Septic Tank Estimation
Septic Tank Estimation
Septic Tank Estimation
Sanitary items
Includes flush type latrines and connections with
sewer lines of septic tank.
Estimation is taken as no. of fittings including
fitting charge.
Latrine seat, flushing cistern, flushing pipe etc.
can be taken as one item including fittings.
Wash- hand basins, bath tubs, Urinals etc. are
estimated per number for complete work.
Contd.
• Fittings like valve, cowl, gully trap, master tap etc.
are estimated per number.
• Pipe lines of different materials and diameter are
taken in running meter including fittings,
excavation, jointing, refilling etc. complete.
• Length measured along the centre line of the
pipes and fittings.
• Manhole is a hole in the ground used to access
the sewers or other under ground installations.
• Manholes and inspection chambers are estimated
per no. including G.I. manhole cover
Contd.
• Detailed estimate of manhole and I.C. can be
prepared separately if required.
• Latrine seat, siphon, foot rest, flushing cistern,
flushing pipes are taken separately per
number
• Septic tank
• Used in rural areas, factories, unsewered
urban and semi urban areas for disposal of
night soil
Contd.
• Capacity
• Liquid capacity- 0.07 to 0.13 cu.m. per head
• Minimum width- 60cm
• Minimum liquid depth – 100cm below water level and
30cm above water level- free board
• Two chambers with a partition wall L/2 distance from
inlet end
• 15 cm X 15cm partition wall at 45cm from the bed of
tank. 15 cm above liquid surface
• Small tanks – one chamber with hanging baffle walls.
Contd.
• Length of tank L= 2 to 4 times width, B
• Other parts
• 20cm thick brick wall
• Foundation- floor concrete 1:3:6 or 1:2:4
• Plastering inside and outside – cement mortar 1:3,
12mm thick.
• Floor slope 1 in 20.
• Cover R.C.C slab 1:2:4 c.c. with circular opening
covered with C. I manhole cover.
• Small tank – R.C.C slab strips
Contd.
• Connecting pipe – 100mm dia. S.W or C.I.
• Inlet and outlet may be provided with T
junction.
• Ventilation pipe 50mm dia. 1.8m height above
roof slab.
• Soak pit or seepage pit
• Diameter not less than 90cm
• Depth not less than 1.5 m
Contd.
• Constructed with lining of dry brick or stone
open jointed backed with not less than 7.5 cm
thick coarse aggregate. Upper 45 cm should
be made with masonry in mortar for
strengthening, to prevent entry of outside
water and rats. Cover is R.C.C slab
• Absorption area 1 to 1.5 sq.m. per user
• It should be raised above ground level
Design of septic tank
• 25 user capacity
• Liquid capacity of tank = 0.1 cubic meter per user= 2.5
cu. m.
• Take liquid depth 1.4 m., free board= 0.3m
• Floor area= 1.8 sq.m.
• Take length= 2.25 B, LxB=1.8 sq. m.
• 2.25xBxB=1.8
• B= 0.9m
• L= 2.25X 0.9= 2.02=2m.
• Take 30cm free board, total depth= 1.7m
• Tank size = 2m long, 0.9m wide and 1.7m deep
Contd.