PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Pipe and fittings for site water line including domestic water line and fire
water line.
2. Valves.
3. Hydrants.
4. Underground pipe markers.
5. Bedding and cover materials.
B. Related Sections:
1. Section 312300 - Excavation and Fill: Product and execution requirements
for excavation and backfill required by this section.
2. Section 221116- Water Distribution Piping
3. Section 033000- Cast in Place Concrete
4. Section 230501- Basic Mechanical Procedures and Methods.
5. Section221319- Plumbing Specialties
6. Section 230593- Testing Adjusting and Balancing
B. Valves:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes valve, fittings and accessories.
C. Hydrant:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes hand trimming excavation, gravel sump, hydrant,
valve, connection, and accessories.
D. Backflow Preventers:
1. Basis of Measurement: By the unit.
2. Basis of Payment: Includes backflow preventer, fittings and accessories.
1.3 REFERENCES
D. ASTM International:
1. ASTM B88M - Standard Specification for Seamless Copper Water Tube
(Metric).
2. ASTM C858 - Standard Specification for Underground Precast Concrete
Utility Structures.
3. ASTM D698 - Standard Test Method for Laboratory Compaction
Characteristics of Soil Using Standard Effort (12,400 ft-lbf/ft3 (600 kN-
m/m3)).
4. ASTM D1557 - Standard Test Method for Laboratory Compaction
Characteristics of Soil Using Modified Effort (6,000 ft-lbf/ft3 (2,700 kN-
m/m3)).
5. ASTM D1785 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Plastic Pipe, Schedules 40, 80, and 120.
6. ASTM D2241 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Pressure-Rated Pipe (SDR Series).
7. ASTM D2466 - Standard Specification for Poly (Vinyl Chloride) (PVC)
Plastic Pipe Fittings, Schedule 40.
8. ASTM D2855 - Standard Practice for Making Solvent-Cemented Joints with
Poly (Vinyl Chloride) (PVC) Pipe and Fittings.
9. ASTM D2922 - Standard Test Method for Density of Soil and Soil-
Aggregate in Place by Nuclear Methods (Shallow Depth).
10. ASTM D3017 - Standard Test Method for Water Content of Soil and Rock in
Place by Nuclear Methods (Shallow Depth).
11. ASTM D3035 - Standard Specification for Polyethylene (PE) Plastic Pipe
(DR-PR) Based on Controlled Outside Diameter.
12. ASTM D3139 - Standard Specification for Joints for Plastic Pressure Pipes
Using Flexible Elastomeric Seals.
1.4 SUBMITTALS
B. Product Data: Submit data on pipe materials, pipe fittings, valves and accessories.
A. High Density Polyethylene Pipe: AWWA C901 ASTM D3035, for 315 400 560 710
900 1000 1000 kPa pressure rating:
1. Fittings: AWWA C901 molded or fabricated.
2. Joints: Compression Butt fusion.
3. Pipe and fittings shall be to ISO 4427-2, DIN 8074/8075 or AWWA C906.
Pipe shall be supplied in straight pieces and not rolled on a drum. The ends
of each pipe shall be plain and suitable for heat fusion. Pipe and fittings shall
be class 10 kg/cm2 minimum with PE compound number required to give
pressure rating not less than 10 bars.
4. Materials used shall have a standard PE code designation 3408 and a
minimum hydrostatic design basis of 1600 psi according to AWWA C906
Table 1.
5. Manufacturers shall provide certification that stress regression testing has
been performed on the pipe products. Materials shall also meet elevated
temperature requirements as given in Table 2 AWWA C906.
6. Fittings shall be to AWWA C906, extruded or injection molded suitable for
class of pipe required. Joints for pipes and fittings shall be by heat fusion and
in strict accordance with pipe manufactures recommendations. Joints shall
have a tensile strength equal to that of the pipe. Fusion temperature, interface
pressure, alignment and cooling time, shall be according to manufactures
recommendations.
7. Tests on PE Compounds: Where PE is used for potable water, PE compounds
in pipes and fittings shall contain no ingredients in an amount that has been
demonstrated to migrate into water in quantities considered to be toxic. PE
compounds shall be tested and certified suitable for potable water by the
National Sanitation Foundation (NSF) Testing Laboratory – USA, or the
Canadian Standard Association (CSA) Testing Laboratory, or other
accredited testing agency. Tests shall be made in accordance with
requirements no less restrictive than those in the NSF Standard No. 14
(1976), Sectionc 3. The seal and mark of the testing laboratory shall be
included on pipes and fittings HDPE Valves, DN80 (3-Inch NPS) and
Smaller:
8. Provide metal water-service valves, instead of HDPE valves, for sizes larger
than DN80 (3-inch NPS).
A. 64 mm and Smaller: Brass or Bronze body, non-rising stem, inside screw, single
wedge or disc, compression IPS ends, with control rod, post indicator, extension box
and valve key.
B. 75 mm and Larger: AWWA C500, Iron body, bronze trim, non-rising stem with
square nut, single wedge, flanged mechanical joint ends, control rod, post indicator,
extension box and valve key.
A. 50 mm and Smaller: Brass body, Teflon coated brass ball, rubber seats and stem
seals, Tee stem pre-drilled for control rod, AWWA IPS compression inlet end, and
compression IPS outlet with electrical ground connector, with control rod, extension
box and valve key.
A. 50 mm to 600 mm: AWWA C508, iron body, bronze trim, 45 22 degree swing disc,
renewable disc and seat, flanged ends.
2.5 HYDRANT
B. Hydrant: AWWA C502, UL 246, dry barrel type, inside dimension of 175 mm
minimum, with minimum 125 mm diameter valve seat opening; minimum net water
area of barrel not less than 190 percent of valve opening; 150 mm bell or mechanical
joint inlet connection with accessories, gland bolts, and gaskets.
D. Hose and Streamer Connection: Match sizes and type of thread with utility company
fire department, two hose nozzles, one pumper nozzle.
E. Finish: Primer and two coats of enamel Special coating color in accordance with
utility company fire department requirements.
A. Plastic Ribbon Tape: Bright colored, continuously printed, minimum 150 mm wide
by 0.10 mm thick, manufactured for direct burial service.
B. Trace Wire: Magnetic detectable conductor, clear brightly colored plastic covering,
imprinted with "Water Service” in large letters.
C. Soil Backfill from Above Pipe to Finish Grade: Soil Type S1 S2, as specified in
Section 312300. Subsoil with no rocks over 150 mm in diameter, frozen earth or
foreign matter.
2.8 ACCESSORIES
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify building service connection and municipal utility water main size, location,
and invert are as indicated on Drawings.
3.2 PREPARATION
A. Cut pipe ends square, ream pipe and tube ends to full pipe diameter, remove burrs.
3.3 BEDDING
A. Excavate pipe trench in accordance with Section 312300 for Work of this Section.
B. Form and place concrete for pipe thrust restraints at change of pipe direction. Place
concrete to permit full access to pipe and pipe accessories. Provide sq m thrust
restraint bearing on subsoil.
C. Place bedding material at trench bottom, level fill materials in one continuous layer
not exceeding 150 200 mm compacted depth; compact to 95 percent.
D. Backfill around sides and to top of pipe with cover fill, tamp in place and compact to
95 percent.
A. Maintain separation of water main from sewer piping in accordance with code.
G. Install pipe to allow for expansion and contraction without stressing pipe or joints.
I. Form and place concrete for thrust restraints at each elbow or change of direction of
pipe main.
K. Install plastic ribbon tape continuous over top of pipe. Buried 150 mm below finish
grade, above pipe line.
B. Center and plumb valve box over valve. Set box cover flush with finished grade.
C. Set hydrants plumb; locate pumper nozzle perpendicular to and facing roadway.
F. Provide drainage pit 900 mm square by 600 mm deep filled with 50 mm washed
gravel. Encase elbow of hydrant in gravel to 150 mm above drain opening. Do not
connect drain opening to sewer.
A. Install positive displacement meters in accordance with AWWA M6, with isolating
valves on inlet and outlet. Provide full line size bypass with globe valve for liquid
service meters.
A. Install water service in accordance with utility company requirements with water
meter with by-pass valves and sand strainer.
B. Install water meter and backflow preventer in concrete vault located on site. Refer to
Plumbing Specialties section.
E. Install 1.2 mm galvanized sheet metal sleeve surrounding service main to 150 mm
above floor and 1800 mm minimum below grade. Size for 50 mm minimum of glass
fiber insulation stuffing.
B. Perform pressure test on domestic site water distribution system in accordance with
AWWA C600.
L = (SD\/¯¯P)/133,200
L = allowable, in gallons per hour
S = length of pipe tested, in inches
D = nominal diameter of pipe, in inches
p = average test pressure during leakage test, in pounds per square inch (gauge)
10. When leakage exceeds specified acceptable rate, locate source and make
repairs. Repeat test until specified leakage requirements are met.
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Sanitary sewage pipe.
2. Force main pipes
3. Underground pipe markers.
4. Manholes.
5. Catch basins and plant area drains.
6. Slow down chambers.
7. Bedding and cover materials.
B. Related Sections:
1. Section 312300 - Excavation and Fill: Product and execution requirements
for excavation and backfill required by this section.
2. Section 221316- Drainage Piping
3. Section 221319- Plumbing Specialties
4. Section 033000- Cast in Place Concrete
5. Section 230501- Basic Mechanical procedures and methods.
6. Section 230593- Testing Adjusting and Balancing
B. Cleanout:
1. Basis of Measurement: By the unit for nominal depth of m.
2. Basis of Payment: Includes hand trimming excavating, foundation pad, unit
installation with accessories, and connection to sewer piping.
1.3 REFERENCES
B. ASTM International:
1. ASTM A74 - Standard Specification for Cast Iron Soil Pipe and Fittings.
2. ASTM A746 - Standard Specification for Ductile Iron Gravity Sewer Pipe.
3. ASTM C14M - Standard Specification for Concrete Sewer, Storm Drain, and
Culvert Pipe (Metric).
4. ASTM C76M - Standard Specification for Reinforced Concrete Culvert,
Storm Drain, and Sewer Pipe (Metric).
5. ASTM C443M - Standard Specification for Joints for Circular Concrete
Sewer and Culvert Pipe, Using Rubber Gaskets (Metric).
Uptown Cairo – Village Z3 – Utilities 333000 - Sanitary Sewerage Utilities
IFC-Rev.00 Page 1 of 8 October 2018