
respectively.
Figure 1.12
An example of representing apparent power and real power
Electric Motors 15
So of the 750 kVA drawn from the source, only 600 kW, or 80% of it, can do useful
work. The reactive power, necessary to establish electromagnetic fields, adds a
considerable burden to the source.
Low power factor is caused by inductive loads such as transformers and electric
motors. Unlike resistive loads that create heat by consuming kilowatts, inductive loads
require the current to create magnetic fields to produce the desired work.
A pure inductor dissipates no heat, so it has a power factor of zero.
Power factor is a measure of a particular motor’s requirements for magnetizing
amperage can be expressed as (for a three-phase electric motor):
U = voltage (V)
Appliances are energy conversion devices. As dictated by the rules of power factor and
efficiency, the energy consumed by an appliance is always greater than the energy
provided by it.
Figure 1.13
Torque characteristics of various types of DC Motors
Figure 1.14
Torque characteristics of AC Induction Motors
Figure 1.15
Torque characteristic of a Synchronous Motor
18 Motor Protection, Control & Maintenance
Figure 1.16
Simple view of squirrel cage induction rotor
Figure 1.17
Simple view of slip ring induction rotor
Figure 1.18
Shaded pole single phase induction motor
1.7.1. DC Motors
The Stator, apart from providing physical support, houses the pole pieces, which project
inward and provide a path for the magnetic flux. The ends of the pole pieces that are near
the rotor spread out over the rotor surface to distribute the flux evenly over the rotor
surface. These ends are called the ‘pole shoes’. The exposed surface of a pole shoe is
called the ‘pole face’, and the distance between the pole face and the rotor is called the
‘air gap’. The poles on DC Motors are called salient poles, because they stick out from
the surface of the stator.
1.7.2. AC Motors
Synchronous Motor: The rotor is essentially a large electromagnet. The magnetic
poles on this rotor can be of either salient (“protruding” or “sticking out” of the surface of
the rotor) or non-salient construction (constructed flush with the surface of the rotor).
Non-salient pole rotors are normally used for rotors two and four pole rotors. Salient pole
rotors are normally used for rotors with four or more poles. Because the rotor is subjected
to changing magnetic fields, it is constructed of thin laminations to reduce eddy current
losses. As the field circuit on the rotor must be fed with DC current, special arrangement
must be made to transfer the power. Normally slip rings and brushes are employed for
this purpose.
The Stator is normally made of preformed stator coils in a double layer winding. It
consists of several coils in each phase, distributed in slots around the inner surface of the
rotor, because it is simply impossible to put all the conductors into a single slot. In large
motors, each coil is preformed units consisting of a number of turns, each turn insulated
from the others and from the side of the stator itself. The voltage in any single turn of
wire is very small, and it is only by placing many of these turns in series that reasonable
voltages can be produced.
Induction Motor: The Stator is the outer cylindrical frame of the motor, which is
made either of welded sheet steel, cast iron or cast aluminium alloy. This may include a
feet or a flange for mounting. It comprises:
22 Motor Protection, Control & Maintenance
x The magnetic path, which comprises a set of slotted steel laminations pressed
into the cylindrical space inside the outer frame. The magnetic path is
laminated to reduce eddy currents, lower losses and lower heating
x A set of insulated electrical windings, which are placed inside the slots of the
laminated magnetic path. The cross-sectional area of these windings must be
large enough for the power rating of the motor. For a 3-phase motor, 3 sets of
windings are required, one for each phase
Figure 1.19
Stator and rotor laminations
The rotor
This is the rotating part of the motor. As with the stator above, the rotor consists of a
set of slotted steel laminations pressed together in the form of a cylindrical magnetic path
and the electrical circuit. The electrical circuit of the rotor can be either:
x Wound Rotor type, which comprises 3 sets of insulated windings with
connections brought out to 3 sliprings mounted on the shaft. The external
connections to the rotating part are made via brushes onto the sliprings.
Consequently, this type of motor is often referred to as a slipring motor
x Squirrel Cage Rotor type, which comprises a set of copper or aluminium bars
installed into the slots, which are connected to an end-ring at each end of the
rotor. The construction of these rotor windings resembles a 'squirrel cage'.
Aluminium rotor bars are usually die-cast into the rotor slots, which results in
a very rugged construction. Even though the aluminium rotor bars are in
direct contact with the steel laminations, practically all the rotor current flows
through the aluminium bars and not in the laminations
Electric Motors 23
Figure 1.20
Assembly details of a typical AC induction motor
Figure 1.21
Speed-Torque curves of Motor Vs Load
At the time of engineering the drive system, the speed / torque / power characteristics
developed at the motor shaft and how well these characteristics suit the driven machine
must be considered. The four essential parameters that must be considered are:
x Breakaway Torque, the torque required to put the machine into motion.
Normally it is greater than the torque required to maintain motion (running
torque). Very often, the breakaway torque combined with process torque
determines a drive selection.
x Process Torque, the torque required to pull, push, compress, stretch or
otherwise process or act upon the material being transported by or through the
machine. On some machines, process torque may be so significant as to
determine the drive power rating. On other machines, this load may be
insignificant. The process torque load is superimposed on all other static and
dynamic torque requirements of the machine.
x Accelerating Torque, the torque required to bring the machine to its
operating speed within a given time. With most machines, the load is largely
frictional and a standard drive rating may have adequate torque for
satisfactory acceleration. However, certain machines classified as "high
inertia" with flywheels, bull gears or other large rotating masses may require
drive selection based upon the power required to accelerate the load within a
given time.
x Running Torque, the torque required to maintain the motion of the machine
in a steady state condition, after getting accelerated to the desired operating
speed.
Electric Motors 25
The characteristics (especially the speed - torque curves) of both the driven machine
and the driving machine play very important role in the selection process. Broadly loads
can be classified into four basic categories and their characteristics will be as follows:
x Constant Torque
x Constant Horsepower
x Squared-Exponential Loads - torque varies directly as the speed, and power as
the square of speed.
x Cubed-Exponential Loads - torque varies as the square of speed, and power as
the cube of speed.
A limited number of machines may have operating characteristics which are a
composite function of these basic types and hence need a careful evaluation before
selecting the drive system.
DC Shunt motor
The speed of a shunt motor (up to the rated speed) displays a drooping characteristic
with respect to the torque delivered. It means that the speed decreases slightly as the
torque increases. The rate of decrease in the speed is normally directly proportional to the
torque demanded by the load. The torque developed by a shunt motor is proportional to
the armature current, but with a deviation from the linear characteristic due to the effect
of armature reaction. Because of its excellent speed regulation the shunt motor was the
most preferred drive for variable speed applications. The ease of manipulating the speed
by varying either the field current (using separately excited DC motor) or armature
voltage gives it a great edge over other kind of motors for high rating variable speed
applications. Normally by increasing the armature voltage applied to the rotor the speed is
increased till the rated speed of the motor is attained. Further speed increase is achieved
by reducing the field current. The power developed by a shunt motor varies in proportion
with the speed as long as it is under the armature voltage control. In the field weakening
mode, the power developed by the motor remains constant. This is because, in this zone
of operation the torque developed by the motor decreases as the speed increases.
DC Series motor
The speed torque characteristic of a series motor is hyperbolic, with the speed
decreasing as the torque increases. The motor develops very high torque at low speeds
and very high speed at low torques. Hence the motor finds application where the load
remains connected forever, without any possibility of even accidental load throw off.
Also the very high initial torque makes it ideally suitable for traction duty of a
locomotive.
26 Motor Protection, Control & Maintenance
DC Compound motor
This motor has both series field winding and shunt field winding and is used to obtain
an intermediate performance, which is between that of a shunt motor and that of a series
motor. It means that the characteristics of such a motor lie in between those of shunt and
series motors. Even though cumulatively compounded – shunt and series fields aid each
other – motor is the only one that can be seen being used, differentially compounded –
series field winding opposes the shunt field winding – motor can also be used, but suffers
from lack of stable operation.
Synchronous motor
As constant speed drives, these motors find application in driving large compressors,
crushers etc. Even though they develop torque only at synchronous speed, their
efficiency, inherent ability to correct power factor – even of the local power system –
make them economically attractive. The speed of a synchronous motor is a constant
irrespective of the torque developed by the motor up to the pull-out (maximum) value. It
means that a synchronous motor runs at a constant speed till the point to which it is
capable of delivering the load torque. Once the torque crosses this value, it goes out of
synchronsim and comes to a stop. However some of these motors are fitted with damper
windings in the rotor to make them self-starting. With this winding in place, the motor
can be started as an induction motor and can be accelerated up to the synchronous speed
Induction motor
Torque-slip (speed) characteristic of an induction motor is a quite interesting
operational characteristic. This is a very important factor in the selection of an induction
motor drive. Additionally, the ratio of maximum torque to rated torque, ratio of starting
current to rated current, ratio of starting torque to rated torque and the ratio of no load
current to rated current are of equal significance. By adding external resistance the torque
slip characteristic of a slip ring induction motor can be easily modified. Even though the
maximum torque remains unaltered, the corresponding slip increases proportional to the
resistance added to the rotor circuit. The peculiarities in the characteristic of an induction
motor can be appreciated better by understanding the way it functions.
2
2.1. Overview
Even though AC Induction Motors are accepted to be the industrial workhorses,
synchronous motors still find application in many industrial tasks. In spite of the fact that
the initial cost of a synchronous motor is more than that of a conventional AC induction
motor (due to the expense of the wound rotor and synchronizing circuitry) some of the
following benefits make their usage economically feasible:
Precise speed regulation makes the synchronous motor an ideal choice for certain
industrial processes and as a prime mover for generators.
Synchronous motors have speed / torque characteristics which are ideally suited for
directly driving large horse-power, low-rpm loads such as reciprocating compressors.
Synchronous motors can be deliberately operated at various power factors, thereby
making it possible to improve the overall system power factor. Many industries use
synchronous motors to eliminate or reduce utility power factor penalties. An improved
power factor also reduces the system voltage drop and the voltage drop at the motor
terminals.
The main advantage of a synchronous motor is that it will run at constant speed
regardless of load variations up to a point called the pull-out torque. A load higher than
this will pull the motor out of synchronism and cause it to stop. Hence, before getting into
the details of an AC Induction motor, it is worthwhile to have a glance at the construction
of a synchronous motor, as shown in Figure 2.1. In addition to the components of an
induction motor, it will have additionally field windings & brushes.
28 Motor Protection, Control & Maintenance
Figure 2.1
x A set of insulated electrical windings, which are placed inside the slots of
the laminated magnetic path. The cross-sectional area of these windings is
designed based on the power rating of the motor and are large enough for
high current carrying capacity. The purpose is to strike a balance between
the initial cost of the copper used and the recurring copper losses, which
increases with decreasing cross section. For a 3-phase motor, 3 sets of
windings are required, one for each phase.
Figure 2.2
Castings of the stator are usually machined to close tolerances on multi stage transfer
line machines.
The basic stator structure, called the core, is composed of steel laminations (or
stampings), each of them having an appearance as shown in Figure 2.3. These are shaped
in such a fashion so as to form poles around which are wound the copper wire coils. A set
of coils put together and grouped into various patterns form a winding. These primary
windings connect to, and are energized by, the voltage source to produce a rotating
magnetic field. Three-phase windings spaced 120 electrical degrees apart are popular in
industry.
30 Motor Protection, Control & Maintenance
Figure 2.3
High quality magnetic steel laminations forming the cores are varnished so as to be
insulated from each other. They are then stacked together such that slots are formed along
the axis of the motor. Through these slots, synthetic enameled (for insulating between any
two turns) copper wire coils are placed after covering the slots with proper insulation
material. Winding impregnation, i.e., synthetic resin varnish is applied over the windings,
which avoids ingress of moisture. This also avoids entry of acidic / alkaline fumes, grease
and oil. Mechanically, it provides rigidity to withstand higher vibrations and electrically,
protection against tracking. When the bunch of laminations is stacked together, it forms
the core with slots for holding the coils of the windings, as shown in Figure 2.4.
Figure 2.4
Figure 2.5
Simple cross sectional view of a Squirrel Cage Rotor
The set of slotted steel laminations are pressed together to form a cylindrical magnetic
path by accommodating the electrical circuit. The electrical circuit of the rotor can be
either:
x Squirrel Cage Rotor type, which comprises a set of copper or aluminium
bars installed into the slots, which are connected to an end-ring at each end
of the rotor. The construction of these rotor windings resembles a 'squirrel
cage' and hence the name. A typical squirrel cage is shown in Figure 2.6.
Aluminium rotor bars are usually die-cast into the rotor slots, which results
in a very rugged construction. Even though the aluminium rotor bars are in
direct contact with the steel laminations, practically all the rotor current
flows through the aluminium bars and not in the laminations.
32 Motor Protection, Control & Maintenance
Figure 2.6
Squirrel Cage Rotor
Figure 2.7
Simple view of a Slip Ring Rotor
Irrespective of whether the rotor is of squirrel cage or slip ring type, the rotor
laminations will look alike as shown in Figure 2.8.
3-phase AC Induction Motors 33
Figure 2.8
Rotor core laminations
Figure 2.9
At starting, while the rotor is stationary, the magnetic flux cuts the rotor at synchronous
speed and induces the highest rotor voltage and, consequently, the highest rotor current.
However, the induced voltage in the rotor produces a magnetic field, which is in
opposition to the stator’s magnetic field – as per Lenz’s Law. Hence the induced
magnetic field gets attracted (because of the opposite polarity) and tries to be aligned with
the main rotating magnetic field.
Once the rotor starts to accelerate in the direction of the rotating field, the rate at which
the magnetic flux cuts the rotor windings reduces and the induced rotor voltage decreases
proportionately. The frequency of the rotor voltage and current is also reduced.
When the speed of the rotor approaches synchronous speed at no load, both the
magnitude and frequency of the rotor voltage becomes small. Had the rotor reached
synchronous speed, the rotor windings would be moving at the same speed as the rotating
flux, and the induced voltage (and current) in the rotor would be zero. Without rotor
current, there would be no rotor field and consequently no rotor torque. To produce
torque, the rotor must rotate at a speed slower (or faster) than the synchronous speed.
Consequently, the rotor settles at a speed slightly less than the rotating flux, which
provides enough torque to overcome bearing friction and windage. The actual speed of
the rotor is called the Slip Speed and the difference in speed is called the Slip.
Consequently, induction motors are often referred to as Asynchronous Motors because the
rotor speed is not quite in synchronisation with the rotating stator flux. The amount of
slip is determined by the load torque, which is the torque required to turn the rotor shaft.
For example, on a 4-pole motor, with the rotor running at 1490 r/min on no-load, the
rotor frequency is 10/1500 of 50Hz and the induced voltage is approximately 10/1500 of
its value at starting. At no-load, the rotor torque associated with this voltage is required
to overcome the frictional and windage losses of the motor.
As shaft load torque increases, the slip increases and more flux lines cut the rotor
windings, which in turn increases rotor current, which increases the rotor magnetic field
3-phase AC Induction Motors 35
and consequently the rotor torque. Typically, the slip varies between about 1% of
synchronous speed at no-load to about 6% of synchronous speed at full-load.
( no - n)
Slip = s = per - unit
no
n = no (1 - s) rev/ min
Where,
no Synchronous rotational speed in rev/min
n Actual rotational speed in rev/min
s Slip in per-unit
The direction of the rotating stator flux depends on the phase sequence of the power
supply connected to the stator windings. The phase sequence is the sequence in which
the voltage in the 3-phases rises and reaches a peak. Usually the phase sequence is
designated A-B-C, L1-L2-L3 or R-W-B (Red-White-Blue). In Europe, this is often
designated as U-V-W and many IEC style motors use this terminal designation. If two
supply connections are changed, the phase sequence A-C-B would result in a reversal of
the direction of the rotating stator flux and the direction of the rotor.
Figure 2.10
The equivalent circuit of an AC induction motor
36 Motor Protection, Control & Maintenance
Where,
V Stator Supply voltage
RS Stator Resistance
ES Stator Induced Voltage
XS Stator Leakage Reactance at 50Hz
ER Rotor Induced Voltage
RR Rotor Resistance
NS Stator turns
XR Rotor Leakage Reactance
NR Rotor turns
RC Core losses, Bearing friction,
IS Stator current windage losses, etc
IR Rotor current
XM Magnetizing Inductance
IM Magnetizing Current
Figure 2.11
Under normal conditions all the paths – both the upper and lower parts of the rotor coil
are in parallel electrically, thereby reducing the rotor resistance. This is because the
frequency of the rotor-induced voltage is very low at low slip. Hence the reactance is low
and current flows through all parts of the bar equally. The resulting large cross-sectional
area reduces the resistance. Hence, high efficiency can be achieved at low slips. While
starting, when the slip is very high, the leakage inductance of the coils deep in the rotor
bar is high and hence the rotor current is forced through the low-reactance part of the bar
near the stator.
In the case of double cage rotor, a large low-resistance set of bars are placed deep
inside the rotor and small high-resistance set of bars are placed on the outer surface as
shown in Figure 2.12. Hence, under starting conditions, only the small bar is effective in
providing a path for the current. This serves as a high resistance starting of the rotor and
so the starting torque is quite high. When the rotor is running close to its operating speed,
both the bars are effective and the resistance is very small thereby yielding very good
efficiency.
Figure 2.12
When we consider the speed-torque characteristics, the main driving force for
designing these types of rotor, the benefit of having a higher starting torque can be seen.
3-phase AC Induction Motors 39
Figure 2.13
Figure 2.14
NEMA supports varieties of rotor designs that can be selected appropriately for various
load requirements and the salient points of such designs are as follows:
Design Class A
Starting torque rated torque (large motors); 200 % rated torque (small
motors)
Starting current 500 – 800 %
Full load slip low (< 5 %)
Pullout / full-load torque 200 –300 %
Slip at pullout torque < 20 %
Typical applications Fans, blowers, pumps
40 Motor Protection, Control & Maintenance
Design Class B
Starting torque rated torque (large motors); 200 % rated torque (small
motors)
Starting current 25 % that that of “A” for the same torque
Full load slip low (< 5 %)
Pullout / full-load torque 200 –300 %
Slip at pullout torque < 20 %
Typical applications Same as Design Class A
Design Class C
Starting torque 250% rated torque
Starting current Low
Full load slip Low (< 5 %)
Pullout / full-load torque 200 –300 % (slightly less than that of Design Class A)
Slip at pullout torque < 20 %
Typical applications High starting torque loads like loaded pumps,
compressors & conveyors
Design Class D
Starting torque 275% rated torque
Full load slip High (7 to11 %)
Typical applications Requiring the acceleration of extremely high inertia loads
like fly wheels
In each of these cases, the rotor lamination punching differs and will be typically as
shown in the Figure 2.15.
3-phase AC Induction Motors 41
Figure 2.15
x Assumed that the starting current does not significantly affect the
temperature rise
x The duration of one duty cycle is 10 min
x The following items should also be specified for this duty cycle:
The Cyclic Duration Factor, which represents the percentage
duration of the loaded period as a percentage of the total cycle
Recommended values for cyclic duration factor are 15%, 25%, 40%,
60%
x The period of the duty cycle is too short for thermal equilibrium to be
obtained
x This type of duty cycle is used for pole changing motors
x The following items should also be specified for this duty cycle
The number of Load Cycles per hour (c/h)
The Inertia Factor FI, which is the ratio of the total moment of inertia
to the moment of inertia of the motor rotor
The Permissible Average Moment of Resistance TV, during the
change of speed given with rated load torque
The Cyclic Duration Factor for each speed of rotation
The Moment of Inertia of the motor rotor (JM)
The combinations of the load and the speed of rotation are listed in
the order in which they occur in use
x Designation examples
S8 - 30c/h - (FI=30) - TV=0.5TN - 24kW - 740rev/m - 30%
S8 - 30c/h - (FI=30) - TV=0.5TN - 60kW - 1,460rev/m - 30%
S8 - 30c/h - (FI=30) - TV=0.5TN - 45kW - 980rev/m - 40% -
(JM=2.2kgm2)
48 Motor Protection, Control & Maintenance
The insulating material used for the electrical machines should satisfy the following
requirements:
x High dielectric strength, high specific resistance, and minimum loss in
alternating electric field
x High mechanical strength and elasticity of material
x Thermal strength of insulation; the insulating material should preserve its
insulation and mechanical properties when subjected to the operating
temperatures of the windings for a long time
x The material should remain unaffected by chemical influences
The temperature rise permissible can be determined from the maximum permissible
temperature minus the ambient temperature.
For electrical machines, following are types of insulating material have been classified
and standardized as follows:
x Class A Insulation: Cotton, silk, paper, and similar organic materials
impregnated or immersed in oil, and enamel applied on enamelled wires.
The limiting hot-spot temperature for class A insulation is 1050C
x Class E Insulation: An intermediate class of insulating materials between
Class A and Class B insulation material
x Class B Insulation: Mica, asbestos, glass fiber, and similar inorganic
materials in built-up form with organic binding substances. The limiting
hot-spot temperature for class B insulation is 1300C
3-phase AC Induction Motors 49
For purposes of motor design, most motor specifications, such as IEC, AS/NZS,
specify a maximum ambient temperature of 40oC. The temperature rise of the induction
machine is the permissible increase in temperature, above this maximum ambient, to
allow for the losses in the motor when running at full load.
Insulation Class E B F H
Table 2.1
Maximum temperature ratings for insulation materials
From these tables, note that electrical rotating machines are designed for an overall
temperature rise to a level that is below the maximum specified for the insulation
materials.
For example, using class F insulation,
Max Ambient + Max Temperature Rise = 40oC + 100oC = 140oC
which gives a thermal reserve of 15oC.
The larger the thermal reserve, the longer the life expectancy of the insulation material.
When operating continuously at the maximum rated temperature of its class, the life
expectancy of the insulation is about 10 years. Most motors do not operate at such
extreme conditions because an additional safety margin is usually allowed between the
calculated load torque requirements and the actual size of the motor chosen for the
application. So life expectancy of a motor, which is correctly matched to its load and
with suitable safety margins, can reasonably be taken as between 15 to 20 years.
If additional thermal reserve is required, the motor can be designed for an even lower
temperature. It is common practice for the better quality manufacturers to design their
motors for Class-B temperature rise but to actually use Class-F insulating materials. This
provides an extra 20oC thermal reserve that will extend the life expectancy to more than
20 years. This also means that the motor could be used at higher ambient temperatures of
up to 50oC or more, theoretically up to 65oC.
All rotating electrical machines generate heat as a result of the electrical and
mechanical losses inside the machine. Losses are high during starting or dynamic
braking. Also, losses usually increase with increased loading. Cooling is necessary to
continuously transfer the heat to a cooling medium, such as the air. The different
methods of cooling rotating machines are classified in the standards IEC 34.6 and AS
1359.21.
50 Motor Protection, Control & Maintenance
For AC Induction motors, cooling air is usually circulated internally and externally by
one or more fans mounted on the rotor shaft. To allow for operation of the machine in
either direction of rotation, fans are usually of the bi-directional type and made of a
strong plastic material, aluminium or steel. In addition, the external frames of motor are
usually provided with cooling ribs to increase the surface area for heat radiation.
The most common type of AC motor is the Totally Enclosed Fan Cooled (TEFC)
motor, which is provided with an external forced cooling fan mounted on the non-drive
end (NDE) of the shaft, with cooling ribs running axially along the outer surface of the
motor frame. These are designed to keep the air flow close to the surface of the motor
along its entire length, thus improving the cooling and self-cleaning of the ribs. An air
gap is usually left between the ribs and the fan cover for this purpose.
Internally, on smaller TEFC motors, the rotor end-rings are usually constructed with
ribs to provide additional agitation of the internal air for even distribution of temperature
and to allow the radiation of heat from the end shields and frame.
Special precautions need to be taken when standard TEFC induction motors are used
with AC Variable Speed Drives, powered by VVVF converters. For operation at speeds
below the rated frequency of 50Hz, the shaft mounted fan cooling efficiency is lost. For
constant torque loads, it is sometimes necessary to install a separately powered forced
cooling fan (IC 43) to maintain adequate cooling at low speeds. On the other hand, for
prolonged operation at high speeds above 50Hz, the shaft mounted fan works well but
may make excessive noise. Again, it may be advisable to fit a separately powered
cooling fan.
Larger rotating machines can have more elaborate cooling systems with heat
exchangers.
The system used to describe the method of cooling is currently being changed by IEC,
but the designation system currently in use is as follows:
x A prefix comprising the letters IC (Index of Cooling)
x A letter designating the cooling medium - this is omitted if only air is used
x Two numerals which represent:
The cooling circuit layout
The way in which the power is supplied to the circulation of the
cooling fluid - fan, no fan, separate forced ventilation, etc
IC 01 - Open machine
- Fan mounted on shaft
- Often called 'drip-proof' motor
3-phase AC Induction Motors 51
IC 40 - Enclosed machine
(New : IC 410) - Surface cooled by natural
convection and radiation
- No external fan
IC 41 - Enclosed machine
(New : IC 411) - Smooth or finned casing
- External shaft-mounted fan
- Often called TEFC motor
IC 43 A - Enclosed machine
(New : IC - Smooth or finned casing
416A) - External motorised Axial fan
supplied with machine
IC 43 R - Enclosed machine
(New : IC 416R) - Smooth or finned casing
- External motorised Radial fan
supplied with machine
IC 61 - Enclosed machine
(New : IC 610) - Heat Exchanger fitted
- Two separate air circuits
- Shaft-mounted Fans
- Often called CACA motor
Table 2.2
Designation of the most common methods of cooling
52 Motor Protection, Control & Maintenance
Figure 2.16
Series Inductance Starting method (eg Series Chokes) drops the voltage applied across
the motor.
Auto-transformer Starting method, as shown in Figure 2.17, uses reduced voltage being
applied to the motor windings during starting, with the help of a variable voltage
transformer or variance.
3-phase AC Induction Motors 53
Figure 2.17
Auto-transformer starting method
Series Resistance Starting (eg Liquid resistance starter) makes the voltage to drop
across the motor winding with a good amount of starting torque.
Solid State Soft-Starting (eg Smart Motor Controller) is a variable frequency drive used
for the sake of controlling the initial inrush currents without having any effect on the
developed torque, depending on the configuration employed.
Rotor Resistance Starting requires a slip ring motor to control the speed of the motor.
Most of the above motor starting techniques reduce the voltage at the motor stator
terminals, which effectively reduces the starting current as well as the starting torque.
From the equivalent circuits and formulae for AC induction motors, covered earlier in
this chapter, the following conclusions can be drawn about reduced voltage starting:
Both the stator current and output torque during starting are proportional to the
square of the voltage. During star-delta starting, the voltage is reduced to 0.58
of its rated value. The current and torque are reduced to 0.33 of prospective
value. Thus,
2
I Start v (Voltage )
2
T Start v (Voltage )
The following checklist and reference to the preceding sections provides a guide to the
selection procedure:
x Type and Torque requirements of the mechanical load
x Method of Starting
x Acceleration time
x Type of construction of AC induction motor
Squirrel cage rotor
Wound rotor with slip rings
Foot mounted
Flange mounted
x Environmental conditions
Ambient temperature
Altitude
Dust conditions
Water
x Cable connections
x Direction of Rotation
x Duty cycle
x Speed control (if required)
In general, the selection of the motor is dictated by the type of load and the
environment in which it will operate. The selection of a cage motor or slip ring motor is
closely related to the size of the machine, the acceleration time required (determined by
load) and the method of starting (determined by the electrical supply limitations).
3-phase AC Induction Motors 55
From the point of view of price, reliability and maintenance, the cage motor is usually
the first choice. In general, slip ring motors are required when:
x The load has a high starting torque requirement, but the supply dictates a
low starting current
x The acceleration time is long due to high load inertia, such as a fan
x Where duty dictates frequent starting, inching or plugging
These are general comments because cage motors can be successfully used in all the
above situations.
Slip ring motors are sometimes used for limited speed control. The slip can be
controlled by changing the external rotor resistance. As demonstrated earlier, the overall
efficiency of this method is poor, so this method can only be used if the speed does not
deviate too far from the rated speed. The slip power is dissipated as heat in the external
rotor resistors.
At the time of engineering the drive system, the speed / torque / power characteristics
developed at the motor shaft and how well these characteristics suit the driven machine
must be considered. The four essential parameters that must be considered are:
x Breakaway Torque, the torque required to put the machine into motion.
Normally it is greater than the torque required to maintain motion (running
torque). Very often, the breakaway torque combined with process torque
determines a drive selection.
x Process Torque, the torque required to pull, push, compress, stretch or
otherwise process or act upon the material being transported by or through
the machine. On some machines, process torque may be so significant as to
determine the drive power rating. On other machines, this load may be
insignificant. The process torque load is superimposed on all other static
and dynamic torque requirements of the machine.
x Accelerating Torque, the torque required to bring the machine to its
operating speed within a given time. With most machines, the load is
largely frictional and a standard drive rating may have adequate torque for
satisfactory acceleration. However, certain machines classified as "high
inertia" with flywheels, bull gears or other large rotating masses may
require drive selection based upon the power required to accelerate the load
within a given time.
x Running Torque, the torque required to maintain the motion of the machine
in a steady state condition, after getting accelerated to the desired operating
speed.
The characteristics (especially the speed - torque curves) of both the driven machine
and the driving machine play very important role in the selection of a VSD. Broadly loads
can be classified into four basic categories, the torque characteristic being represented as
in Figures 2.18 and 2.19, and their characteristics will be as follows:
56 Motor Protection, Control & Maintenance
x Constant Torque - About 90% of all general industrial machines, other than
pumps, are constant torque systems. The machine's torque requirement is
independent of its speed. If the machine speed is doubled, its power
requirement gets doubled.
x Constant Horsepower - For machines with constant horsepower loads, the
power demand is independent of speed, and torque varies inversely with
speed. This type is most often found in the machine tool industry and with
center driven winders / coilers in steel rolling mills & paper mills.
Figure 2.18
Simple Loads - Constant Torque & Linear Torque requirement
Figure 2.19
Figure 2.20
Voltage imbalance, at the motor winding input, may result out of even high resistance
connection in one of the phase. A 5 % voltage imbalance can cause lot of overheating in
the stator winding, especially when run at its rated load.
The flow of negative sequence currents can result in abnormal rise in temperature as
the copper losses become multifold. Also there will be a serious reduction in the torque
developing capability of the motor. Hence a deleterious effect of the supply voltage can
be fixed only with proper analysis of the supply voltage to the motor. Otherwise motor
failure will repeat but with the symptom very much differing from the root cause.
Insulation testing is normally carried out using a megger. It is the most commonly
used but most disregarded way of checking the insulation strength. This is because
maintenance personnel will be satisfied with a simple reading of the value, which may
usually be higher than the IEEE stipulated (1+ System voltage in kV) Meg Ohms. For
instance an electrician checking the insulation strength of a 415 V motor winding will be
satisfied with a 2 Meg Ohm reading (more than the IEE stipulated 1.415 Meg Ohms). But
there is much more to be drawn in the test. Suitable temperature correction needs to be
applied, as the IEEE norm is applicable for an ambient temperature of 40 deg C. Even
though such a reading obviates any earth fault condition, the value cannot be recorded,
without the room temperature / appropriate correction applied. Hence such a value cannot
be used for trending purpose. Even if used will not convey any intelligible information.
Also another care needs to be taken - de-humidification of the motor enclosure
internals. To prevent windings getting contaminated from moisture the heaters are to be
energized whenever the motor is not running.
In spite of all these, motor insulation may get damaged due to general ageing.
Resulting faults may manifest in various ways like grounding (earth fault), phase to phase
fault or a turn-to-turn fault. The prime fault is the same in all these cases, insulation
breakdown, but the difference will be in its location.
Grounding occurs when the insulation between the winding coil and the stator slot
breaks down. If the earth fault relay setting is sensitive enough, it may isolate the fault.
Otherwise problem increases in size, i.e., area of insulation breakdown increases, due to
localized intense heat and reaches a stage where the increased leakage current is sensed
by the protection relay and trips the motor. During the process considerable portion of the
stator slot also may get damaged by way of melting down in the vicinity of overheating.
This may call for even re-staggering of the laminations or in the worst kind of damage
replacement of the motor. Phase-to-phase fault is across two separate phases in the same
slot. The potential difference across the point of insulation breakdown varies depending
on the location. Hence the gravity of the effect depends on the location of fault only. To
minimize such faults, slot paper is inserted between different phase coils accommodated
in the same winding. A Turn-to-turn fault occurs in the same coil and hence reduces the
60 Motor Protection, Control & Maintenance
coil’s ability alone. The intensity of such coil’s magnetic field reduces. The resulting
imbalance between different coils’ magnetic field can cause vibration and results in
higher mechanical fatigue on the bearings. Also the localized heating spreads further, due
to the vicious cycle of heat causing insulation damage and insulation breakdown in turn
causing more heat.
The Megger can reveal only a ground fault. In order to detect other faults, motor
winding resistance and inductance are to be measured. There are various types of
instruments and methods available to carry out measurement. High frequency AC
waveform is applied and the winding’s inductance is evaluated between each line. Same
way by applying DC voltage, resistance is measured across each line. However little care
is to be taken during the analysis as winding’s configuration needs to be considered.
Figure 2.21
Turn-to-turn short: Inductance readings in Star / Delta connected windings
Motor winding can be connected in two different ways, namely Star (“Y”) or delta. In
case of a turn-to-turn short, star connected winding will show two low inductance values
and the other one higher. Under the same fault conditions, a delta connected winding will
show one lesser inductance and the other two higher. The figure 2.21 regarding such
connections is self-explanatory.
gets damaged due to the heat. Usually motor goes for rewinding and will be installed
back, immediately after repair and the root cause of the failure will remain unidentified.
The problem takes its toll again but the effect may manifest in various ways like resulting
in a motor rewind or replacement of bearings, but not a rotor repair. Unless otherwise
some deliberate efforts are put for checking the healthiness of rotor, problem persists.
The healthiness of rotor can be checked by measuring the inductance of the winding
with the rotor in different positions. The idea behind this test is that the rotor acts as a
magnet and influences the inductance readings. If the rotor’s integrity is satisfactory, then
the rotor can be considered by symmetrical and hence offers the same magnetic effect
irrespective of its position. A plot of the inductance values versus the rotor position will
be typically sinusoidal under normal conditions. The values will be erratic in case of any
damage, like broken or cracked bars, to the rotor as it results in skewing of the magnetic
filed flux.
Figure 2.22
Inductance for dynamic eccentricity
DC Ramp Testers are used for measuring the ‘insulation’ resistance with the voltage
applied being raised steadily, as a ramp. Modern day instruments include a facility for
trending the results and opening the circuit once the values reach abnormal proportions.
High Current Testing, also known as primary injection, is used for checking the
healthiness of CTs like ratio error within limits, polarity finding etc.
Secondary Injection / Relay Testing kits are used for injecting small currents into the
circuits to be checked and the protective relays – as they operate on very low amperage –
can be checked, calibrated if required. Protective relays, being the heart of any electrical
system, shall be checked periodically and problems noticed shall be rectified
immediately.
High Voltage AC Test / DC HiPot test sets are used for confirming the healthiness of
insulation system. Very high voltages are applied and leakage currents are monitored.
These sets will normally have the provision for shutting off the set in case of a major
abnormality. However they stress the insulation system and may advance an impending
failure causing early breakdowns.
64 Motor Protection, Control & Maintenance
There are various test kits and methods that are useful in Stator Core Fault Detection
like ELCID (Electro Magnetic Core Imperfection Detection), Wedge Tightness
Detection.
Recurrent Surge Oscillogram test (RSO) can be employed for checking the integrity of
the rotor.
Partial Discharge Monitoring kit is used to monitor the discharges resulting out of an
ageing insulation. A proper trending of the results will give an early warning to a possible
insulation failure.
3
3.1. Introduction
Three phase AC induction motors form a major part of the electrical load in any
industry. Very often, the efficiency of a motor and the loss values are also parameters
subject to specific performance guarantees between a manufacturer and a buyer and their
accurate determination is of significance. Even without such guarantees, the losses
represent a continuous wastage of useful resources and therefore, knowledge of the
efficiency of a motor assumes importance. An accurate knowledge about the efficiency
and losses in a machine can result in better motor designs with improved efficiency and
therefore reduced cost of operation. Many motors often work under part load conditions
in actual practice due to various factors involved in motor selection. Conventional designs
exhibit much lower efficiencies in part load operation and therefore there is a lot of scope
for improvements in this area. The subject of losses in AC rotating machines and
calculation of efficiency of a machine at various loads is of considerable practical
interest.
The methods for testing the efficiency of three phase AC induction motors can be
broadly classified as direct or indirect. Direct testing methods, as the name implies, will
measure the input & output power directly.
Hence the formula,
Efficiency = (Output power * 100) / Input power
can be utilized.
In the case of indirect testing methods, the motor losses are calculated from the data
obtained through load or no-load testing. “Output power” in the above formula is
substituted with (Input power – Losses) and the efficiency is calculated.
66 Motor Protection, Control & Maintenance
Germany has its VDE 0530 standard; Great Britain, its BS 2613; Australia & New
Zealand have AS/NZS1359. But they all parallel IEC based standards. Same is the case
with many of the standards world-wide as they are similar, or derivatives of the first two
standards except for the Japanese JEC 37 which uses circle diagram method for the
evaluation of motor performance.
Usually Part 1 of all these standards (equivalent to IEC60034-1) set out methods for
determining the rated output of the electric motor, thermal performance and other related
performance tests (pull up torque, various short circuit tests etc.).
Part 2 (equivalent to IEC60034-2), also known as Test Method B of these standards set
out methods for determining the efficiency of an electric motor, primarily using the
summation of losses for AC cage induction.
Energy Losses and 3 phase AC Induction Motors 67
To sum up, for induction motors there are two widely recognized, most important
standards, namely IEEE Standard 112-Method B and the European IEC 60034-2. The
Japanese standard JEC 37 is also well acclaimed.
All these standards, however, are defined for sinusoidal voltage supplied motors only.
For converter fed motors, no standards exist as such. Normally the stray-load losses range
from 0.5 to 4%. The IEEE standard provides a correct procedure for measuring them. But
these are ignored in the Japanese standard and arbitrarily fixed at 0.5% in the old IEC
standard. Even though the IEC standard is being replaced by the new IEC 61972, it still
recommends a fixed percentage as approximation for the stray load losses in its
alternative procedure. Naturally, these different methods lead to differences in the
measured efficiency values, which can deviate by even above 3%. For example, in a
typical case, when the test methods recommended by IEEE-112 are followed, the
efficiency may work out to 90.0 %. For the same motor, if the testing is carried out using
the methods set out by IEC34-2, it would yield an efficiency of 92.7 %. The efficiency
can be as high as 93.1 % if the test methods stipulated by JEC 37 are adopted. This
difference is unacceptable since it may be comparable to the efficiency gap between an
energy-efficient motor and a standard motor.
The growing importance given to utilization of energy very effectively has started
reflecting in the standards and such initiatives. For instance, three phase electric motors of
0.73 kW to 185 kW manufactured in or imported into Australia must comply with
Minimum Energy Performance (MEPS) requirements. These are set out in AS/NZS
1359.5: 2000 for ensuring minimum efficiency levels. Only exception from MEPS is
submersible motors, integral motor-gear systems, variable or multi-speed speed motors or
those rated only for short duty cycles (IEC60034-2 duty rating S2).
Magnetic losses occur in the steel laminations of the stator and rotor. They are due to
hysteresis and eddy currents, and vary with the flux-density and the frequency. They can
be reduced by increasing the cross-section of the iron in the stator and rotor, by using
thinner laminations, and improved magnetic materials.
Mechanical losses are due to friction in the bearings, ventilation and windage losses.
They can be decreased using low friction bearings and improved fan design.
Stray load losses are due to leakage flux, non-uniform current distribution, and
mechanical imperfections in the air gap and irregularities in the air gap flux density. They
can be reduced by optimal design and careful manufacturing. It is directly related to the
losses in the motor, which depend on the design of the machine.
Losses in an electrical machine are generally of two types; fixed losses and variable
losses. Fixed losses are constant under all load conditions (for a given speed, voltage,
frequency, and other ambient conditions) whereas variable losses are a function of the
load on the machine. In the case of a rotating machine, the fixed losses are:
Note:
a) Hysteresis loss is reduced by having the magnetic circuit constructed of low
hysteresis materials and eddy current loss is reduced by having the core
constructed using thin sheets of magnetic material (called laminations) each
insulated from the adjoining lamination by a coating of non-conducting
varnish. This construction increases the resistance of the eddy current circuit
thereby restricting the area available for flow of eddy currents. Thus it reduces
the value of eddy currents and thereby the losses due to these currents. Also
note that the losses due to eddy currents induced by load current on active
materials and other magnetic parts do not form part of the fixed loss.
b) Core losses are primarily dependent on the magnetic flux (in turn, the supply
voltage) and the frequency of the input power supply and are valid for the
stated conditions only. For example, the hysteresis loss is given by the relation:
Hysteresis loss = Kh . f. Bmax n
Where,
Bmax is the maximum flux density
f is the frequency
n is a value between 1.5 and 2.5 (usually assumed as 2) and
Kh is a constant
Similarly,
Eddy Current loss = Ke . (B . f . W)2
Where,
Bmax is the maximum flux density
f is the frequency
W is the thickness of lamination and
Ke is a constant
Friction losses that are inherently associated (in bearings and other mechanical contact
points) with the rotation of an equipment.
Windage losses due to the action of air, for instance, air impinging on rotating parts,
wastes some energy. In addition to any unintended loss, the fans mounted in the rotor
also absorb energy. Usually, totally enclosed motors have an internal fan for circulation
of cooling air through the air paths in the stator and rotor as well as an external fan that
drives air over the cooling fins on the outer body of the motor.
70 Motor Protection, Control & Maintenance
The symbols used for various parameters measured during the tests are:
Symbol Parameter
Cos I Power factor
F Supply frequency
(I2R)d Winding losses during Dynamometer test
(I2R)0 Stator winding losses at no-load
(I2R)s Stator winding loss
(I2R)r Rotor winding loss
I Line Current
IN Line current at rated load
I0 Line current at no-load
IX Line current at partial load
Kd Dynamometer torque correction
n Operating Speed (Revolutions per minute)
p Number of pole pairs
P1 Input power
P2 Output power
PFE Core loss
Pf Friction and windage loss (sum)
Pk Constant losses
PL Additional load losses (raw data)
PLL Additional load losses (after regression)
P LL% Additional load losses as % of P1
PLLX Additional load losses at partial loads
P0 Input power at no load (represents no load losses)
Pd0 Input power at no load with dynamometer coupled
R Stator line-to-line resistance
Ra Stator line-to-line resistance at an ambient temperature of Ta
RN Stator line-to-line resistance at rated load
R0 Stator line-to-line resistance at no-load
RS Stator line-to-line resistance corrected to ambient
temperature
Energy Losses and 3 phase AC Induction Motors 71
Symbol Parameter
S Slip as per unit of synchronous speed
sd0 Slip during dynamometer test
T Torque
Td Reading of torque measuring device
Td0 Torque reading at no load coupled with dynamometer
U Terminal voltage
U0 Terminal voltage at no-load
UN Rated voltage
Ur Reduced voltage used in calculations to allow for voltage
drop in stator winding
K Efficiency
T Stator winding temperature
Ta Ambient temperature
TN Stator winding temperature at Rated load
Efficiency of a motor is the ratio of output power to input power at a given load and can
be expressed by the formula:
K = P2 / P1 (Eq:1)
Where,
Kis the efficiency (per unit value)
P1 is the input power and
P2 is the output (mechanical) shaft power
Or
K= (P1 – Losses) / P1 (Eq:3)
Out of these, the iron loss and stator winding loss are assumed as taking place on the
stator with the rest of the power passing through the air gap of the motor. The losses
taking place in the rotor are the rotor winding loss, friction loss and additional load loss
with the balance power being available in the form of mechanical output at the motor
shaft. Figure 3.1 illustrates this action.
Figure 3.1
Figure 3.2
Efficiency of an AC Induction Motor vs Load
74 Motor Protection, Control & Maintenance
Note:
The dynamometer itself along with the bearings used to couple it will introduce an
additional torque even at no load and this needs to be corrected. The torque
correction value is added to the measured torque to get the actual motor torque. The
actual motor torque can be obtained using the relation:
T = Td + kd
Where kd is the torque correction value.
Load test should be done starting from the highest to the lowest point. Value of R
before and after the test is to be measured and the arithmetic mean calculated for use in
other tests. The following values should be measured at each load point: U, I, P1, Td, Cos
I , f, and n.
Note:
The value of R is used for computing the stator winding loss.
Method 2:
This is similar to method 1 except that there is no torque measurement. In this method,
it is possible to record the values during the rated load thermal test itself, unless it is
specifically required that efficiency is to be determined at multiple points, in which case
the measurements will be repeated for the rated load and other load points which are
required in addition to rated load.
P0 = PFE + Pf + (I2R)0
P0 = PK + (I2R)0 (Eq:4)
Note:
The rotor winding loss under no-load condition can be neglected since slip will be
close to zero and current flow in the rotor and consequently the loss in rotor cage
winding will be negligible.
The no load stator winding loss can be computed using the expression:
(I2R)0 = 1.5 (I02 . R0) (Eq:5)
Note:
The relation is applicable to both star and delta connected machines. In the case of
a star connected machine, the following are applicable:
The value of R = 2 . per phase value of resistance
The value of phase current is the same as line current
Total stator winding loss at no-load in all three phases is thus:
= 3 . I02 . (R0 /2)
Total stator winding loss at no-load in all three phases is thus calculated as:
The constant loss PK can be found using Eq:4 and Eq:5 since the other two terms of
Eq:4 are already known. The value of PK has to be calculated for the set of readings taken
at different voltages.
To compute the value of Pf , the values of PK should plotted on a graph with U2 on the
X-axis for all values of voltage < 50% of UN and extrapolated to the value of U = 0. The
point of intersection on the Y axis will give the value of Pf. Refer to figure 3.3 for
illustration.
Note:
Since the core loss at voltage equal to 0 is also 0, it follows that the only remaining
component will be the friction and windage loss.
Figure 3.3
Computing Friction and Windage loss (Reference: AS/NZS 1359.102.3:2000)
To compute core loss the following needs to be done. In the graph in fig. 3.3 PK is
plotted using the readings taken at voltage > 60% of UN. Subtract Pf from the value
obtained for PK at U = UN. The resulting value will represent the core loss PFE at UN. An
exact calculation of PFE at rated operating conditions may also take into account the
voltage drop corresponding to this condition in the stator winding and using the resultant
voltage as the basis instead of UN. The necessary calculation for obtaining this voltage is
given in the reference standard.
Calculation of winding losses
Stator winding loss can be computed using the relation similar to that of Eq:5 as shown
below.
(I2R)S = 1.5 (I2 . R) (Eq:6)
78 Motor Protection, Control & Maintenance
Where I, and R corresponds to the readings taken during the load test at different points
on the load curve. Since the resistance of the rotor winding cannot be measured, the rotor
winding loss is indirectly computed using the following equations.
(I2R)r = {P1 - (I2R)S - PFE } . s (Eq:7)
where, s is the per unit value of slip. The rotor winding loss is computed at different
load values substituting the values of P1, Stator winding loss and slip obtained at each
load and the value of core loss as derived earlier for rated operating conditions.
= P1 - P2
Since P2 is required to be known to apply the above formula, it is useful only if the test
includes measurement of the mechanical output. In other words, load test should have
been conducted as per method 1 to apply eq:8 to calculate the value of PL.
The output shaft power can be computed using the relation:
P2 = 2. ST . n
60 x 1000
P2 = T.n (Eq:9)
9550
The value of PL has to be calculated for each load point and plotted against the square
of the torque value (T2) on the X-axis. The curve may only be approximately be linear
and needs to be corrected. The standard suggests regression analysis to obtain a
smoothened straight line. Also, the straight line obtained above will not pass through the
origin (Additional load loss should have a zero value at no-load, since the input at no-load
has been already apportioned to other losses).
Energy Losses and 3 phase AC Induction Motors 79
Figure 3.4
Computing Additional Load loss (Reference: AS/NZS 1359.102.3:2000)
Figure 3.4 shows the final value of additional loss (PLL) at different loads after the
above corrections have been applied.
In case load test has been conducted as per Method 2 which does not involve
measurement of the mechanical torque, the above computation for additional load loss is
not possible. For this purpose, the standard recommends that the additional load losses are
assigned as a percentage of input power. The table 3.2 indicates percentage values to be
used for motors of different standard ratings.
80 Motor Protection, Control & Maintenance
Table 3.2
Assigned Additional Load loss-Percentages (Reference: AS/NZS
1359.102.3:2000)
Motor Rating < 10 kW Motor Rating < 100 kW Motor Rating < 200 kW
kW Per Cent kW Per Cent kW Per Cent
<1 3.00 11 2.32 110 1.67
1.1 2.97 15 2.23 132 1.62
1.5 2.89 18.5 2.17 150 1.58
2.2 2.78 22 2.12 160 1.56
3.0 2.69 30 2.04 185 1.52
4.0 2.61 37 1.98 200 1.50
5.5 2.52 45 1.91
7.5 2.43 55 1.87
75 1.78
90 1.73
The additional load loss at rated load can be computed using the following relations.
PLL = P1 . (% value for motor rating as in fig. 4) (Eq:10)
100
The above value of PLL will be applicable at rated load. For any other part load value,
the following equation can be applied.
where PLX is the additional load loss corresponding to the load current IX, IN and I0
being the full load and no-load values of motor current.
Efficiency can be computed using the equations given in Eq: 2 or Eq:3 as applicable.
For other load points, the losses have to be individually determined for that load and the
efficiency re-computed.
3.6. Dynamometers
The tests discussed in the previous section for finding out the different losses of a
motor and arriving at the efficiency require the motor to be subjected to a mechanical
shaft load of up to 150 % of the rated output. One of the most common ways in which
this can be done is by using a dynamometer. Dynamometer is an apparatus that helps us
to subject a test motor to various combinations of mechanical torque and speed. In a
typical dynamometer test cell, the test machine shaft is coupled to the dynamometer via
couplings and a drive shaft. When the machine is running, the dynamometer can exert a
braking force on the motor. Sensors on the dynamometer measure motor speed and
torque. Knowing these values, we can calculate the power output of the test machine. It
must be noted that, the measurement of speed must be done accurately and dynamometers
available in the market use shaft mounted digital encoders for precise measurement of
speed.
Dynamometers allow us to reproduce a desired point on the speed-torque characteristic
of the machine being tested under controlled conditions. Their function is to generate a
braking torque which acts in the direction opposite to the rotation of the motor. Some of
the devices are also capable of generating torque at standstill condition (zero RPM).
Others apply a torque that is a function of the rotational speed of the motor but which is
adjustable at any point.
Apart from applying a load, some form of torque measurement is also necessary so that
the output power of the motor can be determined using this measurement directly. Refer
to Method 1 of motor load test in the previous section. In the absence of this
measurement, other assumptions become necessary to compute the motor efficiency (such
as allocation of additional load losses outlined earlier). In this section, we will review
various types of dynamometers used for load testing of motors in detail. To understand
how dynamometers work, we will first discuss how a simple mechanical brake can be
used to load a motor.
Figure 3.5
Principle of a Brake
Assuming that a pressure of P is applied by the brake with area of contact with the
drum being A, the braking force F will be obtained by the relation:
F = P . P. A
Where P is a constant called the friction coefficient which in turn depends on the
material properties of the mating surfaces.
The torque caused by the brake can be calculated as:
T = F.R
Where,
T is the torque
R is the radius of the brake drum and
F is the braking force
The braking force as well as torque will be in a direction opposite to the direction of
rotation of the motor. The motor therefore has to produce a torque equal to that of the
brake in the direction of rotation in order to maintain equilibrium (that is, in this case, a
constant speed of revolution).
In order to avoid the transverse force being applied on the drum and thereby the motor
shaft, it is usual to have two brake shoes placed diametrically opposite to each other.
Refer to figure 3.6.
Energy Losses and 3 phase AC Induction Motors 83
Figure 3.6
A pair of Brake shoes operating on a brake drum
Assuming that the braking force of the shoes is identical, the brake system generates a
couple of opposing forces F, separated by the distance D (equal to the diameter of the
brake drum) with the torque being given by the relation:
T = F.D
While this is a very simple method of measuring the motor torque, the arrangement has
certain drawbacks. The following are the main problems:
x The entire output power of the motor is being absorbed by the brake drum.
Unless proper arrangements exist for cooling the brake, it can get overheated
and burn.
x This method is not accurate and cannot account for the torque produced by the
brake drum itself when on no-load (a measurement which is necessary for
accurate determination of losses).
x Manual torque measurements and their correlation with other parameters need
the motor to be run at stable load for a period of time required for the
mechanical and electrical parameter readings to be noted down. This may
result in excessive heating.
x Behavior of the motor under fluctuating load conditions cannot be easily
studied.
The more sophisticated dynamometers try to address these drawbacks by a variety of
features and we will discuss such devices in the paragraphs that follow. But before that,
we will discuss the principle of how loads can be applied on motors through a coupled
electrical generator.
84 Motor Protection, Control & Maintenance
Figure 3.7
A rope Brake
Once the motor is started and running at its rated speed, the spring balance reading
reduces and gives a reading equal to the rope tension in the upper half. Rope tension in
the lower half is equal to the calibrated weights. The rotational force developed by the
motor will be opposing the tension in the rope and develops a force that can be measured
– the difference between the rope tension in the bottom half and the rope tension in the
upper half.
Now the torque can be calculated as the product of this rotational force and the
distance between the centre of the pulley and the centre of the rope (measured on a
horizontal plane). This distance is equal to half of the sum of the rope’s diameter and the
pulley’s diameter.
P = (2 * pi * T * n) / 550 hp
Figure 3.8
Use of a belt around a brake drum for torque measurement
Energy Losses and 3 phase AC Induction Motors 87
The belt is in contact with the surface of the drum with an angle of contact of 180
degrees with either end of the belt fixed to a force measurement gauge. The brake belt is
subjected to an initial force at rest by the use of a tensioning arrangement. When the
motor is at rest the force registered by both gauges is equal. However, when the motor is
running, the braking force generated along the length of the belt causes the force on either
gauge to change. The difference between the readings of the gauges is a measure of the
braking force. To explain further:
Let FT be the initial force registered by both gauges A and B . The action of the brake
generates a couple with the force F. Now the readings of gauges A and B will be
respectively:
FA = FT + F
FB = FT - F
The difference between the reading of the gauges is:
FA - FB = 2. F
The torque T developed by the braking system is given by:
T = R . (FA - FB)
= 2.F.R
with R being the radius of the brake drum. Thus T is the same as the torque generated
by the braking couple. The initial brake tension should be adjusted that the braking does
not produce a slack on the belt in the side of gauge B.
Various types of highly sophisticated, accurate torque transducers are available in the
market and are used for precise measurement of torque. A strain gauge system measures
strain through the change in resistance of a metal foil or wire that is bonded to a stressed
element. A phase displacement system measures the windup of a rotating shaft. Strain
gauge systems using slip rings are less expensive as compared to Phase displacement
systems that are economical for turbomachinery.
As a matter of fact, most of the available dynamometers are used not just for motor
testing but mainly for testing of mechanical prime movers such as Diesel engines and
automobile drives especially those used in motor-racing. The latter application has given
rise to extensive improvements in dynamometer design and sophisticated peripheral
systems for measurement and control, since very fast-varying load conditions must be
possible in order to simulate actual road duty requirements. Such designs include
computer-based data acquisition and control. The control circuits simulate load
requirements and a data acquisition system records dynamically all the machine and load
parameters at a fast rate (impossible to record manually) for later analysis. Power
electronics is used for regenerative type loading with PLCs for load control, operation
monitoring and protection and data communication for connecting the sensors with data
acquisition systems and the control commands to the to the dynamometer.
Figure 3.9
Typical testing set up using a Dynamometer
Different types of dynamometers behave differently and have their own typical
advantages. Practical systems often use multiple types of dynamometers coupled to a
common shaft so that all possible loading conditions can be obtained for simulation.
We will briefly discuss the different types of dynamometers below.
When oil is used as the dynamometer medium, it gets hot very quickly and its viscosity
goes down. As this happens, the power required to pump it changes dramatically and will
in turn change the power drawn by the dynamometer. Water has the same tendency,
although to a lower degree. Water and oil pumps also tend to mix air with the fluids,
causing them to become aerated, or "foamy", changing the viscosity and again changing
the power drawal. This type of dynamometer is a low cost device but difficult to control
and requires higher maintenance. Moreover, the entire power of the motor being tested
must be absorbed by the fluid and this can become a limitation.
Figure 3.10
Working principle of an Eddy Current Dynamometer
Table 3.3
Typical Specification of an Eddy Current Dynamometer
Parameters Specification
Form of dynamometer Air cooled, compressed air
Braking torque-Nominal N.cm 150
Rated Speed RPM 1800
Peak Speed RPM 6000
Power dissipation (rated) Watts 300
Excitation voltage V DC 90V DC
Excitation current (max) A 2.5
Torque sensor Reaction type-force sensor
Load cell Full bridge, strain sensitive
Load cell excitation (max) 10 V DC
Sensitivity (nominal) 1mV/V
Load cell bridge resistance 350 Ohms
Load cell accuracy class 0.2
Speed sensing Toothed wheel/inductive proximity sensor
Air flow nominal lpm 7
Pressure at inlet 3 bar
Weight kg 48
Figure 3.11
Typical characteristics of an Eddy Current Dynamometer
Note: Dotted line represents Power and continuous line represents Torque in the above
figure.
Figure 3.12
Typical characteristics of an Hysterisis Dynamometer
(braking) and motoring modes very easily. Motoring mode is useful if the rotating parts
of the test machine have to be rotated by external means (say, to find the mechanical loss
at any given speed). Both AC and DC type dynamometers can be designed to work in
regenerative and non-regenerative configurations. The requirements can be summarised
as follows.
x Quick, pre-programmed load changes
x Operation at a range of speeds with independent torque variation
x Low inertia of rotating mass
x Possibility of regeneration in braking regime
x Braking and motoring mode of operation
The point to be noted about regeneration is that, the generated power must be at mains
frequency and almost at mains voltage if power has to be pushed back into the power
supply mains. Since the test machine may have to be tested over a wide speed range,
regeneration is invariably done using inverters so that the above requirement can be met.
In the case of a DC dynamometer, the output DC is utilized directly as input to inverter.
In the case of an AC dynamometer the output which can be at different frequencies
(corresponding to the speed of the test machine), it is converted first to DC and then to
AC. Digital controls acting upon pulse-width modulated inverters are used to achieve this
functionality.
In the case of non-regenerative mode, the requirements are simpler. In the case of a DC
dynamometer, the machine acts as a separately-excited generator and control of field
voltage is used to control the output which is dumped into a resistive load. With an AC
machine, a similar method is adopted except that a thyristor controlled rectifier is used to
get variable DC output which in turn can obtain the desired output. It should be noted that
the output voltage of the dynamometer in either case is also a function of speed and thus
the output power will be limited at low speeds.
Motoring requirement will need the dynamometer to be run using external power with
speed regulation. This means that a DC dynamometer will require a controlled armature
supply through a thyristor rectifier operated from mains supply. The AC dynamometer
will have to be run as a variable speed motor through an inverter drive also from mains
supply.
Though both DC and AC dynamometers are available as a part of test kits, AC
dynamometers are considered superior in view of their low inertia and consequently
better loading response and also the absence of commutator/brushes and thereby reduced
maintenance.
Figures 3.13 to 3.16 illustrate the principle of the different types of dynamometers
discussed above. These are only meant for the purpose of understanding the approach
adopted in these machines. The actual dynamometer designs may vary in details and will
also differ from manufacturer to manufacturer.
94 Motor Protection, Control & Maintenance
Figure 3.13
Block Diagram-DC non-regenerative Dynamometer
Figure 3.14
Block Diagram-DC Regenerative Dynamometer
Energy Losses and 3 phase AC Induction Motors 95
Figure 3.15
Block Diagram-AC non-regenerative Dynamometer
Figure 3.16
Block Diagram-AC Regenerative Dynamometer
96 Motor Protection, Control & Maintenance
4
A failure of electric motor can be either due to mechanical fault(s) or electrical fault(s)
or due to both. A mechanical failure, in turn, can be either due to a bearing problem or
due to improper mechanical fitting of the components of the motor or even a root cause
lying in the electrical system may show up the symptoms mechanically. In either case
there is a possibility of vibrations giving a sufficient clue. If the vibrations are monitored
and trended properly an impending failure may show up as an increasing vibration. In the
earlier days, electrical symptomatic problems could be gauged only during off-line
testing. But nowadays there are lot of methods to diagnose such dormant problems and if
applied and analyzed properly can avoid repeated failures or even breakdowns.
It is the duty of the electrical maintenance professional to gain a good understanding
about various mechanisms that can cause motor failures. Then effective usage of
discretion in diagnosing the root cause of a failure must be applied. Based on these
findings, practical action plans have to be devised. These plans shall be meticulously
implemented in order to overcome the problems permanently. An electrical engineer must
always remember that the obvious defect noticed may not be the real cause. The very
cause of the failure may still be lying dormant in the system and again may result in the
same failure or in a different failure for the same basic reason. Unless this approach is
adopted the Plant will be witnessing repetitive failures and unplanned outages. Hence
each and every motor failure has to be investigated thoroughly and, if required, the issue
may be taken up with the OEMs (Original Equipment Manufacturers).
x Mechanical failure
x Auxiliaries failure
Insulation failures (as covered in Chapter 1, are related to stator insulation mainly) is
the most important type of failure mode for an electric motor. This mode alone
contributes a major chunk to the cases of motor failures. It is believed that more than 50
% of the motor failures are due to insulation failure alone. It can occur due to the stresses
resulted by the thermal, electrical, mechanical & environmental processes that are
deviating from the designed values or from the specification originally envisaged in the
detailed engineering. These failures can manifest in various forms like winding
shorts, insulation to ground faults etc.
Thermal processes harming insulation systems are usually a result of overheating of the
winding due to various reasons like overload, too-frequent starts, a higher ambient
temperature than the designed one, inadequate ventilation, hard-to-start (also known as
high inertia) loads etc. Motor ventilation related problems, i.e., inadequate cooling will be
mainly due to, congestion on fan cover, improper spacing at the end of motor etc.
Rotor bar failure is an important failure mode of especially large motors. It can be
due to the manufacturing defects or complications developing out of improper operational
& maintenance practices. Design problems that can create this problem are casting
defects, loose laminations, improper protection provided for operation in harsh
environments etc.
Operational problems that can contribute to this failure are frequent starts, inadequate
cooling for the motor etc.
Maintenance problems like incorrect fitting, incorrect alignment can cause excessive
vibration & overheat in the rotor.
Rotor failures can also arise due to rubbing with stator because of bearing failure,
eccentricity of the rotor resulting out of bent shaft or improper air gap.
Auxiliaries failure are failures related to the power supply, electrical circuits & cable
termination. Unless due care is taken to fix these problems the motor may go out of
service. In some extreme cases like imbalance in voltage, negative sequence currents etc.,
the motor insulation failure and even vibrations can be seen.
Motor Failure Analysis 99
Figure 4.1
Typical heating and cooling curves of a motor
100 Motor Protection, Control & Maintenance
Typical motor heating curve is shown in Figure 4.1. As shown in this figure, a motor
will have another curve called as cooling curve. Based on the heat dissipating efficiency
of the cooling circuit – comprising the cooling fans assembly, finned structure of the yoke
etc. – the temperature of the motor drops exponentially with respect to time, once the
motor is de-energized and allowed to coast down.
As the motor is started, since the starting currents and hence the power dissipated is
very high the temperature keeps on increasing. During this period the cooling circuit will
be almost ineffective.
If the motor gets tripped at time t1 with the motor temperature T1 and then allowed to
cool down, the motor temperature decreases and would have touched T3 after time t2.
Instead, if the motor is re-started, before complete cool down, the temperature of the
motor will shoot up to a temperature (T2 as shown in the figure) which will be much
higher than T3. This temperature may be tolerable for the motor as this re-start being the
first one. However, if another such step is repeated the temperature of the motor may
attain dangerous proportions unless it the motor is designed for such purpose. In practice,
the values of these vary from each rating of motor to the other. Also for the same rating
they differ from manufacturer to manufacturer and based on the specification given by the
user.
Hence too-frequent-starts is the most detrimental aspect to the life of a motor, as both
the stator and rotor get heavily stressed out during every start. Stator’s insulation
degradation process rate gets multiplied with the rise in temperature.
Also the rotor’s thermal aging process gets accelerated. This is because the rotor will
be running at much lesser speeds during starting and hence the induced currents are also
high. Because of this excessive heat and the resulting thermal uneven expansion, the rotor
bars may crack (at the joints where the bars are welded to the shorting ring) after
expanding unevenly even with respect to the rotor. Due to the cracks the electrical
resistance of the bars increases and hence heating of the rotor bars also increases. Since
the current is diverted through other rotor bars, they get overheated. All these result in a
localized overheating of the rotor bars. These high temperatures of the rotor may cause
bowing effect thereby reducing air gap / bearing clearances. This can result in mechanical
damage to the rotor.
a much longer time to take the load to full speed. Hence the associated copper losses will
also be huge, thereby overheating the motor. This often leads to the burnout of the motor.
When an energy efficient motor – which has a much higher starting current and
somewhat lower starting torque – is used for replacing a standard motor the motor
starting torque may not be sufficient for driving a high inertia load. Starting current can
also be excessively high causing possible damage to equipment.
In motor-reversing applications, the motor needs to be selected / designed properly.
This is because, certain types of electrical braking can impose substantial losses. For
example a full-voltage reversal (plugging) will result in four times the normal
acceleration losses.
To take care of these factors various protection techniques can be employed and are as
follows:
Internal temperature protection: In case of a repeated failure of a motor, direct
measurement of the temperature can be resorted to, in order to safeguard the motor
against overheating. While rewinding in the motor shop, internal-temperature protectors
can be embedded within the new winding. Such devices sense the actual winding
temperature directly and will trip the motor starter when it reaches an unsafe temperature.
This way the protection can be made very reliable as compared to the inherently less-
sensitive indirect relay-sensing methods. Furthermore, the direct temperature-sensing
method takes care of the motor's thermal storage and cooling capacities – instead of
utilizing the extrapolation techniques used by the indirect temperature measurement relay.
Solid-state protection: The advent of modern solid-state protective relays has
simplified the job. In these, the motor's losses are actually computed from current
measurements using sophisticated "symmetrical component" techniques. Based on this,
the motor temperature profile is developed and then adjusted to the cooling profile. Such
an extrapolation is used to determine an approaching unsafe temperature. This provides a
much closer degree of protection than indirect methods under more difficult conditions of
operation. The great strides in the development of electronics and the reducing costs of
solid-state protective devices have made this kind of protection available in less costly
designs. So the application of these relays even for lower rating motors is turning out to
be economical.
Earlier generation relays, typically electromagnetic ones, used to simulate a motor’s
heating and cooling characteristics by means of thermal sensitive heater elements. Since
there cannot be any discrimination employed between the heating associated with starting
and in normal conditions, the heater element needs to be designed for not responding to
600 %. This makes the relay to be a bit insensitive during normal operation. The problem
used to get further compounded when used for high load inertia loads which have longer-
than-normal starting times. This kind of application drastically reduces the degree of
protection with an increased probability of a motor burnout.
In order to cater to the needs of a high inertia load, if efficiency is not a bar, NEMA
Design D motor can be used. But a careful evaluation is needed while selecting this motor
and a good compromise between its price and the efficiency is required. This type of
motor accelerates and decelerates the load much more rapidly and develops high torque
from zero to full speed.
Another feasible solution is to enhance the quality of the winding insulation while re-
winding the motor.
102 Motor Protection, Control & Maintenance
A belt drive, as shown in Figure 4.2, must be not be too tight as to overload the motor
or put unwanted extra force on the motor bearings. At the same time it should be tight
enough to avoid it from slipping. Adjust the tension by changing the distance between the
motor and driven load. The tension must be just enough to prevent excessive bow on the
slack side.
Figure 4.2
Typical Belt drive
104 Motor Protection, Control & Maintenance
Belt tension is determined by the sound the belts make when the drive is first started.
Belts will produce a loud squeal that slowly vanishes as the speed approaches rated value.
If the belt tension is too tight or too loose the operation becomes inefficient and damages
can occur. Do not change the pulley pitch diameter to change tension. This will result in a
different fan speed than desired.
Misalignments in belt drives can be categorized as angular and parallel.
Angular misalignment normally results from improper mounting of motor / reducer. A
skewed bushing or a bent shaft can also contribute to angular misalignment. It is
measured as angle between shafts or in Mils per Inch of coupling diameter. Normally an
angular misalignment of less than 0.002 in for each inch diameter of pulley is considered
to be fine.
Parallel misalignment is the misalignment arising out of mounting of motor / reducer
on different planes as shaft centerlines don’t coincide. It is normally measured in Total
Indicated Run out, TIR in Mils (0.001”).
Bearing misalignments can be classified as static and dynamic.
Static misalignment arises due to a non varying static load (like deflection) and is due
to axes being not co-linear or the supports being not in the same plane.
Dynamic misalignment normally arises due to a bent shaft, which results in a balance
problem as well as clearance problems in the bearings resulting in undue fatigue.
Motor / Reducer Soft Foot is a problem associated with warped or bent machine foot or
an uneven mounting base. This in turn causes high stress on motor housing and bearings
thereby resulting in higher vibrations. Such problems can be confirmed by using a dial
indicator. Observation has to be made for any excessive movement while loosening one
foot at a time.
Adjust belt alignment by moving the motor or driven load pulley inward or outward
along the shaft.
The pulley’s horizontal alignment can be carried out by ensuring that the pulley face is
perpendicular to the centerline of the conveyor. This ensures the bearings are co-linear.
Slightly oversized bearing mounting holes on the conveyor structure along with welded
adjusting bars facilitate proper installation. Vertical alignment is done by ensuring that
the shaft centerline is matching the elevation of the reducer shaft centerline.
The developments being witnessed in the modern day have introduced good quality
insulation material that can endure higher temperatures with little negative impact on
their longevity. In spite of all these things, motor insulations do fail and hence needs a
check mechanism to keep the deterioration under control or to take a corrective action
pro-actively. To do so, the insulation degradation process needs to be understood
properly.
Basically, this degradation process can be attributed to the ageing phenomenon, which
gets further accelerated with various types of stresses due to thermal, electrical,
mechanical or environmental reasons.
106 Motor Protection, Control & Maintenance
Figure 4.3
Fluting of a bearing
Electromagnetic induction from the stator winding to the rotor shaft is more prevalent
in long axial machines. The shaft voltage is due to small dissymmetries of the magnetic
field in the air gap that are inherent in a practical machine design. Most induction motors
are designed to have a maximum shaft voltage to frame ground of < 1 V rms. The
induced shaft voltages cause bearing current to flow in a circulating path from the shaft,
thru drive end non-insulated bearing, thru the stator frame, thru non-drive end non-
insulated bearing and back to the shaft. This circuit basically has very low resistance.
Hence even though the induced shaft voltage is low in magnitude, a high circulating
current flows through both motor bearings. Hence, theoretically it is advisable to provide
insulated bearing at least on one side to break this circuit, whenever the estimated the
likely shaft voltage is going to be higher. This may happen typically for motors with a
rating greater than 250 horsepower. However, during transient start and stop conditions
across the AC line, magnetic dissymmetries appear as increased shaft voltage, resulting in
bearing current flow and reduced life. The traditional electromagnetic solution to induced
shaft voltage on larger frames is to insulate the non-drive end bearing. This does not
mitigate shaft voltage but rather the resulting bearing current. Voltage pulses fed by the
inverter contain such high frequencies, that the leakage inductances of the motor winding
provide paths for currents to leak to earth. This induces a voltage between the shaft ends.
If the induced voltage is high enough to overcome the impedance of the lubrication film
of the bearings, a circulating type of high frequency bearing current occurs.
Electrostatic induced shaft voltage may be present in any situation where rotor charge
accumulation can occur. Examples are belt driven couplings, ionized air passing over
rotor fan blades or high velocity air passing over rotor fan blades as in steam turbine. The
electrostatic solution is to keep the shaft and frame at the same potential by installing a
shaft grounding brush to reduce electrostatic build up and reduce shaft voltage to 70 - 400
mV. This value is not enough to cause damaging bearing current to flow.
108 Motor Protection, Control & Maintenance
Electrostatic coupled shaft voltage from external rotor sources, such as a static
exciter in a turbine generator, is possible and historically solved with the application of a
shaft grounding brush. Electrostatic coupled shaft voltage from external stator sources,
such as a PWM inverter.
of sinusoidal power supply that always add to zero, the three phases of the PWM (Pulse
Width Modulated) drive, although they balance in peak amplitude, do not balance
between phases instantaneously because the pulses are of different widths. The resulting
common mode voltage is a source of bearing currents.
Regular three-phase sinusoidal power supply is balanced and symmetrical under
normal conditions, i.e., the peak-to-peak voltages are equal for all the three lines and the
shape of each of the three waveforms is identical. Hence, the vector sum of the three
phases always equals to zero. Thus, it is normal that the neutral is at zero volts, however
this is not the case with the PWM inverter’s output. While the voltages may be balanced
in peak amplitude, it is impossible to achieve perfect balance between phases
instantaneously, when pulses of different widths are produced. When this happens, the
neutral will not be zero and the voltage can be defined as a common mode voltage source.
This creates a potential between the inverter output and earth which will force currents
through stray impedances present between anything connected to the inverter phases,
such as the motor cables and motor windings, and earth. This is known as common mode
current.
Frequency converters built with BJTs (bipolar junction transistor), SCRs (silicon
controlled rectifier) or GTOs (gate turn-off thyristors) are operable at a switching
frequency less than 600Hz and hence make lot of audible noise. However, the IGBT
(insulated gate bipolar transistor) came onto the scene and these represented a huge
improvement in drive technology, increasing the switching frequency up to 20 kHz,
reducing harmonics and audible noise. But these improvements have been bought at a
price: IBGT technology has resurrected bearing problems due to electrical discharge,
creating a new challenge to manufacturers of electric motors. The new problems arose
because PWM inverters equipped with IGBT inverters distort the sinusoidal supply
generating high frequency harmonics and high (dv/dt)s. The inverter switching
mechanism also creates what is called common-mode voltage.
Due to the high switching frequencies of IGBT inverters, parasitic capacitances
between stator winding and stator, and between rotor and stator winding become relevant.
These capacitances result from the common mode voltage and lead to a common mode
current flowing through the motor bearings. They are called on to handle two types of
bearing currents that have been identified. The first these, conductive-mode bearing
current, is discharged continuously during a period of time when bearings exhibit good
conductivity. In contrast, the second type, discharge-mode bearing current, is discharged
in discrete time intervals. The former prevails at lower speeds, because the good electrical
contact between the rolling elements and bearing raceways connects the rotor to ground
through the outer bearing race, whereas the latter is more significant for higher inverter
output frequencies, as the electrical conductivity of the bearing decreases, enabling the
capacitive voltage to build up till it is able to break down the dielectric resistance of the
grease. Although both types of currents are present at the same time, it can be said that
the discharge bearing current is the more critical. The conductive bearing current is
usually less harmful to bearings, as it is a low-amplitude current that flows continuously
without arcing. However, it increases bearing temperature, accelerating grease
deterioration and reducing bearing life. On the other hand, the high energy level of the
discharge bearing current works like an electro-erosion machine, resulting in bearing pits
or flutes. The amplitude of bearing currents depends on operating conditions such as
speed, temperature, lubrication type, motor size etc.
110 Motor Protection, Control & Maintenance
From all these factors, motor size is probably the most significant, as the larger the
motor the larger its parasitic capacitances. Motor design can also have reasonable
influence over bearing current amplitudes. Manufacturers offer a number of options as a
means of overcoming the damage to bearings caused by electrical discharge. The most
obvious of these is insulated bearings, which are used where it is desirable to achieve
perfect insulation of the bearing from its application environment. However, the method
increasingly used to achieve insulation is ceramic coating, which is very expensive,
typically adding anything from GBP 600 to 700 to the price of motors with frame sizes in
the range from 315 to 355. Another option for applications where some passage of current
can be accommodated is a shaft grounding brush. A much less costly option than
insulated bearings, the shaft brush reduces stray current through the motor bearings by
half, as a result of short-circuiting the path between rotor and stator. By employing a shaft
brush it is possible to keep voltages below the so-called "fritting voltage" which is
responsible for the development of bearing defects due to electric current discharge.
Although damage cannot be completely prevented by employing this measure, the extent
of damage can be kept within such limits that the life expectancy of the bearing is not
affected.
ABB has recently patented a motor winding designed to eliminate circulating bearing
currents. The design divides the stator winding into an even number of equal parts per
phase. The groups are then distributed uniformly between ac supply connections at both
ends of the stator. This generates a high-frequency net current flowing equally, and in
opposite directions, through the windings. By dividing the windings into two branches,
we have a better chance of balancing the high-frequency common mode currents and
getting more symmetric flux distribution
The solution pits one high-frequency net current against a current of equal magnitude
flowing in the opposite direction. The currents, in effect, cancel each other out, and the
bearings roll on, unmolested.
5
Testing
A motor has many rotating parts and hence deterioration in these components due to
wear and tear becomes inevitable. Also, as the stator and the winding insulation are
expected to bear with temperatures crossing 100 deg C, the insulation material degrades
over a period of usage. To assess the condition of these components and materials - so
that the motor can be re-conditioned in a predictive manner - a wide range of tests are
available. These tests taken up in a pro-active manner will provide very cost effective,
condition-based solutions for the asset-manager.
The insulation, left unattended to, may reach a threshold point where it cannot tolerate
the system voltage any more and yields to the stresses. This damages the integrity of the
motor severely and finally breaks down the insulation. However, such motor failures due
to insulation breakdown can cause catastrophic damages to the equipment, loss of
production or de-rating of power output, lengthy forced outages and heavy costs to the
utility. Hence it is wiser to detect the insulation deterioration at its nascent stage and
identify potential failures as early as possible. One of the very popular and most feasible
tests is determination of insulation resistance.
Insulation resistance:
Insulation resistance measurement is the easiest field test that can be employed to
monitor the health of the winding’s insulation and is popular in most of the countries as
“megger," test. This test applies DC voltage, usually 500 or 1000 Volts, to the object
under test and measures the resistance of the insulation. Low current leakage is measured
and converted to a measurement of Meg, Gig or Terra-Ohms.
NEMA standards stipulate a minimum resistance to ground, at 40 degrees C ambient,
of 1 Meg Ohm per kV of rating plus 1 Meg Ohm. Medium size motors in good condition
will generally have an insulation resistance in excess of 50 Meg Ohms. A low reading
usually indicates a bad insulation condition, may be caused by contamination or ageing or
excessive heat. Contamination may be due to moisture, conductive dirt or oil. Excessive
heat may be due to a constant overloading of the motor. In case the value measured is
below the value obtained by the above equation, the motor requires attention and the
resistance value needs to be improved. As per the above, a 440 V rated motor has to have
a minimum insulation resistance of 1.44 Meg Ohms.
A megger reading of a motor, alone, conveys very little information about incipient
faults, if any. A better method would be, trending of the insulation resistance - a curve
recording resistance, with the motor cold and hot, and date - that indicates the rate of
deterioration. This curve provides the information needed to decide if the motor can be
safely left in service until the next scheduled inspection time.
However a megger test indicates winding’s insulation condition with respect to ground
only and does not measure turn-to-turn insulation condition. It cannot reflect localized
weaknesses. Also the stress on insulation due to operating voltage peaks will be more
severe than those of due to megger voltage. For example, the DC output of a 500-volt
megger is below the normal 625-volt peak (for a normal supply rms voltage of 440 V
AC) each half cycle of an AC motor. Hence a better study demands additional data.
The insulation material being a natural dielectric can be conceived to be a pool of
dipoles (a set of +ve and -ve charges). When DC potential is applied, the dipoles will
begin to align with negative towards the conductors and positive towards ground
(opposite charges attract). As the dipoles polarize, the effective capacitance of the circuit
changes and the resulting current (leakage) across the dielectric boundary decreases. The
megger takes the leakage current and converts it from milli or micro-amps to Meg Ohms
(or Gig Ohms, or Terra-ohms). A greater current leakage implies a worse condition of the
insulation.
Testing 113
Motor insulation testers come in two primary varieties, low and high voltage. The
former, as they apply low potential, are less destructive. But high voltage insulation
testers can be very dangerous if a voltage equal to or higher than the motor nameplate
voltage is applied. In all Insulation testers, the current is limited so that there is less
potential for damage to the test object. In order to detect the faulty insulation, the applied
voltage must be selected in such a way as to create an even energy level across the
insulation surface of the object being tested. This will happen in areas that do not
properly polarize, the material condition has changed in the insulation system, or there is
continuity between the conductors and ground (direct short).
Dielectric insulation materials in electric motors are chemicals and follow the
arrhenious chemical equation for chemical changes due to temperature. The actual
temperature at which the insulation resistance measurements are made will effect the
leakage across the insulation boundary. Hence, as the temperature increases, the amount
of potential leakage across the insulation system increases, causing a reduced insulation
test result. This requires temperature correction of insulation test results for trending.
Also the temperature of the object must stabilize and can be 30 minutes or more after de-
energization. Otherwise the readings will turn out to be inaccurate and there is no pint in
trending these values. As shown in Figure 5.1, the actually measured insulation resistance
values when plotted against time without temperature correction will yield a picture that
shows wild variations based on which it may be inferred that there can be some serious
problem.
Figure 5.1
Trending of Insulation Resistance
114 Motor Protection, Control & Maintenance
R40 = k R
R – insulation resistance measured at the specific temperature.
R40 – insulation resistance corrected to a temperature of 40 0C.
k - the temperature correction factor.
The relationship between the insulation resistance and the ambient temperature of
measurement is typically logarithmic and will be as shown in Figure 5.2 where the
temperature of the insulation under test is shown on the X-axis. The temperature
correction factor, k to be applied is shown on the Y-axis. This factor, when applied as per
the above formula, brings the insulation resistance measured at any temperature to its
equivalent at 400C, as stipulated by IEEE standards.
Figure 5.2
Reference curve for temperature correction of IR value
Testing 115
Moisture has a dielectric constant and hence damp windings or even humidity will
have a direct effect on these measurements. The deviation will be quite appreciable when
the temperature of the insulation being tested is less than the dew point. It will cause an
abnormally low test result that will not represent the actual conditions of the insulation
system during operation. Hence a correction needs to be applied. For large machines,
usually the corrections to be applied will be supplied by the manufacturer.
Disadvantages:
The insulation resistance tests will only monitor the boundary surface area between the
coils and ground. Therefore winding shorts, insulation defects on the end turns of the
coils and insulation breakdown or contamination within insulation components not
directly in contact with the stator frame, will not have any bearing on the test results.
Hence such faults cannot be detected in their initial stages and hence cannot be totally
relied upon.
This methodology of checking insulation resistance detects defects associated with
brittle or damaged insulation and a significant area of insulation getting damaged is a pre-
requisite for detection of an abnormality. However to diagnose an impending problem,
the quality and dielectric property of the insulation needs to be checked and is done by
determining the polarization index.
Figure 5.3
Polarization phenomenon – Dipolar orientation
Polarization happens slowly, when a voltage less than the operating voltage of the
motor is applied. While measuring Meg Ohm value, a standard of one minute can be
applied (or once the energy level within the instrument and the system being tested has
stabilized) in order to produce a test result. The polarization process can be presented in
the form of a curve by plotting the total leakage current – the sum of absorption current,
surface leakage current & dielectric charging current – against time in minutes. From this
curve, it can be seen that there will be a gradual increase in the reading of the insulation
resistance. This is because of the charging of the insulation system, much like a capacitor.
This results in the charging of the capacitor like dielectric medium and hence a reduction
in the absorption current. The reduction of this absorption current results in an increase
in the resistance. The ten minute reading divided by the one minute reading gives the
Polarization Index, the PI value of the insulation system and serves as an indication of the
average polarization of the material. IEEE recommends a value of 2.0 or higher as
acceptable. However motors with unstable insulation systems can also give values close
to or greater than 2.0, but still be defective. Hence it is always recommended to look at
the PI Profile and not just the Index.
It must also be borne in mind that, according to the IEEE 43-2000, insulation values
over 5,000 Meg Ohms need not be evaluated using PI.
Testing 117
Even though this test gives an insight into the healthiness of the insulation system, it
also looks at only the ground insulation and will not see the problems neither in the turn-
to-turn insulation nor the weaknesses in the insulation system.
Hi Pot tests are High Voltage testing methods and are aimed at checking the strength of
the insulation. They operate on the principle of breakdown happening in the presence of
strong electric fields. What happens is that a loose charge (electron or ion) somewhere in
the air is accelerated by the field (electric field), and if the field is very great, the charge
can pick up enough speed before it hits another atom to be able to knock an electron off
that atom. As a result, more and more ions are produced and their motion produces a
discharge or spark.
5.3. DC Hipot
This test can uncover insulation weaknesses. In addition to measuring overall
insulation resistance to ground, it provides information on insulation dielectric
strength. In this sense, it can detect insulation weaknesses that are likely to fault to
ground if subjected to the high transient voltage surges that commonly occur on industrial
power systems.
DC high potential testing is very similar to a meg-ohm test with the exception that the
actual leakage current, in micro amperes, is also measured and plotted. In the case of the
high potential test (as per IEEE Std 95 Recommended Practice for Insulation Testing of
Large AC Rotating Machinery With High Direct Voltage) a voltage up to twice the rated
voltage plus 1,000 Volts multiplied by 1.732 is applied in order to stress the insulation
system. The potential harm from this test comes when the voltage is incorrectly applied or
the full potential (voltage) is applied at once. This can cause violent polarization of the
insulation system, which may damage the equipment at some small points in the system,
in a localized manner. Hence, the test is widely considered potentially destructive.
In this test, the motor frame is grounded and a DC voltage applied and increased
gradually in step increments up to the maximum recommended test voltage. At each step
up to this voltage, leakage current in microamperes in read and plotted against the
corresponding dc test voltage. The resulting plot should be a straight line.
Magnitude of leakage current and resulting slope of the line alone doesn’t give the real
information. The number of discrete steps in which the test is performed is
optional. However, taking more steps in smaller voltage increments yields better results
and minimizes the possibility of test voltage overshoot. Most of the DC high potential
test sets incorporate over current trips to protect the winding if a weakness is
detected. The most sensitive of these over current protective circuits can operate when
leakage current is as low as one micro amp.
The most important criterion is that the plot must be a straight line. Any abrupt
upswing in the slope of the plot indicates an insulation flaw and in such a case, the test
must be immediately aborted to prevent the winding from failing under test. The motor
can be returned to service, but winding reconditioning or replacement should be planned
at the earliest convenient opportunity.
The DC Hi Pot is also a test that only looks at the ground wall and is of no value for
the turn-to-turn insulation.
118 Motor Protection, Control & Maintenance
5.5. AC hipot
AC high potential tests impress a high voltage sine wave across the insulation system
by applying a voltage of twice the motor rated voltage plus 1,000 volts. Hence only a
good insulation system without any contamination or degradation can pass the test. In
case of even moisture being present in moderate quantities can damage the insulation
system.
In case of weak insulation, even if the damage is highly localized, the damage spreads
to the surroundings as the ionization process easily spreads like a wild fire. Unlike the DC
high pot test the defect point gets ionized very easily as the AC voltage has the potential
for penetration through the dielectric. Once the spark is generated, an impulse occurs
within the insulation system, which can cause other sparks to occur in the next weakest
parts of the insulation system. This generates tracking and carbon paths develop across
Testing 119
the insulation. The fault is characterized by snapping sounds, an odor of ozone and visible
arcs. Once this occurs, direct paths to ground exist through the carbonized insulation.
Hence it can be summed up that this test is highly destructive, even as compared to a
DC Hi Pot test, as AC penetrates through the dielectric medium much easier. Low voltage
capacitance to ground tests, however, are non-destructive and are very good early
indicators of degradation modes in your insulation systems.
Figure 5.4
Equivalent circuit of a dielectric
120 Motor Protection, Control & Maintenance
Parameters that are computed from the measurements performed are discharging void
volume ratio (if discharges are present), effective phase of occurrence of discharges,
characterizing constants (if variations are due to stress grading) and effective area
involved in slot discharges (if slot discharges are present).
The results will be analyzed in order to assess the winding insulation with regard to
extent of de-lamination, condition of binding resin / varnish, condition of slot corona
shield, end winding surface condition etc.
Figure 5.5
Vector components of test voltage and current
The currents drawn by the specimen shown in Figure 5.4 can be vectorially represented
as shown in Figure 5.5. The ratio between the resistive component and the total current
drawn gives the power factor. The dissipation factor of the insulation system can be
defined as the ratio of the capacitive current to the resistive component.
The typical setup for the measurement of the Tan Gҏ of an insulation system is as shown
in Figure 5.6. In this process capacitance values between the three windings - among
themselves and with respect to earth for each can be represented as shown below and
accordingly can be measured.
Testing 121
Figure 5.6
Tan G - Test connection
Capacitance and tan delta measurements will be performed using a transformer ratio
arm bridge. Measurements will be performed at increments that will not exceed 0.2*vl.
Maximum test voltage will be vl/1.732 rms (v1 being the line voltage).
Power factor & dissipation factor are different means of expressing the same quality.
However usage of power factor is advantageous because of its range – varying between 0
and 1.0. A typical plot of power factor for a 11 kV, 8.6 MVA synchronous machine will
be as shown in Figure 5.7.
122 Motor Protection, Control & Maintenance
Figure 5.7
A typical plot of power factor and voltage
Measurement of Partial Discharge (PD) has been for long, an important aspect of
quality control of HV apparatus and insulation materials. Recent developments have
made possible usage of the PD kits for on-site diagnosis tool by the utilities
Partial discharges occur when minor defects are present in electrical insulation
systems. When partial discharges occur repetitively in solid insulation material, the
destructive energy released deteriorates the insulation material at that site. Over a period
of time, this deterioration spreads to others in its vicinity and may lead to failure of
insulation.
Premature failures of insulation systems have been attributed to the action of partial
discharges. For this reason testing for partial discharges in an insulation system has been
adopted as a quality control measure for applications where high reliability is a concern.
Figure 5.8
A typical PD measurement setup
In this test, with the set up as shown in Figure 5.8, partial discharge pulse patterns will
be monitored and recorded using a transformer ratio arm bridge with appropriate coupling
capacitors.
The partial discharge pulse patterns will be analyzed with regard to pulse count, pulse
magnitude, polarity dependence and phase to identify the nature of discharges which can
then be classified as:
x Internal Discharges
x Surface Discharges
x Slot Discharges
124 Motor Protection, Control & Maintenance
Quantitative values are normally not available for sensing the PD activity and hence
trending can be regarded as critical. Only trending can reveal the impending danger.
Contrary to PD test in laboratories the PD diagnostic test on-site is in general
extremely disturbed by electromagnetic interference. Practically, the background noise
level substation is about 10 to 100 times higher than in HV labs, which can be
electromagnetically shielded. Aging of the HV insulation may cause a continuous
increase of the PD level and finally a breakdown failure. Usually the PD level exceeds the
basic disturbance level before the breakdown occurs. Therefore total breakdown can be
prevented if PD values are detected above basic disturbance level.
The main aim of on-site PD diagnostic tests is the identification of dangerous PD
faults. The detectable PD level of such fault mostly exceeds the basic disturbance level,
as expressed in Figure 5.9.
Figure 5.9
Stress - PD activity versus time
Figure 5.10
Turn-to-turn short & coil-to-coil short detection in a Surge comparison test
Testing 127
Figure 5.11
An open coil connection / complete grounding detection in a Surge comparison test
128 Motor Protection, Control & Maintenance
Figure 5.12
Group-to-group / phase-to-phase shorts detection in a Surge comparison test
Testing 129
Hence the surge test is always started with minimum possible values and is gradually
increased. Once the pattern begins to flicker or separate, voltage is to be immediately
reduced as the dielectric limit of the insulation is already reached.
Due care must be taken before using these testers as the test is considered to be
potentially destructive because of the following reasons:
Moisture and other contaminants ionize quickly and at a different rate than air and far
faster than the insulation system. When testing a winding that is in service, when
contaminants exist, tracking can occur across the points of the insulation where
contaminants exist.
Surge testers can be used for evaluating pass / fail for impulses, but not for detecting
the actual condition of the insulation system (ie: dry/brittle insulation, age, etc.). While
AC high potential and surge testing have been effective, in the past, for motor
manufacturers and motor repair centers, they remain a potentially dangerous method for
evaluating the insulation system of motors in the field. This is because the motor systems
that have been in use have aged insulation and winding contamination. Mixed with the
required testing conditions (clean and dry environment at the winding), makes these tools
highly risky for field testing.
In case of Load Point Test Voltage, Current, Electrical Power, Power Factor Speed
(RPM), Direction, Torque, Mechanical Power and Efficiency are measured and
calculated.
As many different load steps as needed can be programmed for a given motor-under-
test, or a continuous speed vs. torque curve can be generated.
To measure a specific Load Point, the dynamometer is set to control in either speed
mode or torque mode, depending on customer preference. If the dynamometer is
controlling speed (speed mode testing), then a speed is established by the dynamometer
and torque is produced based on the capabilities of the motor. If the dynamometer is
controlling torque (torque mode testing), then a load is established by the dynamometer
and speed is produced based on the capabilities of the motor. In either case, once the
desired point is established, the tester can measure speed, torque, voltage and current
(amps) depending on how the individual tester is configured.
The most commonly used single load point is the full load point. This means that the
speed selected is the motor’s rated speed (if speed mode testing is used) or the load
selected is the motor’s rated torque (if torque mode testing is used).
In case of Locked Rotor Test Voltage, Current, Electrical Power & Power Factor are
measured.
Another common load point is known as “Locked Rotor” or “Stalled Torque”. A full
current is applied to a Hysteresis Brake, Dynamometer, or by simply clamping or
“locking” the motor shaft and energizing the motor. More torque is produced by the
Dynamometer / Brake than the motor can produce. In this state the shaft cannot turn,
simulating the rotor being “locked” or “blocked”.
This test is very hard on a motor. There is a large amount of current that flows into the
rotor, causing it to heat up rapidly. As a result, this test must be performed very quickly.
A motor, with a locked rotor, draws up to six or seven times its rated current (sometimes
more). The power supply used must be capable of regulating the motor voltage
adequately during rapid changes in current to ensure the proper voltage is maintained
when the data is being taken. Locked rotor torque testing is important. If the motor cannot
produce enough torque to overcome the friction in the load, as it sits without rotating, the
motor can be energized but it will not start the load. If the motor remains in this state for
very long it will overheat and fail.
Eddy current brakes are available in a wide range of torques and configurations, from
fractional to hundreds of horsepower, air and water cooled. They provide smooth and
controllable loads and operate without any physical contact of interactive members. They
produce no torque at zero speed. This makes them ideal for applications where low speed
control is not required. Note that locked rotor testing can still be accomplished using a
conventional friction brake.
Hysteresis brakes are for small fractional sizes. They operate without any physical
contact being made to the interactive members and they provide smooth and controllable
loads. This results in virtually no wear on the components, with the exception of the shaft
bearing. They are ideal for motor testing from zero speed (locked rotor) all the way up to
full speed. Hysteresis brakes often exhibit a minimum torque, so care must be taken to
assure that the minimum torque is acceptable.
Testing 131
AC vector drives can be used as brakes and they produce full torque at zero speed so
they can be used for locked rotor testing. They have a very fast response (often needed for
switch cutout testing) and, in some cases, sophisticated electronics that can determine
shaft torque without the use of an additional instrument. Because the drive can act as a
motor, it can help accelerate smaller motors being tested on systems that can
accommodate much larger motors.
Electrical signature analysis is the procedure of acquiring the motor current & voltage
signals, performing signal conditioning and analyzing the derived signals to identify the
various faults. The three phase signals are collected either directly (for a LT motor) or
through a CT (for a HT motor). Thus, motors can be tested from the control panel,
enabling easy testing of remote, inaccessible or hazardous area motors. A FFT (Fast
Fourier Transform) analyzer is required for converting the signals from the time domain
to the frequency domain. Motor current acts as an excellent transducer for detecting faults
in the motor. Spectrum analysis of the motor’s current & voltage signals can hence detect
various faults without disturbing its operation. Typical faults that can be detected are:
Rotor bar damage, Misalignment / unbalance, Foundation looseness, Static eccentricity,
Dynamic eccentricity, Core damage, Loose wedges, Inter-turn shorts, Defective bearings
etc.
The full capability of each technology looks at only a portion of the electric motor
system. Therefore, the best approach is a combination of technologies. In addition, each
technology, when properly applied will give the ability to compare test results. With this
a more accurate program can be made by mentioning the frequency of testing, based on
the importance of the equipment.
6
Motors have been an integral part of industry and these wonderful pieces of machinery
are being improved upon on a continual basis. Modern design and manufacturing
technologies have introduced significant improvement in efficiency and energy savings.
However, the maintenance practices have not improved much due to various reasons.
Many of the industries still employ the age-old practices. Electric motor manufacturers
also differ in their recommended methods of bearings maintenance. For example, while
some of them recommend that the motor should be shut down for greasing, others allow
lubrication when the motor is running. Bearing failure, therefore, has become the most
common mechanical failure in AC induction motors.
Figure 6.1
Terminology connected with a typical Bearing
In order to carry out a bearing failure analysis, there is a need to understand the basic
types of bearings, especially with regard to their susceptibility to get exposed to the
external environments, along with their advantages and disadvantages. Normally,
depending on the manufacturer, motor enclosures may vary from open to totally enclosed
and bearings from open to sealed.
Open Bearing: A single row, deep groove ball bearing is sometimes called a Conrad
bearing and is listed by AFBMA (Anti-Friction Bearing Manufacturers Association) as
Type BC (single row radial contact without filling slot).
The Conrad open bearing, as shown in Figure 6.2, is assembled by eccentrically
offsetting the thinner and outer races to allow the insertion of balls. This type of bearing,
therefore, has uninterrupted raceways (no filling slot) which permit excellent bearing
performance under light to moderate radial loads, relatively moderate thrust loads and
combined radial and thrust loads.
Bearing Failure Analysis 135
Figure 6.2
A typical Open Bearing
This bearing is also somewhat self-aligning and typically allows for a minor
misalignment without affecting the bearing operation and life. It can take unrestricted re-
greasing, as it is not susceptible to over-greasing. The friction is minimum, thereby
allowing a cooler bearing operation. However due care must be taken against
contamination and restricting the migration of the grease out of the bearing cavity.
Sealed Bearing: This is a variation of the standard deep groove, Conrad bearing and
the construction of the raceway, cage and ball assembly is the same except for the
incorporation of mechanical non-metallic seals between the inner and outer rings. Hence,
a "sealed" bearing, as shown in Figure 6.3, cannot be re-lubricated.
Figure 6.3
A typical Sealed Bearing
136 Motor Protection, Control & Maintenance
This makes the bearing maintenance-free and entry of the contaminants is restricted to
a great extent. The only maintenance that can be carried out on these bearings is the
replacement. The bearing life is limited by the amount of lubrication packed between the
seals of the bearing and the lubricant life. Sealed bearings cannot be used for larger sizes
due to the excessive heating.
Shielded Bearing: This is very much similar to the sealed-type bearing except that the
shielded bearing has a metallic rather than a non-metallic shield. The metal member is
secured to the outer race with a close running clearance to the inner race. A shielded
bearing can be re-lubricated but with due care. A shielded bearing may be shielded on
one side or both sides, as shown in Figure 6.4, and retains the lubricant at the rolling
elements regardless of the chamber fill.
Figure 6.4
A typical Shielded Bearing
The shield restricts contamination from getting into the rolling elements at installation
and during operation. However, excessive pressure with no relief provided can force the
shield against the cage or balls, thereby losing re-greasability and can cause immediate
failure.
repeated failures and the resulting additional expenses. Hence expert services are
normally hired.
Even if the failure analysis is left to an expert, the actual collection of information by
the user can contribute a lot in correctly diagnosing a bearing failure. A premature
bearing failure is usually symptomatic of other problems that, if left untreated, will cause
the same kind of failure to occur again. Hence it is necessary to send the failed bearing to
an expert for analysis and diagnosis of the problem. Such an analysis helps maintenance
departments in determining the root cause of a bearing failure and pinpoint action that can
be taken to prevent future failures. For example, a bearing subjected to abnormal
operating conditions may only apparently exhibit signs of lubrication failure. The
lubricant may have failed all right, but poor lubrication delivery, maintenance methods,
or the wrong lubrication type may have been the root cause of the failure.
To understand why additional analysis in this case is necessary, one must realize that
an abnormal operating condition often produces excessive heat within a bearing. Heat
buildup lowers the viscosity of the lubricant, reducing the thickness of the fluid film that
separates bearing surfaces. The result is metal-to-metal contact and bearing failure. The
surface damage and increased friction that results from metal-to-metal contact further
increases the bearing's operating temperature, reducing the lubricant's viscosity and fluid-
film thickness even more. Under such conditions, continued operation seriously
jeopardizes the bearing and results in bearing failure. An immature analysis may end up
by diagnosing the problem as a lubrication problem. When a bearing fails, there is a
certain sequence of events that occurs. A trained analyst examining a failed bearing can
read those events.
The process of getting to the root cause of a bearing failure is not very straightforward.
It often is difficult to determine the mode or modes of failure from a severely damaged
bearing. The following facts should be borne in the minds by plant maintenance
personnel and steps must be integrated into the system of monitoring the machinery
accordingly:
x Complete information about the bearing, its application and its history are
definitely of great help in fixing the root cause of failure.
x A history of the bearing in the form of condition-monitoring data is valuable
and speeds up the analysis. When an analyst determines the cause of failure,
the maintenance department is in a better position to implement changes to
increase the life of the replaced bearing.
x Correct interpretation of condition-monitoring data that makes the analyst's
search for a cause of bearing failure easier can also be used to prevent failures
before they occur. For example, trending of the vibration data may reveal an
increasing pattern. Accordingly the monitoring may be beefed up and the
frequency of taking the readings may be increased as long as they are within
limits.
Condition monitoring data can also signal that a bearing should be removed from
service before a failure that may result in damage, occurs.
138 Motor Protection, Control & Maintenance
Figure 6.5
Flaking phenomenon in Bearings
x Fluting. Various possibilities due to the bearing currents flowing through the
bearings are the cause o fluting and are dealt with in the last section of
Chapter 4.
x Indentations. Indentations on the races are due to standstill bearings damaging
them permanently.
x Surface distress.This is a clear indication of improper lubrication. In spite of
the best machining efforts, asperities – peaks and troughs at the microscopic
level – will remain on the surface of any material. Naturally, this is applicable
to bearings races as well. Lubricant loaded in the bearing serves the purpose
of covering them at the sub-microscopic level. It acts as a gliding medium
avoiding the surface asperities from into contact with each other, even
momentarily. If for any reason, the lubricant film between raceways and
rolling elements becomes too thin, this functionality gets affected. Small
cracks then form in the surfaces and are known as surface distress. Slowly
these microscopic cracks, on the surface only, will increase in their size very
gradually and can surface out as roughness of the bearings. Smearing of the
material can be seen in the next stage. This slowly transforms into sub-surface
cracking of the material leading to a possible seizure.
standby drive in a plant should not be allowed to remain idle for long. A
bearing should never be dropped.
x Ineffective sealing can result in the contamination of the lubricant thereby
resulting in the damage of the raceways.
x Improper fitment that is too tight with resultant insufficient internal bearing
clearance will result in a rubbing pattern around the circumference of the
raceway, positioned in the center. The pattern will be very wide in the
direction of the radial load.
If the root cause analysis is carried out properly, the cause of bearing failures can be
broadly attributed to one of the following four types in order of incidence rate from very
high to low:
x Poor lubrication practices coupled with errors in specifying bearings: The
topic is covered in the following parts of the manual.
x Fatigue: Overloading, unbalance, misalignment etc. cause unintended loads
on the bearing that can pull down the service life of bearings.
x Poor installation: Usage of improper tools, fitment techniques and lack of
training play havoc in reducing the life of bearings.
x Contamination: Appropriate sealing methods not being in place particularly in
challenging operating environments damage the bearings in no specified time.
6.3.3. Diagnostics
Normally maintenance menu includes temperature monitoring of the bearings. These
values while providing insight into potential bearing problems, does not really reveal the
actual condition of bearing components as accurately as vibration monitoring and
lubricant analysis. An elevated bearing temperature affects the lubricant's viscosity and
can lead to failure. Therefore, maintenance professionals should attempt to find out why a
bearing is overheating and try to correct the situation.
There are many predictive technologies with varying levels of sophistication that can
spot the degeneration of a bearing before it fails. Some common ones are outlined below.
x SPM
x Vibration analysis
x FFT analyzers
x Electrical Signature analysis
SPM, acronym of Shock Pulse Meter, is widely used for measuring the roughness in a
bearing. It directly indicates the healthiness of a bearing. Based on the reading of SPM it
can be decided whether a bearing can continue in operation or not. Usually trending will
not be taken with this instrument. It is more of a “Continue” or “Stop” sort-of-decision
only. In case of any intermediate reading, vibration analysis will be taken up.
Bearing Failure Analysis 141
Vibration analysis can best utilized for trending the developments. It is used for pin
pointing the problem in a system as it can detect the source of problem. Vibration
analysis is used to analyze the condition of various components, including rolling-
element bearings. By analyzing vibration signatures produced by bearing components, a
vibration analyst can pinpoint bearing damage caused during operation. Any unusual
pattern generated at one of these suspected frequencies is cause for immediate concern.
FFT (Fast Fourier Transform) analyzers, are handheld data loggers etc that can
store the data of the analysis carried out. They can later be downloaded to a computer for
further analysis using specific software. These features facilitate the detection, analysis,
and correction of machine problems. A frequency analysis feature can overlay bearing
defect frequencies on collected spectra to facilitate the detection and identification of
machine and component problems.
While mounting a bearing due care must be taken to handle it with its inner cage. It
means pulling a bearing onto a shaft by the outer race subjects it to tremendous stresses,
which it is not designed to take and hence may fail prematurely. Also the manufacturer’s
instructions must be clearly adhered to. Bearing heating must be taken as a serious issue
and should be handled in a controlled manner. Due care must be taken, especially while
heating with induction heaters, as a thermal differential between the inner race and outer
race of the bearing results in reduced internal clearances. This may take dangerous
proportions if proper care is not taken.
Due care must be taken regarding the fitment of the bearing with the specified
tolerances clearly taken into consideration. The allowed interference between the bearing
outer race and the bearing housing and the bearing inner race and the shaft must be
strictly followed. A fit too tight can cause the bearings to deform resulting in undue
stresses. Too loose a fitting may result in the spinning of the bearing races with respect to
their mating surface, either the shaft or the bearing housing.
Each of the abnormal conditions discussed in this article can lead to premature or
catastrophic bearing failure. When two or more such conditions exist at the same time,
the bearing will only fail sooner.
Conventional wisdom teaches that such an ideal motor bearing environment can be
provided by using a dry-running lip seal or using sealed (lubricated-for-life) bearings.
Indeed, for many light-duty applications, such bearing protection techniques are often
sufficient to allow bearings to last as long as the equipment itself. However, these bearing
protection methods have not significantly reduced the rate of bearing failure in severe-
duty industrial motors.
Even then there are instances of bearings failing because of inadequate lubrication
caused by lubricant loss even in sealed bearings. Lip seals invariably wear out well before
the bearing fails, and sealed bearings inherently foreshorten the life of a bearing to the
service life of the contained grease (usually only about 3,000 to 5,000 hours for most
industrial services).
Contamination due to dirt and other foreign matter also should cause concern. Dirt and
other hard particles such as metal and chips from abrasive wheels can get into the bearing
raceways and be squeezed between the balls and raceway. This will cause roughness of
the race and ball and will eventually cause failure. If the particles are a consistency of a
very fine dust, they will act like a lapping compound and cause accelerated wear of the
races and ball.
A specific procedure must be followed that removes the old grease while charging the
bearing enclosure with new grease. The grease fitting and plug must not be over tightened
because they're tapered and they can act as a wedge, causing the enclosure to crack.
By adopting the most appropriate methodology with adapted frequency and suitable
quantity the rolling elements can be maintained clean and well lubricated. By thinking
ahead and taking bearing maintenance seriously the average bearing life can be extended.
compound when mixed with the grease, resulting in premature failure of the bearing
because of surface degradation.
Vapor-blocking bearing isolators are among the more successful devices presently
available to prevent water vapor from entering a stationary bearing. When the motor shaft
is rotating, the isolator opens, eliminating the possibility of friction and wear. However,
when the shaft is stationary, the isolator closes, preventing movement of air or water
across its face. With no wear from rotating friction, the seal may last indefinitely, and
surely as long as the fatigue-failure life of the bearing.
Lip seals, contact seals, and frequent grease replacement help minimize the amount of
dirt and other air-borne abrasives that can contaminate bearing lubricant. These solutions,
however, have some drawbacks. Lip seals have a short service life, and frequent grease
displacement is expensive and messy.
Preventing water contamination is a major challenge to bearing housing design. Close
shaft-to-end bell clearances cannot stop the movement of humid air. Contact seals will
quit contacting, resulting in large gaps that allow movement of air and water vapor across
the bearing. One successful approach to keeping air-borne dirt and liquids out of an
operating bearing is to install a labyrinth-type non-contact seal over the bearing housing.
These bearing isolators, readily available from suppliers, combine a tortuous labyrinth
path with impingement and centrifugal forces to trap and remove air-borne dirt and
liquid; virtually no contamination can reach the bearing. Because the bearing isolator is a
non-contact device, it will generally be the longest-lasting component of the motor.
Typical bearing isolators are mechanical devices that permanently isolate the bearing
from its operating environment - keeping humidity and moisture from entering the
bearing enclosure during stop and start cycles. Basically, these isolators contain grease
lubricant within the bearing enclosure while keeping external contaminants such as sand
out. But for the bearing lubrication system to work properly, the bearing enclosure must
remain intact.
The unique technology has been developed over a number of years to provide total
bearing protection by ensuring zero leakage of lubricant to atmosphere and total
exclusion of contaminants from the bearing housing. Lip seals are primarily designed to
keep lubricants in, and are not always effective at keeping contaminants out. Surveys
have shown that even a tiny amount of water or dirt in the lubricant can drastically reduce
bearing operating life.
6. . e e ri e
The belt drive mechanism is the simplest form of transferring the power from motor
shaft to the driven equipment’s shaft. A belt drive is essentially a method of transferring
rotary motion between two parallel shafts. The belts transferring torque by surface
friction need to be in tension. This results in the need for adjustable shaft centers or using
tensioning pulleys.
Following are the basic varieties of belts that are used for realizing such torque
transfer:
Bearing Failure Analysis 147
x Flat belts are usually made of rubber with cord reinforcement. They transfer
torque by friction of the belt over a pulley. The belt can be made from other
materials like leather, woven cotton etc. These are susceptible to slip and
hence need tensioners. These are suitable for high speed applications.
x belts ee belts usually comprise a set of tensile members with a wear
resistant outer cover. They are set into pulley grooves and rely on the wedging
action. The materials employed like polyurethane, hi-text woven textiles make
them smooth and reliable. They have better torque transferring capability.
They are more compact than a flat belt.
x edge belts poly ee belts are an improvement over V-belts and are vee
grooved along the inner surface. Hence it combines the high traction
capability of vee-belt into a single belt. These are narrower and lighter than
V-belts resulting in reduced centrifugal separating force. Hence the belt-
pulley contact pressure will be much better. Accordingly the frictional torques
are not so deleterious in this kind of belts. A different form would be with
cogging (inside material cut in the form of teeth). This ensures that the
bending stresses, especially while passing over the pulley curvature that can
be dangerous, on the belt are minimized.
Figure 6.5
arious types of elts
Synchronous or Timing belt provides positive coupling between the belt and the pulley
as the teeth provided along the inside surface serve the purpose like a geared coupling.
The mating between the teeth and the pulley is always ensured, unless there is a major
slackness, thereby allowing no slip.
For reliable operation of a belt drive, for that sake any equipment, it must be designed
properly with due consideration for the loading pattern, possible service factors of the
driving motors, starting conditions, operating conditions, environmental conditions & the
tolerance levels of the pulleys.
148 Motor Protection, Control & Maintenance
Even a best-designed belt drive should be properly engineered – tailored to suit the
requirements of the system like specifying the best size and number of belts needed. This
of course starts at the time of specification and continues through the plant operation.
Pulley tolerance levels must be within the industry set norms. Heavy duty components
and/or structural members like frame work, motor mounting structures, machine pads,
concrete structures shall be properly sized to carry the load. Also, the spacing between the
motor and the driven pulley and their alignment are very critical. The belts need to be
protected, but at the same time must remain well ventilated. Any modifications should be
carried out only after referring to the designer.
While specifying the requirements for a belt drive, proper information about the
ambient temperature extremities, presence of chemical vapours, lubricants, cutting fluids
employed, possible harshness in weather conditions, the equipment’s exposure to
sunlight, humidity etc. must be given to the supplier. Accordingly, the selection of
material and technologies can be done by the designer. The protections required for the
belt drive should also be engineered based on these data.
Handling / Environment related issues
In spite of the improvement in the manufacturing technologies and better quality
materials being employed, belt drives still fail.
One of the various reasons for such failures is improper handling of the belts. Force
should never be applied on the belts at the time of installation or replacement of the belts.
While installing the center distance should be reduced or the idler released to reduce the
tension. Otherwise the belt may get damaged or the internal cord reinforcement may
break. Hence, to carry out such jobs, adjustment of tension is an imperative. This may be
done by reducing it initially and setting it properly back. Belts should never be twisted or
bent below the minimum recommended diameter.
Rubber belts normally have a shelf life of 8 years, if stored properly - no direct
sunlight, temperature, humidity maintained within the specified limits. Contact the
supplier for details. Never go by thumb rules as the material quality and manufacturing
technology is a continually changing affair.
Given below are some other considerations by way of maintenance for belts:
x Storing belts in the original shipping cartons is the most desirable method,
provided original integrity is restored back after every opening.
x Keep the belts away from ozone sources such as arc welders and other
electrical equipment or motors.
x Don’t leave any room for contamination.
x V-belts may be stored by hanging them on properly designed belt racks or
hooks.
x Synchronous belts should be stored on their sides on shelves.
x Belts should not be coiled too tightly or by bending them sharply.
x Belt drive systems should always be protected from abrasive damage by using
adequate drive guards.
x Keep drive guards clear to disallow the build-up of any foreign material.
Bearing Failure Analysis 149
Ensuring proper tension in the belts must be a regular affair. Regular checks must be
carried out to ensure this. Maintenance personnel must show genuine concern and reduce
the frequency, if required, even from the designer recommended levels. However, such
deviations must be parallely be taken up with the OEM. The frequency will be more in
the case of flat / V-belts. Even though synchronous belts may not require frequent
correction, checking needs to be carried out periodically as otherwise it can have a
detrimental effect on the teeth.
Manufacturer's recommendations should be meticulously followed to determine the
tension values. The ideal tension for a V-belt drive is the lowest tension at which the belt
will not slip at the highest load condition.
At the time of commissioning, run-in procedure is adopted, where the drive is started
and run under full load and then stopped. Checking and retensioning to the recommended
values will be taken up as running of the belts under full load allows them to seat
themselves into the grooves.
A rule of thumb regarding belt drive alignment:
x Sheave alignment on V-belt drives should be less than 1/2° or 1/10-in. per
foot of drive centre distance.
x Synchronous belts should be controlled to within 1/4° or 1/16-in. per foot of
drive centre distance.
6.6. a an e
Balance can be defined as the state of the mass distribution within the rotating
assembly about its axis of rotation. The eccentricities of this mass distribution are referred
to as unbalance. Unbalance can create forces on bearings, structure, shaft, couplings etc.
and the effect manifests as vibration.
The amount of unbalance is stated in units of mass times a distance, such as grams
inches ounce inches gram centimeters or gram millimeters
Unbalance is a major source of machine vibration. Vibration in turn is defined as the
unwanted motion of a body in response to forces imposed upon that body. Vibrations
150 Motor Protection, Control & Maintenance
result in premature failure of the associated and even surrounding equipment. They create
unacceptable noise and general discomfort to those around such machines.
Vibration in assembled motors can be typically measured as amplitude (peak to peak)
in inches, or as elocity in inches per second pea or as elocity in millimeters per
second
The balancing act can be defined as a deliberate correction of the eccentricities of the
mass distribution in rotating elements so as to have a homogeneous distribution of mass
and hence the minimum possible unbalance.
A simple test to determine gross weight unbalance is to put the rotor – balance problem
is related to only rotating elements – on two knife edges, as if to check the run out of a
shaft. Rotate it and allow it to slow down to still condition. If every time the rotor is
stopping at the same position, it indicates an unbalance.
Static unbalance is the simplest as the mass is excessive at one point. This results in
unbalance and can be eliminated by balancing in one or at the most in two planes.
Couple is an unbalance resulting out of two excessive mass points in two opposing
directions. Hence it needs to be balanced in two planes.
Dynamic unbalance is a combination of both Static unbalance and Couple unbalance.
Either two-plane methods are trial-and-error procedures are to be adopted for correction.
Balancing can be carried out either by trial-and-error method for in situ corrections or
by using a computerized balancing machine that can be used for balancing in a workshop.
In case of the former method, the vibration levels are taken prior to balancing and the
measurements are repeated with each balancing weight added or removed on a trial basis.
In the latter case, the rotor alone needs to be mounted on the adjustable arms supporting
the knife edges. The rotor is then run at a speed, which need not be the rated speed, and
the data is collected. The machine does the necessary analysis, with prior data that is fed
into it and displays the weight and phase angle at which it is to be added.
6. . rage iss es
A bearing is normally supplied in a pack sealed by the manufacturer. Due note should
be taken of its preservation aspects.
In case the original pack is opened for inspection purpose, due care must be taken to
wrap it back properly to avoid any ingress of moisture. The pack must be made air tight.
The pack must be stored in a cool, dry place. Moisture absorbent substances like silica
gel, should be placed in the wooden boxes containing the bearings packs. This is to avoid
moisture in the environment of bearings storage.
Sometimes the original rust preventive coat, applied by the bearing manufacturer, may
get wiped off while inspecting. So a coat of rust preventive coat should be applied again
before storing it.
Bearings planned for long storage should not be cleaned with kerosene, diesel etc.
152 Motor Protection, Control & Maintenance
The bearings storage area must be free of any storage of acids or any other corrosive
chemicals.
When the bearing is in installed condition, the old grease should be removed and
bearings relubricated with new grease before re-using the motor. For this
purpose, disassemble the bearing housings and clean the inside of the housings, the
housing plates, caps and the bearings with a suitable solvent.
Rotate the shaft to check for roughness in bearings or interference between rotating and
stationary parts. Perform a bench test on the unit to check for excessive amp. draw, noise,
or vibration. Regrease the motor bearings (as applicable) in accordance with the unit’s
operating instruction folder.
6. . er i e a r ading
As per NEMA Standard MG1-1.42 "service factor of an ac motor is a multiplier which,
when applied to the rated horsepower, indicates a permissible horsepower loading which
may be carried under the conditions specified..." Those "conditions," include a winding
temperature rise at the service factor horsepower that exceeds the rated insulation system
temperature by 10° C. Normally motors are designed to deliver their rated horsepower
under voltage variations of ± 10% of rated and frequency variations of ± 5% of rated. The
combined variation of voltage and frequency is limited to ± 10%. When operated within
these limits, with shaft load at or less than rated, the motor current and winding
temperatures will remain within rated values, and normal motor life can be expected.
Hence service factor of a motor gives an idea of the increased power output (or overload
capacity) that the motor is capable of providing under certain conditions. Service factors
that can normally be seen will be 1.0, 1.15 & 1.25. A service factor over 1.0 must be
clearly indicated on the nameplate of the motor. Some times it is mentioned as SFA –
service factor amperes.
One must read between the lines, when it comes to service factor loading. The normal
rated voltage and frequency need to be maintained in order to load the motor up to this
power. Even then the temperature rise of 10° C will be there. This may lead to lowering
of the life of winding insulation by half.
The cost of the motor with a higher service factor, for the same rating, class of
insulation etc., will naturally be higher. This is because, a higher service factor means that
the motor must be capable of operation at higher loads and hence must have better heat
dissipation capability. This is possible only by increasing the size of the motor and hence
at a higher cost.
Hence operation of a motor at its service factor loading is worth only for short periods
and shall not be indulged in running continuously at that higher load. Also the voltage
source has to be very stable. There should not be any concern for the longevity of the
motor.
Hence the advantage that can be taken out of such flexibility can be restricted to only
unforeseen conditions like plant upsets, startups that may not be too frequent and
unpredictable climatic conditions that may be bring in sporadic requirements.
It shall always be borne in mind that continuous operation at service factor load can
lead to a higher rate of motor failure due to insulation breakdown. The increased load
Bearing Failure Analysis 153
may also put stress on other components and may reduce life of the most vulnerable
component, the bearing. Also the efficiency, power factor, and speed of the motor at
service factor load may vary from their values at rated load. Efficiency can typically be
expected to decrease, as motors will have optimal performance only for the rated load.
A motor with a higher service factor will not deliver a higher torque or the same
efficiency; it plays only a sacrificial role to meet dire needs. If a consistent overload is
expected, it may be even better to replace the motor with that of a higher rating. This will
increase the operational efficiency and may be economical.
154 Motor Protection, Control & Maintenance
7
. . nr d i n
Of all motors, squirrel cage induction motors, particularly the TEFC type (Totally
Enclosed, Fan Cooled), have become extremely popular mainly because of their simple,
rugged construction and good starting and running torque characteristics. The TEFC
design improves the mechanical life of the motor because dust and moisture are excluded
from the bearings and windings. This type of motor has proved to be extremely reliable
with an expected lifetime of up to 40 years when used in the correct application.
However, the industry is witnessing failures in this kind of motors also, for various
reasons, in spite of these much-improved designs and the continually improving
maintenance practices. According to the statistics gathered by the ABB Group, as shown
in Figure 7.1, 81% of such motor failures could have been avoided by using an accurate
and effective relay for protecting the motor concerned.
156 Motor Protection, Control & Maintenance
Figure 7.1
Protecti e functions needed to detect the motor dri e faults
Figure 7.2
emperature rise ersus time for a motor
Protection of Motors 157
At this point, the temperature of the motor remains constant for a particular load, at a
particular ambient temperature. As the load on the motor changes, this stabilized
temperature varies depending on the balance between the heating and cooling
phenomena. At higher, persistent loads the motor temperature may reach dangerous
values. If the motor is left to continue in these conditions, for long, the stator insulation
may start breaking down resulting in the failure of the motor. Even if the motor doesn’t
break down immediately, the high temperatures to which the insulation system is
subjected to, will accelerate the degradation process of the insulation system (the details
are already covered in the topic on insulation failure in Chapter 4). In this context it is
worth remembering that higher the operating temperature of a motor the lesser the service
life of the motor. Also, it has been proven empirically that for every 10 0C rise in
temperature, the life of a motor reduces to half.
Hence, the basic intention of the thermal overload protection is to safeguard the motor
against such overheating of the stator insulation system so as to extend the life of the
motor. However, there is a trade-off between the loading of a motor and its protection.
This demarcation line drawn between the load current and time is called as thermal
capability curve or motor thermal withstand characteristic of the motor. Also it will have
two different curves – the cold one involving no thermal trip and the hot one connected
with a thermal trip. Operation of the motor above the thermal capability curve can be
detrimental to the motor’s life in the long run, if not immediately, and the motor is said to
be thermally overloaded. Therefore, this protection is called as thermal overload
protection.
Also known as running protection, this is intended to protect the motor against only
persistent overloads, while in operation. The National Electric Code (NEC) defines Motor
Overload Protection as that which is intended to protect motors, motor-control apparatus,
and motor branch-circuit conductors against excessive heating due to motor. This is not
expected to protect the components against a ground fault or a short circuit fault. Hence a
protection against thermal overloads is aimed at enhancing the longevity of a motor.
Motors can be protected against thermal overload by two broad methods – indirect
method is by simulating the motor internal conditions by sensing the current flowing
through it and direct method by sensing the temperature within the motor. Indirect
methods employ thermal overload relays or magnetic overload relays or through
differential current sensing systems. Direct methods can be are of inherent type or
thermostat type. Inherent type engages bi-metallic strip to sense the ambient temperature,
motor internal temperature, internal motor heating and the current flowing in the circuit.
These are used for small (FHP) motors. Using thermostat type the motor winding
temperature is directly sensed and the contact is used for tripping the motor. Usually it is
used in conjunction with thermal overload relays.
The cooling time constants during operation are approximately equal to those for
temperature rises, while at standstill they are four to six times the values given in the
table.
A[mm]
Type 355 400 450 500 560 630 710 800 900 1000 1120 1250
O 20 25 28 30 35 40 50 60 65 70
R 45 50 55 60 70 80 90 100 110
U 30 35 40 45 50
A = Shaft height (mm)
O = Open Type (IP23)
R = Closed type with air/air heat-exchanger (IP54)
U = Fully clad with cooling finds (IP54)
Table 7.1
ean thermal time constants of asynchronous motors from rown o eri in relation to motor rating and type
the heating time of the windings from cold and could trip before a motor/load
combination with a long run-up time had reached running speed.
On the other hand, during several sequential starts and stops, the device could
underestimate the cooling time of the windings, allowing the motor windings to overheat.
This situation can very easily arise with the bimetallic thermal overload relays commonly
used on motor starters even today. Under certain conditions, bimetallic thermal overload
relays do not provide full protection because the device does not have exactly the same
thermal heating and cooling characteristics as the motor which it is protecting. The
heating and cooling time constants of a bimetallic relay are much the same but in actual
installations it should be borne in mind that a stopped motor has a longer cooling time
constant than that for a running motor. When a motor has stopped, the fan no longer
provides a forced draft and cooling takes longer than when the motor is running on no
load. A simple bimetallic device is a compromise and is calibrated for normal running
conditions. As soon as an abnormal situation arises, difficulties can be expected to arise.
To illustrate the point, take the case of a motor that has been running at full load for a
period of time when the rotor is suddenly stalled. Figure 7.1 shows typical temperature
curves of the winding temperature (solid line) compared to the heating and cooling curve
of the protective device (dotted line). Starting at a normal continuous running
temperature of 120°C, the current increases for the locked rotor condition and
temperature rises to 140°C when the thermal device trips the motor after some seconds.
After about 10 minutes, the bimetal will have cooled to ambient, but the windings will
only have reading 100°C. With the bimetal reset, it is then possible to attempt a restart of
the motor. With the rotor still locked, high starting currents cause the temperature to
quickly rise to 165°C before the bimetal again trips the motor.
Considering that a similar sequence of events as described above can again be
repeated, where the different cooling times of the motor and bimetal strip allow the
bimetal to reset before the windings have cooled sufficiently, and if the motor is again
restarted after another 10 minutes, the winding temperature is likely to exceed 180°C, the
critical temperature for Class B insulation materials. This illustrates the importance of an
accurate simulation by the protection device in both conditions where the motor is
running and when the motor is stopped.
Nowadays, solid-state electronic relays are able to deliver various functionalities
integrated under one casing. They extend all the protections offered earlier by
electromechanical relays. Apart from this, they can be programmed as universal relays
suitable for even the smallest motor to even a multi MW rated motor. With the earlier
relays, one was required to specify the rating of a motor for which it is intended to be
used. These digital relays have lot of special features to their credit as mentioned blow:
x Compact as compared to their conventional equivalents.
x Very stable against temperature variations
x Longer calibration accuracy – some of the relays hardly require any testing
x Versatility – there is no need of specifying the motor rating before hand
x Reliability is very high
x Very low power consumption
160 Motor Protection, Control & Maintenance
The most recent versions of motor protection relays are digital, microprocessor based
ones and have the capability to incorporate various, programmable protections. Even their
prices are also making them very attractive as compared to their earlier counterparts,
especially after considering the various functionalities.
Typically a new generation microprocessor based motor protection relay can fulfill the
following protections for any rating motor:
x Overload protection
x Locked rotor protection
x Phase and ground fault protection
x Unbalanced current protection
x Load jam
x Load loss of induction motor etc.
All these are covered accurately with the bare minimum data that needs to be fed into
the relay at site. Typical information required for the purpose are:
x Motor full load current
x Locked rotor current
x Locked rotor thermal limit time
x Motor service factor etc.
They use an element that accounts for the I2r heating effect of both the positive- and
negative-sequence current. The element is a thermal model defined by the motor
nameplate data entered as settings. The model estimates motor temperature and compares
it to thermal limit trip and alarm thresholds. The relay trips to prevent overheating for the
abnormal conditions of overload, locked rotor starting, too frequent or prolonged starts,
and unbalanced current.
These relays typically include:
x Thermal overload protection, monitoring all three-phases with thermal
replicas for direct and frequency convertor controlled drives
x Short circuit protection
x Start-up and running stall protection
x Phase unbalanced protection
x Single-phasing protection
x Earth fault protection
x Undercurrent protection
x Digital read-out of set-values, actual measured values and memorized values
x Self supervision system
x Outstanding accuracy
x Optimum philosophy
Protection of Motors 161
The present day concept is use of microprocessor based numerical relays for both HV
and LV motors (say beyond 50 KW), as the relays come with lot of features which allow
them to be interchangeable, ensures site settings and give valuable feedback on the load
details whenever a trip occurs or not.
Figure 7.3
otor Current during tart Conditions
When determining the current and time settings of the overload protection it can be
assumed that the motor starting current remains constant and equal to the standstill value
of the whole of the starting time.
. . a ing rs
Refer to Figures 7.4 and 7.5. Should a motor stall when running or be unable to start
because of excessive load, it will draw a current from the supply equivalent to the locked
rotor current. It is obviously necessary to avoid damage by disconnecting the machine as
quickly as possible if this condition arises.
162 Motor Protection, Control & Maintenance
Figure 7.4
elay operation times less than stall withstands time: relay gi es stall protection
Protection of Motors 163
Figure 7.5
elay peration time greater than stall with stand time: elay does not gi e stall protection
tbI.R.
motor speed
Whether or not additional features are required for the stalling protection depends
mainly on the ratio of the normal starting time to the allowable stall time and the accuracy
with which the relay can be set to match the stalling time/current curve and still allow a
normal start.
. . er rren er ad
Over current protection for motors is usually required to safeguard the motor against
short circuit mainly to take care of phase faults. In order to provide an effective
protection, phase fault current shall be greater than starting current. Otherwise the
protection will act during normal starts. In such extreme cases, differential protection
shall be provided for the motor. An instantaneous, high set, simple protection provides
reliable, inexpensive coverage against phase faults. The operation of this instantaneous
protection may involve, typically, 70 – 130 milli second at twice the current setting.
IDMT characteristics suiting the motor’s thermal capability curve are realized using
the overload units to provide protection against long duration, light and medium
overloads. NEC recommends provision of such overload coverage in each phase.
However thermal capability curve of a motor represents an approximate average of the
safe thermal zone of operation only and cannot be the exact model of the motor. Also the
overload protection requirement varies considerably with size and design.
166 Motor Protection, Control & Maintenance
Figure 7.7
ransient o er current during first few cycles when starting a motor
factor. The torque developed by the motor, whether of locked rotor or of breakdown will
be proportional to the square of the voltage applied.
Average accelerating torque is given as:
[(voltage available at motor bus / rated motor voltage) 2 (rated torque)] - Load torque
Hence, due to the reduced accelerating torque, the motor will have problems in starting
and reaching full speeds. Also a running motor may lose speed and draw heavy currents.
Hence under voltage protection is invariably provided for induction motors. Typically,
by sensing a bus under voltage condition all the connected motors to that bus are tripped
out.
The under voltage setting is normally 75 to 80 %.
Either an increase or a decrease in voltage results in increased heating of the motor at
the rated load and hence may accelerate the deterioration of the insulation system, in the
long run.
Similarly, over voltage can be detrimental to the insulation system as the temperature
rises because of increased slip due to either an under voltage or an over voltage.
. . nder re en
AC motors operate successfully under running conditions at rated load and at rated
voltage with a variation in the frequency up to 5 percent above or below the rated
frequency.
Performance within this frequency variation will not normally be as per the standards
established for operation at rated frequency.
At a frequency lower than the rated frequency, the speed is decreased. Since the
magnetic flux in the machine, which is proportional to the inverse of frequency at a
particular voltage increases, locked-rotor torque also increases and power factor
decreases.
Also this may result in over magnetization of the core of the motor that, in turn, may
result in overheating of the stator due to increased iron losses. If left unchecked, this may
cause severe damage to the motor.
Normally, the result being overheating that is protected separately, motor feeders will
not be separately provided with this protection. Frequency cannot be different from the
source to even the remotest utilization point, unlike voltage that can drop even
atrociously. However the impact of this aspect being very serious the protection is
provided at the source itself, be it generator or the switchgear incomer of the particular
plant.
168 Motor Protection, Control & Maintenance
.6. esi se
These aspects are purely applicable to synchronous machines only. During a pole-slip
condition, negative currents can be induced into the field which is opposite of the normal
positive current flow produced by the excitation system.
Hence, a large negative induced current with no current path will result in a very high
positive voltage transient across the power rectifiers. The large voltage transient can
cause damage to the solid-state devices and produce severe pitting on the slip rings.
With the application of the crowbar SCR circuit, the voltage sensing circuit will detect
the positive induced field voltage and gate on the appropriate SCR to allow the negative
current to flow from the field through the discharge resistor. When the crowbar circuit
turns on, the rectifier bridge will be inhibited to prevent overload into the crowbar
discharge resistor.
The out-of-step conditions (loss of synchronism) of a synchronous machine may occur
as a result of pole slipping and hence pole slipping protection also detects loss of
synchronism, but with the excitation intact.
Synchronous motors can develop torque only in synchronism. Overloading, beyond
motor’s capability, may result in slowing down of the rotor. Once synchronism is lost, the
motor will not be able to develop any torque. This is called ‘a motor going out of step’.
Since the rotor of a synchronous motor is applied DC voltage and the rotor doesn’t
have any induced voltage, no AC voltage is supposed to be present when the motor is
operating synchronously. Hence synchronous motors with brush type excitation can be
easily protected against out of step or loss of synchronism by means of AC detection
circuits connected to the rotor. Such circuits will detect pullout resulting from excessive
shaft load or too-low supply voltage and protect the motor against overheating and the
resulting damages.
Both effects may cause severe mechanical and thermal stresses to the machine. Loss of
excitation protection is generally used to guard against the consequences of a partial or
complete failure of the excitation. An under impedance relay is used to recognize this
event.
. . ss e iai n
Synchronous motors can be protected against loss of excitation by a low-set
undercurrent relay connected to the field. This relay should have a time delay drop out.
On large synchronous motors an impedance relay is frequently applied that operates on
excessive VAR flow into the machine, indicating abnormally low field excitation. If an
under voltage unit is part of the relay, its function should be shorted out because loss of
motor field may produce little or no voltage drop. Operation of synchronous motors
drawing reactive power from the system can result in overheating in parts of the rotor that
do not normally carry current. Some loss-of-field relays (device 40) can detect this
phenomenon.
Protection of Motors 169
. . nad er en energi a i n
Inadvertertent energization protection is needed for synchronous motors especially to
avoid any accidental closing of the breaker when the supply to the motor fails and the
motor is coasting down. Due to the stored energy in the drive, especially from the driven
side, motor starts acting like a Generator. Under such circumstances, the supply being
restored will be out of phase with motor generated voltage and there can be a resultant
flashover.
While giving permissive start to a motor, there can be an accidental energization which
can cause physical damages to the equipment in spite of all precautions to avoid closing
of the breaker of a motor satisfying all the mandatory conditions,.
. . er ing
At frequencies lower than the rated frequency, the speed decreases. Since the magnetic
flux in the machine, which is proportional to the inverse of frequency at a particular
voltage increases, locked-rotor torque also increases and power factor decreases. Also this
may result in over magnetization of the core of the motor that in turn may result in
overheating of the stator, due to increased iron losses. If left unchecked, further fall in
frequency will result in saturation of the magnetic core thereby impairing its torque
delivering capability.
This kind of protection must invariably be provided in applications where the
frequency of the supply is varied in order to obtain variable speeds. All modern day
variable frequency drives have this protection built into the logics and hence they are
called as variable voltage variable frequency drives, VVVF drives in short.
By reducing the over fluxing of the motor, and hence the iron losses, the motor runs
cooler and more efficiently, the power factor is maintained at the most appropriate value
for every condition of load, which, in turn, reduces the apparent reactive power.
This will bring about a significant reduction in the apparent power demand which may
reduce the input real power as well. This kind of protection is popularly known as V/Hz
protection or “V / f” control.
. . a r e i n a e era i n i e
Stall condition of a motor is the result of a hard-to-start load causing a blockage of its
rotation. This results in the motor drawing heavy current without any scope for reduction
on its own. One of the easiest ways to detect such conditions is sensing of the motor’s
speed. It can safely be concluded that motor is stalled, if the zero speed (standstill)
condition of the motor continues, even after energizing the motor. However, it may not
always be feasible to provide such detection and the circuits must depend on the current
drawing pattern to discriminate against a normal starting current. The motor manufacturer
will give the motor’s withstanding capability. The protection must be strictly in
agreement with this. Else the motor will be seriously damaged.
This majority of loads are such that the starting time of normal induction motors is
about or less than 10 seconds, while the allowable stall time to avoid damage to the motor
170 Motor Protection, Control & Maintenance
algorithm incorporated in it and based on the data entered by the user & actual data
acquired by it.
. . ega i e se en e rren s
Analysis of negative sequence currents (one of the three symmetrical components of
any type of current) are particularly of more importance in the case of large rating motors
(1000 HP and above).
Symmetrical components of three phase currents consist of:
x Positi e se uence currents: normally present during a typical steady state
condition.
x egati e se uence currents: present only during unbalance.
x ero se uence currents: present only when earth is also involved in the
unbalance.
Negative- and zero-sequence currents are usually only present in substantial levels
during unbalanced, faulted conditions.
Figure 7.8
he Positi e egati e and ero Components
sequence current) of 5 %. For the same level of unbalance, a motor with this ratio as 4
needs to be derated by less than 10 %.
The reduction in output for the machines having ratios of starting to running current of
4, 6 and 8 respectively is shown in figure 7.9.
Figure 7.9
a imum continuous output ersus oltage unbalance
. . era ing a rs
The performance of AC induction motors, or for that sake any equipment, is influenced
by various factors like ambient temperature, quality of the incoming power supply etc.
these factors need to be specified explicitly while procuring, especially when the
operating conditions differ widely from the standard values. For instance, when an
induction motor is required to be operated at an ambient temperature exceeding 40 degree
C, it must be clearly spelled out at the procurement stage itself.
Once a standard motor is available and needs to be utilized for an application with the
operating conditions differing from the originally intended ones, the motor’s rating has to
be suitably derated.
The factors that need to be considered in derating a motor’s performance are:
x Supply Voltage
x Supply Frequency
174 Motor Protection, Control & Maintenance
x Ambient Temperature
x Altitude of the location of installation
AC motors are designed to operate on voltages and frequencies that are well
standardized. For example, NEMA standards specify voltage ratings of 380 V, 400 V,
415 V … at 50 Hz. Similarly, for 60 Hz of supply frequency, voltage ratings of 115 V,
200 V, 230 V, 460 V, 575 V are standardized.
A small variation in supply voltage can have a great influence on a motor’s
performance. For example, when the voltage is 10% below the rated voltage of the motor,
the motor has 20% less starting torque. This reduced voltage may prevent the motor from
getting its load started or keeping it running at rated speed. A 10% increase in supply
voltage, on the other hand, increases the starting torque by 20%. This increased torque
may cause damage during startup. A conveyor, for example, may lurch forward at startup.
A voltage variation will cause similar changes in the motor’s starting amps, full-load
amps, and temperature rise. It can be generalized that a 10 % rise in voltage will result in
an increase in motor performance of 20 %.
In the same way, an increase in frequency of 5 % results in a corresponding increase in
the speed and a 10 % decrease in the motor starting torque. Conversely, a decrease in the
supply frequency by 5 % results in a proportionate reduction in speed and a 11 % increase
in the starting torque. Hence suitable corrections have to be applied to the standard
motors accordingly.
Standard motors are designed to operate below 3300 feet (1000 m). The motors
operating at temperatures above 1000 meters have to be derated because of the impaired
cooling of the motor due to the light air at higher altitudes. The thin air at higher altitudes
will have less cooling effect on the motor as the net heat transfer, due to the reduced air
mass, goes down. At an altitude of above 5000 ft, the derating factor becomes 0.94.
Roughly for every 1600 feet rise in altitude, the derating factor reduces by 0.04.
Figure 7.10
Earth fault protection
Care must be taken to ensure that the relay does not operate from spill current due to
the saturation of one or more current transformers during the initial peak of the starting
current; this can be as high as 2.5 times the steady state r.m.s value, and may cause
operation, given the fast operating speed of the normal relay. To achieve stability under
these conditions, it is usual to increase the minimum operating voltage of the relay by
inserting a stabilizing resistor in series with it (refer figure 7.10).
Current sensing is the best method to detect and locate earth faults. However, system
capacitance, unbalanced loads, current-sensor limitations, and harmonics affect current
measurement and limit the lower level of practical earth-fault detection.
Current flowing to earth has only two paths—it can flow to earth through an earth fault
or it can flow to earth through distributed capacitance. Current flowing to earth through
distributed capacitance can cause sympathetic tripping during an earth fault and it can
cause nuisance tripping during normal operation. If the earth-fault trip level is high
enough to eliminate sympathetic tripping, nuisance tripping due to unbalanced and
176 Motor Protection, Control & Maintenance
harmonic capacitive current is usually not a problem. Charging current is defined as the
current that flows to earth when one phase of an unearthed system is faulted to earth.
When a motor is started across the line, the inrush current can have a DC-offset
component that can cause an output from a core-balance current transformer. Such
transient characteristics are unpredictable because the switch can close at any point in the
electrical cycle. Transient conditions typically last less than 100 ms and nuisance earth-
fault trips can be avoided by setting a longer trip delay time or by using a digital filter to
reject the dc component. All current transformers, including the window-type core-
balance CTs used to detect earth-fault (zero-sequence) current, have practical limitations.
A minimum excitation current is required in the primary coil before there can be a
proportional output current. Excitation current is a function of burden, CT construction,
and size. Sensitive earth-fault detection requires excitation current to be small. A large
fault current, such as a phase-to-phase fault or an earth fault on a solidly earthed system,
can saturate a current transformer. Saturation occurs when a CT cannot maintain a
secondary current waveform proportional to a large primary current. Secondary current
characteristics in this case are unpredictable and earth-fault protection may not operate.
Stability against external faults is guaranteed thanks to the use of a stabilizing resistor.
To detect high-impedance faults and provide machine-winding protection, the earth-
fault current pickup level should be less than 20% of the prospective earth-fault current.
The pickup level of all system earth-fault protection devices should be the same, and
coordination should be accomplished by varying trip delay times.
However, most recent developments have made this new generation, digital
(microprocessor based) relays much more intelligent, requiring very few parameters to be
set by the user at site. At the same time they provide very fast, reliable response in
clearing the faults.
25 = Synchronization check
27 = Bus/Line under voltage
32 = Reverse power (anti-motoring)
38 = Over temperature (RTD)
39 = Bearing vibration
40 = Loss of excitation
46 = Negative sequence / unbalance (phase current imbalance)
47 = Negative sequence under voltage (phase voltage imbalance)
49 = Bearing over temp (RTD)
50 = Instantaneous over current
51 = Time over current
51V = Time over current -- voltage restrained
55 = Power factor
59 = Bus over voltage
60FL = Voltage transformer fuse failure
67 = Phase/Ground directional current
79 = Auto re-close
81 = Bus over / under frequency
37 Under current
48 Incomplete Sequence
49S (26) Locked Rotor
49/51 Over load
50 Short Circuit
50GS/51GS Ground Fault
51R Jam (Running)
59 Over voltage
60V Voltage unbalance
62 Timer
66 Successive
81L/H Under-and Over frequency
87M Differential
86M Lock-out Auxiliary
Protection of Motors 179
Figure 7.11
Typical protection logics for a Synchronous motor
Protection of Motors 181
Figure 7.1
Typical protection logics for an Induction motor
182 Motor Protection, Control & Maintenance
8
Motors are considered as workhorses across all industries. Naturally, they need to be
properly controlled - to realize their full potential - the way industry demands from them.
This may include reliable starting at the moment of requirement (vertical startup), and
controlling their start / stop through safety / operational interlocks. Also it may include
the control of speed for some of the special equipments requiring variable speed drive
either smoothly or in steps. Reversing the direction or braking the motor speed by various
means involving regenerative or dissipating techniques may also be required for certain
other applications.
In order to carry out these tasks effectively, one has to have a conceptual understanding
of these requirements.
The backbone of all these controls is the power circuit, which need to be designed,
engineered, installed and maintained well in order to have a reliable operation. Control
circuit is like the nervous system of a human body wherein various stimuli are received,
processed and necessary commands are issued for effective control of the intended
operation.
.1. he o er Circuit
The power circuit is the backbone of a motor control arrangement and needs to be
strong for a trouble free operation. It refers to all the conductors and connections that
exist from the point at which the voltage is tapped from the MCC (Motor Control Center)
bus through all intermediate points up to the connections at the motor. The power circuit
typically includes isolators / disconnects, fuses, contactors / circuit breakers, overloads,
cables and lug connections.
184 Motor Protection, Control & Maintenance
In industrial power distribution systems, usually connectors and conductors are the
source of a majority of the faults that reduce motor efficiency. It needs to be understood
that a motor even in perfect health, gets affected due to problems like harmonics, voltage
imbalances, current imbalances, etc. if installed into a faulty power circuit. As these
problems become more severe, the horsepower rating of motor drops, causing
temperatures to increase and insulation damages to occur. In particular, high resistance
connections resulting in voltage imbalances will reduce the horsepower rating
significantly.
One method of detecting high resistance connections is by performing phase to phase
resistance testing. On a three phase motor, the three resistance measurements should be
nearly identical. In an ideal case, there would be a 0% resistive imbalance. As one or
more phases develop a high resistance, the resistive imbalance increases, indicating a
fault. Any problem related to power / voltage imbalance will then result in negative
sequence currents.
These type of problems can be overcome by using proper power cables, lugs and
proper crimping. The bi-metallic effect, ie., increase of contact resistance due to two
dissimilar metals like copper and aluminium, causes various problems. Minimum
possible contact resistance and balanced impedance resulting in balanced voltages &
currents shall be the ultimate goal of any good power circuit design and its maintenance.
As the problem becomes more severe the temperature increases, thereby heating the
components in its vicinity and reducing the power developing capability of the motor.
Some of the fault mechanisms that cause high resistance connections and the
corresponding actions to be taken to mitigate them are:
x Corrosion of terminals, due to oxidation resulting out of moisture or corrosive
environments, can be avoided by proper sealing of the motor terminal box.
x Looseness of cables, due to vibrations can be avoided by ensuring proper
tightness at regular intervals or by providing suitable locking mechanisms.
x Looseness in bus bars can be kept under check by carrying out regular
maintenance.
x Corroded fuse clips and corroded contacts should be identified, and repaired
or replaced in good time.
x Open leads, proper sizing of conductors should be identified and the reasons
for such failures should be investigated, root cause be identified and suitable
long term action taken.
x High resistance points in the power circuit should be checked whenever
possible and if found each section starting from the upstream of the fuse up to
the motor terminal box should be checked sequentially.
. . he Control Circuit
The control circuit being similar to the nervous system of a human body, should be
engineered with due care to cover all aspects of motor control, not only in the normal
conditions but also to handle abnormal conditions / emergencies.
Motor Control 185
The circuit is normally powered by a separate electrical system (at a different voltage
level, say 110 V AC most commonly). Such a step down transformer (typically, 415 V /
110 V) is called a control transformer. The main advantage of this low voltage for the
control circuit is safety. The push buttons for start and stop of the motor is usually in the
field and the operation (non-electrical) personnel using them have very little
understanding about the hazards involved.
In the power circuit shown in Figure 8.1, all the components except the contactor are
static (no closing / opening operation) under normal operating condition. The contactor
transfers the electrical power from the incoming source to the motor based on the
requirement. Only during abnormal conditions, where the motor gets overloaded, does the
overload relay come into action. So the control of the contactor based on the requests /
commands received (and the safety conditions prevailing over the circuit), the contactor
needs to be either closed or opened. This becomes the essence of a control circuit’s basic
function.
Figure 8.1
pical tarter
The switching ON / OFF of the power contactor is linked up to the auxiliary relay, M.
If M gets ON, the contactor gets ON and the motor gets energized under normal operating
conditions. In the same way, the motor stops if M drops off.
The control circuit, through the overload relay’s auxiliary contact, monitors the most
important condition of the motor being not overloaded. In case of the overload being
sensed, M will drop instantaneously. The OFF push button’s NC (normally closed)
contact is monitored by the relay M.
An NC contact is specifically used to provide a “fail-safe” condition. It means that the
relay M cannot be closed, even when all other conditions are fulfilled, unless the OFF
186 Motor Protection, Control & Maintenance
push button’s integrity is established. This includes the push button wiring in the field and
the cable connecting the MCC and field. If, for some reason, the wiring is out of service -
may be due to a loose connection – M will not pickup. To clarify further, let us consider
the NO of the OFF push button is used for healthiness. The motor will be running in spite
of a wiring disconnection at the OFF push button. Under such conditions, the motor
cannot be stopped using the OFF push button. If a wiring problem exists before starting
the motor with NC logic, motor won’t start at all. The problem needs to be fixed prior to a
start and hence the motor can be stopped positively in case of need.
When everything else is in order, the motor gets started with the pressing of ON push
button, as the relay M picks up. However when the hand is removed from the push
button, M drops out. Hence, to keep the relay M in picked up condition, its own NO
contact is used in parallel with the push button contact. So, once the relay M picks up, the
ON push button gets bypassed thereby allowing the motor to continue without bypassing
any other interlock. This is called the latching contact of M.
Figure 8.2
e en for the co ponent of tarter
The various types of possible causes are indicated for a particular type of problem in
Table 8.1. The checks to be carried out and the remedial action to be taken are to be
correlated from Table 8.2.
One word of caution: continuity needs to be checked off-line only. Equivalent on-line
checking with the voltage supply not isolated, is by finding the voltage drop (in a series
circuit) one-by-one section.
Also please note that most of the recommended checks are suitable for off-line only. In
case of any doubt contact an experienced electrical engineer or the supplier / OEM.
From the above equation, it can be inferred that the starting torque just equals the full
load torque when the full load slip is 4 % and the starting current is 5 times that of the full
load current. Under such starting conditions, the motor must accelerate to normal speed as
quickly as possible. Otherwise, the motor winding may get overheated beyond tolerable
limits. Hence the load on the motor must be very light, to facilitate acceleration of the
motor, at the time of starting.
Since the currents drawn are huge, starting of large rating motors may not be supported
by the supply systems. Even if supported, staggering of the start of various motors has to
be planned meticulously.
Figure 8.3
pical connection of a re uce olta e tarter ith an
Motor Control 195
The following devices are commonly used in industry for reduced voltage starting.
Referring to the above, the characteristics of stator voltage control are as follows:
x Starting current inrush decreases as the square of the reduction in supply
voltage.
x Motor output torque decreases as the square of the reduction in supply
voltage.
x For reduced stator voltage, starting torque is always lower than DOL starting
torque.
x Reduced voltage starting is not suitable for applications that require a high
breakaway torque.
Figure 8.4
pical connection of a tar elta tarter
However this method of reduced voltage starting can be utilized only when the
reduction in voltage per phase and the resultant reduction in starting torque to one-third of
its full-voltage value will be able to accelerate in a reasonable time.
8.4.5. Autotransformer
Reduced voltage is obtained by connecting the autotransformer in Star as shown in
Figure 8.5.
Figure 8.5
pical connection of an utotran for er tart
Motor Control 197
If the voltage is reduced by a fraction x, the current drawn from the system becomes x2.
Also the starting torque reduces by the same factor. This method of starting is much
superior to that of stator impedance starting. Also a smooth starting and high acceleration
can be achieved by smoothly varying the voltage to the full line value.
x Reduces mechanical shock on the driven machinery, hence the name soft
starting
x Reduces the starting current surge in the electrical power supply system
x Reduces water hammer during starting and stopping in pumping systems
Usually this method of starting is applied for very large, frequently started machinery.
It is highly expensive but has a promising future because of the ever improving
electronics and their economic feasibility.
. . Bra ing
Motor braking refers to stopping a running motor. Removing the supply given to the
motor will make it stop. However, due to inertia, the motor will tend to rotate for some
time before halting. To stop the motor quickly, a braking mechanism is required. This is
called motor braking.
While operating electrical drives, it is often necessary to stop the motor quickly and to
reverse it. Particularly, in electrical hoist or crane applications, it is required to control the
torque of the drive motor so that the load does not have undesired acceleration. Some
applications require accurate positioning of motor shaft.
The speed and accuracy of stopping and reversing operations of motors improve the
productivity of the system. For example, take the rolling mill motor application. In such
applications, braking torque is required which may be either electrical or mechanical.
Braking can be broadly classified as:
x Electrical braking
x Mechanical braking
198 Motor Protection, Control & Maintenance
Equipment Equipment of higher rating Equipment like brake shoes, brake lining,
than the motor rating may and brake drum are required.
be required in certain
braking applications.
Table 8.4
Comparison of electrical and mechanical breaking
From the above comparison of electrical and mechanical braking, it is seen that
electrical braking is more effective and superior to mechanical braking. However, for
safety reasons, in hoist or crane applications a standby mechanical brake system is also
provided to avoid accidents in case of power failure. However, in case of severe operating
cycle of the motor, electrical braking should be employed only when it is highly desirable
to control retardation and limit the braking time.
Motor Control 199
II I
Braking Motor
Speed
C
Ia (b ) Ia(Td)
Ta Iast Current
or (Torque)
IV
III
Figure 8.6
egenerati e braking of ind ction motor
Motor Control 201
As the speed of the motor decreases, the braking torque makes the motor run at
constant speed and arrests its tendency to rotate faster. Due to the effects of stator
resistance, the maximum torque developed during regeneration is greater than the
maximum torque during motoring.
For example, in cranes and hoists, the motor has a tendency to run faster than the
synchronous speed. This situation occurs when the hoist is raising an empty cage. Due to
counter weight, the cage may acquire dangerous speeds. The transition takes place almost
automatically, a torque is developed to arrest the acceleration, and regeneration takes
place. Automatic regeneration arrests undue acceleration. In such cases, rotor resistance
control may be employed to get better braking torque.
Regenerative braking is also possible with a pole change motor when the speed is
changed from high to low. It can also be easily accomplished in variable frequency drives
by decreasing the frequency of the motor momentarily - the synchronous speed decreases
and conditions favorable to regeneration are created.
As the motor speed decreases, the frequency is continuously reduced so that braking
takes place at constant torque and stator current, until the motor comes to zero speed.
During regenerative braking, there is a possibility of dangerous speeds if the operating
point during braking falls in the unstable region of the characteristic. This happens if the
load torque is greater than the breakdown torque of the motor. The torque developed
cannot brake the motor and undue acceleration takes place. This possibility can be
eliminated by means of a high resistance in the rotor.
+
Re - +
Rt +
Vt C E V
-
+ -
D
-
Figure 8.7
namic braking of ind ction motor
The DC flowing through the stator sets up a stationary field. This induces rotor
currents that produce a torque to bring the rotor to rest quickly. The torque developed and
retardation during braking may be controlled by the amount of the DC power. Additional
resistances r1 and r2e in the stator and rotor circuits control the DC excitation and braking
torques respectively.
202 Motor Protection, Control & Maintenance
An equivalent circuit and phasor diagram of the motor during dynamic braking are
shown in figure 8.8.
3
Speed
r1
r2
B
-n1 T L2 C
Figure 8.8
i alent circ it and phasor diagram of the motor d ring d namic braking
When the stator is fed from DC, the MMF produced is stationary. The MMF depends
upon the stator connections for feeding DC, the number of turns and the current. The
possible connections of the stator for feeding DC are shown in figure 8.9.
Motor Control 203
F E F E
+
R R
GA HB
HB GA
-
Motoring Plugging
P M
R
GA
HB
Figure 8.9
tator connections for C d namic braking
+ +
Speed
V
- -
V - Varied
Smoothly
Tg = Tb Torque
Figure 8.10
Changing of phase se ence for co nter c rrent braking of a phase ind ction motor
F E
Figure 8.11
peed tor e c r e of an ind ction motor d ring pl gging
The braking torque developed prevents any acceleration of the rotor and the rotor
works at uniform speed as shown in figure 8.11.
The total braking torque (TP) may be controlled with a variable rotor resistance, which
limits the braking current.
Motor Control 205
8.8.3. Plugging
Braking of a synchronous motor by the plugging method has major disadvantages like
very heavy braking current flow causing line disturbances and ineffective torque.
Plugging can be used for braking if the motor is a synchronous induction motor and
only if the machine is working as an induction motor.
120 X Frequency
Synchronous Speed (rpm) =
No. of Pole pairs
206 Motor Protection, Control & Maintenance
For example, if the motor has two poles, then at 50 Hz frequency motor rpm will be
3000 rpm. With the same supply, a 4 pole motor will run art 1500 rpm.
However all the AC motors will not run at synchronous speeds. Only synchronous
motors run at these speeds. Induction motors run at speeds slightly lower than the
synchronous speed and hence are known as asynchronous motors. In any case the speed
will be either at or very close to the synchronous speeds and the approximate speed /
synchronous speed is dependent on the number of poles.
So if we can re-connect a (2*P) pole motor as a P pole motor, the speed of the motor
can be doubled. This method of changing the speed of a motor is known as pole changing
method and a typical wiring diagram is shown as Figure 8.12. However the motor needs
to be designed differently so that such changes can be carried out in the control circuit.
Figure 8.12
peed control b pole changing method
Motor Control 207
By varying the frequency of the supply, synchronous speed of these AC motors can be
varied.
In contrast to the mechanical and hydraulic variable speed control methods, electrical
variable speed drives are those in which the speed of the electric motor itself, rather than
an intermediary device, is controlled. Variable speed drives that control the speed of DC
motors are loosely called C ariable speed dri es or simply C dri es and those that
control the speed of AC motors are called C ariable speed dri es or simply C dri es.
Almost all electrical VSDs are designed for operation from the standard 3-phase AC
power supply system.
Historically, two of the best known electrical VSDs were the Schrage motor and the
Ward-Leonard system. Although these were both designed for operation from a 3-phase
AC power supply system, the former is an AC commutator motor while the latter uses a
DC generator and motor to effect speed control.
Ward-Leonard system
The Ward-Leonard system comprises a fixed speed 3-phase AC induction motor
driving a separately excited DC generator that, in turn, feeds a variable voltage to a shunt
wound DC motor. So this is essentially a DC variable speed drive.
Figure 8.13
he ard eonard s stem
DC drives have been used for variable speed applications for many decades and
historically, were the first choice for speed control applications requiring accurate speed
control, controllable torque, reliability and simplicity. The basic principle of a DC
variable speed drive is that the speed of a separately excited DC motor is directly
proportional to the voltage applied to the armature of the DC motor. The main changes
208 Motor Protection, Control & Maintenance
over the years have been concerned with the different methods of generating the variable
DC voltage from the 3-phase AC supply.
In the case of the Ward-Leonard system, the output voltage of the DC generator, which
is adjusted by controlling the field voltage, is used to control the speed of the DC motor
as shown in Figure 8.13. This type of variable speed drive had good speed and torque
characteristics and could achieve a speed range of 25:1. It was commonly used for winder
drives where torque control was important. It is no longer commonly used because of the
high cost of the three separate rotating machines. In addition, the system requires
considerable maintenance to keep the brushes and commutators of the two DC machines
in good condition.
In modern DC drives, the motor-generator set has been replaced by a thyristor
converter. The output DC voltage is controlled by adjusting the firing angle of the
thyristors connected in a bridge configuration connected directly to the AC power supply.
Figure 8.14
asic constr ction of a p lse C ariable speed dri e
Motor Control 209
AC/DC converters of this type are relatively simple and robust and can be built for
VSDs of up to several megaWatts with good control and performance characteristics.
Since the DC motor is relatively complex and expensive, the main disadvantage of this
type of VSD in comparison to an AC VSD, is the reliability of the DC motor. Although
the maintenance requirements of a DC motor are inherently higher than an AC induction
motor, provided that the correct brush grade is used for the speed and current rating, the
life of the commutator and brushgear can be quite long and maintenance minimal.
The fundamental principles of a DC variable speed drive, with a shunt wound DC
motor, are relatively easy to understand and are covered by a few simple equations as
follows:
x The armature voltage VA is the sum of the internal armature EMF VE and the
volt drop due to the armature current IA flow through the armature resistance
RA.
Armature Voltage A E A A
x The output torque of the motor is proportional to the product of the armature
current and the field flux.
Output Torque v A)
x The direction of the torque and direction of rotation of the DC motor can be
reversed either by changing the polarity of ), called field reversal, or by
changing the polarity of A, called armature current reversal. These can be
achieved by reversing the supply voltage connections to the field or to the
armature.
x The output power of the motor is proportional to the product of torque and
speed.
Output Power v n
From these equations, the following can be deduced about a DC motor drive:
x When the armature voltage A has reached the maximum output of the
converter, additional increases in speed can be achieved by reducing the field
flux. This is known as the field eakening range. In the field weakening
range, the speed range is usually limited to about 3:1, mainly to ensure
stability and continued good commutation.
x The motor is able to develop its full torque over the normal speed range. Since
torque is not dependent on A, the full-load torque output is possible over the
normal speed range, even at standstill (zero speed).
x The output power is zero at zero speed. In the normal speed range and at
constant torque, the output power increases in proportion to the speed.
x In the field weakening range, the motor torque falls in proportion to the speed.
Consequently, the output power of the DC motor remains constant.
Figure 8.15
or e and po er of a C dri e o er the speed range
Although a DC machine is well suited for adjustable speed drive applications, there are
some limitations due to the mechanical commutator and brushes, which:
x Impose restrictions on the ambient conditions, such as temperature and
humidity
x Are subject to wear and require periodic maintenance
x Limit the maximum power and speed of machines that can be built
Motor Control 211
Figure 8.16
ain components of ario s t pes of ariable speed dri e
a ard eonard s stem
b h ristor controlled C dri e
c oltage so rce in erter C dri e
d oltage so rce C dri e
Frequency control, as a method of changing the speed of AC motors, has been a well-
known technique for decades, but it has only recently become a technically viable and
economical method of variable speed drive control. In the past, DC motors were used in
most variable speed drive applications in spite of the complexity, high cost and high
maintenance requirements of the DC motors. Even today, DC drives are still often used
for the more demanding variable speed drive applications. Examples of this are the
sectional drives for paper machines, which require fast dynamic response and separate
control of speed and torque.
Motor Control 213
Developments in power electronics over the last 10 to 15 years has made it possible to
control not only the speed of AC induction motors but also the torque. Modern AC
variable speed drives, with fl ector control can now meet all the performance
requirements of even the most demanding applications.
In comparison to DC drives, AC drives have become a more cost effective method of
speed control for most variable speed drive applications up to 1000 kW. It is also the
technically preferred solution for many industrial environments where reliability and low
maintenance associated with the AC squirrel cage induction motor are important.
The fundamental principles of an AC variable speed drive are relatively easy to
understand and are covered by a few simple equations as follows:
x The speed (n) of the motor can be controlled either by adjusting the supply
frequency (f) or the number of poles (p). In an AC induction motor, the
synchronous speed, which is the speed at which the stator field rotates, is
governed by the simple formula:
120 f
Synchronous Speed, nS rev/min
p
Although there are special designs of induction motors, whose speed can be changed in
one or more steps by changing the number of poles, it is impractical to continuously vary
the number of poles to effect smooth speed control. Consequently, the fundamental
principle of modern AC variable speed drives is that the speed of a fixed pole AC
induction motor is proportional to the fre enc of the AC voltage connected to it.
In practice, the actual speed of the rotor shaft is slower than the synchronous speed of
the rotating stator field, due to the slip between the stator field and the rotor.
The slip between the synchronous rotating field and the rotor depends on a number of
factors, being the stator voltage, the rotor current and the mechanical load on the shaft.
Consequently, the speed of an AC induction motor can also be adjusted by controlling the
slip of the rotor relative to the stator field.
Unlike a shunt wound DC motor, the stator field flux in an induction motor is also
derived from the supply voltage and the flux density in the air gap will be affected by
changes in the frequency of the supply voltage. The air-gap flux ()) of an AC induction
motor is directly proportional to the magnitude of the supply voltage ( ) and inversely
proportional to the frequency (f).
Air-gap Flux, ) v
f
214 Motor Protection, Control & Maintenance
To maintain a constant field flux density in the metal parts during speed control, the
stator voltage must be adjusted in proportion to the frequency. If the flux density is
allowed to rise too high, saturation of the iron parts of the motor will result in high
excitation currents, which will cause excessive losses and heating. If the flux density is
allowed to fall too low, the output torque will drop and affect the performance of the AC
Drive. Air-gap flux density is dependent on both the frequency and the magnitude of the
supply voltage.
So the speed control of AC motors is complicated by the fact that both voltage and
frequency need to be controlled simultaneously, hence the name variable voltage, variable
frequency (VVVF) converter.
x In a way similar to the DC motor, the output torque of the AC motor depends
on the product of the air-gap flux density and the rotor current R. So, to
maintain constant motor output torque, the flux density must be kept constant
which means that the ratio V/f must be kept constant.
Output Torque, v ) R Nm
x The direction of rotation of the AC motor can be reversed by changing the
firing sequence power electronic valves of the inverter stage. This is simply
done through the electronic control circuit.
x Output power of the AC motor is proportional to the product of torque and
speed.
Output Power, v n kW
Figure 8.17
ain components of a t pical t pe C dri e
Motor Control 215
The mains AC supply voltage is converted into a DC voltage and current through a
rectifier. The DC voltage and current are filtered to smooth out the peaks before being fed
into an inverter, where they are converted into a variable AC voltage and frequency. The
output voltage is controlled so that the ratio between voltage and frequency remains
constant to avoid over-fluxing the motor. The AC motor is able to provide its rated torque
over the speed range up to 50 Hz without a significant increase in losses.
The motor can be run at speeds above rated frequency, but with reduced output torque.
Torque is reduced as a result of the reduction in the air-gap flux, which depends on the
/f ratio. The locus of the induction motor torque–speed curves are at various frequencies
are shown in the figure below. At frequencies below 50 Hz, a constant tor e output from
the motor is possible. At frequencies above the base frequency of 50 Hz, torque is
reduced in proportion to the reduction in speed.
Figure 8.18
oc s of the motor tor e speed c r es at ario s fre encies
One of the main advantages of this VVVF speed control system is that, whilst the
controls are necessarily complex, the motors themselves can be of squirrel cage
construction, which is probably the most robust and maintenance free form of electric
motor yet devised. This is particularly useful where the motors are mounted in hazardous
locations or in an inaccessible position, making routine cleaning and maintenance
difficult. Where a machine needs to be built into a flame-proof or even water-proof
enclosure, this can be done more cheaply with a squirrel cage AC induction motor than
for a DC motor.
On the other hand, an additional problem with standard AC squirrel cage motors, when
used for variable speed applications, is that they are cooled by means of a shaft mounted
fan. At low speeds, cooling is reduced, which affects the loadabilit of the drive. The
continuous output torque of the drive must be derated for lower speeds, unless a
separately powered auxiliary fan is used to cool the motor. This is similar to the cooling
requirements of DC motors, which require a separately powered auxiliary cooling fan.
216 Motor Protection, Control & Maintenance
From the equations above, the following deductions can be made about an AC drive:
x The speed of an AC induction motor can be controlled by adjusting the
frequency and magnitude of the stator voltage. Motor speed is proportional to
frequency, but the voltage must be simultaneously adjusted to avoid over-
fluxing the motor.
x The AC motor is able to develop its full torque over the normal speed range,
provided that the flux is held constant, (V/f ratio kept constant). A standard
AC motor reaches its rated speed, when the frequency has been increased to
rated frequency (50 Hz) and stator voltage V has reached its rated magnitude.
x The speed of an AC induction motor can be increased above its nominal 50
Hz rating, but the V/f ratio will fall because the stator voltage cannot be
increased any further. This results in a fall of the air-gap flux and a reduction
in output torque. As with the DC motor, this is known as the field weakening
range. The performance of the AC motor in the field weakening range is
similar to that of the DC motor and is characterized by constant power,
reduced torque.
x The output power is zero at zero speed. In the normal speed range and at
constant torque, the output power increases in proportion to the speed.
x In the field weakening range, the motor torque falls in proportion to the speed
and the output power of the AC motor remains constant.
Figure 8.19
or e and po er of an C dri e o er the speed range
Motor Control 217
x Stator voltage: Affects both the flux and the rotor current.
x Rotor current: For a SCIM, this depends on the rotor design. For a WRIM,
this depends on the external rotor connections
Output Torque v ĭ R Nm
Since both ) and R decrease with the voltage, the output torque of the motor falls
roughly as the square of the voltage reduction. So when voltage is reduced, torque
decreases, slip increases and speed decreases. The characteristic curves in Figure 8.20
show the relationship between torque and speed for various values of the supply voltage.
218 Motor Protection, Control & Maintenance
Figure 8.20:
or e speed c r es of an ind ction motor ith red ced s ppl oltage
1 o le el of s ppl oltage
4 igh le el of s ppl oltage
5 ll rated s ppl oltage
From this figure, the speed stabilizes at the point where the motor torque curve, for that
voltage, intersects with the load–torque curve. The application of this technique for speed
control is very limited because the resulting speed is dependent on the mechanical load
torque. Consequently, speed holding is poor unless speed feedback is used, for example
by installing a shaft encoder or tachometer on the motor.
Figure 8.21
or e speed c r es of a ith e ternal rotor resistance
1 igh e ternal rotor resistance connected
6 o e ternal rotor resistance connected
ormal rotor resistance
As with stator voltage control, this method of speed control has a number of
limitations. The speed holding capability, for changes in mechanical load, is poor. Again,
this method of control is more often used to control starting torque rather than for speed
control. In contrast to stator voltage control, which has low starting torque, rotor c rrent
control can provide a high starting torque with the added advantage of soft starting.
The following devices are commonly used in industry for rotor current control:
x Air-cooled resistor banks with bypass contactors
x Oil-cooled resistor banks with bypass contactors
x Liquid resistor starters with controlled depth electrodes
x Thyristor converters for rotor current control and slip energy recovery
Figure 8.22
pical connections of a ith rotor resistance starter
When the rotor current is controlled by external rotor resistors, a considerable amount
of heat, known as the slip energy, needs to be dissipated in the resistor banks. In practice,
rotor resistors are used for starting large induction motors and to accelerate heavy
mechanical loads up to full speed. At full speed, the resistors are bypassed by means of
contactors and the motor runs with a shorted rotor. Consequently, these losses occur for
relatively short periods of time and are not considered to be of major significance.
However, when rotor resistors are used for speed control over an extended period of
time, the energy losses can be high and the overall efficiency of the drive low. At
constant output torque, the energy losses in the resistors are directly proportional to the
slip. So as the speed is decreased, the efficiency decreases in direct proportion. For
example, a WRIM running at 70% of rated speed at full load will need to dissipate
roughly 30% of its rated power in the rotor resistors.
8.23. The rotor current is controlled by adjusting the firing angle of the rectifier bridge.
With the rectifier bridge turned off, the rotor current is zero and with the thyristor bridge
full on, the rotor current approaches the rated current. The rectifier bridge can be
controlled to provide any current between these outer limits. Instead of dumping the slip
energy into a resistor, it is smoothed through a large choke and converted back into 3-
phase AC currents, which are pumped back into the mains at 50 Hz through a matching
transformer. The thyristors of the rectifier bridge are commutated by the rotor voltage,
while the thyristors of the inverter bridge are commutated by the supply voltage. The DC
link allows the two sides of the converter to run at different frequencies. The tacho is used
for speed feedback to improve the speed holding capability of this variable speed drive.
Using SER technique, the slip energy losses can be recovered and returned to the
power supply system, thus improving the efficiency of the drive.
Figure 8.23
he main components of a slip energ reco er s stem
Some interesting aspects of the slip energy recovery system are as follows:
x The rotor connected SER converter need only be rated for the slip energy,
which depends on the required speed range. For example, for a speed range of
80% to 100% of rated motor speed, the SER converter should be rated at
roughly 20% of motor power rating. If the speed range needs to be broadened
to 70% to 100%, the rating of the SER converter needs to be increased to
roughly 30% of motor power rating. In contrast, stator connected VVVF
converters, commonly used for the speed control of squirrel cage induction
motors, need to be rated for >100% of the motor power rating.
x Because the SER converter rating is lower than motor rating, the slip power at
starting would exceed the rating of the converter. It has become common
practice to use an additional rotor resistance starter, selected by contactors
from the control circuit, for the starting period from standstill. These resistors
can be air-cooled, oil-cooled or the liquid type. Once the WRIM motor has
been accelerated up to the variable speed range, the SER converter is
connected and the resistors disconnected. These resistors have the added
222 Motor Protection, Control & Maintenance
The slip energy recovery system is most often used by large water supply authorities
for soft starting and limited speed control of large centrifugal pumps, typically 1 MW to
10 MW. In these applications, they are a more cost effective solution than the equivalent
stator connected AC or DC drives. Another increasingly common application is the
starting and limited speed control (70% to 100%) of large SAG mills in mineral
processing plants, typically 1 MW to 5 MW.
8.11. Cycloconverters
A cycloconverter is a converter that synthesizes a 3-phase AC variable frequency
output directly from a fixed frequency 3-phase AC supply, without going via a DC link.
The cycloconverter is not new and the idea was developed over 50 years ago using
mercury arc rectifiers.
Figure 8.24
he main components of a c clocon erter
The low frequency AC waveform is produced using two back-to-back thyristors per
phase, which are allowed to conduct alternatively. By suitable phase angle control, the
output voltage and load current can be made to change in magnitude and polarity in cyclic
fashion. The main limitation of the cycloconverter is that it cannot generate frequencies
higher than the AC supply frequency. In fact, a frequency of about 30% of the supply
Motor Control 223
frequency is the highest practically possible with reasonable waveforms. The lower the
frequency, the better the waveform. The system is inherently capable of regeneration
back into the mains.
The cycloconverter requires a large number of thyristors, and the control circuitry is
relatively complex but, with the advent of microprocessors and digital electronics, the
implementation of the control circuits has become more manageable.
Because of the low frequency output, cycloconverters are suited mainly for large slow
speed drives, where it is used to drive either a large induction motor or a synchronous
motor. Typical applications are SAG or ball mills, rotary cement kilns, large crushers,
mine-winders, etc.
8.12. Servo-drives
er o dri es are used in those drive applications which require a high level of
precision, usually at relatively low powers. This often includes rapid stop-start cycles,
very high acceleration torques, accurate positioning with controllable velocity and torque
profiles.
The use of servo-drives for industrial manufacturing and materials handling has also
become far more common, particularly for accurate positioning systems. This type of
drive differs from a normal open loop VVVF drive in the following respects:
x Accuracy and precision of the motor speed and torque output are far in excess
of what is normally possible with AC induction motors
x A servo-motor is usually designed to operate with a specific servo-converter
x Response of the servo-drive system to speed change demand is extremely fast
x Servo-drives provide full torque holding at zero speed
x Servo-drive inertia is usually very low to provide rapid response rates
Servo-drives are beyond the scope of this book and will not be covered here.
In figure 8.26, reversing connections of a 3-Phase induction motor with star delta
starter are shown. The phases L1 & L2 have been interchanged.
Forward Reverse
A B C Motor A B C
A B C A B C
Starter
L1 L2 L3 L1 L2 L3
Figure 8.25
e ersing a three phase motor
Motor Control 225
Reverse
Forward
A1 B1 C1 Motor A1 B1 C1
A2 B2 C2 A2 B2 C2
A1 B1 C1 Starter A1 B1 C1
A2 B2 C2 A2 B2 C2
L1 L2 L3 L1 L2 L3
Figure 8.26
e ersing a star delta motor
226 Motor Protection, Control & Maintenance
9
9.1. Introduction
Selection of an AC Variable Speed Drive, also known as Variable Voltage Variable
Frequency (VVVF) Electrical Drive, has become the natural choice of the modern day
drive designer for any variable speed application. The main driving force behind this
selection process is the Squirrel Cage Induction Motor (SCIM) that can be used as the
prime mover. This because a SCIM is the most cost effective motor that can be designed
for any kind of environment. The advent of IGBTs and the tremendous growth in the
quality of AC power electronic components & great strides in the development of high
power micro controllers have fuelled this paradigm shift. The booming market for AC
Variable Frequency Drives serves as a testimony to this. However there are certain
associated complexities that are to be properly addressed while selecting the components
and engineering the systems, otherwise the benefits will not accrue to the end user as
envisaged. This needs an understanding about the basic control system, various types of
controls and components of such a system.
Any VSD consists of three principal elements:
1. The drive controller is the brain that converts the fixed voltage and frequency of
the AC power into an adjustable power output to control the drive motor over a
wide speed range. It includes sensing circuits to hold or regulate the motor at the
desired speed with variations in the source voltage and changes in motor load. It
also includes protective circuitry and devices to prevent damage from overloads,
power source transients and output power faults. It forms a major part of the
overall control system.
228 Motor Protection, Control & Maintenance
2. The drive motor is the muscle that translates electrical energy into mechanical
motion. The output is a shaft rotation, which varies in proportion to the power
enabled by the drive controller. The motor shaft is normally coupled to a gear
reducer or other mechanical power transmission device to further reduce the
motor speed to a level useable by the driven machine.
3. The operator control is the interface meant for integrating the drive with its
operational control system like DCS – Digital Control System, meant for process
control employing distributed digital controls. It sets the reference for the speed
of the drive at which the process requirement is felt.
Figure 9.1
ain components of an C ariable speed dri e
With the rapid advances in digital electronics over the last decade, modern VSD
control systems are able to utilize one or more microprocessors to realize various
functionalities very effectively.
The control systems are designed to achieve the following main objectives:
x High level of eliabilit
x High in erter performance to ensure that the output current waveform
provides sufficient motor torque, at selected speed, with minimum of motor
losses
x inimi ed n erter losses
x Possibility to integrate the control s stem into the o erall process control
s stem with facilities for external control and communications interfaces
x High tolerance to po er s ppl fl ct ations and
Table 9.1
eneral re irements for po er in a ariable speed dri e
The simplest method of providing auxiliary power to the converter control circuits is
from an auxiliary transformer connected to the mains. Multiple secondary windings are
necessary to provide isolation for the control circuits and the device drivers.
The major problem with this approach arises when there is an interruption of the mains
power. Control of the inverter is lost and the VSD has to be stopped, even for short dips
in the supply. In many drive applications, there is a requirement for VSDs to 'ride
thro gh' voltage dips of short duration.
Consequently, most modern AC converters use itched ode o er pplies
(SMPS), fed directly from the DC Link, to provide the auxiliary power to the control
system. These are essentially DC-DC converters. The main advantage of this approach
is that control power can be maintained right up to the time that the motor stops,
irrespective of the condition of the mains supply. When the mains power fails, auxiliary
power is maintained initially from the large capacitors connected across the DC Link and
later from the inertia of the motor itself. When mains power is interrupted, most AC
converters are programmed to reduce frequency and retrieve (regenerate) power from the
motor, which behaves as an AC induction generator when the frequency is reduced.
There are many types of switched mode power supplies, including fl back converters,
for ard converters and bridge converters. They can be isolated or non-isolated and have
single or multiple outputs. Since they operate at high frequency (10 kHz to 100 kHz),
they are physically much smaller than conventional mains frequency transformer based
power supplies and despite the added complexity of SMPSs, they are of comparable cost.
Due to the modular nature of modern drives, it is common to have multiple auxiliary
power supplies, each of which is dedicated to a single module of the VSD, such as the
control module, the pulse amplifier driver stage, the cooling fans, etc. These different
SMPSs may operate independently from the DC Link or from a central SMPS that
converts the DC Link voltage to a single isolated low voltage supply, such as 24 VDC.
Each module may then take its power requirements from this 24 VDC power supply.
As shown in Table 9.1, the e ice ri er o er pplies need to be provided with 4
or 6 isolated power outputs. These need to be isolated because the three power electronic
switches connected to the Positive terminal of the DC Link have their Emitter (IGBT &
BJT), Source (MOSFET) or Cathode (GTO) terminals connected to the output phases to
the motor. This terminal is the reference terminal for the driver stage, while the Base or
Gate terminal must be driven positi e to t rn on or negati e to t rn off. The power
Control Systems for AC Variable Speed Drives 231
supply reference point for each of these three devices is at a different potential, therefore
requiring isolation.
The three power electronic switches connected to the Negative terminal of the DC Link
all have their Emitter, Source or Cathode terminals connected to the Negative bus, and so
a single power supply could be used for all three device driver circuits. This explains why
a minimum of 4 isolated power supplies shown in the table. However, it is more common
to use 6 identical power supplies to operate the device driver stages, as there are benefits
in terms of modularity and commonality of wiring.
There are two main methods for deriving these device driver power supplies. The first
is to provide the six isolated supplies from either a mains frequency transformer or a
SMPS, in the same way all other control power is produced. An alternative is to provide
a single high frequency square wave supply, which is coupled directly into the six driver
circuits through dedicated high frequency (usually toroidal) transformers that are part of
each driver circuit. Separate rectifier and regulation circuits then provide the necessary
plus and minus supplies for each driver stage.
The cooling fans for the converter heat sinks can be powered from the SMPS or
directly from the mains, whichever is a cheaper solution. The major drawback of the
mains supply is the inability to deal with the different mains voltages and frequencies
which are found throughout the world. This can usually be solved by supplying the fan
through an auxiliary transformer with several primary connections to match the most
common voltage options.
The first method is the most common method, an example of which is shown in Figure
9.2. Charging resistors are inserted between the input supply and the capacitor bank to
limit the current when power is first applied. Once the capacitors are charged, these
resistors would introduce additional losses in the VSD and therefore need to be bypassed
232 Motor Protection, Control & Maintenance
during normal operation. A relay (small VSDs) or contactor (large VSDs) is used to
bypass the charging resistors and carry the full rated current of the drive.
The control of the relay may be either via a simple timer circuit with a fixed time delay
between power being applied and the inverter stage being enabled. A better method is to
monitor the DC bus voltage and the bypass relay is closed after a certain voltage level has
been attained. In the better quality VSDs, feedback may be provided from each of the
power supplies in the central controller to verify their status.
Figure 9.2
ample of a C b s pre charging circ it
Some form of interlock needs to be provided to ensure that the relay is closed before
allowing the inverter stage to operate. If not, the high load current through the VSD will
heat up and burn out the charging resistors. In addition, it is critical that all power
supplies have had the opportunity to stabilize and establish regulation. As a result, most
VSDs have a start p lock o t circuit that delay starting for a short period after the VSD
is powered up.
There are many variations on this theme, for example, the resistors and relay can be
either in the DC link or the 3-phase supply lines. There may be a single set of large
resistors and one large relay or there may be multiple sets of smaller resistors and relays.
Other variations of this technique include the use of semi-conductor bypass switches.
The main ad antages of this method are:
x Simplicity of the control circuit
x Cheap and easy to implement
The second, less common, approach is to replace the normal diode rectifier with a
phase- controlled rectifier bridge. This allows the capacitor voltage to be increased
gradually, by controlling the firing angle, and thereby controlling the inrush current. This
method is most often used on VSDs with larger power ratings above about 22kW.
The main ad antages of this method are:
x Conduction losses are lower
x Physical size is reduced by not having the relay
Figure 9.3
C b s charging sing a phase controlled th ristor bridge
The type of control used in VSD control systems follows an approach similar to that
used in normal industrial process control The level of control can be:
x imple pen oop Control with no feedback from the process
x Closed oop Control with feedback of a process variable
x Cascade Closed oop Control with feedback from more than one variable
Figure 9.4
chematic of a closed loop control s stem
The desired value of the load, such as the speed, can be set manually by an operator
turning a potentiometer (analog system) or by dialling up a value on a keypad (digital
system). If the VSD is part of a complex control system, the desired value can be passed
down from the rocess Control stem C or C , either by means of a 4-20mA
signal (analog system) or by means of a serial data link (digital system).
If each quantity in the control loop was directly proportional to the quantity before it,
simple open-loop control of speed would be adequate, without the need for feedback of
the Process Variable (PV). In AC drives, if accurate speed control is required, then
feedback of the torque and speed variables is necessary. In particular, the motor current
responds to an increase in motor frequency with a rise time dependent on its leakage
inductance. On the other hand, the motor speed follows the torque with a rise time
dependent on its inertia. While these inaccuracies may be acceptable in simple
applications, such as pump speed control, it may not be acceptable for other difficult
applications, such as the variable speed drives in a paper machine, where several drives
operate in tandem. In these difficult applications, improved performance can be obtained
with the use of several closed-loop control systems working together, known as multi-
loop or cascade control.
This type of closed-loop control system has been redrawn in figure 9.5 to emphasize
the most important control aspects. The term closed loop feedback control emphasizes
the nature of the control system, where feedback is provided from the output back to the
input of the controller.
236 Motor Protection, Control & Maintenance
Figure 9.5
closed loop feedback control s stem
Figure 9.5 could be misleading because, in practice, the error point is usually part of the
controller.
A Vector Control Drive uses a similar strategy. In the design of the or e Control
oop, it is assumed that the rate of change of c rrent is m ch faster than the rate of
change of speed This is equivalent to assuming that the motor is running at a constant
speed. Consequently, the Current Loop only has to allow for the time delay between the
output frequency and the current. As well as giving the desired inverter output frequency,
it also gives the desired inverter voltage since the two are related. Both quantities are
passed to the PWM switching logic, which controls the inverter switching sequence and
speeds (see Figure 9.6).
The C rrent Control oop compensates for the electrical transients, mainly the
winding inductance and resistance.
The block diagram of the cascaded loop controller comprises:
x An outer (major) Speed Control Loop
x An inner (minor) Torque Control Loop
Figure 9.6
Cascade controller for speed and tor e
Figure 9.7
esponse of and controllers to a step inp t
a tep inp t control change
b roportional Controller tp t
c roportional ntegral Controller tp t
feedback in the cascaded closed loop controller. Both these currents can readily be
measured and accounts for the simple control of the DC Drive.
In an C nd ction otor (refer to equivalent circuit in Figure 9.8), the flux producing
current (IM) and torque producing current (IR) are "inside" the motor and cannot be
measured externally or controlled separately. As in the DC drive, these two currents are
also roughly at 90o to one another and their vector sum makes up the tator C rrent
which can be measured (Figure 9.9). This is what makes the vector control of an AC
motor more difficult than its DC counterpart. The challenge for the AC Flux-Vector
drive is to distinguish and control these two current vectors without the benefit of two
separate circuits and only being able to measure and control the stator current.
The strategy of an AC Vector Control drive is to calc late the indi id al c rrent
ectors to eventually enable separate control of the flux current and/or the torque current
under all speed & load conditions. As in the DC drive, the aim is to maintain a constant
flux current in the motor.
The calculation of the current vectors involves the measurement of the available
variables (such as the stator current (IS), stator voltage (VS), phase relationship,
frequency, shaft speed, etc) and applying them to a "Motor Model", which includes the
motor constants (such as the stator resistance & inductance, the rotor resistance &
inductance, the magnetizing inductance, number of poles, etc). Because of the many
variables, there are many possible applications of a motor model, from simple estimation
of motor conditions to those which are very comprehensive and very accurate. The more
detailed the motor model, the more processing power is required.
Figure 9.8
implified e i alent circ it of an C ind ction motor
Under motor no load conditions almost all the no-load stator current IS comprises the
magnetising current. Any torque-producing current is only required to overcome the
windage and friction losses in the motor. Slip is almost zero, stator current lags the
voltage by 90o, so power factor is close to zero (CosI = 0).
At lo motor loads the stator current IS is the ector s m of the magnetizing current IM
(unchanged), with a slightly increased active torque-producing current. Stator current
lags the voltage by a large angle I, so power factor is poor (CosI << 1). Slip is still
small.
At high motor loads the stator current IS is the ector s m of the magnetising current
IM (unchanged), with a greatly increased active torque-producing current, which increases
240 Motor Protection, Control & Maintenance
in proportion to the increase in load torque. Stator current lags the voltage by an angle I,
so the power factor has improved to be close to the full load power factor (CosI = 0.85).
Figure 9.9
C rrent ectors in an C ind ction motor
Therefore, the central part of the vector control system is the cti e otor odel
which continuously models the conditions inside the motor. It does the following:
x Continuously calculates in real time the Torque-producing current by
implementing the following activities:
Stores the motor constants in memory to be used as part of the
calculation
Measures stator current and voltage in each phase
Measures speed (with encoder) or calculates speed (no encoder)
For adequate dynamic response of the drive, the model calculations need to be done at
least more than 2,000 times per second, which gives an update time of less than 0.5 ms.
Although this is easily achieved with modern high speed processors, the ability to
continuously model the induction motor at this speed only became viable within the last
10 years or so with the development of 16-bit microprocessors. Initially, sufficient
processing power for Vector control was quite expensive, but over a period of time, the
cost of the processors has come down and processing speed has increased significantly.
The main difference between a traditional fixed V/f ratio VVVF Converter and a
modern Vector Control drive is almost entirely in the control system and the extent to
Control Systems for AC Variable Speed Drives 241
which the Active Motor Model for Vector control is implemented to control the switching
pattern of the IGBTs of the Inverter.
The power circuit for a Vector converter is almost identical to that used by a VVVF
drive:
x ectifier to convert 3-phase AC to a DC Voltage
x nd cti e choke to reduce harmonics on the supply side
x C link with capacitor filter to provide a smooth and steady DC voltage
xA semicond ctor in erter bridge to convert the DC to a PWM variable
voltage variable frequency output suitable for an AC induction motor
x A microprocessor based digital control circ it to control the switching,
provide protection and provide a user interface
x The base voltage and base frequency used for this ratio are taken from the
motor nameplate
x Finally, the signal passes to the PWM Switching Logic module, that controls
the switching pattern of the IGBT switches to provide the voltage pattern at
the output terminals according to the PWM algorithm (sine-coded, etc)
x There is usually no speed feedback from the motor. It is ass med that the
motor is responding to and following the output frequency (open-loop control)
x The current feedback from the current transducer is there mainly for
protection, indication and to set a current limit. It is not used as part of the
control strategy
It is necessary to monitor the stator current flowing to the motor. The drive usually
monitors total current and cannot distinguish between Im and Ir.
Figure 9.10
lock control diagram of fi ed f dri e
This current is not used to control torque, but is aimed at the following functions:
x Measures actual current for the I2t overload protection of the motor
x Provides protection of the power electronic components
x Provides a C rrent imit The control system reduces the frequency command
signal when the current exceeds a predetermined value. Usually, current limit
is set to 150% of the rated motor current
x Some newer V/f drives provide lip Compensation as a strategy for improving
the speed holding capability in an attempt to maintain relatively constant
motor speed even with changes in the motor load torque. As the output torque
increases, the motor current increases, which can be used to adjust the output
frequency of the converter. For example, at full rated load, the full slip value
can be added to the output frequency. With slip compensation, improved
speed regulation can be obtained from an induction motor without a speed
feedback device
This method of open loop fixed V/f control is adequate for controlling steady-state
conditions and simple applications, such as pumps, fans and conveyors, which allow a lot
Control Systems for AC Variable Speed Drives 243
of time for speed changes from one level to another and where the consequences of the
changes in the process are not severe.
This type of drive is not well suited to the following:
x Applications where motors run at low speeds (below 5Hz). The torque at low
speed is generally poor because the stator volt drop significantly affects the
magnitude of the flux-producing current. Many V/f drives include a "Start
Boost" when allows the V/f ratio to be boosted at starting in an attempt to
improve the flux and consequently the starting torque
x Applications which require higher dynamic performance
x Applications that require direct control of motor torque rather than motor
frequency
x The dynamic performance of this type of drive with shock loads is poor
The result is a greatly improved torque, particularly at low speeds, to provide high
breakaway and acceleration torque and an improved dynamic response to shock loads.
However, this type of drive does not provide torque control, it is still a only speed control
device. In addition, speed holding capability is substantially improved.
This type of drive can also be operated with an encoder, providing closed loop control
of the speed. This substantially improves the speed holding capability of the VS drive
with speed regulation of 0.1%.
244 Motor Protection, Control & Maintenance
Figure 9.11
lock diagram of the fl ector con erter control circ it
Table 9.2
When setting up high performance VSD controllers, a modest roportional gain gives
a good transient response, while the ntegral gain gives high steady state accuracy. PI-
controllers have the advantage that they can maintain a non-zero output to drive the
converter although their input is zero. This is an advantage in closed-loop control
because high accuracy should lead to zero error at the controller input.
Suitable values of P and I determine the step and ramp parts of the response
respectively and have to be calculated for each Inverter-Motor-Load combination.
x The al es of and for the speed loop are dependent on the motor flux, load
friction and inertia as they influence the response of speed to current
x The al es of and for the c rrent loop depend on the inverter gain, motor
resistance and leakage inductance, since they influence the response of current
to the motor frequency
In modern digital drives, the P and I values for both current and speed loops can be set
by keypad or, alternatively, most modern digital drives usually include an algorithm for
self t ning. This removes the difficulties of 'tuning the loops', which was traditionally
necessary with older analog DC Drives. The P and I gains of the speed loop can be set up
during commissioning to meet application requirements and seldom need to be changed.
There are a number of disadvantages of the Vector controlled AC drive, when
compared to a DC Drive:
x The Vector controller is far more complex and expensive when compared to
the simple cascade controller of a DC Drive
x Encoder speed feedback is usually necessary to obtain accurate feedback of
the motor shaft speed. Fitting these encoders to a standard squirrel cage AC
induction motor is often difficult and makes the motor more expensive. In
recent years, 'Sensorless' Vector Control has been developed where an
encoder is not required. The approximate speed is calculated by the processor
from the other available information, such as voltage and current. However,
the speed accuracy and dynamic response of these drives is inferior to those
using encoders
x The nature of the drive itself often requires the AC motor to operate at high
torque loadings at low speeds. The standard squirrel cage AC induction
motor then requires a separately powered cooling fan, installed at the ND end
of the motor
x Regenerative braking is more difficult with a Vector drive than with a DC
drive. Resistive type d namic braking systems are most often used with AC
Vector control drives
Control Systems for AC Variable Speed Drives 247
Several methods have been developed over the years to measure the current and
convert it into an electronic form suitable for the drive controller. The method chosen
depends on the required accuracy of measurement and the cost of implementation. The
main methods of measurement are as follows:
x C rrent h nt where the current is passed through a link of pre-calibrated
resistance. The voltage measured across the link is directly proportional to
the current passing through it. This method was often used in drives with
analog control circuits
x all ffect ensor where the output is a DC voltage, which is directly
proportional to the current flowing through the sensor. High accuracy and
stability over a wide current and frequency range are amongst the main
advantages of this device. This device is commonly used with modern digital
control circuits
The performance of a normal core type current transformer is usually not adequate for
power electronic applications because its performance at low frequencies is poor and
accuracy of measurement of non-sinusoidal waveforms is inadequate. The main methods
of current measurement are described in detail in Appendix B.
that some action is taken to stop the current exceeding the desired limit point. This action
may be only indirectly related to current, such as a change in frequency or voltage.
A third need for current feedback is to provide a current signal roughly proportional to
load. This signal may be used internally by the drive to optimize motor Volts/Hertz or
provide slip compensation, where the frequency is increased slightly as load increases to
improve speed regulation. The signal may also be made available for external use by the
user as a load indication signal. As outlined earlier in this chapter, the stator current of
the motor is only roughly proportional to the mechanical load, since the stator current is
the vector sum of the magnetising current IM and the torque-producing current IR.
Motor current feedback can also be used to provide thermal protection of the motor.
This requires a thermal model of the motor to be implemented in the drive control system,
using frequency and current feedback and motor parameters to estimate the internal
temperature of the motor, using an I2t replica in the converter. If current level exceeds a
set point for a period of time, the motor protection will trip the drive and give an
indication of a motor thermal overload.
For example, consider an application where a 22kW motor would take 10secs to
accelerate a high inertia load at 150% rated torque and current. If the operator sets the
acceleration time to 5 seconds, this would require 300% rated torque and around 500%
current to accelerate the load. Clearly, a drive rated at 150% current overload will not be
able to achieve the desired acceleration time. In this situation, a modern, well-designed
VSD will not trip, but will modify its acceleration time to maintain the DC Bus current at
the current limit point. While the operator may not have been able to achieve the desired
acceleration time, this is clearly preferable to the drive tripping on over current every time
it starts.
Analog speed transducers are increasingly being replaced by digital devices, which are
more compatible with modern digital control systems.
The main methods of speed measurement are described in detail in Appendix C.
250 Motor Protection, Control & Maintenance
10
Figure 10.1
pical temperat re de rating chart for Con erter
Figure 10.2
ltit de de rating chart for t pe con erter Compliments of llen radle
Figure 10.3
o er s ppl motor and earthing connections
It should be borne in mind that the AC converter VSD provides short-circuit and
overload protection for the cable and motor.
A separate earth cond ctor between the converter and motor is recommended for both
safety and noise attenuation. The earth conductor from the motor m st be connected back
to the PE terminal of the converter and should not be connected back to the distribution
board. This will avoid any circulating high frequency currents in the earth system.
When armored or shielded cables are used between the converter and motor, it may be
necessary to fit a barrier termination gland at the motor end when the cable is longer than
about 50m. The reason is that the high frequency leakage currents flow from the cable
through the shunt capacitance and into the shield. If these currents return via the motor
and other parts of the earthing system, the interference is spread over a larger area. It is
preferable for the leakage currents to return to the source via the shortest route, which is
via the shield itself. The shield or teel ire rmo r (SWA) should be earthed at both
the converter end and to the frame of the motor.
As a practical example let us consider the case of a current source inverter, as shown in
Figure 10.4, feeding an electrical motor, driving a pump, requiring typically power up to
500 kW. Since the cost of a LV / MV frequency converter is much cheaper as compared
to that of a HV, the motor is selected to be a LV motor. Hence the power circuit starts
with a step down transformer, typically a Dy11 transformer. For the sake of its protection
from over temperature, a Pt100 RTD (resistance temperature detector) is embedded in the
transformer core and is connected to the Transformer protection relay.
258 Motor Protection, Control & Maintenance
Figure 10.4
ingle line diagram of a t pical c rrent so rce in erter
The secondary of the transformer is connected to an isolator, which is used only for
the sake of maintaining the inverter panel. This power, through appropriately rated fast
acting fuses, branches out into power circuit, auxiliary fans & auxiliary circuits. The
contactor, being used for extending power, is in the power circuit between such fuses and
the inverter assembly. The output of the inverter is connected to the motor through power
cables.
It has to be appreciated that the contactor’s position cannot be in the downstream of the
inverter as the opening out of the contactor for some reason will subject the inverter to a
sudden, step load throw off situation which will create over voltage on the inverter
output.
Similarly, the contactor cannot be in the upstream of the power fuse, as the dropping of
the contactor will result in total powering down of the controller even.
Installation and Fault Finding 259
Sufficient separation from other equipment is necessary to permit the unrestricted flow
of cooling air through the heat sinks and across the electronic control cards. A general
r le of th mb is that a free space of mm should be allowed around all sides of the
VSD. When more than one VSD are located in the same enclosure, they should
preferably be mounted side by side rather than one above the other. Care should also be
taken to avoid locating temperature sensitive equipment, such as thermal overloads,
immediately above the cooling air path of the VSD.
Adequate provision must be made to dissipate the converter losses into the external
environment. The temperature rise inside the enclosure must be kept below the
maximum rated temperature of the converter.
k Max mb
Where,
A Effective heat conducting area in m2 (Sum of surface areas not in contact with
any other surface)
P Power Loss of heat producing equipment in Watts
TMax Maximum permissible operating temperature of Converter in oC
TAmb Maximum temperature of the external ambient air in oC
k Heat transmission coefficient of enclosure material
Example
Calculate the minimum size of an IP54 Cubicle for a typical PWM type Frequency
Converter rated at 22kW.
The following assumptions are made:
x The converter losses are 600 Watts at full rated load
x The converter is to be mounted within an IP54 cubicle made of 2mm steel.
x The enclosure is effectively sealed from the outside and heat can only be
dissipated from the enclosure by conduction through the steel and by
radiation from the external surface into the outside air
x The cubicle stands on the floor with its back against the wall in an air-
conditioned room with a maximum ambient temperature 25oC
x The converter can operate in a maximum temperature of 50oC
x The Heat transmission coefficient is 5.5 (typical for painted 2mm steel)
Installation and Fault Finding 261
The first step is to calculate the minimum required surface area of the enclosure. This
can be done by applying the formula for surface area.
If the cubicle is standing on the floor against a wall, this area applies only to the top,
front and two sides of the enclosure. A suitable cubicle can be chosen from a range of
standard cubicles or could be fabricated for this installation. In either case, it is important
to take into account the dimensions of the converter and to ensure that there is at least
100mm space on all sides of the converter.
With these requirements in mind, the procedure is to choose or estimate at least two of
the dimensions and the third can be derived form the above equation. This calculated
dimension must then be checked to ensure that the required 100mm clearance is
maintained.
For a cubicle with dimensions H x W x D standing on the floor against the wall, the
effective heat conducting area is
A = HW + 2HD + WD
Assuming that a standard cubicle is chosen with a height of 2.0m and a depth of 0.5m,
the width is derived from:
A = 2.0W + 2 + 0.5W
A = 2.5W + 2
Using the required heat dissipation area from the above calculation
4.36 = 2.5W + 2
or,
2.5W = 2.36
W = 0.94
Based on the requirements of heat dissipation, the width of the cubicle would have to
be larger than 0.94m. In this case a standard width of 1.0m would be selected.
Clearances around the sides of the converter should be checked. With typical
converter dimensions of H x W x D = 700 x 350 x 300, the cubicle chosen would provide
more than 100mm of clearance around all the converter and also leave sufficient space for
cabling and other components.
From this calculation, it is clear that the overall dimensions of the cubicle can be
reduced by the following changes:
x Standing the cubicle away from the wall, at least 200mm
x Reducing the ambient temperature by turning down the air-conditioning
x Providing ventilation to the cubicle to improve heat transfer
262 Motor Protection, Control & Maintenance
Natural ventilation
This type of ventilation relies on the convectional cooling airflow through vents near
the bottom and top of the cubicle and is normally called the "chimney" effect.
Figure 10.5
at ral entilation of a con erter in a c bicle
Forced ventilation
This type of ventilation relies on cooling airflow assisted by a fan located either near
the top or the bottom of the cubicle. It is difficult to maintain a high IP rating with
ventilated cubicles, so ventilated cubicles need to be located in a protected environment,
such as a dust-free equipment room.
For cooling purposes, a certain volume of airflow is required to transfer the heat
generated inside the enclosure to the external environment. The required airflow can be
calculated from the following formula:
Max mb
Where,
V Required airflow in m3 per hour
P Power Loss of heat producing equipment in Watts
TMax Maximum permissible operating temperature of Converter in oC
TAmb Maximum external ambient temperature in oC
Installation and Fault Finding 263
Figure 10.6
orced entilation of a con erter in a c bicle
Example
Calculate the airflow ventilation requirements of the 22kW Converter used in the
example above, using the same assumptions.
The required airflow to maintain adequate cooling:
3
m h
An airflow of 75 m3/h is necessary to remove the heat generated inside the enclosure
by the converter and to transfer it to the outside. In this case, the dimensions of the
cubicle are based purely on the minimum physical dimensions required for the converter
and any other equipment mounted in the cubicle.
This airflow could be achieved by the convectional flow of air provided that the size of
the top / bottom openings is large enough and the resistance to airflow is not
unnecessarily restricted by dust-filter pads. Alternatively, a fan assisted ventilation
system would be necessary to deliver the required airflow.
If the heatsink is recessed through the back mounting plane of the enclosure, most of
the heat will be dissipated to the environment external to the cubicle. The portion of the
converter with the control circuits remains within the enclosure. With a suitable seal
around the converter, the enclosure can be relatively small and rated at >IP54 without the
need for forced or convectional airflow ventilation.
The heatsink portion projecting outside the enclosure can be exposed to the
environment with a lower IP rating (eg IP20) or it can be arranged to project into a
cooling airduct system, which ducts the heat outside the building. Figure 10.7 shows a
typical mounting arrangement of this type of converter with the heatsinks projecting into
a cooling duct.
Figure 10.7
on erter mounted it e tsin outside t e cu ic e
11
11.1. Introduction
A plant designer has always been under tremendous pressure while estimating the
power requirements of a drive, as any overrating will result in high running costs. This is
because, the efficiency of standard motor used to dwindle at lower loads resulting in
higher losses and loss of more energy. The technological developments in the motor
manufacturing industry have introduced “Energy efficient motors” with due importance
given to the reduction in the operational costs of motors irrespective of their loading.
Another great development of modern day motor protection systems is the deployment
of digital protection relays with lot of capabilities and versatility of operation. A simple
cost benefit analysis reveals that they are highly economical for medium & high rating
motors. Also they can be used to provide a reliable cover for critical motors against a vast
variety of faults.
Intelligent controllers have revolutionized the way motors are utilized for various types
of applications causing a paradigm shift from DC to AC for variable speed drive
applications. This is especially a boon for maintenance professionals as AC motors,
especially squirrel cage induction motors, having the most robust construction of all
motors, can be used in place of maintenance intensive DC motors. As a result the
equipment availability has obviously been enhanced.
As the causes of motor failures are associated mostly with improper lubrication, focus
on lubrication techniques has witnessed great developments and new varieties of greases
& calibrated grease guns are available in the market.
Another thrust given to extending bearing life by the new innovative technologies is
the availability of bearing isolators that effectively seal the bearing internals from the
external environment.
266 Motor Protection, Control & Maintenance
Improvised condition monitoring techniques are the result of the great strides made by
the instrumentation engineering, resulting in the availability of handheld, highly
sophisticated tools.
Reliable on-line diagnostics are the result of the great developments in the field of
electronics and computer sciences.
Improved testing methods are the result of constant research and development and the
enhanced understanding about the concepts of the electromagnetic concepts and provide
better methods for proper analysis of the incipient faults. All these things put together has
helped the industry in shifting the focus to a reliability-centered approach of maintenance,
instead of just preventive or predictive.
11. . n r ici nt d i n t od rn tr nd
The drive for conservation of energy has been scaling new heights in every field and
the electrical motor manufacturers are contributing their part by continually improving
the design aspects of motors. Developing new line of energy efficient motors is one such
major milestone in this journey. The key advantage of employing these motors is that the
efficiency achieved can be very high and remains almost constant throughout the normal
loading range from 100 % to even 50 % - unlike the standard motors wherein it can drop
drastically for such a loading range.
The following features employed in the motor manufacturing arena have improved the
efficiencies of motors over the standard type motors:
x Usage of more copper in the stator winding has greatly reduced the copper
losses.
x Increased length of stator and rotor core has reduced the magnetic flux density
in the air gap of the machine. This in turn has resulted in reduced magnetic
saturation and core losses.
x More steel used in the stator enhances the heat transfer rate ensuring reduced
operating temperature of such motors.
x Shaft mounted cooling fans are re-designed to have reduced windage losses.
x Special, high grade sheet steel used in the stator reduces the hysterisis losses.
x Thin gauge of the sheet steel used in the stator ensures close bonding of the
laminations and very high internal resistivity of the steel thereby reducing the
eddy current losses.
x Careful, close machining of the rotor is allowing the air gap to reduce and to
be more uniform thereby reducing the stray load losses.
Due to the ever increasing competition, motor manufacturers are adopting different,
better designs and specific techniques (apart from all those mentioned above) like better
quality materials etc., to minimize the losses in their motors.
New Technologies and Developments 267
Bipolar chopper driver: A class of step motor driver, which uses a switch mode
(chopper) technique to control motor current and polarity. i o r indicates the capability
of providing motor phase current of either polarity (+ or -).
Breakaway torque: The torque required to start a machine in motion. Normally it is
greater than the running torque.
Brush: Current conducting material in a DC motor. Usually graphite or a combination
of graphite and other materials. The brush rides on the commutator of a motor and forms
an electrical connection between the armature and the power source.
Brush less motor: Class of motors those operate using electronic commutation of
phase currents, rather than electromechanical (brush-type) commutation. Brushless
motors typically have a permanent magnet rotor and a wound stator.
Canadian Standards Association (CSA): The agency that sets safety standards for
motors and other electric equipment used in Canada.
Capacitance: As the measure of electrical storage potential of a capacitor, the unit of
capacitance is the farad, but typical values are expressed in microfarads (MFD).
Capacitor: A device that stores electrical energy. It is normally used on single phase
motors.
Capacitor Start Motor: Capacitor-Started, induction-run motors. They provide high
starting and break-down torque, medium starting current and are used on hard starting
applications such as compressors, positive displacement pumps, farm equipment, etc.
Capacitor-Start, capacitor-run: Similar to capacitor-start motors, except that they
have higher efficiency. They are generally used in higher HP single phase ratings.
Centrifugal Start Switch: A mechanism that disconnects the starting circuit (start
winding) when the rotor reaches approximately 75% of operating speed (usually in 2 or 3
seconds).
C-face mounting: A standard NEMA mounting design, where the mounting holes in
the face are threaded to receive the mating mounts.
Class B insulation: A NEMA insulation specification. Class B insulation is rated to an
operating (internal) temperature of 130°C.
Class F insulation: A NEMA insulation specification. Class F insulation is rated to an
operating (internal) temperature of 155°C
Class H insulation: A NEMA insulation specification. Class H insulation is rated to an
operating (internal) temperature of 180°C.
Closed loop: A broadly applied term, relating to any system in which the output is
measured and compared to the input. The output is then adjusted to reach the desired
condition. In motion control, the term typically describes a system utilizing a velocity
and/or position transducer to generate correction signals in relation to desired parameters.
Cogging (Cogging torque): A term used to describe non-uniform angular velocity.
Cogging appears as a jerkiness, especially at low speeds.
Commutation:
1. A term which refers to the action of steering currents or voltages to the proper motor
phases so as to produce optimum motor torque. In brush type motors, commutation is
Appendix A: Terminology Associated with Electric Motors 273
Duty cycle: For a repetitive cycle, the ratio of on time to total cycle time.
Duty cycle (%) = [On time / (On time + Off time)] x 100%
It is the relationship between operating time and the resting time of an electric motor.
Continuous Duty: The operation of loads for over one hour.
Intermittent Duty: The operation during alternate periods of load and rest. Usually
expressed as 5 minutes, 30 minutes or one hour.
Dynamic braking: A passive technique for stopping a permanent magnet brush or
brush less motor. The motor windings are shorted together through a resistor, which
results in motor braking with an exponential decrease in speed.
Efficiency: The ratio of power output to power input. The ratio of the useful work
performed and the energy expended in producing it.
Electrical time constant: The time required for current to reach 63.2% of its final
value for a fixed voltage level. Can be calculated from the relationship te=L/R where L is
inductance (henries) and R is resistance (ohms).
Encoder: A feedback device which converts mechanical motion into electronic
signals. The most commonly used, rotary encoders, output digital pulses corresponding to
incremental angular motion. For example, a 1000-line encoder produces 1000 pulses
every mechanical revolution. The encoder consists of a glass or metal wheel with
alternating transparent and opaque stripes, detected by optical sensors to produce the
digital outputs.
Enclosure: Term used to describe the motor housing.
ODP: Open Drip Proof, housing has openings in end shields and shell to allow air to
cool the motor. Normally used in “clean" applications.
TEFC: Totally Enclosed Fan Cooled, housing has no openings. Motor is cooled by an
external fan on the non-drive end of the motor shaft. (motor is not air tight or water
proof). Normally used in dirty, oily or damp applications.
TENV: Totally Enclosed Non-Ventilated. Not equipped with an external cooling fan,
depends on convection air for cooling.
TEAO: Totally Enclosed Air Over. Air flow from the driven or external device
provides cooling air flow of the motor.
Endshield: Also referred to as "End Bell". The part of the motor that houses the
bearing supporting the rotor, and acts as a protective guard to the internal parts of the
motor.
Excitation: The act of creating magnetic lines of force from a motor winding by
applying voltage.
Feedback: A signal which is transferred from the output back to the input for use in a
closed loop system.
Ferrite: A type of permanent magnet consisting of ceramic compounds made up of
oxides of iron, barium and strontium.
Field: The stationary part of a DC motor, commonly consisting of permanent magnets.
Sometimes used also to describe the stator of an AC motor.
Appendix A: Terminology Associated with Electric Motors 275
Form factor: The ratio of RMS current to average current. This number is a measure
of the current ripple in a SCR or other switch-mode type of drive. Since motor heating is
a function of RMS current while motor torque is a function of average current, a form
factor greater than 1.00 means some fraction of motor current is producing heat but not
torque.
Four quadrant: Refers to a motion system which can operate in all four quadrants;
i.e., velocity in either direction and torque in either direction. This means that the motor
can accelerate, run, and decelerate in either direction.
Frame: Standardized motor mounting and shaft dimensions as established by NEMA
or IEC.
Frequency: An expression of how often a complete cycle occurs. Cycles per second
describe how many complete cycles occur in a given time increment. Hertz (hz) has been
adopted to describe cycles per second so that time as well as number of cycles is
specified. The standard power supply in North America is 60hz. Most of the rest of the
world has 50hz power.
Friction: A resistance to motion caused by contact with a surface. Friction can be
constant with varying speed (Coulomb friction) or proportional to speed (viscous
friction).
Full Load Amperes (FLA): Line current (amperage) drawn by a motor when
operating at rated load and voltage on motor nameplate. Important for proper wire size
selection, and motor starter or drive selection. Also called full load current.
Full Load Torque: The torque a motor produces at its rated horsepower and full-load
speed.
Fuse: A piece of metal, connected in the circuit to be protected, that melts and
interrupts the circuit when excess current flows.
Generator: Any machine that converts mechanical energy into electrical energy.
Hall sensor: A feedback device which is used in a brush less servo system to provide
information for the amplifier to electronically commutate the motor. The device uses a
magnetized wheel and hall effect sensors to generate the commutation signals.
Hertz: Frequency, in cycles per second, of AC power. Named after H.R. Hertz, the
German scientist who discovered electrical oscillations.
High Voltage Test: Application of a voltage greater than the working voltage to test
the adequacy of motor insulation. Often referred to as high potential test or "hi-pot".
Holding torque: Sometimes called static torque, holding torque specifies the
maximum external torque that can be applied to a stopped, energized motor without
causing the rotor to rotate. Generally used as a figure of merit when comparing motors.
Horsepower: An index of the amount of work a machine or motor can perform. One
horsepower is equal to 746 watts. Since power is equal to torque multiplied by speed,
horsepower is a measure of a motor's torque and speed capability; e.g., a 1 HP motor will
produce 36 lb-in. at 1,750 rpm.
Formula:
HP = Torque (lb-in.) x Speed (RPM) / 63,025
276 Motor Protection, Control & Maintenance
Or,
HP = Torque (lb-ft.) x Speed (RPM) / 5,252
Or,
HP = Volts x Amps x Efficiency / 746
A measure of the rate of work. 33,000 pounds lifted one foot in one minute, or 550
pounds lifted one foot in one second. Exactly 746 watts of electrical power equals one
horsepower.
Hybrid step motor: A motor designed to move in discrete increments of steps. The
motor has a permanent magnet rotor and a wound stator. Such motors are brushless.
Phase currents are commutated as a function of time to produce motion.
Idle current reduction: A step motor driver feature that reduce the phase current to
the motor when no motor motion is commanded (idle condition) for a specified period of
time. Idle current reduction reduces motor heating and allows high machine throughputs
from a given motor.
Indexer: Electronics which convert high level motion commands from a host
computer, PLC or operator panel into step and direction pulse streams for use by the step
motor driver. Indexers can be broadly divided into two classes. A preset indexer typically
accepts distance, velocity and ramp time inputs only. The more sophisticated
programmable indexer is capable of complex motion control and includes program
memory.
Inductance: The electrical equivalent to mechanical inertia; that is, the property of a
circuit, which has a tendency to resist current flow when no current is flowing, and when
current is flowing has a tendency to maintain that current flow. Pacific Scientific
measures inductance (line-to-line) with a bridge at 1000 Hz and with the rotor positioned
so the back-EMF waveform is at the peak of the sinusoid.
Inductance (mutual): Mutual inductance is the property that exists between two
current carrying conductors or coils when magnetic lines of force from one link with
those of the other.
Inertial match: For most efficient operation, the system coupling ratio should be
selected so that the reflected inertia of the load is equal to the rotor inertia of the motor.
Insulation Class: The rating assigned to the maximum temperature capability of the
insulating components in a motor or other piece of equipment.
International Electrotechnical Commission (IEC): The worldwide organization that
promotes international unification of standards or norms. Its formal decisions on technical
matters express, as nearly as possible, an international consensus.
Impedance: The total opposition in an electric circuit to the flow of an alternating
current. Expressed in ohms.
Induction Motor: The simplest and most rugged electric motor, it consists of a wound
stator and a rotor assembly. The AC induction motor is named because the electric
current flowing in its secondary member (the rotor) is induced by the alternating current
flowing in its primary member (stator). The power supply is connected only to the stator.
The combined electromagnetic effects of the two currents produce the force to create
rotation.
Appendix A: Terminology Associated with Electric Motors 277
Poles: Magnetic devices set up inside the motor by the placement and connection of
the windings. Divide the number of poles into 7200 to determine the motor's normal
speed. For example, 7200 divided by 2 poles equals 3600RPM.
Poles: Refers to the number of magnetic poles arranged on the rotor of the brushless
motor. Unlike an AC motor, the number of poles has no direct relationship to the base
speed of the motor.
Power factor: Ratio of true power (kW) to apparent power (kVA).
PTC (Positive Temperature Coefficient): A positive temperature coefficient
thermistor is used to detect and protect a motor winding from exceeding its maximum
temperature rating. Resistance of the device increases with an increase in temperature.
Pull-out torque: The maximum friction load, at a particular inertial load, that can be
applied to the shaft of a synchronous motor (running at constant speed) and not cause it to
lose synchronism.
Pulse rate: The frequency of the step pulses applied to a step motor driver. The pulse
rate, multiplied by the resolution of the motor/driver combination (in steps per
revolution), yields the rotational speed in revolutions per second.
Pulse Width Modulation (PWM): 1. A PWM controller (amplifier) switches DC
supply voltage on and off at fixed frequencies. The length of the on/off interval or voltage
waveform is variable.
2. Pulse width modulation (PWM), describes a switch-mode (as opposed to linear)
control technique used in amplifiers and drivers to control motor voltage and current.
PWM offers greatly improved efficiency compared to linear techniques.
Regeneration: The action during motor braking, in which the motor acts as a generator
and takes kinetic energy from the load, converts it to electrical energy, and returns it to
the amplifier.
Relay: A device have two separate circuits, it is constructed so that a small current in
one of the circuits controls a large current in the other circuit. A motor starting relay
opens or closes the starting circuit under predetermined electrical conditions in the main
circuit (run winding).
Reluctance: The characteristics of a magnetic field which resists the flow of magnetic
lines of force through it.
Repeatability: The degree to which a parameter such as position or velocity can be
duplicated.
Resistance, Hot (RH): The motor's terminal resistance value specified at the hot
winding temperature, which is at the motor's maximum rated temperature.
Resolution: The smallest increment into which a parameter can be broken down. For
example, a 1000 line encoder has a resolution of 1/1000 of a revolution.
Resolver: An electromagnetic feedback device which converts angular shaft position
into analog signals. These signals can be processed in various ways, such as with an RDC
(resolver-to-digital converter) to produce digital position information. There are two basic
types of resolvers; transmitter and receiver. A transmitter-type is designed for rotor
primary excitation and stator secondary outputs. Position is determined by the ratio of the
sine output amplitude to cosine output amplitude. A receiver-type is designed for stator
280 Motor Protection, Control & Maintenance
primary excitations and rotor secondary output. Position is determined by the phase shift
between the rotor output signal and one of the primary excitation signals.
Resonance: Oscillatory behavior caused by mechanical limitations.
Restart torque: The maximum friction load, at a particular inertial load, that can be
applied to the shaft of a synchronous motor without causing it to lose synchronism when
accelerating to a constant speed from standstill.
Resistor: A device that resists the flow of electrical current for the purpose of
operation, protection or control. There are two types of resistors-fixed and variable. A
fixed resistor has a fixed value of ohms while a variable resistor is adjustable.
Ringing: Oscillation of a system following a sudden change in state.
RMS Current (Root Mean Square Current): In an intermittent duty cycle
application, the RMS current is equal to the value of steady state current which would
produce the equivalent motor heating over a period of time.
RMS Torque (Root Mean Square Torque): In an intermittent duty cycle application,
the RMS torque is equal to the value of steady state torque which would produce the
equivalent motor heating over a period of time.
Rotor: The moving part of the motor, consisting of the shaft and magnets. These
magnets are analogous to the field winding of a brush-type DC motor.
Rotation: The direction in which a shaft turns is either clockwise (CW) or
counterclockwise (CCW). When specifying rotation, also state if viewed from the shaft
end or the opposite shaft end of the motor.
Rotor: The rotating component of an induction AC motor. It is typically constructed of
a laminated, cylindrical iron core with slots of cast-aluminum conductors. Short-
circuiting end rings complete the "squirrel cage," which rotates when the moving
magnetic field induces current in the shorted conductors.
Service Factor: A measure of the overload capacity built into a motor. A 1.15 SF
means the motor can deliver 15% more than the rated horsepower without injurious
overheating. A 1.10 SF motor should not be loaded beyond its rated horsepower. Service
factors will vary for different horsepower motors and for different speeds.
Settling time: The time required for a parameter to stop oscillating or ringing and
reach its final value.
Shaded Pole Motor: (Single Phase) Motor has low starting torque, low cost. Usually
used in direct-drive fans and small blowers, and in small gearmotors.
Shock loading: A load that produces extremely high peak torques for very short
durations. This type of load is associated with conveyorized grinding, crushing and
separation processes.
Short Circuit: A fault or defect in a winding causing part of the normal electrical
circuit to be bypassed, frequently resulting in overheating of the winding and burnout.
Split Phase (or more specifically Split-Phase start-induction run): (Single Phase)
Motor has moderate starting torque, high breakdown torque. Used on easy-starting
equipment, such as belt-driven fans and blowers, grinders, centrifugal pumps, gearmotors,
ect.
Appendix A: Terminology Associated with Electric Motors 281
Torque: The turning effort or force applied to a shaft, usually expressed in inch-pounds or
inch-ounces for fractional and sub-fractional HP motors.
t rting or ue Force produced by a motor as it begins to turn from standstill and
accelerate (sometimes called locked rotor torque).
u o d or ue The force produced by a motor running at rated full-load speed at
rated horsepower.
re do n or ue the maximum torque a motor will develop under increasing load
conditions without an abrupt drop in speed and power. Sometimes called pull-out torque.
u or ue The minimum torque delivered by a motor between zero and the rated
RPM, equal to the maximum load a motor can accelerate to rated RPM.
Torque Constant: An expression of the relationship between input current and output
torque. For each ampere of current, a fixed amount of torque is produced.
Torque-to-inertia ratio: Defined as the motor's holding torque divided by the inertia of its
rotor. The higher the ratio, the higher a motor's maximum acceleration capability will be.
Transformer: Used to isolate line voltage from a circuit or to change voltage and current
to lower or higher values. Constructed of primary and secondary windings around a common
magnetic core.
Underwriters Laboratories (UL): Independent United States testing organization that sets
safety standards for motors and other electrical equipment.
Unipolar driver: step motor driver configuration that uses a unipolar power supply and is
capable of driving phase current in only one direction. The motor phase winding must be
center tapped (6 or 8 lead) to operate with a unipolar driver. The center tap is used instead of
providing the current reversal of a bipolar driver.
Viscous Damping: Inherent losses are present in all motors which result in lower torque
delivered at the output shaft than developed at the rotor. Losses which are proportional to
speed (i.e. speed dependent terms such as windage, friction, eddy current) are related through
the motor's "viscous damping" constant, measured as the slope of the damping curve.
Voltage: A unit of electromotive force that, when applied to conductors, will produce
current in the conductors.
Voltage constant: May also be termed back-EMF constant. When a motor is operated, it
generates a voltage proportional to speed, but opposing the applied voltage. The shape of the
voltage waveform depends upon the specific motor design. For example, in a brushless motor,
the waveshape may be trapezoidal or sinusoidal in nature. All Pacific Scientific brushless
motor designs have a sinusoidal voltage constant. For a sine waveform, the voltage constant
can be measured from line-to-neutral or line-to-line and expressed as a peak value or "RMS"
value.
Watt: The amount of power required to maintain a current of 1 ampere at a pressure of one
volt when the two are in phase with each other. One horsepower is equal to 746 watts.
Winding: Typically refers to the process of wrapping coils of copper wire around a core,
usually of steel. In an AC induction motor, the primary winding is a stator consisting of wire
coils inserted into slots within steel laminations. The secondary winding of an AC induction
motor is usually not a winding at all, but rather a cast rotor assembly. In a permanent magnet
DC motor, the winding is the rotating armature.
T
ote
is t e ser es s er gener com rison guide et een energ e icient motors nd
st nd rd motors under rious o ding conditions
b) or e ct det i s in orm tion is to e o t ined rom t e m nu cturer concerned
Appendix B: A Study of Efficiencies of Motors 285
2).
a). Which is the most widely used motor in the industrial environment?
3).
c). What are the probable causes for rotor bar failures?
3).
4).
b). What kind of Tan delta trend (increasing or decreasing) is considered to be dangerous to
the equipment? Why?
5).
6).
a). What is the most essential protection to be provided for an electrical motor, irrespective
of its size and rating?
b). What are the typical protections to be provided for a large sized (above 1000 HP)
Induction motor?
292 Motor Protection, Control & Maintenance
.1. ro 1
Consider an induction motor of 1.10 kW, 415 V, 50 Hz, 4-pole with a rated slip of 2 %.
What is the synchronous speed of the motor? What is the rated speed of the motor?
Hint: Slip is a reflection of the difference of the speed of the synchronous, revolving
magnetic field and the speed of the motor.
. . ro
While testing a motor, it is recommended to take the inductance values of all the three
phases. With the stator alone, the three phase windings show a considerable degree of
balance. However, in assembled condition of the motor a set of 24 or 36 readings need to
be taken with the rotor in different positions, equally shifted, to detect any kind of
eccentricity of the rotor. Following inductance values were observed with the rotor in
various positions and the readings (some of the typical values capturing the trend) are as
follows:
294 Motor Protection, Control & Maintenance
What is the probable cause for such readings? What kind of remedial actions will you
recommend?
. . ro
Calculate the shaft power output of a 6 pole, 50 Hz, 3-phase induction motor with the
rated torque as 160 N-m and slip of 4 %.
. . ro
In the above case, if the torque loss in windage and friction is 12 N-m and the all
inclusive stator losses are 1000 W calculate efficiency of the motor.
. . ro
A test specimen of 11 / 3.3 kV Transformer’s insulation, when applied a voltage of
1.5 kV, was found to be drawing a resistive current of 0.96 mA and a total current of
48 mA. What is the approximate Tan delta of the insulation at this particular
condition? What will be the PF at this point?
. . ro
A 22 kW, 3-phase, 415 V, 40 A, 50 Hz, 960 rpm. 0.88 PF squirrel cage induction
motor drives a pump. The total inertia of the drive system is 1.2 kg-m2.
Determine the number of starts per minute this drive can be subjected to without
exceeding the total power dissipated in the motor under rated conditions. Assume a
ratio of stator to rotor resistance of unity and neglect magnetizing current and
rotational losses.
int nerg ost t e motor during st rting under no o d
Zs
t tor resist nce otor resist nce
Appendix D: Problems 295
. . ro
Considering the same 22 kW of the above problem and the same assumptions, what
will be the effect on the no. of starts restriction if the motor is of 2 pole construction?
. . ro
Consider a motor of 1000 kW, 996 rpm rating with an inertia of 80 kg-m2; driving a
fan of Load Inertia: 1875 kg-m2. Load Torque required at 650rpm can be assumed to
be 45%; Frictional Torque can be assumed to be 10%. Calculate the acceleration time
of the motor up to 650 rpm assuming that the motor has to accelerate without driving
the load (solo).
. . ro
The above referred drive system is engineered such that the motor gets coupled to the
load at 650 rpm. What is the torque available for the motor to accelerate in this loaded
condition? Calculate the acceleration time to reach a speed of 700 rpm.
.1 . ro 1
One of the turbine driven pumps is facing repetitive failure at the turbine. Also due to
the energy savings potential involved with an electric motor, it was decided to replace
the turbine with an electric motor that can develop a shaft power of 30 kW. Typically
a standard 30 kW motor has efficiencies of 92.90, 92.40 & 91.40 % corresponding to a
loading of 100 %, 75 % & 50 % respectively. While procuring the new motor it was
realized that at a premium (in the price) new generation, energy efficient motor can be
bought that has a promised efficiency of 94.5 % for 100 % & 75 % loading. At 50 %
loading, its efficiency is 93.8 %. The Plant normally runs for 120 days at 100 %
capacity and for 130 days & 100 days at 50 % and 75 % respectively. It can be
assumed that the motor loading is proportional to Plant capacity utilization.
Take the unit rate of power and price of a standard motor & an energy efficient motor
from the Instructor. Find out the pay back period of the additional cost, if the energy
efficient motor is opted.
296 Motor Protection, Control & Maintenance
tud 1
Case Study 2
There are two identical motors M1 & M2 with the perennial problem of high bearing
temperatures, crossing 75 deg C even at an ambient temperature of 30 deg C and hence
suffering from premature failure. Both of them are of class F insulation but loaded
differently. Their winding temperatures are 135 deg C and 95 deg C for M1 and M2
298 Motor Protection, Control & Maintenance
respectively. By using synthetic grease (temperature tolerant one), problem for one of the
motors was resolved.
Which motor's problem could be solved this way and what was the root cause? What will
kind of problem can be there with the other motor?
Case Study
What is the most essential protection to be provided for an electrical motor, irrespective
of its size and rating? Substantiate your idea.
Appendix E: Case Studies 299
Case Study
A 3.3 kV, 700 kW motor of 0.90 PF (with a CT ratio of 200 / 1 A in the breaker) is being
used for a prolonged start application to run a fan. A newly procured digital protection
relay needs to be programmed. How do you set the basic protections using this data?
What kind of information would you seek from the motor manufacturer / fan supplier?
Case Study
What can be the effect on a motor’s acceleration with reduced voltage applied to it?
Consider a motor taking 48 sec to accelerate full speed with normal voltage applied. If the
voltage is reduced by 10 % how much time it may require for the same conditions?
300 Motor Protection, Control & Maintenance
Case Study
What are the parameters to be considered while engineering a drive for variable speed
application?
Appendix F
Consider an induction motor of 1.10 kW, 415 V, 50 Hz, 4 pole with a rated slip of 2 %.
What is the synchronous speed of the motor? What is the rated speed of the motor?
Hint: Slip is a reflection of the difference of the speed of the synchronous, revolving
magnetic field and the speed of the motor.
S ut
60 X Frequency
Synchronous Speed (rpm) =
No. of Pole pairs
302 Motor Protection, Control & Maintenance
= 1500 rpm
As given in Chapter 2,
( no - n)
Slip = s = per - unit
no
= 1470 rpm
( no - n)
Slip = s = per - unit
no
= 1 pu
= 50 Hz
(b). At the rated speed, the slip of the motor is given as 0.02.
= 1 Hz
* Note that the slip of an AC induction motor is a load dependent instantaneous value
and varies dynamically.
e 2
While testing a motor, it is recommended to take the inductance values of all the three
phases. With the stator alone, the three phase windings show a considerable degree of
balance. However, in assembled condition of the motor a set of 24 or 36 readings need
to be taken with the rotor in different positions, equally shifted, to detect any kind of
eccentricity of the rotor. Following inductance values were observed with the rotor in
various positions and the readings (some of the typical values capturing the trend) are
as follows:
Angle 0 30 60 90 120 150 180
L of ‘U” phase in mH 86 145 124 102 86 72 85
L of ‘V” phase in mH 40 61 82 138 140 71 62
L of ‘W” phase in 84 64 41 62 84 114 83
mH
What is the probable cause for such readings? What kind of remedial actions will you
recommend?
S ut
140
100
80
60
40 L of ‘U” phase in mH
L of ‘V” phase in mH
20
L of ‘W” phase in mH
0
0 30 60 90 120 150 180
Rotor Angle
Figure F.1
Curves depicting the Inductance values
It can be seen from the above curves that all the three exhibit a variation that can be
approximated to sinusoidal waveform. However the peak values of each phase are
differing from each other.
This is a clear case of rotor eccentricity but there can be two types of eccentricity as
outlined in Chapter 2, static and dynamic. In case of the latter, the inductance values
will not exhibit sinusoidal pattern and all of them are up or down, depending on which
phase is closest to the rotor at a given degree rotation
Hence, this particular case is due to static eccentricity. This type of eccentricity is
caused by problems like a misaligned end bell or the shaft sitting low in the bearing.
The physical result is that the shaft is always in the same place out of the electric
center as shown below:
Appendix F: Answers to the Problems 305
Figure F.2
A case of Static Eccentricity
e
Calculate the shaft power output of a 6 pole, 50 Hz, 3 phase induction motor with the
rated torque as 160 N-m and slip of 4 %.
S ut
* Please note that the generic usage of such terms like torque, power, speed etc. implies
the value corresponding to the rated conditions, unless otherwise specified.
In the above case, if the torque loss in windage and friction is 12 N-m and the all
inclusive stator losses are 1000 W calculate efficiency of the motor.
S ut
Step-1: Calculation of rotor copper losses:
In this case, Shaft power output and losses are known, hence the efficiency can be
calculated using the equation:
e
A test specimen of 11 / 3.3 kV Transformer’s insulation, when applied a voltage of
1.5 kV, was found to be drawing a resistive current of 0.96 mA and a total current of
48 mA. What is the approximate Tan delta of the insulation at this particular
condition? What will be the PF at this point?
S ut
Step-1: Vectorial representation
The currents drawn by various components can be represented as shown in Figure 5.5
(reproduced here as F.3)
Here, IT = 48 mA
IR = 0.96 A
Figure F.3
Vector components of test voltage and current
308 Motor Protection, Control & Maintenance
* It needs to be understood that the dissipation factor (Tan G) and power factor of a
specimen under test varies with the applied voltage. Also it should be noted that both
the values are close to each other. This holds good for a good quality insulator –
where the resistive component is very less. As the resistive component keeps rising,
the Tan Gvalue rises drastically, but the power factor rises gently. The theoretical
extremities for Tan G vary between 0 and Dinfinity whereas for power factor it is
between 0 and 1. Hence most of the analysts prefer the power factor instead of the
dissipation factor
e
A 22 kW, 3-phase, 415 V, 40 A, 50 Hz, 960 rpm. 0.88 PF squirrel cage induction
motor drives a pump. The total inertia of the drive system is 1.2 kg-m2.
Determine the number of starts per minute this drive can be subjected to without
exceeding the total power dissipated in the motor under rated conditions. Assume a
ratio of stator to rotor resistance of unity and neglect magnetizing current and
rotational losses.
Hint: Energy lost by the motor during starting under no load = ½
J
Zs2 (1 + Stator
resistance / Rotor resistance).
S ut
Step-1: Calculation of energy lost under full load condition
e
Considering the same 22 kW of the above problem and the same assumptions, what
will be the effect on the no. of starts restriction if the motor is of 2 pole construction?
S ut
Step-1: Calculation of the energy lost during start conditions
e
Consider a motor of 1000 kW, 996 rpm rating with an inertia of 80 kg-m2; driving a
fan of Load Inertia: 1875 kg-m2.
Load Torque Required at 650rpm can be assumed to be 45%; Frictional Torque can be
assumed to be 10%.
Calculate the acceleration time of the motor up to 650 rpm assuming that the motor
has to accelerate without driving the load (solo).
Hint: Angular acceleration = (Final speed, rps – Initial speed, rps) / Acceleration
Time.
310 Motor Protection, Control & Maintenance
Motor torque available for acceleration of the motor from zero speed, in de-coupled
(no load) condition is the torque motor is capable of delivering, after overcoming the
frictional loads.
In this case, the frictional losses are given to be 10 %. Hence the motor is capable of
using only 90 % of its rated torque to accelerate.
Torque (N-m)
Moment of Inertia, J (kg-m2) =
Angular acceleration (rad / m2)
Acceleration time from zero speed to the required speed is the ratio between the
required speed in rps and the angular acceleration that can be imparted to the motor
shaft. Hence,
Acceleration time in de-coupled condition from zero speed to a speed of 650 rpm
= (2
S
650 / 60) / 107.82 seconds
= 0.63 second
Appendix F: Answers to the Problems 311
The above referred drive system is engineered such that the motor gets coupled to the
load at 650 rpm. What is the torque available for the motor to accelerate in this loaded
condition? Calculate the acceleration time to reach a speed of 700 rpm?
Motor torque available for acceleration of the motor in coupled condition is the torque
the motor is capable of delivering, after overcoming the frictional losses and the load
requirements.
In this case, the frictional losses are given to be 10 % and the load torque required at
650 rpm is given to be 45 % of the ratted torque. Hence, the motor is capable of using
only 45 % of its rated torque to accelerate in loaded condition.
Acceleration time from 650 rpm to the required speed of 700 rpm is
= (2
S
700 – 650) / 60) / 2.206 sec
= 2.375 seconds
If the motor has to start from zero speed in no-load condition and gets coupled at 650
rpm, the motor requires 3.005 seconds to reach 700 rpm.
e
One of the turbine driven pumps is facing repetitive failure at the turbine. Also due to
the energy savings potential involved with an electric motor, it was decide to replace
the turbine with an electric motor that can develop a shaft power of 30 kW. Typically
a standard 30 kW motor has efficiencies of 92.90, 92.40 & 91.40 % corresponding to
a loading of 100 %, 75 % & 50 % respectively. While procuring the new motor it was
realized that at a premium (in the price) new generation, energy efficient motor can be
bought that has a promised efficiency of 94.5 % for 100 % & 75 % loading. At 50 %
loading, its efficiency is 93.8 %. The Plant normally runs for 120 days at 100 %
312 Motor Protection, Control & Maintenance
capacity and for 130 days & 100 days at 50 % and 75 % respectively. It can be
assumed that the motor loading is proportional to Plant capacity utilization.
Take the unit rate of power and price of a standard motor & an energy efficient motor
from the Instructor.
Find out the pay back period of the additional cost, if the energy efficient motor is
opted.
S ut
Step-1: Calculation of the units consumed with a standard motor in a year
The amount of energy to be supplied to the drive based on the loading pattern has to
be worked out, as shown in the following table. This is common for both the motors.
Based on the efficiency applicable for each loading condition, the energy that will be
drawn by the motor is calculated, in the case of standard motor as shown below:
Based on the efficiency applicable for each loading condition, the energy that will be
drawn by the motor is calculated, in the case of the energy efficient motor as shown
below:
kWh required by the load Efficiency at the kWh absorbed by the Motor
for the particular period particular load in the corresponding period
86400 94.5 91428.571
48000 94.5 50793.651
46800 93.8 49893.39
181200 192115.61
Based on this data, energy savings of around 4039 kWh can be expected per annum
by putting the energy efficient motor into operation.
Step-3 Pay back period for the additional cost of the energy efficient motor
Pay back period in the event of selecting the energy efficient motor, for this particular
case is given by:
Additional cost of the energy efficient motor
= ------------------------------------------------------------- Years
(Average cost per kWh of electrical energy* 4039)
Appendix G
1).
To transmit electrical current to the moving armature through the brushes that ride
on the commutator.
It is not required for the other type of motors, induction type of motors, because
they do not need any external, solid supply.
2).
a). Which is the most widely used motor in the industrial environment?
Squirrel cage induction motor (SCIM) is the most commonly used motor in
industries.
314 Motor Protection, Control & Maintenance
Speed control & torque control are complicated for this type of motor.
3).
c). What are the probable causes for rotor bar failures?
Casting defects, loose laminations, frequent starts, incorrect fitting, incorrect alignment,
rubbing with stator, eccentricity of the rotor resulting out of bent shaft or improper air gap.
4).
5).
a). What is the significance for the Tan delta for an insulator?
Tan delta for an insulator reveals the capacitive characteristic of the material.
b). What kind of Tan delta trend (increasing or decreasing) is considered to be dangerous
to the equipment? Why is it so?
Appendix G: Answers to the Self-help Questions 315
Increasing trend needs to be regularly monitored. It indicates the dilution of the dielectric
nature of the insulator.
6).
7).
a). What is the most essential protection to be provided for an electrical motor, irrespective of its
size and rating?
Thermal Overload protection.
b). What are the typical protections to be provided for a large sized (above 1000 HP) Induction
motor?
x Negative sequence current
x Over current
x Earth fault
x Stalling
x Too frequent starts
x Unbalanced voltage
x Under voltage
x Over voltage
316 Motor Protection, Control & Maintenance
Appendix H
Case Study
Once these values are felt to be causing concern, regular close monitoring would be
warranted. Since the equipment will be in operation, these measurements cannot be taken.
In such a case Partial Discharge measurements, which can be taken on-line, will act as
saviors. A regular, close monitoring is possible only with these on-line measurement kits.
Case Study 2
There are two identical motors M1 & M2 with the perennial problem of high bearing
temperatures, crossing 75 deg C even at an ambient temperature of 30 deg C and hence
suffering from premature failure. Both of them are of class F insulation but loaded
differently. Their winding temperatures are 135 deg C and 95 deg C for M1 and M2
respectively. By using synthetic grease (temperature tolerant one), the problem for one of
the motors was resolved.
Which motor's problem could be solved this way and what was the root cause? What
will kind of problem can be there with the other motor?
So proper vibration analysis and if possible electrical signature analysis may gibe a
proper diagnosis and the problem can be solved forever.
Case Study
What is the most essential protection to be provided for an electrical motor, irrespective
of its size and rating? Substantiate your idea.
Irrespective of the size / rating, every motor requires a protection to safeguard the
machine against overloading.
x This is because, every motor has got a very high probability of getting overloaded at
some point of time, which can be at any time.
x Overload relay, if not perfectly, has a capability to respond to even other types of
faults like, under voltage (resulting in overload), over current, single phasing etc.
x Overload protection is the only one which safeguards a motor almost close to the
thermal capability curve, with very few exception points like stalling cases with the
starting time greater than the allowable stalling time etc.
Case Study
A 3.3 kV, 700 kW motor of 0.90 PF (with a CT ratio of 200 / 1 A in the breaker) is
being used for a prolonged start application to run a fan. A newly procured Digital
protection relay needs to be programmed. How do you set the basic protections using this
data? What kind of information would you seek from the motor manufacturer / fan
supplier?
Digital (Microprocessor based) Motor protection relays require very few inputs /
settings and provide a vast variety of protections.
With the available information, the thermal characteristic can be programmed for the
basic protections without going for a protection characteristic close to the thermal
capability curve of the motor (thermal withstand characteristic).
Rated current of this motor works out to 136 A. Hence, the following can be fed into
the relay:
x CT primary current: 200 A
x CT secondary current: 1 A
x Motor rated current: 136 / 200 = 0.68 A (Thermal protection)
x Over-voltage: + 10 %
x Under voltage: - 10%
x Earth fault: 200 mA
x Negative sequence currents: 0.27 A (40 % of rated current).
The following data needs to be collected from the motor manufacturer / fan supplier:
320 Motor Protection, Control & Maintenance
x Acceleration time
x Motor stall withstand current & time
x Motor thermal capability curve
x Motor starting current
x Motor locked rotor current
x No. of starts allowable / hr.
Case Study
What can be the effect on a motor’s acceleration with reduced voltage applied to it?
Consider a motor taking 48 sec to accelerate full speed with normal voltage applied. If the
voltage is reduced by 10 % how much time it may require for the same conditions?
Considering a squirrel cage induction motor, a motor’s starting torque reduces by 19 %
as the torque is proportional to the square of the voltage. Motor when started with 90 %
voltage will have the torque at 81 % of that available with full voltage.
The acceleration time of a motor is
x Directly proportional to the inertia and
x Inversely proportional to the torque.
Hence, after considering the frictional & load torque requirements to be negligible as
compared to the acceleration torque – as no data is available* – the acceleration time may
be approximately increased by 25 %. It means that the acceleration time will be more
than 60 seconds.
* Since the acceleration time is more than 48 seconds, the load is absorbing most of the motor
torque. Hence the load torque can’t be ignored comfortably, but the assumption is made due to
lack of information.
Case Study
What are the parameters to be considered while engineering a drive for variable speed
application?
The characteristics (especially the speed - torque curves) of both the driven machine
and the driving machine play very important role in the selection of a VSD.
The speed / torque / power characteristics developed at the motor shaft and how well
these characteristics suit the driven machine must be considered.
The four essential parameters that must be considered are:
x Breakaway Torque, the torque required to put the machine into motion.
x Process Torque or Load torque
Appendix H: Answers to the Case Studies 321
x Accelerating Torque, the torque required to bring the machine to its operating
speed within a given time.
x Running Torque
322 Motor Protection, Control & Maintenance
Appendix I
Practical Exercises
The problems covered below are to be solved using the demo software tools
developed by Electric Motor Engineering & Consulting. The instructors may re-
build on the problems below, to refine the training module and to demonstrate the
basic principles discussed during the lecture sessions on the respective topics.
It may please be noted that studying the design problems by varying certain
characteristics at a time, for a particular model, gives a deeper insight into the
fundamentals and hence such an approach is adopted here.
e s t e des C t s S t a et used
C
While designing a DC motor to be run on a supply of 100 VDC and developing a load
torque of 216 oz-in at 1000 rpm the following data was taken as the basis:
Armature OD 3 inch 76.2 mm
Armature Stack ID 0.24 inch 6.1 mm
Armaturer Stack Length 2 inch 50.8 mm
No.Of Laminations 80 80
Lamination Thickness 0.025 inch 0.6 mm
Winding Lap Winding
Turns/Coil 81 81
Wire gage (AWG) 24 24
Copper Weight 20.85 ounce 591.09 gms
Armature length over co (Shaft
not included) 4.236 inch 107.6 mm
324 Motor Protection, Control & Maintenance
Consider designing a DC motor with the same physical dimensions running on a supply
of 100 VDC, but suitable for running at 3000 rpm. What will be the impact on the
winding characteristics such as the number of turns to coil?
e 2
In the above example of designing motors of different speeds, of 1000 rpm and 3000 rpm,
how will the armature resistance, no load current, power output & efficiency be
influenced?
Considering the same situation as in the above examples of two designs of 1000 rpm and
3000 rpm DC motors, how will the Frictional, eddy current, hysterisis & copper losses be
different?
Continuing with the same example check the variations that are to be incorporated in the
Brush & commutator dimensions.
Appendix I: Practical Exercises 325
du t t S t a et used
While designing an AC induction motor, the following data was taken as the basis:
Armature OD 3 inch 76.2 mm
Armature Stack ID 0.24 inch 6.1 mm
Armaturer Stack Length 2 inch 50.8 mm
No.Of Laminations 80 80
Lamination Thickness 0.025 inch 0.6 mm
Winding Lap Winding
Turns/Coil 81 81
Wire gage (AWG) 24 24
Copper Weight 20.85 ounce 591.09 gms
Armature length over co (Shaft
not included) 4.236 inch 107.6 mm
Lead Wire Gage 16 AWG 1.29 mm
Lead Wire Length 12 inch 304.8 mm
Housing OD 3.906 inch 99.2 mm
Housing ID 3.711 inch 94.3 mm
Housing Thickness 0.098 inch 2.5 mm
Housing Axial Length 4 inch 101.6 mm
Magnet Type Arc FERRITE #7 TDK
Magnet Length 2.25 inch 57.2 mm
Magnet Angle 65.3 degrees 65.3 gms
Magnet OD 3.711 inch 94.3 mm
Magnet ID 3.051 inch 77.5 mm
Magnet Thickness 0.33 inch 8.4 mm
Magnet Weight 16.1 oz 456.43 gms
No. Of Poles 4 4
Commutator OD 0.99 inch 25.1 mm
Commutator ID 0.24 inch 6.1 mm
Commutator Length 0.432 inch 11.0 mm
No.Commutator Bars 21 21
Brush Width 0.148 inch 3.8 mm
Brush Axial Length 0.182 inch 4.6 mm
No.Brush 2 2
Brush Material Silver Graphite
Motor Length 5.686 inch 144.4 mm
Motor OD 3.906 inch 99.2 mm
Shaft OD 0.24 inch 6.1 mm
What is the implication on the values of various leakage / magnetizing reactance
and power factor of an induction motor when a motor is designed with an enhanced
rating (from 100 W to 300 W) - keeping the same rated voltage, frequency, no. of
poles etc.?
326 Motor Protection, Control & Maintenance
While up-rating a design model of an induction motor, what can happen with the
characteristics of winding such as the value wire gauge, turns per coil, copper ratio, stator
slot fill, etc.?
e
How do the values of stator iron & copper losses, rotor copper losses, % slip and
efficiency vary with the power rating of an induction motor, keeping the same rated
voltage, frequency, no. of poles etc.?
For a particular design of motor, how do the values of torque and current corresponding
to full load and stall conditions vary when the power output of the motor is to be revised,
say from 100 W to 300 W?
Appendix J
Solutions to Practical Exercises
While designing a DC motor that is to be run on a supply of 100 VDC and developing a
load torque of 216 oz-in at 1000 rpm, the following data was taken as the basis:
Armature OD 3 inch
Armature Stack ID 0.24 inch
Armature Stack Length 2 inch
No. of Laminations 80
Lamination Thickness 0.025 inch
Lamination Material 0
Lap
Winding Winding
Turns/Coil 81
Wire gage (AWG) 24
No.Of Wires In Hand 1
Copper Weight 20.85 ounce
Armature length over co (Shaft not included) 4.236 inch
Lead Wire Gage 16 AWG
Lead Wire Length 12 inch
Housing OD 3.906 inch
Housing ID 3.711 inch
Housing Thickness 0.098 inch
Housing Axial Length 4 inch
Magnet Type Arc FERRITE #7 TDK
Magnet Length 2.25 inch
Magnet Angle 65.3 degrees
Magnet OD 3.711 inch
Magnet ID 3.051 inch
328 Motor Protection, Control & Maintenance
Consider designing a DC motor with the same physical dimensions running on a supply
of 100 VDC, but suitable for running at 3000 rpm. What will be the impact on the
winding characteristics such as the number of turns to coil and the gauge of the winding?
ue t t e e s eed t e t a d t e sa e t ue t e t ea et
de e e e e e t e t d ss se t as t e
a d y e t s a t u a ase t e au e s u d t a e edu ed t
2 2 2
e 2
In the above example of designing motors of different speeds, of 1000 rpm and 3000 rpm,
how will the armature resistance, no load current, power output and efficiency be
influenced?
Sl. No. Attribute, Units 1000 rpm 3000 rpm
1 Armature Resistance, Ohm 7.015 1.096
2 No load current, Amps 0.051 0.16
3 Power output, Watts 162 387
4 Efficiency 77% 89%
ue t t e e ss se t t e a atu e d e ate a t e
es sta e a e e e ted t edu e a d t e data s at S a e
s t e sa e
Appendix J: Solutions to Practical Exercises 329
e ut ut a t s t a t t e du t s eed a d t e t ue
de e ed y t S e t e t ue de e ed s e u ed t e sta t t s ase
t e e ut ut s e e ted t e e t e as s at S
a e
Considering the same situation as in the above examples of two designs of 1000 rpm and
3000 rpm DC motors, how will the Frictional, eddy current, hysterisis and copper losses
be different?
Sl. No. Attribute, Units 1000 rpm 3000 rpm
1 Armature total friction loss, Watts 0.23 1.25
2 Eddy Current loss Watts 0.55 4.81
3 Hysterisis loss Watts 3.73 11.04
4 Copper loss Watts 41.96 28.33
e t u t e t dea s t e u e ts e u t e
s eed t se a e t s a u ed y t e e ss se t t e du t s
esu t e es sta e t u e ta d e e sses
du t t S t a et used
While designing an AC induction motor, the following data was taken as the basis:
e
Armature OD 3 inch 76.2 mm
Armature Stack ID 0.24 inch 6.1 mm
Armaturer Stack Length 2 inch 50.8 mm
No.Of Laminations 80 80
Lamination Thickness 0.025 inch 0.6 mm
330 Motor Protection, Control & Maintenance
100 W 300 W
Stator resistance/phase 5.23 5.34
Equivalent rotor resistance, Ohms 5.25 5.76
Stator reactance, Ohms 12.73 12.6
Equivalent rotor reactance, Ohms 11.67 10.71
Magnetizing reactance, Ohms 185 171
Power Factor 0.56 0.80
e e at a du t t a s e u e s
a d e u u d st ut a d e e edu ed ea a e ea ta e
s tu esu ts a ette e a t
Appendix J: Solutions to Practical Exercises 331
While up-rating a design model of an induction motor, what can happen with the
characteristics of winding such as the value wire gauge, turns per coil, copper ratio, stator
slot fill etc.?
100 W 300 W
Turns/coil 42 40
Wre gage AWG American Wire Gage
(Magnet Wire) 24 23.5
Cu Ratio Copper Ratio or Copper fill in
Slots(50%-90% 81% 87%
St slot Fill Ratio of actual copper in stator
slot / Gross slot area 0.28 0.3
u s e edu es t e at e ss se t as t e
e a d e et ee e a edu ed au e e e at as t e
e de t e t e sses due t eased u e ts as a
esu t t e e e at
e
How do the values of stator iron and copper losses, rotor copper losses, % slip and
efficiency vary with the power rating of an induction motor, keeping the same rated
voltage, frequency, no. of poles etc.?
100 W 300 W
Stator iron / core loss
(Watts) 27.88 27.61
Stator copper loss (watts) 7.93 29.23
Rotor copper loss (Watts) 1.63 19.69
%slip @ full load 1.606 6.158
Efficiency % 72.80% 79.70%
For a particular design of motor, how do the values of torque and current corresponding
to full load and stall conditions vary when the power output of the motor is to be revised,
say from 100 W to 300 W?
100 W 300 W
Full Load Torque in-lb 0.71 2.25
Full Load Torque kg-m 0.0082 0.026
Full Load Current-Ampere 0.71 1.35
Stall Torque in-pound 1.96 2.44
Stall Torque in kg 0.889 1.107
Stall Current (Ampere) 4.2 4.47
332 Motor Protection, Control & Maintenance
Bibliography
C du t t s
1.1 Leroy Somer Moteurs: 3-Phase TEFC Cage Induction Motors Technical
Catalogue
1.2 Sprecher+Schuh: "Contactor Selection Made Easy", Publication 2200T, 1985
1.3 Rockwell Allen-Bradley: "A comprehensive Guide to Understanding Electric
Motor Fundamentals", Publication 150-2.7, June 1994.
1.4 Odendal EJ, Harley RG : "AC Variable Speed Drives for Engineers"
1.5 I J Nagrath, D P Kothari: Electric Machines
1.6 S K Pillai: A First Course on Electrical Drives
2 e ee t s
a a e s eed d ea at s
3.1 Control Techniques Drives PLC: "Drives and Servos Yearbook 1990-1",
ISBN 0 9515101 0 X
3.2 Danfoss: "Facts worth knowing about Frequency Converters", 1990,
Publication D-0192-3
3.3 Reliance Automation: "AC Drive Application Training Manual"
3.4 Allen-Bradley: "Soft Starting - Safe Driving", seminar notes
334 Motor Protection, Control & Maintenance
3.5 Odendal EJ, Harley RG: "AC Variable Speed Drives for Engineers", 2nd
edition
3.6 "Electrical Control Technology", Tafe External Studies College, WA.
3.7 Reliance Electric: "Vector Drive Basics", Publication D-7161
3.8 ABB Drives: ABB Brochures and Application Guides
3.9 Fuji Electric: Fuji Brochures and Application Guides
3.10 PDL Electronics: PDL Brochures and Application Guides
a sa d
4.1 Schaffner Elektronik AG : "Output Filters for use with Frequency Converters
in Motor Drive Applications", Publication 690-364A, 1994
4.2 Janiszewski GM, "AC Line Harmonics and Variable Speed Drives
Explained", Electrical Focus, February/March 1994
4.3 Sanders G, "Supply Harmonics caused by AC Variable Frequency Drives",
Pacific Power Centre for Energy Efficiency, 1992
4.4 Alex Gosman, "Electromagnetic Compatibility - What faces our
Manufacturers", EA Electrical Engineering Review, February 1995
4.5 van Coller JM, "Recommended Limits for Voltage Waveform Distortion",
EPCC, 1992
Sta da ds tat ee t a a es
Table I.1
List of important IEC Rotating Electrical Machines Standards with the equivalent national
standards in Australia, France, Germany and U.K.
336 Motor Protection, Control & Maintenance
Other International Standards which are relevant to Variable Speed Drives are:
IEC 529: Classification of Degrees of Protection provided by Enclosures
IEC 721 : Classification of Outdoor Environmental Conditions - Temperature and
Humidity
IEC 892 : Effects of an imbalance in the voltage system on the characteristics of three-
phase squirrel-cage induction motors
IEC 1000: Electromagnetic Compatibility (EMC)
ISO 281 : Bearings - Basic Dynamic Loadings and Nominal Bearing Life
ISO 1680: Acoustics - Test code for measuring airborne noise emitted by electrical
rotating machines
ISO 8821: Mechanical Vibration - Balancing conventions on shaft keys and related
parts
Other Australian Standards which are relevant to Variable Speed Drives are:
AS 1000 : The International System of Units (SI) and its application
AS 1023 : Low Voltage Switchgear and Controlgear - Protection of Electric Motors
Part 1: Built-in Thermal Detectors and Associated Control Units
Part 2: Thermal Overload Protective Devices
Part 3: Inherent Overheat Protectors
AS 1029: Low Voltage Contactors
AS 1136 : Switchgear and Controlgear Assemblies for Voltages up to 1000 VAC
AS 1202 : AC Motor Starters (Up to and including 1000V)
Part 1: Direct-on-line (full voltage) Starters
Part 2: Star-delta Starters
Part 3: Autotransformer Starters
Part 4: Rheostat Rotor Starters
Part 5: Semiconductor (solid state) Starters
AS 1360-10: Rotating Electrical Machines of Particular Types or for Particular
Applications
Part 11: Dimensions and Performance of Small Power Electrical Machines
Part 60: Stepping Motors
AS 1359.102.3: Determination of losses and efficiency of three-phase cage induction
motors
AS 1852: International Electrotechnical Vocabulary
AS 2279: Disturbances in Mains Supply Networks
Appendix K: Bibliography 337
The following USA Standards (de facto international standards) are usually used for
serial Data Communications with Variable Speed Drives:
EIA-232(Also sometimes called RS-232): Interface between Data Terminal Equipment
(DTE) and Data Circuit-terminating Equipment (DCE) employing Serial Binary Data
Interchange
EIA-422(Also sometimes called RS-422 or TIA-422): Electrical Characteristics of
Balanced Voltage Digital Interface Circuits
EIA-485(Also sometimes called RS-485 or TIA-485): Electrical Characteristics of
Generators and Receivers for use in Balanced Digital Multipoint Systems
IEEE 518: IEEE Guide to the Installation of Electrical Equipment to