SECTION 331000 WATER & IRRIGATION- UTILITIES

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:
1. Pipe and fittings for site water line including domestic water line and fire
water line.
2. Valves.
3. Hydrants.
4. Underground pipe markers.
5. Bedding and cover materials.

B. Related Sections:
1. Section 312300 - Excavation and Fill: Product and execution requirements
for excavation and backfill required by this section.
2. Section 221116- Water Distribution Piping
3. Section 033000- Cast in Place Concrete
4. Section 230501- Basic Mechanical Procedures and Methods.
5. Section221319- Plumbing Specialties
6. Section 230593- Testing Adjusting and Balancing

1.2 UNIT PRICE - MEASUREMENT AND PAYMENT

A. Pipe and Fittings:


1. Basis of Measurement: By the linear meter. Basis of Payment: Includes hand
trimming excavation, pipe and fittings, bedding, concrete thrust restraints,
connection to building service piping, and to municipal utility water source.

B. Valves:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes valve, fittings and accessories.

C. Hydrant:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes hand trimming excavation, gravel sump, hydrant,
valve, connection, and accessories.

D. Backflow Preventers:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes backflow preventer, fittings and accessories.

1.3 REFERENCES

A. American Association of State Highway and Transportation Officials:


1. AASHTO T180 - Standard Specification for Moisture-Density Relations of
Soils Using a 4.54-kg (10-lb) Rammer and a 457-mm (18-in.) Drop.
Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation
IFC–Rev.00 Page 1 of 8 October 2018
B. American Society of Mechanical Engineers:
1. ASME B16.18 - Cast Copper Alloy Solder Joint Pressure Fittings.
2. ASME B16.22 - Wrought Copper and Copper Alloy Solder Joint Pressure
Fittings.

C. American Society of Sanitary Engineering:


1. ASSE 1012 - Backflow Preventer with Intermediate Atmospheric Vent.
2. ASSE 1013 - Reduced Pressure Principle Backflow Preventers.

D. ASTM International:
1. ASTM B88M - Standard Specification for Seamless Copper Water Tube
(Metric).
2. ASTM C858 - Standard Specification for Underground Precast Concrete
Utility Structures.
3. ASTM D698 - Standard Test Method for Laboratory Compaction
Characteristics of Soil Using Standard Effort (12,400 ft-lbf/ft3 (600 kN-
m/m3)).
4. ASTM D1557 - Standard Test Method for Laboratory Compaction
Characteristics of Soil Using Modified Effort (6,000 ft-lbf/ft3 (2,700 kN-
m/m3)).
5. ASTM D1785 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Plastic Pipe, Schedules 40, 80, and 120.
6. ASTM D2241 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Pressure-Rated Pipe (SDR Series).
7. ASTM D2466 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Plastic Pipe Fittings, Schedule 40.
8. ASTM D2855 - Standard Practice for Making Solvent-Cemented Joints with
Poly (Vinyl Chloride) (PVC) Pipe and Fittings.
9. ASTM D2922 - Standard Test Method for Density of Soil and Soil-
Aggregate in Place by Nuclear Methods (Shallow Depth).
10. ASTM D3017 - Standard Test Method for Water Content of Soil and Rock in
Place by Nuclear Methods (Shallow Depth).
11. ASTM D3035 - Standard Specification for Polyethylene (PE) Plastic Pipe
(DR-PR) Based on Controlled Outside Diameter.
12. ASTM D3139 - Standard Specification for Joints for Plastic Pressure Pipes
Using Flexible Elastomeric Seals.

E. American Welding Society:


1. AWS A5.8 - Specification for Filler Metals for Brazing and Braze Welding.

F. American Water Works Association:


1. AWWA C104 - American National Standard for Cement-Mortar Lining for
Ductile-Iron Pipe and Fittings for Water.
2. AWWA C105 - American National Standard for Polyethylene Encasement
for Ductile-Iron Pipe Systems.
3. AWWA C111 - American National Standard for Rubber-Gasket Joints for
Ductile-Iron Pressure Pipe and Fittings.
4. AWWA C151 - American National Standard for Ductile-Iron Pipe,
Centrifugally Cast, for Water.
5. AWWA C500 - Metal-Seated Gate Valves for Water Supply Service.
Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation
IFC–Rev.00 Page 2 of 8 October 2018
6. AWWA C502 - Dry-Barrel Fire Hydrants.
7. AWWA C504 - Rubber-Sealed Butterfly Valves.
8. AWWA C508 - Swing-Check Valves for Waterworks Service, 2 in. (50 mm)
Through 24 in. (600 mm) NPS.
9. AWWA C509 - Resilient-Seated Gate Valves for Water-Supply Service.
10. AWWA C600 - Installation of Ductile-Iron Water Mains and Their
Appurtenances.
11. AWWA C606 - Grooved and Shouldered Joints.
12. AWWA C700 - Cold-Water Meters - Displacement Type, Bronze Main
Case.
13. AWWA C701 - Cold-Water Meters - Turbine Type, for Customer Service.
14. AWWA C702 - Cold-Water Meters - Compound Type.
15. AWWA C706 - Direct-Reading, Remote-Registration Systems for Cold-
Water Meters.
16. AWWA C900 - Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. through 12
in., for Water Distribution.
17. AWWA C901 - Polyethylene (PE) Pressure Pipe and Tubing, 1/2 in. through
3 in., for Water Service.
18. AWWA M6 - Water Meters - Selection, Installation, Testing, and
Maintenance.

G. Underwriters Laboratories Inc.:


1. UL 246 - Hydrants for Fire - Protection Service.

1.4 SUBMITTALS

A. Section 230501 - Basic Mechanical Procedures and Methods.

B. Product Data: Submit data on pipe materials, pipe fittings, valves and accessories.

C. Manufacturer's Certificate: Certify Products meet or exceed specified requirements.

1.5 CLOSEOUT SUBMITTALS

A. Project Record Documents: Record actual locations of piping mains, valves,


connections, thrust restraints, and invert elevations.

B. Identify and describe unexpected variations to subsoil conditions or discovery of


uncharted utilities.

1.6 QUALITY ASSURANCE

A. Maintain one copy copies of each document on site.

B. Valves: Manufacturer's name and pressure rating marked on valve body.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store valves in shipping containers with labeling in place.

Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation


IFC–Rev.00 Page 3 of 8 October 2018
PART 2 PRODUCTS

2.1 WATER PIPING

A. High Density Polyethylene Pipe: AWWA C901 ASTM D3035, for 315 400 560 710
900 1000 1000 kPa pressure rating:
1. Fittings: AWWA C901 molded or fabricated.
2. Joints: Compression Butt fusion.
3. Pipe and fittings shall be to ISO 4427-2, DIN 8074/8075 or AWWA C906.
Pipe shall be supplied in straight pieces and not rolled on a drum. The ends
of each pipe shall be plain and suitable for heat fusion. Pipe and fittings shall
be class 10 kg/cm2 minimum with PE compound number required to give
pressure rating not less than 10 bars.
4. Materials used shall have a standard PE code designation 3408 and a
minimum hydrostatic design basis of 1600 psi according to AWWA C906
Table 1.
5. Manufacturers shall provide certification that stress regression testing has
been performed on the pipe products. Materials shall also meet elevated
temperature requirements as given in Table 2 AWWA C906.
6. Fittings shall be to AWWA C906, extruded or injection molded suitable for
class of pipe required. Joints for pipes and fittings shall be by heat fusion and
in strict accordance with pipe manufactures recommendations. Joints shall
have a tensile strength equal to that of the pipe. Fusion temperature, interface
pressure, alignment and cooling time, shall be according to manufactures
recommendations.
7. Tests on PE Compounds: Where PE is used for potable water, PE compounds
in pipes and fittings shall contain no ingredients in an amount that has been
demonstrated to migrate into water in quantities considered to be toxic. PE
compounds shall be tested and certified suitable for potable water by the
National Sanitation Foundation (NSF) Testing Laboratory – USA, or the
Canadian Standard Association (CSA) Testing Laboratory, or other
accredited testing agency. Tests shall be made in accordance with
requirements no less restrictive than those in the NSF Standard No. 14
(1976), Sectionc 3. The seal and mark of the testing laboratory shall be
included on pipes and fittings HDPE Valves, DN80 (3-Inch NPS) and
Smaller:
8. Provide metal water-service valves, instead of HDPE valves, for sizes larger
than DN80 (3-inch NPS).

2.2 GATE VALVES

A. 64 mm and Smaller: Brass or Bronze body, non-rising stem, inside screw, single
wedge or disc, compression IPS ends, with control rod, post indicator, extension box
and valve key.

B. 75 mm and Larger: AWWA C500, Iron body, bronze trim, non-rising stem with
square nut, single wedge, flanged mechanical joint ends, control rod, post indicator,
extension box and valve key.

Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation


IFC–Rev.00 Page 4 of 8 October 2018
2.3 BALL VALVES

A. 50 mm and Smaller: Brass body, Teflon coated brass ball, rubber seats and stem
seals, Tee stem pre-drilled for control rod, AWWA IPS compression inlet end, and
compression IPS outlet with electrical ground connector, with control rod, extension
box and valve key.

2.4 SWING CHECK VALVES

A. 50 mm to 600 mm: AWWA C508, iron body, bronze trim, 45 22 degree swing disc,
renewable disc and seat, flanged ends.

2.5 HYDRANT

A. Hydrant: In accordance with utility company fire department requirements.

B. Hydrant: AWWA C502, UL 246, dry barrel type, inside dimension of 175 mm
minimum, with minimum 125 mm diameter valve seat opening; minimum net water
area of barrel not less than 190 percent of valve opening; 150 mm bell or mechanical
joint inlet connection with accessories, gland bolts, and gaskets.

C. Hydrant Extensions: Fabricate in multiples of 150 mm with rod and coupling to


increase barrel length.

D. Hose and Streamer Connection: Match sizes and type of thread with utility company
fire department, two hose nozzles, one pumper nozzle.

E. Finish: Primer and two coats of enamel Special coating color in accordance with
utility company fire department requirements.

2.6 UNDERGROUND PIPE MARKERS

A. Plastic Ribbon Tape: Bright colored, continuously printed, minimum 150 mm wide
by 0.10 mm thick, manufactured for direct burial service.

B. Trace Wire: Magnetic detectable conductor, clear brightly colored plastic covering,
imprinted with "Water Service” in large letters.

2.7 BEDDING AND COVER MATERIALS

A. Bedding: Fill Type A1 A2 A3 A4 as specified in Section 312300.

B. Cover: Fill Type A1 A2 A3 A4, as specified in Section 312300.

C. Soil Backfill from Above Pipe to Finish Grade: Soil Type S1 S2, as specified in
Section 312300. Subsoil with no rocks over 150 mm in diameter, frozen earth or
foreign matter.

2.8 ACCESSORIES

A. Concrete for Thrust Restraints: Concrete type specified in Section 033000.


Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation
IFC–Rev.00 Page 5 of 8 October 2018
2.10 MANUFACTURERS

Approved Manufacturers: Subject to compliance with requirements.

PART 3 EXECUTION

3.1 EXAMINATION

A. Verify building service connection and municipal utility water main size, location,
and invert are as indicated on Drawings.

3.2 PREPARATION

A. Cut pipe ends square, ream pipe and tube ends to full pipe diameter, remove burrs.

B. Remove scale and dirt on inside and outside before assembly.

C. Prepare pipe connections to equipment with flanges or unions.

3.3 BEDDING

A. Excavate pipe trench in accordance with Section 312300 for Work of this Section.

B. Form and place concrete for pipe thrust restraints at change of pipe direction. Place
concrete to permit full access to pipe and pipe accessories. Provide sq m thrust
restraint bearing on subsoil.

C. Place bedding material at trench bottom, level fill materials in one continuous layer
not exceeding 150 200 mm compacted depth; compact to 95 percent.

D. Backfill around sides and to top of pipe with cover fill, tamp in place and compact to
95 percent.

3.4 INSTALLATION - PIPE

A. Maintain separation of water main from sewer piping in accordance with code.

B. Group piping with other site piping work whenever practical.

C. Install pipe to indicated elevation to within tolerance of 20 mm.

D. Install ductile iron piping and fittings to AWWA C600.

E. Install grooved and shouldered pipe joints to AWWA C606.

F. Route pipe in straight line.

G. Install pipe to allow for expansion and contraction without stressing pipe or joints.

Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation


IFC–Rev.00 Page 6 of 8 October 2018
H. Install access fittings to permit disinfection of water system

I. Form and place concrete for thrust restraints at each elbow or change of direction of
pipe main.

J. Establish elevations of buried piping with not less than m of cover.

K. Install plastic ribbon tape continuous over top of pipe. Buried 150 mm below finish
grade, above pipe line.

3.5 INSTALLATION - VALVES AND HYDRANTS

A. Set valves on solid bearing compacted soil.

B. Center and plumb valve box over valve. Set box cover flush with finished grade.

C. Set hydrants plumb; locate pumper nozzle perpendicular to and facing roadway.

D. Set hydrants to grade, with nozzles at least 500 mm above ground.

E. Locate control valve 100 mm away from hydrant.

F. Provide drainage pit 900 mm square by 600 mm deep filled with 50 mm washed
gravel. Encase elbow of hydrant in gravel to 150 mm above drain opening. Do not
connect drain opening to sewer.

3.6 INSTALLATION - METERS

A. Install positive displacement meters in accordance with AWWA M6, with isolating
valves on inlet and outlet. Provide full line size bypass with globe valve for liquid
service meters.

3.7 SERVICE CONNECTIONS

A. Install water service in accordance with utility company requirements with water
meter with by-pass valves and sand strainer.

B. Install water meter and backflow preventer in concrete vault located on site. Refer to
Plumbing Specialties section.

C. Install water service to 1500 mm of building. Connect to building water service.


Refer to Section Plumbing Specialties Section.

D. Water meter located within building.

E. Install 1.2 mm galvanized sheet metal sleeve surrounding service main to 150 mm
above floor and 1800 mm minimum below grade. Size for 50 mm minimum of glass
fiber insulation stuffing.

F. Water service connection to be brass, saddle and tapping device materials to be


ductile iron.
Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation
IFC–Rev.00 Page 7 of 8 October 2018
3.8 DISINFECTION OF DOMESTIC WATER PIPING SYSTEM

A. Flush and disinfect system

3.9 FIELD QUALITY CONTROL

A. Section 230593- Execution Requirements: Field inspecting, testing, adjusting, and


balancing.

B. Perform pressure test on domestic site water distribution system in accordance with
AWWA C600.

C. Pressure test system to 1380 kPa. Repair leaks and re-test.


1. After completion of pipeline installation, including backfill, but prior to final
connection to existing system, conduct, in presence of Architect/Engineer,
concurrent hydrostatic pressure and leakage tests in accordance with AWWA
C600.
2. Provide equipment required to perform leakage and hydrostatic pressure
tests.
3. Test Pressure: Not less than 1380 kPa or 345 kPa in excess of maximum
static pressure, whichever is greater.
4. Conduct hydrostatic test for at least two-hour duration.
5. No pipeline installation will be approved when pressure varies by more than
34 kPa at completion of hydrostatic pressure test.
6. Before applying test pressure, completely expel air from section of piping
under test. Provide corporation cocks so air can be expelled as pipeline is
filled with water. After air has been expelled, close corporation cocks and
apply test pressure. At conclusion of tests, remove corporation cocks
removed and plug resulting piping openings.
7. Slowly bring piping to test pressure and allow system to stabilize prior to
conducting leakage test. Do not open or close valves at differential pressures
above rated pressure.
8. Examine exposed piping, fittings, valves, hydrants, and joints carefully
during hydrostatic pressure test. Repair or replace damage or defective pipe,
fittings, valves, hydrants, or joints discovered, following pressure test.
9. No pipeline installation will be approved when leakage is greater than that
determined by the following formula:

L = (SD\/¯¯P)/133,200
L = allowable, in gallons per hour
S = length of pipe tested, in inches
D = nominal diameter of pipe, in inches
p = average test pressure during leakage test, in pounds per square inch (gauge)

10. When leakage exceeds specified acceptable rate, locate source and make
repairs. Repeat test until specified leakage requirements are met.

END OF SECTION 331000


Uptown Cairo – Village Z3 – Utilities 331000-Water & Irrigation
IFC–Rev.00 Page 8 of 8 October 2018
SECTION 333000 SANITARY SEWERAGE UTILITIES

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:
1. Sanitary sewage pipe.
2. Force main pipes
3. Underground pipe markers.
4. Manholes.
5. Catch basins and plant area drains.
6. Slow down chambers.
7. Bedding and cover materials.

B. Related Sections:
1. Section 312300 - Excavation and Fill: Product and execution requirements
for excavation and backfill required by this section.
2. Section 221316- Drainage Piping
3. Section 221319- Plumbing Specialties
4. Section 033000- Cast in Place Concrete
5. Section 230501- Basic Mechanical procedures and methods.
6. Section 230593- Testing Adjusting and Balancing

1.2 UNIT PRICE - MEASUREMENT AND PAYMENT

A. Pipe and Fittings:


1. Basis of Measurement: By the linear meter.
2. Basis of Payment: Includes hand trimming excavation, bedding, pipe and
fittings, connection to building service piping and to municipal sewer.

B. Cleanout:
1. Basis of Measurement: By the unit for nominal depth of m.
2. Basis of Payment: Includes hand trimming excavating, foundation pad, unit
installation with accessories, and connection to sewer piping.

1.3 REFERENCES

A. American Association of State Highway and Transportation Officials:


1. AASHTO T180 - Standard Specification for Moisture-Density Relations of
Soils Using a 4.54-kg (10-lb) Rammer and a 457-mm (18-in.) Drop.

B. ASTM International:
1. ASTM A74 - Standard Specification for Cast Iron Soil Pipe and Fittings.
2. ASTM A746 - Standard Specification for Ductile Iron Gravity Sewer Pipe.
3. ASTM C14M - Standard Specification for Concrete Sewer, Storm Drain, and
Culvert Pipe (Metric).
4. ASTM C76M - Standard Specification for Reinforced Concrete Culvert,
Storm Drain, and Sewer Pipe (Metric).
5. ASTM C443M - Standard Specification for Joints for Circular Concrete
Sewer and Culvert Pipe, Using Rubber Gaskets (Metric).
Uptown Cairo – Village Z3 – Utilities 333000 - Sanitary Sewerage Utilities