Multi-Functional Primary Test System For Substation Commissioning and Maintenance
Multi-Functional Primary Test System For Substation Commissioning and Maintenance
Multi-Functional Primary Test System For Substation Commissioning and Maintenance
2
Ground Micro ohmmeter
resistance meter 400 ADC
29 kg / 64 lbs
single phase wall outlet
Winding resistance meter
400 A DC Multimeter
(V, I, R, Z, ...)
800 AAC
2 kA (with booster)
Step up transformer
2 000 V
15 Hz - 400 Hz transformers)
4
>> Durable case design for rough environments with
test field accuracy
>> Long lifetime due to high quality components
>> Premium quality cables and clamps
>> Comprehensive documentation (e.g. user manual
with connection diagrams, software help function,
videos, application notes)
5
CPC 100 product family – Extended range of applications
The CPC 100 covers a lot of different applications in and around substations as well as at the manufacturer’s production site.
Extended by a high number of valuable accessories the application range of the CPC 100 is further expanded.
Thus it is the ideal instrument for all major applications in the area of primary testing.
CPC 100
Applications
6
Extended range
with accessories
Grounding box
HV-source
Remote control Power and distribution transformer
diagnosis (page 12 – 13)
Compensation reactor
Resonance circuit
7
Current transformer (CT) testing
With the CPC 100 many standard electrical tests for CTs
can be performed with one single device saving testing
time and labor costs. Additionally, unconventional CTs, like
Rogowski coils and IEC 61850 integrated systems, can also
be tested.
+ CPOL2
The CPOL2 can check the correct
polarity along the different
connection points in the secondary
wiring by analyzing the sawtooth
signal injected into the CT’s primary
Your benefits side using the CPC 100.
8
Winding resistance measurment
Using the winding resistance measurement function also Current transformer testing
allows the user to calculate the accuracy limiting factor (ALF) >> CT ratio (with burden)
for protection circuits and the instrument security factor (FS) up to 800 A or 2 000 A with CP CB2, 5 kVA output power
for metering circuits.
>> CT burden
up to 6 A AC | secondary
Power/dissipation factor (PF/DF) measurement
>> CT excitation curve
When combined with the CP TD1, the CPC 100 is also (knee point) up to 2 kVAC
capable of performing PF/DF measurements. This helps >> Polarity check with CPOL2
to assess the insulation condition of the CT. up to 800 A or up to 2 000 A with CP CB2
+ CP CB2 + CP TD1
With the CP CB2 primary injection of For high-voltage CTs, insulation material
current up to 2 kA can be realized for tests are very important and can be easily
CT testing. done with the CP TD1 accessory.
9
Voltage transformer (VT) / potential transformer testing
Your benefits
10
Disturbance-free measurement
The VT‘s secondary signal may be difficult to measure if it Voltage/potential transformer testing
is small in amplitude – especially if neighboring parts of the >> VT ratio
substation are in operation. In case of strong disturbances, up to 2 kVAC | polarity and burden
the user can select a frequency different to that of the >> VT burden
power system and utilizes the “frequency selective mea- up to 130 VAC | secondary
surement” function. Thus only the VT‘s output signal with
>> VT secondary voltage withstand test
this particular frequency is measured while all other signals
up to 2 kVAC
are filtered out.
>> Polarity check with CPOL2
up to 2 kVAC
>> VT electronics
up to 2 kVAC
+ CPOL2 + CP TD1
The CPOL2 can check the correct polarity For high-voltage VTs, insulation material
along the different connection points in tests are very important and can be easily
the secondary wiring by analyzing the done with the CP TD1 accessory.
sawtooth signal injected into the VT’s
primary side using the CPC 100.
11
Power transformer testing
Your benefits
12
Power/dissipation factor (PF/DF) measurement
For PF/DF measurement on power transformers and Power transformer testing
bushings, the CPC 100 is combined with the CP TD1. >> DC winding resistance (up to 100 ADC)
Measuring this factor over a broad frequency range – in >> Transformer demagnetization (with CP SB1)
addition to mains frequency – helps to better assess the
>> Dynamic load tap changer diagnostics
insulation condition, for example detect whether the
(on load tap changer test) (up to 100 ADC | optionally with CP SB1)
cellulose or the oil is contaminated by moisture.
>> Transformer turns ratio (TTR) per tap
up to 2 kVAC | including polarity and excitation current |
Dynamic resistance measurement (DRM)
IEC 61387-1 support for transformer with unconventional vector groups
The DRM can be performed as a supplementary
>> Automatically determination of the transformer’s
measurement in order to analyze the OLTC’s switching
vector group (with CP SB1)
process. The CPC 100 + CP SB1 injects a DC current in
the same way that it does for static winding resistance >> Leakage reactance / short circuit impedance (up to 6 A AC)
measurements with the the addition of recording the >> Transformer, bushing: power/dissipation factor
dynamic behaviour of the diverter switch. Based on this + insulation capacitance
non-invasive testing method, failures can be detected up to 12 kV, 300 mA | frequency from 15 Hz to 400 Hz | with CP TD1
without opening the OLTC compartment. >> Insulating fluids: power/dissipation factor
up to 12 kV, 300 mA | with CP TD1 and CP TC12
>> Excitation current per tap (up to 12 kV, 300 mA | with CP TD1)
>> Frequency response of stray losses (FRSL)
>> Surge arrestors: leakage current and watt losses
up to 12 kV, 300 mA | with CP TD1
HV-source
13
Line impedance measurement
X in Ω
Line parameters for distance protection
Correct line parameters are crucial for reliable and selective
distance protection. The set of parameters contains the
s m
positive and the zero sequence impedance (Z1, Z0) as well
30 0
as the k-factor (kL, RE/RL and XE/XL, k0).
t =
100 % of
ms
2
L
Line length
Z
0
These parameters are often calculated from software
e 2,
n ce
t1 =
tools, which do not provide actual line parameters due to
Zo n
e da
e 1,
unknown soil properties, such as different soil resistivities,
im p
Zo n
n c e l a te d
pipelines or other unknown conductors. This leads to
L in e
n
d
p e alc o u
under- or overreach of your distance protection relay
im l t : C - gr
u
o
resulting in outage and loss of grid stability.
Fau ase -t
da
Ph
Zone under- and overreach
The most frequent faults on power lines are ground faults. R in Ω
In particular, inaccuracies from software calculation effect
this kind of fault. The example on the right shows a zone
overreach for a ground fault due to an incorrect k-factor
setting. In this case the assumed k-factor is higher than the
actual one. Therefore, a ground fault at the remote end of
the line is seen incorrectly in the first zone.
Incorrect k-factor (tendancy to overreach)
Mutual coupling
With this unique testing equipment, the mutual coupling
impedance between parallel lines can also be determined
to consider coupling effects for correct parameterization.
Your benefits
14
Testing with the CPC 100
The main unit CPC 100 generates the frequency variable Cable and transmission line diagnosis
test current and measures current and voltage by applying >> Line impedance and k-factor
digital filtering for high accuracy. The complex loop up to 100 A | with CP CU1
impedance is then calculated accordingly. >> Mutual coupling
The CP CU1 provides galvanic isolation between the line up to 100 A | with CP CU1
under test and the CPC 100 as well as impedance matching >> Positive or zero sequence impedance
for short and long lines.
The CP GB1 protects the test equipment and the user
from any unexpected overvoltage on the line under test.
Furthermore it allows a direct connection to the power line
for a convenient execution of the test.
A dedicated test template provides the positive and
the zero sequence impedance as well as the k-factor in
commonly used formats. Furthermore it shows the actual
zone reach for each fault type based on the measured
values and relay parameters that are currently being used.
+ CP CU1
The CP CU1 allows the safe connection
of the CPC 100 to a power line or
HV cable. The impedance matching
transformer within the CP CU1 ensures
optimum power transfer from the
CPC 100 to the power line.
Ground grid
CP GB1 15
Grounding system testing
Your benefits
Ground grid
>> Determine true test values by
power line injection
>> Simple and accurate step and touch
voltage measurements with handheld
HGT1 device
>> Reduction factor measurement on
ground wires and cable shields
16
Step and touch voltage measurement
Step and touch voltage measurements according to Ground system analysis
EN 50522 and IEEE 81 are performed with the HGT1. >> Ground grid impedance for large systems
This handheld device employs frequency selective up to 100 A | with CP CU1
measurements for effective noise suppression. >> Step and touch voltage
Furthermore, tests can be executed quickly and easily since up to 100 A | with CP CU1 and HGT1
long test cables for connecting to the main device are no >> Ground grid impedance for small systems
longer necessary. up to 6 A AC
Dedicated test templates assess measured step and touch >> Soil resistivity
voltages according to EN 50522 and IEEE 80 automatically. up to 6 A AC
+ HGT1
Primary Test Manager (PTM) and
HGT1 enable you to quickly, simply
and conveniently measure ground
impedance as well as step and touch
voltage. Due to a new approach there
is no operational personal required at
the CPC 100 anymore. Together, the
test director and assistants perform all
measurements out in the field in order to
avoid miscommunication and selection of
inadequate test points.
When testing large ground grids the potential of the ground grid under test and
the counter electrode must not overlap. This is done in order to ensure human
safety in a worst case scenario, which is always crucial. The CPC 100 + CP CU1
overcomes this problem by injecting the test current into a remote substation via
an existing power line.
17
Rotating machines diagnosis
Why test rotating machines? PF/DF measurement and PF/DF tip-up test
Rotating machines, such as motors and generators, are The PF/DF measurement is used as a maintenance tool for
highly important components in power generation and entire windings. The portable solution CPC 100 + CP TD1 +
industrial applications. Therefore machine reliability and CP CR500 allows PF/DF measurements to be carried out at
availability are in high demand. Motors and generators are nominal frequency.
exposed to high thermal, mechanical and electrical stress The measurement results can be compared with previous
that influences their reliability and life expectancy. measurements, factory acceptance tests or a phase-to-
Premature failure may lead to significant economical phase comparison can be made. An acceptable
losses, due to unexpected outages and possible damage to PF/DF offers assurance that the insulation condition allows
the asset itself. In order to plan maintenance effectively, it reliable operation.
is essential to have accurate condition information about Furthermore, a parallel partial discharge measurement
when components need to be repaired or replaced. allows for a more detailed diagnosis of the type of fault.
A variety of electrical tests can be performed with the The CPC 100 + CP TD1 can be used as HV source for the
CPC 100 over the complete life cycle of machines to partial discharge measurement.
increase their reliability, prevent premature failures and to The measurement complies with international standards
extend reliable service life. such as IEC 60894 and IEEE 286.
Your benefits
18
DC winding resistance measurement
A DC resistance measurement is performed to detect Rotating machines diagnosis
possible contact problems in the stator and rotor winding >> Power/dissipation factor tip-up test
of a machine. at 50 Hz / 60 Hz
up to 12 kV | 5 A| with CP TD1 and CP CR500
The CPC 100 offers an integrated micro ohmmeter with
a maximum output of 400 A. The 4-wire method is used >> Power/dissipation factor test with variable frequency
to detect connection problems in the stator winding (bad up to 12 kV | frequency from 15 Hz to 400 Hz | with CP TD1
soldering contacts) as well as contact problems on the pole >> HV source for testing rotating machines
connectors of the rotor winding. up to 12 kV | max. 2 µF | with CP TD1 and CP CR500
Both failures can be the root cause of a local hotspot and >> DC winding resistance measurement
potentially damage the machine. up to 400 A DC and 5 kVA down to the microohm range.
+ CP CR500 + CP TD1
The CP CR500 compensator Insulation condition assessment of
reactor enables the CP TD1 to be motors and generators. The CPC 100
used with test objects with large + CP TD1 can provide up to 12 kV. It
capacitance such as large motors can be be used as HV source and
and generators. PF/DF measurement system at the
same time.
19
Gas-insulated switchgear testing
>> The complete test system is difficult to transport, The CPC 100 + CP RC system comprises several small and
because it consists of very heavy and large light-weight components (< 21 kg / 46 lbs) which can
components. be transported by one person. With its modular design
GIS tests can even be accomplished at test sites with
>> It is difficult to use it at test sites with limited space,
limited space.
such as wind turbines.
>> The HV test lead must be connected to, and
disconnected from, the GIS system for testing. This
normally includes a time-consuming venting and
refilling process of the SF6 gas.
Your benefits
20
Powerful voltage withstand testing
When combined with the CP RC1, the CPC 100 allows GIS testing
withstand tests with a maximum test voltage of 200 kV >> Withstand test
to be carried out on GIS systems up to a rated voltage of up to 235 kV | max 1.6 nF | with CP RC2
123 kV. The CPC 100 + CP RC2 is appropriate for testing >> HV source for partial discharge measurements
GIS systems with a rated voltage of up to 145 kV and a up to 235 kV | max 1.6 nF | with CP RC2
maximum test voltage of 235 kV. This package is supplied
with the additional CP AT1 auto-transformer to guarantee
the necessary output power of the CPC 100 for higher loads.
+ CP CR + CP TR + CP AT1
With the compensating reactor The isolation transformer CP TR The auto-transformer CP AT1
4 mH CP CR4 or 6 mH CP CR6 provides a potential-free output allows to connect the mains
the CP CR compensates the signal and compensates the supply of the CPC 100 to a
capacitance in a modular fashion. capacitive load. three-phase 16 A power outlet,
and delivers the required power
for the test setup.
21
Switchgear and circuit breaker testing
Your benefits
22
Insulation testing of circuit breakers
For power/dissipation factor measurements on CBs, the Switchgear / circuit breaker testing
CPC 100 is combined with the CP TD1. Measuring this >> Contact resistance
factor over a wide frequency range – in addition to mains up to 400 ADC
frequency – helps to better assess the insulation condition. >> Bushing: power/dissipation factor (tan δ)
+ insulation capacitance
12 kV, 300 mA | frequency from 15 Hz to 400 Hz | with CP TD1
23
Commissioning and trouble shooting of protection systems
CB
Busbar
Your benefits
Control room
24
Timing of CBs with overcurrent elements
For testing of CBs or load breaker switches with integrated Protection installation testing
overcurrent elements, the CPC 100 can inject AC primary >> CT ratio (with burden)
currents up to 800 A (or 2000 A together with the current up to 800 A or 2000 A with the CP CB2, 5 kVA output power
booster CP CB2), and measure the time from the start of >> CT burden
the injection to the interruption of the current. up to 6 A AC | secondary
VT CT
Wiring
terminal
HV yard
25
IEC 61850-9-2 Sampled Values testing
0111000
Your benefits CT
800 A
26
Sampled Values testing with the CPC 100
The CPC 100 test system performs closed-loop testing Sampled Values testing
whereby a test signal is injected on the primary side >> SV CT ratio test and polarity check
of the current / voltage sensors. The MU converts the up to 800 A or up to 2 000 A , 5 kVA output power | with the CP CB2
sensor output into a SV stream which is published to the >> SV VT ratio test and polarity check
substation network. The CPC 100 then reads the data up to 2 kVAC
back from the network in order to perform a variety of
>> Automatic MU detection
different tests.
>> Automatic voltage / current channel detection
Automatic MU and channel detection is achieved by
>> Frequency selective voltage / current meter
injecting a test signal with a specific wave form. An
optimized and time-effective algorithm searches for the >> Noise level measurement
unique test pattern within all the available MUs on the >> Amplitude response of the signal processing chain
network to identify the correct channel for testing. up to 800 A or up to 2 kVAC | frequency from 15 Hz to 400 Hz
0111000001
MU Substation
Network
VT
27
Operation of CPC 100: front panel
Operating from the front panel The test template can be seen as a test plan. It tells the user
which measurements to make and provides the basis for
Selecting test cards directly the overall test report.
Operating the CPC 100 manually provides the quickest Test templates can be prepared in advance in the office on
results with minimal training and preparation – perfect for the PC – without the CPC 100 connected – and can then be
users who only operate the device occasionally. The user just executed on site, step by step. Users can also create their
selects the test card to be used, connects the CPC 100 to the own test templates and define, which test cards they want
asset and performs the test by pressing the start button. to include.
The settings and results of all manual tests can be stored
Using pre-defined test templates on a flash memory and transfered to a PC using a USB
memory stick or ethernet connection.
Additionally, pre-defined test templates help the user to
perform frequently used tests conveniently and efficiently.
A number of test cards (for example, power/dissipation
factor, winding resistance, ratio measurement, etc.) are
combined into one test template. An example is the
template containing all the recommended measurements
for testing a current transformer.
28
Customized reporting: Microsoft Excel™
After transferring the test results to a PC, report templates Different ways to operate
in numerical and graphical form are available.
The CPC 100 offers different operating modes, to meet
The measurement data – including settings and results as the personal preferences of the user:
well as administrative information such as date and time, >> From the front panel:
filename, etc. – can also be imported to these templates Selecting test cards directly
for customized reporting, graphical result evaluation and
>> From the front panel:
further analyses.
Using pre-defined test templates
Microsoft Excel™ reports provide the basis for client-
>> Fully automated:
specific reporting and allow test reports to be adapted to
Using Primary Test Manager™ (see next page)
utility or manufacturer specific formats. Further content,
such as company logos, can also be added.
Test reports can then be printed in a variety of languages.
Test report
29
Step by step through the test procedure with Primary Test ManagerTM
Easy management of location, asset and test data due to a structured database, PTM supports in the best possible
implemented search and filter functions and automatic data synchronization. wiring diagrams and asset-specific
30
Executing diagnostic tests Result analysis and reporting
PTM helps to define the test asset with specific nameplate A real-time overview of the test results is given during the
views. It indicates mandatory and recommended measurement and an instant “pass/fail” assessment of
parameters, making data entry fast and easy. the test results is displayed based on specified limit values.
Based on the nameplate values, PTM generates a PTM automatically generates reports including all asset-
customized test plan according to current standards and related information and the tests that have been performed.
guidelines for each asset. This way PTM is able to provide This gives a comprehensive overview of the test object, test
you with a comprehensive test plan for assessing the results and assessment.
condition of your asset thoroughly.
Comparison tools for detailed analysis
Easy connection due to wiring diagrams For a detailed analysis, different test results can be
Pre-configured wiring diagrams based on selected assets compared side-by-side or trended over time. Users can
help to set up the CPC 100 correctly. This minimizes the choose between a time- and type-based comparison
likelihood of measurement errors and speeds up the as well as a phase-based comparison.
testing process.
Customized, individual reports
User can adapt reports to their needs in PTM. Reports can
be generated in Microsoft Word™, Microsoft Excel™ and
as a PDF file.
They can be further adapted by e.g. compiling the included
parts, providing comments or incorporating a company logo.
way during execution of diagnostic tests via For a comprehensive analysis, PTM offers automatic result assessment
test plans according to international standards. and comparison as well as customized reporting.
31
Front panel and connection possibilities
1 4 5 9 11 15 16
2 19
12 13
17
3
6 7 8 10 14
18
32
29
28
30 31 32
20 21 22
23
24 25 26 27
19. Keys for the quick selection of applications 29. Serial interface for devices such as CP TD1
20. Keys for the quick selection of the desired view 30. Plug to connect external safety functions
21. LCD monitor 31. Socket for the connection of the CPC 100
22. Soft-touch keys which change their function to a network or direct connection to a
according to the selected application PC’s network connector
23. Keys for selecting stacked test cards 32. USB memory stick connection
24. Numerical keyboard
25. Advanced jog-dial hand wheel with “click”
(Enter) function
26. Up / down keys for navigation and entering values
27. Test start / stop button
28. User manual
33
Technical data CPC 100
CPC 100
6 A AC 10
0 ... 6 A >2h 55 V 330 VA 15 Hz ... 400 Hz 1 A AC < 0.05 % < 0.05 % < 0.15°
3 A AC10 0 ... 3 A >2h 110 V 330 VA 15 Hz ... 400 Hz 10 A DC < 0.03 % < 0.08 % –
400 A DC 0 ... 400 A 2 min. 6.5 V 2 600 VA DC 1 A DC < 0.03 % < 0.08 % –
0 ... 200 A >2h 6.5 V 1 300 VA DC 30 V < 0.05 % < 0.05 % < 0.10°
6 A DC 4, 10
0 ... 6 A >2h 60 V 360 VA DC 3V < 0.10 % < 0.05 % < 0.10°
2 000 A AC 3 with an optional current booster (CP CB2) 300 mV < 0.15 % < 0.05 % < 0.10°
V2 AC 8, 11
10 MΩ 3V < 0.03 % < 0.08 % < 0.10°
300 mV < 0.08 % < 0.08 % < 0.10°
Voltage outputs
30 mV < 0.10 % < 0.25 % < 0.15°
Range Amplitude5 tmax Imax Powermax5 f
2 kV AC 3 0 ... 2 kV 1 min. 1.25 A 2 500 VA 15 Hz ... 400 Hz V DC4, 7 10 V < 0.03 % < 0.08 % –
0 ... 2 kV >2h 0.5 A 1 000 VA 15 Hz ... 400 Hz 1V < 0.03 % < 0.08 % –
1 kV AC 3 0 ... 1 kV 1 min. 2.5 A 2 500 VA 15 Hz ... 400 Hz 100 mV < 0.05 % < 0.10 % –
0 ... 1 kV >2h 1.0 A 1 000 VA 15 Hz ... 400 Hz 10 mV < 0.05 % < 0.15 % –
500 V AC 3 0 ... 500 V 1 min. 5.0 A 2 500 VA 15 Hz ... 400 Hz
Additional features of the measuring inputs
0 ... 500 V >2h 2.0 A 1 000 VA 15 Hz ... 400 Hz
Automatic range switching (except Amplifier test card)
130 V AC10 0 ... 130 V >2h 3.0 A 390 VA 15 Hz ... 400 Hz Galvanically separated potential groups: I AC/DC ; V1 & V2 ; V DC
AC frequency range: 15 Hz to 400 Hz (except Amplifier test card)
Protection of I AC/DC input: 10 A very fast acting (FF) fuse 4
Internal measurement of outputs (Accuracy6)
Binary input for dry contacts or voltages up to 300 V DC7
Amplitude Amplitude Phase Trigger criteria: Toggling with potential-free contacts or
Output Range Reading Full scale Full scale voltages of up to 300 V
Error Error Error Input impedance: > 100 kΩ
Response time: 1 ms
800 A AC – < 0.10 % < 0.10 % < 0.10°
400 A DC – < 0.20 % < 0.05 % – Output to input synchronization
2 kV AC 2 000 V < 0.05 % < 0.05 % < 0.10° Test cards Quick, Amplifier test card
1 000 V < 0.05 % < 0.05 % < 0.15° Sequencer, Ramping
Frequency range 48 Hz ... 62 Hz 48 Hz ... 62 Hz
500 V < 0.05 % < 0.05 % < 0.20°
Synchronization V1 AC V1 AC, V2 AC, I AC
5A < 0.20 % < 0.05 % < 0.10° inputs (automatic range switch) (fixed to maximum range)
500 mA < 0.05 % < 0.05 % < 0.10° Input 10 % of input range full scale
magnitude
Output 5 % of output range full scale
magnitude
Settling time 100 ms after 5 % of 1 000 ms after 5 % of
output range full scale output range full scale
is reached is reached
Signal changes All quantities must be No changes of frequency
ramped within 20 signal and phase. Magnitude
periods changes without limitation.
Output follows within
250 ms
Phase tolerance 0.5 ° within the limits as specified above
34
Resistance measurement
4-wire measurement with 400 A DC output and 10 V DC input All input / output values are guaranteed for one year within an
ambient temperature of 23 °C ± 5 °C / 73 °F ± 10 °F, a warm-up time
Current Resistance Voltage Accuracy (full scale)
longer than 25 min. and in a frequency range of 45 Hz to 60 Hz or DC.
400 A 10 μΩ 4 mV Error < 0.70 %
Accuracy values indicate that the error is smaller than ± (value read x
400 A 100 μΩ 40 mV Error < 0.55 % reading error + full scale of the range x full scale error).
400 A 1 mΩ 400 mV Error < 0.50 % 1. With a mains voltage of 230 V using a 2 × 6 m high-current cable
at an ambient temperature of 23 °C ± 5 °C / 73 °F ± 10 °F.
400 A 10 mΩ 4V Error < 0.50 %
2. The power and maximum voltage may be reduced above 60 Hz
4-wire measurement with 6 A DC output and 10 V VDC input or below 50 Hz.
Current Resistance Voltage Accuracy (full scale) 3. Output can be synchronized with V1 AC in Quick, Sequencer,
6A 100 mΩ 0.6 V Error < 0.35 % Ramping and Amplifier test cards.
6A 1Ω 6V Error < 0.35 % 4. The inputs and outputs are protected with lightning arrestors
between the connector and against the protective earth. In the
1A 10 Ω 10 V Error < 0.25 % event of application of energy exceeding a few hundred Joule the
2-wire measurement with 10 V VDC input lightning arrestors apply a permanent short-circuit to the input /
output.
Current Resistance Voltage Accuracy (full scale)
5. The power and amplitude may be reduced above 200 Hz or
> 5 mA 100 Ω Error < 0.60 % below 50 Hz.
> 5 mA 1 kΩ Error < 0.51 % 6. 98 % of all units have an accuracy better than specified as “typical”.
> 5 mA 10 kΩ Error < 0.50 % 7. This input is galvanically separated from all other inputs.
8. V1 and V2 are galvanically coupled but separated from all other
Power supply and mechanical data inputs.
9. There are power restrictions for mains voltages below 190 VAC.
Single-phase, 100 VAC ... 240 VAC, 16 A
nominal9 10. Fuse-protected.
Single-phase, 85 VAC ... 264 VAC (L-N or L-L) 11. When using the CTRogowski test card, the 3 V V2 AC input uses
permissible an additional software based integration method. In the range of
50 Hz < f < 60 Hz, this results in a phase shift of 90 ° as well as an
Frequency, nominal 50 Hz / 60 Hz additional phase error of ± 0.1 ° and an additional amplitude er-
Power consumption < 3 500 VA (< 7 000 VA for a time < 10 s) ror of ± 0.01 %. For frequencies in the range of 15 Hz < f < 400 Hz,
the phase error is not specified, and the amplitude error can be
Connection IEC 320 / C20
up to ± 0.50 % higher.
Weight 29 kg / 64 lbs (case without protection cover)
Dimensions 468 × 394 × 233 mm (18.4 × 15.5 × 9.2 in),
(W × H × D) cover, without handles.
Equipment reliability
Shock IEC / EN 60068-2-27, 15 g / 11 ms,
half-sinusoid, each axis
Vibration IEC / EN 60068-2-6, frequency range from
10 Hz to 150 Hz, continuous acceleration 2 g
(20 m /s2 / 65 ft /s2), 10 cycles per axis
35
Technical data CPC 100 accessories
36
CP CU1 – Coupling unit
In combination with the CPC 100 the CP CU1 is used for line parameter measurements and ground testing.
37
Technical data CPC 100 accessories
38
Ordering information
CPC 100 Standard Package Package including CPC 100 and all accessories to perform
VE000611
includes CPC 100 Basic Package common electrical tests on instrument and power transformers.
CPC 100 Enhanced Package In addition to the standard package powerful tools for
VE000621
includes CPC 100 Standard Package substation comissioning are provided.
39
Ordering information
40
CPC 100 Upgrade Options
PTM advanced for HGT1 Upgrade option for the Ground Impedance and Step & Touch
VESM0626
Upgrade Option Voltage Set to use the guided PTM workflow with your HGT1.
41
A strong and safe connection
Don Platts
Application Specialist
42
Wenyu Guo
OMICRON Academy
Christoph Engelen
Technical Support
43
OMICRON is an international company serving the electrical power industry with
innovative testing and diagnostic solutions. The application of OMICRON products
allows users to assess the condition of the primary and secondary equipment on
their systems with complete confidence. Services offered in the area of consulting,
commissioning, testing, diagnosis and training make the product range complete.
Customers in more than 140 countries rely on the company’s ability to supply leading-
edge technology of excellent quality. Service centers on all continents provide a broad
base of knowledge and extraordinary customer support. All of this together with our
strong network of sales partners is what has made our company a market leader in the
electrical power industry.
The following publications provide further information on the solutions described in this
brochure:
For more information, additional literature, and detailed contact information of our
worldwide offices please visit our website.