Operating Instructions: Standard Converter - Cabinet Type UNL133
Operating Instructions: Standard Converter - Cabinet Type UNL133
Operating Instructions
Type UNL133
No. of p.
Prep. 01-07-30 A.K.
Appr. 01- 08-23 T.G. Operating Instructions 32
Resp. REV. B 4.9.03 / Mo
ATPE
Document number Lang. Rev. ind. Page
(1)
Maintenance and Repair Instructions
Important Notice
Our experience has shown that if the information and recommendations contained in
this " Operating Instructions" are observed, the best possible reliability of our products is
assured.
The data contained herein purports solely to describe the product and is not a warranty
of performance or characteristics. It is with the best interest of our customers in mind
that we constantly strive to improve our products and keep them abreast of advances in
technology. This may, however, lead to discrepancies between a product and its
"Technical Description" or " Operating Instructions".
This document has been carefully prepared and reviewed. However, should in spite of
this the reader find an error, he is requested to inform us at his earliest convenience.
It is scarcely possible for the operating instructions for technical equipment to cover
every eventuality which can occur in practice. We would therefore request you to notify
us or our agent in the case of all unusual behaviour, which does not appear to be
covered by these operating instructions.
It is pointed out that all local regulations must be observed when connecting and
commissioning this equipment in addition to these operating instructions.
Any work that has to be carried out inside the equipment, such as changing soldered
links or fitting or removing resistors, may only be performed by correspondingly qualified
personnel.
We cannot accept any responsibility for damage incurred as a result of mishandling the
equipment regardless of whether particular reference is made in these operating
instructions or not.
We lay particular stress on the fact that only genuine spare parts should be used for
replacements.
All rights with respect to this document, including applications for patent and registration
of other industrial property rights, are reserved. Unauthorized use, in particular
reproduction or making available to third parties, is prohibited.
24 h - Hot line for urgent service inquiries: +41 844 845 845
Contents Page
1. Introduction 4
1.1. Using these Operating Instructions 4
1.2. Definition of symbols used in this document 4
1.3. Related documents 4
2. Description of equipment 5
2.1. Overview 5
2.2. Key to Types and Variants 6
2.3. Mechanical layout 7
2.3.1. General assembly of variant without isolator, forced ventilation 7
2.3.2. General assembly of variant with isolator, forced ventilation 8
2.3.3. General assembly of variants without isolator, natural ventilation 9
2.4. Description of individual units 10
2.4.1. Converter module G01 10
2.4.2. Snubber F01 11
2.4.3. Types of ventilation 12
3. Safety Regulations 14
3.1. Safety conditions 14
3.2. The results of non observation 14
3.3. Requirements for involved personnel 15
4. Maintenance 16
4.1. Introduction 16
4.2 Maintenance work 16
4.2.1. 3 monthly on the working equipment 16
4.2.2. Yearly with the equipment on shutdown 17
5. Repairs 18
5.1. Important points to be observed before work starts 18
5.1.1. Converter cabinets with isolators 18
5.1.2. Converter cabinets without isolators 20
5.2. Fault sources and fault elimination 20
5.2.1. Thyristor defect 21
5.2.2. Fault in the snubber 23
5.2.3. Faults in the ventilator box 26
5.2.4. Overheating through poor cabinet ventilation 27
5.3. Changing a thyristor 28
5.3.1. Tools and auxiliary materials 28
5.3.2. Replacement of thyristors UNS 4680 Var. 87,88,89,98 29
5.4. Function check 31
6. Spares 32
1. Introduction
1.1. Using these Operating Instructions
The contents of these instructions will provide you with all the information necessary for
the maintenance and repair of the electrical components of a Converter Cabinet Type
UNL 133 .
General Warning
This symbol in front of the text warns of situations or conditions which can
endanger life or cause potentially fatal injuries. The description indicates the
procedure to be followed in order to avoid risks.
Dangerous Voltage
This symbol indicates that dangerous voltages are involved which can
endanger life or cause potentially fatal injuries.
Attention Attention is used to mark the parts of the text which contain information on
situations and conditions which, if they are not paid attention, can cause
material damage or equipment failure.
Note Note is used to mark the parts of the text which contain information on
situations and conditions which, if they are not paid attention, can lead to
undesirable operating conditions or automatic shutdown.
2. Description of equipment
2.1. Overview
A converter cabinet of the UNL 133 type has a modular construction and consists of
the following units:
The converter module UNS 4680 is a fully controlled 3-phase bridge with six thyristors
cooled on both sides. To protect the thyristors against overcurrents, which can result
from internal or external short-circuits, each thyristor branch has an ultra fast fuse with
defect indication switch.
Snubber (-F01)
The snubber (overvoltage protective circuit) UNS 4681 protects the six thyristors in the
converter module from undesirable overvoltages. The unit has a 3-phase protection on
the input side and the fuses are fitted with a defect indication switch.
The external resistor is part of the snubber, however it must be ordered separately.
A natural or forced ventilation is provided for the converter modules. Forced cooling can
consist of simple, redundant or reinforced ventilation.
At parallel operation (n-1 redundancy) the converter modules are equipped with current
seonsors at the positive and negative connections. Thus an automatic current balance
can be achieved and the functionality of each semiconductor can be observed. The
current sensors transfer the measured current values to the control board (COB) UNS
2880. Defective thyristors are indicated on the converter display (CDP) UNS 0885.
The type key UNL 133 defines the converter cabinet i.e. the parts which are built
into a cabinet of 1000 x 1000 x 2200 mm.
The last 2 digits in the type designation UNL 133 identify the type of thyristor being
used and the snubber.
The Variant Var. _ _ _ _ defines the ventilation and the degree of IP protection:
UNL 133 Var. for UN 5000 applications with Gate Driver Interface (GDI)
Type of ventilation:
1 without (natural ventilation)
2 with 2 fans
3 with 2+2 fans (redundant ventilation)
4 with 4 fans (rectified ventilation)
Eintritts- / Austrittsöffnungen:
00 Specified by customer
03 4 grids with filter IP31/ roof grid IP30
08 2 grids with filter IP31/ roof hood w/o flaps IP31
09 2 grids with filter IP54/ roof hood with flaps IP54
Schutzart:
0 IP00 or specified by customer
3 IP30
4 IP31
5 IP54
The following diagram shows the side view of the cabinet. The arrows indicate the
airflow caused by natural convection.
To identify the module a type plate (1) is provided on the right-hand side. The type plate
contains all the information necessary for the ordering of spare parts.
CIN
(1)
GDI
(1) Assembly plate with the diodes (-V1 to -V6), capacitor (-C1) and fuse holder (-F02)
with three fuses.
(2) Resistor (-R1). The resistor is part of the snubber, however it must be ordered
separately.
-R1
(2)
(2)
(2)
(3)
M1 M3
Arrangement of the fans and switches with S1 S3
full set.
-E01
3. Safety Regulations
Warning signs are fitted to all cabinet doors to warn of the operating voltages present in
the control cabinets (over 50 volts), but in particular to warn of the voltages occurring in
the power section (over 1000 volts possible) and the enormous short-circuit currents
which may occur. These signs warn personnel against opening the doors during
operation.
Symbol Meaning
Work on the electrical equipment can only take place if the affected voltage carrying
parts are switched off on all sides and earthed. Should this not be possible, the following
special procedures must be taken:
The work area must be fenced off and a yellow warning notice ”Danger - High Voltage”
is to be provided.
Precautions are to be taken to prevent any switched off equipment being switched on
again through a control fault or a third person, e.g. by using a locked off key switch to
prevent a switch on.
Non observation of the safety regulations can result in the danger of electrocution for
the personnel involved and extensive damage to the equipment.
If the intended maintenance work is not or only partially carried out, damage can result
leading to high repair costs. In particular dirt and dust layers can build up in the
converter with a great risk of flashover which can cause enormous damage.
The maintenance personnel are trained for carrying out the mechanical as well as the
electrical installation work e.g. as necessary for fan replacement.
The maintenance personnel are familiar with the accident prevention procedures at their
working place and trained in first aid and fire extinguishing procedures .
They or a supervisor are familiar with the operation of control elements, operating and
alarm indicators of the excitation unit both on the excitation unit itself (Local Operation)
and in the Control Room (Remote Operation).
They or a supervisor are aware of the power supply concept for the excitation unit as
well as the emergency stop procedures and, in the event of an emergency, could switch
off the power.
4. Maintenance
4.1. Introduction
Although the electronic components display no signs of wear, and only slight signs of
ageing, the converter cabinet includes a range of conventional electromechanical
components, e.g. fans, which are subject to a certain degree of wear.
Due to air circulation dirt can build up in the converter. Faston plug connections can
become loose through vibration.
Attention: During maintenance and repair work only original replacement parts
are to be used. In order to ensure, in the event of a breakdown, a rapid
and problem free replacement, the important components are to be
procured and held ready in the stores. (For recommended spares see
section 6).
The maintenance work is divided into 3-monthly checks on the working equipment and
more substantial works are to be performed on the occasion of planned revisions during
an equipment shutdown, normally on a yearly cycle. Normally the maintenance work is
limited to checking. Routine maintenance work such as lubricating bearings is not
necessary.
Checking work can be carried out while the converter is still in operation. For all repair
work, such as fan changing, cleaning the converter module, etc., the equipment must be
switched off and the safety regulations and preparation procedures of section 5 strictly
observed.
Checking of the fans (ventilator box or door fans) for abnormal noises. Lubricating the
bearings is not possible. The fans are to be replaced after ca. 25,000 working hours.
The step-by-step procedure for exchanging fans is described in sections 5.2.3 and
5.2.4.
If the converter is provided with standby fans the working fans are to be switched over
periodically. The switching can be carried out while the equipment is working.
Checking of the filter mats for dirt. The mats can be changed with the doors closed (see
section 5.2.4.).
Checking of the dust situation in the converter. With the heavier layers especially on the
heat sinks, cleaning should be with oil free, dry, compressed air.
If an isolator is fitted: Visually check the isolator for dirt and burning off on the contacts.
Checking of the Faston plug connections for grip (the Faston plugs must be positively
engaged).
For equipment without current monitoring it is recommended that the firing of the
thyristors is checked together with the pulse generation of the control electronics (see
operation and maintenance manual of the excitation equipment). If this is not possible, a
simple check can be carried out with the help of a continuity tester. (see section 5.2.1).
After cleaning work on the converter module, the function checks are to be carried out
according to section 5.2.1.
5. Repairs
5.1. Important points to be observed before work starts
In order to carry out the majority of repair work, the affected cabinet must be switched
off and the converter module earthed. In general the whole equipment must be
completely switched off.
Work on the cabinet door e.g. changing the filter mat can be carried out while in
operation.
Certain work can be carried out with the isolator open on variants which have isolators
on each converter cabinet while the remaining equipment is in operation.
Once the isolator has been opened the majority of repair work can be carried out while
the remaining equipment is in operation. Exceptions are works on the snubber circuit
which is located close to the primary side of the isolator connections, which are under
voltage even with the isolator open. Care is also to be taken as the auxiliary voltage for
the fuse monitoring is not interrupted by the isolator.
The following works relate only to parts which are located in the
areas switched off by the isolator. For work on the snubber cicuit,
the preparation procedures must be carried out according to
section 5.1.2.
Despite the isolator, extreme care is to be taken when
carrying out repair work, since the neighbouring cabinets
are not free of voltage. Short-circuit currents can lead to
potentially fatal injuries and major material damage.
Preparation procedures:
2. Remove auxiliary voltage for the fuse monitoring (see equipment circuit diagram).
R01
-Q01
-G01
-E01
Earthing cable
5. In variants with forced ventilation remove the front part of the channelling.
For all works inside the converter cabinet, the equipment must be switched off and the
voltage carrying parts must be earthed.
Preparation procedures:
2. Remove auxiliary voltage for the fuse monitoring (see equipment circuit diagram).
5. In variants with forced ventilation remove the front part of the channelling.
The converters described here are always part of an excitation unit and consist of
control and power components. Breakdowns in a converter cabinet will be reported
through a monitoring contact (e.g. fuse auxiliary contacts) to the control system and the
source can then be localised with the help of the alarm indicator on the control cabinet
as well as the operating instructions on the excitation unit.
The possible sources of faults as well as the procedures for the elimination of the
internal faults within the converter cabinet are listed below:
For more accurate fault diagnosis and its elimination the affected
converter cabinet must be switched off. Then the preparation
procedures of section 5.1 are to be essentially carried out.
For equipment with current flow monitoring the defective semiconductor will be indicated
by an LED on the UNS 0674 operating panel. This also applies to loss of blocking
capabilities and a failure to fire.
For equipment without current monitoring the auxiliary contact on the branch fuses must
be checked:
The blocking ability of a thyristor must be tested before its removal. In the unmounted
position thyristors basically do not work since the silicon layer only makes contact within
the thyristor by pressure. A simple test can be made with a continuity tester (torch, test
buzzer) with a DC voltage of 3V to 10V.
If the tester shows continuity, there is a short circuit in the semiconductor. The element
must be replaced and returned to the manufacturer for a more precise fault diagnosis,
with a brief explanation of the origin of the fault.
If the thyristor blocks in the forward direction the firing can be tested.
- V4
Should the tester show no continuity even when the gate wire is in contact, then either
the cable or the thyristor is defective and the semiconductor must be removed.
Should the tester only show continuity while the gate wire is in contact, it is possible that
the latching current is not reached. According to the size of the layers a current of 100
to 300 mA is required for the thyristor to continue conducting once fired. If this current
cannot be delivered by the continuity tester, the test must be carried out with a stronger
source (a power supply or similar). The voltage must not however be permitted to
exceed 10 V. If the thyristor is supplied with a higher current and still does not fire, it
can be considered to be defective and must be replaced.
In the unmounted condition the gate wire can be tested. If broken, the wire can be
replaced and the thyristor reinstalled. It is important however that the correct quality of
cable and a suitable connection plug is used. If in doubt replace the whole thyristor and
order a gate wire set from the manufacturer.
Note: On changing the gate wire ensure that the plug unit (Faston, etc.) is
tight. This connection can no longer be checked once the thyristor is
mounted.
The gate connection should never be soldered. This can damage the element.
To test the firing directly on the gate when unmounted, the thyristor housing must be
weighted down e.g. with the removed heat sink half. If the thyristor is defective it must
be returned to the manufacturer with a short explanation of the fault situation.
Replacing a thyristor
Function check
1. After changing a fuse the functioning of the fuse monitoring is checked by withdrawing
the red plastic part of the indicating switch until it latches. This simulates the operation
of the fuse. Correct signalling by the control system can now be checked. Finally the
indicating switch can be reset.
2. After cleaning and repair works on the main circuit a visual check and an insulation
check are to be carried out before returning the unit into operation. First check visually
whether all tools have been removed and no loose parts remain in the cabinet. On
completion of repair work remove the earthing from the main circuits and connect
together the five main leads AK1, AK2, AK3, (+) and (-) of the converter module and test
to earth. In this way, the pulse cables are also tested up to the pulse transformer. The
insulation resistance must not be less than 1 MOhm.
3. As a further test the insulation resistance between the heat sinks can also be checked.
For this it is essential that the maximum permitted blocking voltage of the thyristor is
taken into account. The type of converter module is to be noted from the type plate,
then the thyristor type and blocking voltage can be found in the 3BHS121826 E01 data
sheet.
Attention: The maximum blocking voltage of the thyristor must not be exceeded
during testing, otherwise there is a danger of destroying the
component.
1. Measure the capacitor voltage. The capacitor must be discharged, if not, discharge it
with a wire bridge.
2. Open the fuse holders. Defective fuses are indicated by the protrusion of the set stud.
This may either indicate a short circuited diode or a flashover of the capacitor. The fuse
holder can be left open for further measurements.
3. Test the diodes with a continuity tester. The forward direction is presented below.
Depending on the sensitivity of the tester, the resistor must be disconnected first.
(Resistor -R01 ca. 1.2 kOhm).
AK K A
1 2 3
AK K A
1 2 3
6
7
4
5
4. Test the resistor and capacitor with an Ohmmeter. To clearly identify a defective
element it may be necessary to remove the wiring between the components.
Changing of fuses
Only original spare parts should be used when replacing defective fuses. Ensure that
the contact surfaces are clean and insert the fuses with the set stud upwards.
Only original spare parts should be used when replacing defective components. After
replacements, the wiring must be returned to its original state as shown in the following
diagrams:
Part of
plant-wiring
Function check
In order to carry out the function checks, a fused single-phase auxiliary power supply is
required e.g. for fan supply, heating, etc., maximum voltage 440 VAC.
With the fuse holder open, connect the auxiliary power supply to two AC connections of
the snubber, then measure the voltage across the capacitor. If functioning correctly, the
voltage should amount to 1.25 x the effective value of the applied AC with tolerance of
+/- 5%. Now a lead from the auxiliary power supply is moved to the third AC connection
and the measurement is repeated. Finally the fuse holder is closed.
For more accurate fault diagnosis and its elimination the affected
converter cabinet must be switched off. Then the preparation
procedures of section 5.1 are to be essentially carried out.
Changing a fan
Function check
Switch on the fan supply, check for flow direction and quiet working. Check the
operation of the flap and the signalling contact.
Withdraw the air grid from the front. Now the filter mat can be changed. Finally, fix the
air grid back into position.
During installation note the direction of the slats, they have to point downwards.
(1)
(2)
In the next section, the removal of a defective thyristor and the installation of its
replacement is presented in illustrated steps with comments.
For simplification purposes, in the diagram only the upper bridge half is represented. On
the lower bridge half the fuses are mounted under the heat sink. Apart from the
thyristors being the other way round (Anodes and Cathodes are reversed !) the
procedure remains the same.
Different clamping fixtures are used for the 3” thyristors to those used for the smaller
types. Attention should therefore be paid to the converter type when replacing a thyristor
(check with type plates for G01 converter modules). section 5.3.2 applies to 2” and 2.5”
thyristors - section 5.3.3 for 3” thyristors.
No special tools are required to carry out a thyristor change. In addition to the normal
tools like screwdrivers, allen keys, spanners, etc., the following tools and materials are
to be available:
Tools:
Torque spanner 30 Nm
Straightedge
A rustfree steel wire brush
Clamping tool for cable end connectors
Faston cable end connectors 6.3 x 0.8 mm
Auxiliary materials:
Silicon grease:
Temperature resistant silicon grease (Melt temperature > 180o C)
(ABB Identification No. NBT 400 725 P1)
(3)
M5 Install fuse (5) and threaded bolt (4). Tighten nut (3)
(4) with a torque of 22 Nm. Attach auxiliary contact to
fuse.
(8)
(10)
(11)
(13) M2 Push the new thyristor (13) with its holder over the
bolts (12). Connect the gate lead to the thyristor. (In
the event of a defective gate wire: lay out a new wire
(12) and fix with a wire binder. Insert the gate lead into
the pulse transformer: white to connection 6, red to
7).
Note: Before inserting the new gate wire, cut it to the
required length and fit with suitable AMP wire end
terminals.
Minus-Schiene
negative lead D6 State before mounting of new thyristor.
The function checks are described in each section, however in general the following
applies:
After all work on the main circuit before returning the unit into operation, a visual check
is to be carried out along with an insulation check. First check visually whether all tools
have been removed and no loose parts remain in the cabinet. On completion of repair
work remove the earthing from the main circuits and connect together the five main
leads AK1, AK2, AK3, (+) and (-) of the converter module and test to earth. In this way,
the pulse cables are also tested up to the pulse transformer. The insulation resistance
must not be less than 1 MOhm.
After the checks all tools, measuring instruments and test cables are to be taken away.
All covers (contact protection, channelling front cover) are to be put back in position.
6. Spares
When changing assemblies or components only original spare parts are to be used.
In order to be able to carry out the necessary repairs as quickly as possible in the event
of a breakdown, we recommend that you keep certain spare parts in store. The
numbers of these parts is dependent on:
ABB will prepare for you an individual spare parts quotation which takes all of the above
mentioned points into consideration.
Note: On follow-up orders the delivery time e.g. for thyristors can be up to 12 weeks.