Building Dimensions:: Wind Loads
Building Dimensions:: Wind Loads
Building Dimensions:: Wind Loads
BUILDING DIMENSIONS:
Length, l = 144.00 m; Width, w = 116.00 m; Eaves height, h = 13.00 m
h/w = 0.11; l/w = 1.24
Roof angle, a = 2.86 degrees; Ridge height, h1 = 15.90 m
Max spg. of main frame cols. = 8.40 m
Max spg. of wind cols. = 7.50 m
WIND DATA:
Basic wind speed, Vb = 39 m/s...(Fig. 1)
Design life of structure: 100 years
Terrain category: 2; Building category: Industrial
Upwind slope < 3 degrees; Permeability: Medium (Cpi = +/- 0.5)
Building ht. at eaves lvl. (z) =13.00 m
k1 (Risk coefficient) = 1.06...(Table-1)
k3 (Topography factor) = 1.00...(Cl. 6.3.3.1)
k4 (Importance factor) = 1.15...(Cl. 6.3.4)
CANOPY:
Location: Side-A; Height, hc = 5.00 m
h/hc = 2.60 => h/hc > 1.8 => Cpe (a/s) = 0.44
Canopy slopes up => hence Cpe (u/s) = 0.75
Ka,canopy = 0.90
pd,canopy = Kd x Ka,canopy x Kc x pz = 1.05
ROOF MONITOR:
Ka,monitor (column) = 1.00; Ka,monitor (roof) = 1.00
pd,monitor (column) = Kd x Ka,monitor (column) x Kc x pz =1.17
pd,monitor (roof) = Kd x Ka,monitor (roof) x Kc x pz =1.17
Values of Cpe, Cpi, Cp,net and UDL are given in tabular form in the tables that follow.
Element:
Client: ABC
WIND LOAD-CAL
Project: ABC Doc. No.: SAMPLE-CAL Location/ Grids:
Rev. Ppd. by Date Chd. by Date ---
Project: ABC,HYD 2 - - - - Designation:
Structure: PEB 1 - - - - WIND LOAD-CAL
Type: GABLE-FRAME 0 - - . - - Sht. 01 of 05
FORM NO : ECE-E0001
WIND PRESSURE VALUES FOR STAAD LOAD CASE (WL+X)
WL+XP WL+XS
UDL
ID Cpi UDL STAAD Cpi UDL STAAD
Cpe Cp,net Cpe Cp,net
(+ve) (kN/m) dirn (-ve) (kN/m) dirn
w1 0.700 0.50 0.200 1.69 GX 0.700 -0.50 1.200 10.15 GX
w2 0.700 0.50 0.200 0.85 GX 0.700 -0.50 1.200 5.08 GX
w3 0.700 0.50 0.200 1.69 GX 0.700 -0.50 1.200 10.15 GX
w4 0.700 0.50 0.200 0.85 GX 0.700 -0.50 1.200 5.08 GX
w5 -0.200 0.50 -0.700 5.92 GX -0.200 -0.50 0.300 -2.54 GX
w6 -0.200 0.50 -0.700 2.96 GX -0.200 -0.50 0.300 -1.27 GX
w7 - - - - - - - - - -
w8 - - - - - - - - - -
w9 -0.500 0.50 -1.000 -7.55 GZ -0.500 -0.50 0.000 0.00 GZ
w10 -0.500 0.50 -1.000 -3.78 GZ -0.500 -0.50 0.000 0.00 GZ
w11 -0.500 0.50 -1.000 7.55 GZ -0.500 -0.50 0.000 0.00 GZ
w12 -0.500 0.50 -1.000 3.78 GZ -0.500 -0.50 0.000 0.00 GZ
w13 -0.600 0.50 -1.100 9.31 LY -0.600 -0.50 -0.100 0.85 LY
w14 -0.600 0.50 -1.100 4.65 LY -0.600 -0.50 -0.100 0.42 LY
w15 -0.500 0.50 -1.000 8.46 LY -0.500 -0.50 0.000 0.00 LY
w16 -0.500 0.50 -1.000 4.23 LY -0.500 -0.50 0.000 0.00 LY
w17 -0.310 0.00 -0.310 2.73 LY -0.310 0.00 -0.310 2.73 LY
w18 -0.310 0.00 -0.310 1.37 LY -0.310 0.00 -0.310 1.37 LY
w19 - - - - - - - - - -
w20 - - - - - - - - - -
w21 0.700 0.50 0.200 1.96 GX 0.700 -0.50 1.200 11.75 GX
w22 -0.600 0.50 -1.100 10.77 GX -0.600 -0.50 -0.100 0.98 GX
w23 -0.800 0.50 -1.300 12.73 LY -0.800 -0.50 -0.300 2.94 LY
w24 0.700 0.50 0.200 0.98 GX 0.700 -0.50 1.200 5.87 GX
w25 -0.600 0.50 -1.100 5.38 GX -0.600 -0.50 -0.100 0.49 GX
w26 -0.800 0.50 -1.300 6.36 LY -0.800 -0.50 -0.300 1.47 LY
Element:
Client: ABC
WIND LOAD-CAL
Project: ABC Doc. No.: SAMPLE-CAL Location/ Grids:
Rev. Ppd. by Date Chd. by Date ---
Project: ABC,HYD 2 - - - - Designation:
Structure: PEB 1 - - - - WIND LOAD-CAL
Type: GABLE-FRAME 0 - - . - - Sht. 02 of 05
FORM NO : ECE-E0001
WIND PRESSURE VALUES FOR STAAD LOAD CASE (WL-X)
WL-XP WL-XS
UDL
ID Cpi UDL STAAD Cpi UDL STAAD
Cpe Cp,net Cpe Cp,net
(+ve) (kN/m) dirn (-ve) (kN/m) dirn
w1 -0.200 0.50 -0.700 -5.92 GX -0.200 -0.50 0.300 2.54 GX
w2 -0.200 0.50 -0.700 -2.96 GX -0.200 -0.50 0.300 1.27 GX
w3 -0.400 0.50 -0.900 -7.61 GX -0.400 -0.50 0.100 0.85 GX
w4 -0.400 0.50 -0.900 -3.81 GX -0.400 -0.50 0.100 0.42 GX
w5 0.700 0.50 0.200 -1.69 GX 0.700 -0.50 1.200 -10.15 GX
w6 0.700 0.50 0.200 -0.85 GX 0.700 -0.50 1.200 -5.08 GX
w7 - - - - - - - - - -
w8 - - - - - - - - - -
w9 -0.500 0.50 -1.000 -7.55 GZ -0.500 -0.50 0.000 0.00 GZ
w10 -0.500 0.50 -1.000 -3.78 GZ -0.500 -0.50 0.000 0.00 GZ
w11 -0.500 0.50 -1.000 7.55 GZ -0.500 -0.50 0.000 0.00 GZ
w12 -0.500 0.50 -1.000 3.78 GZ -0.500 -0.50 0.000 0.00 GZ
w13 -0.500 0.50 -1.000 8.46 LY -0.500 -0.50 0.000 0.00 LY
w14 -0.500 0.50 -1.000 4.23 LY -0.500 -0.50 0.000 0.00 LY
w15 -0.600 0.50 -1.100 9.31 LY -0.600 -0.50 -0.100 0.85 LY
w16 -0.600 0.50 -1.100 4.65 LY -0.600 -0.50 -0.100 0.42 LY
w17 -0.300 0.00 -0.300 2.64 LY -0.300 0.00 -0.300 2.64 LY
w18 -0.300 0.00 -0.300 1.32 LY -0.300 0.00 -0.300 1.32 LY
w19 - - - - - - - - - -
w20 - - - - - - - - - -
w21 -0.600 0.50 -1.100 -10.77 GX -0.600 -0.50 -0.100 -0.98 GX
w22 0.700 0.50 0.200 -1.96 GX 0.700 -0.50 1.200 -11.75 GX
w23 -0.800 0.50 -1.300 12.73 LY -0.800 -0.50 -0.300 2.94 LY
w24 -0.600 0.50 -1.100 -5.38 GX -0.600 -0.50 -0.100 -0.49 GX
w25 0.700 0.50 0.200 -0.98 GX 0.700 -0.50 1.200 -5.87 GX
w26 -0.800 0.50 -1.300 6.36 LY -0.800 -0.50 -0.300 1.47 LY
Element:
Client: ABC
WIND LOAD-CAL
Project: ABC Doc. No.: SAMPLE-CAL Location/ Grids:
Rev. Ppd. by Date Chd. by Date ---
Project: ABC,HYD 2 - - - - Designation:
Structure: PEB 1 - - - - WIND LOAD-CAL
Type: GABLE-FRAME 0 - - . - - Sht. 03 of 05
FORM NO : ECE-E0001
WIND PRESSURE VALUES FOR STAAD LOAD CASE (WL+Z)
WL+ZP WL+ZS
UDL
ID Cpi UDL STAAD Cpi UDL STAAD
Cpe Cp,net Cpe Cp,net
(+ve) (kN/m) dirn (-ve) (kN/m) dirn
w1 -0.500 0.50 -1.000 -8.46 GX -0.500 -0.50 0.000 0.00 GX
w2 -0.500 0.50 -1.000 -4.23 GX -0.500 -0.50 0.000 0.00 GX
w3 -0.500 0.50 -1.000 -8.46 GX -0.500 -0.50 0.000 0.00 GX
w4 -0.500 0.50 -1.000 -4.23 GX -0.500 -0.50 0.000 0.00 GX
w5 -0.500 0.50 -1.000 8.46 GX -0.500 -0.50 0.000 0.00 GX
w6 -0.500 0.50 -1.000 4.23 GX -0.500 -0.50 0.000 0.00 GX
w7 - - - - - - - - - -
w8 - - - - - - - - - -
w9 0.700 0.50 0.200 1.51 GZ 0.700 -0.50 1.200 9.06 GZ
w10 0.700 0.50 0.200 0.76 GZ 0.700 -0.50 1.200 4.53 GZ
w11 -0.200 0.50 -0.700 5.29 GZ -0.200 -0.50 0.300 -2.27 GZ
w12 -0.200 0.50 -0.700 2.64 GZ -0.200 -0.50 0.300 -1.13 GZ
w13 -0.400 0.50 -0.900 7.61 LY -0.400 -0.50 0.100 -0.85 LY
w14 -0.800 0.50 -1.300 5.50 LY -0.800 -0.50 -0.300 1.27 LY
w15 -0.400 0.50 -0.900 7.61 LY -0.400 -0.50 0.100 -0.85 LY
w16 -0.800 0.50 -1.300 5.50 LY -0.800 -0.50 -0.300 1.27 LY
w17 -0.500 0.00 -0.500 4.40 LY -0.500 0.00 -0.500 4.40 LY
w18 -0.500 0.00 -0.500 2.20 LY -0.500 0.00 -0.500 2.20 LY
w19 - - - - - - - - - -
w20 - - - - - - - - - -
w21 -0.500 0.50 -1.000 -9.79 GX -0.500 -0.50 0.000 0.00 GX
w22 -0.500 0.50 -1.000 9.79 GX -0.500 -0.50 0.000 0.00 GX
w23 -0.800 0.50 -1.300 12.73 LY -0.800 -0.50 -0.300 2.94 LY
w24 -0.500 0.50 -1.000 -4.89 GX -0.500 -0.50 0.000 0.00 GX
w25 -0.500 0.50 -1.000 4.89 GX -0.500 -0.50 0.000 0.00 GX
w26 -0.800 0.50 -1.300 6.36 LY -0.800 -0.50 -0.300 1.47 LY
Element:
Client: ABC
WIND LOAD-CAL
Project: ABC Doc. No.: SAMPLE-CAL Location/ Grids:
Rev. Ppd. by Date Chd. by Date ---
Project: ABC,HYD 2 - - - - Designation:
Structure: PEB 1 - - - - WIND LOAD-CAL
Type: GABLE-FRAME 0 - - . - - Sht. 04 of 05
FORM NO : ECE-E0001
WIND PRESSURE VALUES FOR STAAD LOAD CASE (WL-Z)
WL-ZP WL-ZS
UDL
ID Cpi UDL STAAD Cpi UDL STAAD
Cpe Cp,net Cpe Cp,net
(+ve) (kN/m) dirn (-ve) (kN/m) dirn
w1 -0.500 0.50 -1.000 -8.46 GX -0.500 -0.50 0.000 0.00 GX
w2 -0.500 0.50 -1.000 -4.23 GX -0.500 -0.50 0.000 0.00 GX
w3 -0.500 0.50 -1.000 -8.46 GX -0.500 -0.50 0.000 0.00 GX
w4 -0.500 0.50 -1.000 -4.23 GX -0.500 -0.50 0.000 0.00 GX
w5 -0.500 0.50 -1.000 8.46 GX -0.500 -0.50 0.000 0.00 GX
w6 -0.500 0.50 -1.000 4.23 GX -0.500 -0.50 0.000 0.00 GX
w7 - - - - - - - - - -
w8 - - - - - - - - - -
w9 -0.200 0.50 -0.700 -5.29 GZ -0.200 -0.50 0.300 2.27 GZ
w10 -0.200 0.50 -0.700 -2.64 GZ -0.200 -0.50 0.300 1.13 GZ
w11 0.700 0.50 0.200 -1.51 GZ 0.700 -0.50 1.200 -9.06 GZ
w12 0.700 0.50 0.200 -0.76 GZ 0.700 -0.50 1.200 -4.53 GZ
w13 -0.400 0.50 -0.900 7.61 LY -0.400 -0.50 0.100 -0.85 LY
w14 -0.800 0.50 -1.300 5.50 LY -0.800 -0.50 -0.300 1.27 LY
w15 -0.400 0.50 -0.900 7.61 LY -0.400 -0.50 0.100 -0.85 LY
w16 -0.800 0.50 -1.300 5.50 LY -0.800 -0.50 -0.300 1.27 LY
w17 -0.500 0.00 -0.500 4.40 LY -0.500 0.00 -0.500 4.40 LY
w18 -0.500 0.00 -0.500 2.20 LY -0.500 0.00 -0.500 2.20 LY
w19 - - - - - - - - - -
w20 - - - - - - - - - -
w21 -0.500 0.50 -1.000 -9.79 GX -0.500 -0.50 0.000 0.00 GX
w22 -0.500 0.50 -1.000 9.79 GX -0.500 -0.50 0.000 0.00 GX
w23 -0.800 0.50 -1.300 12.73 LY -0.800 -0.50 -0.300 2.94 LY
w24 -0.500 0.50 -1.000 -4.89 GX -0.500 -0.50 0.000 0.00 GX
w25 -0.500 0.50 -1.000 4.89 GX -0.500 -0.50 0.000 0.00 GX
w26 -0.800 0.50 -1.300 6.36 LY -0.800 -0.50 -0.300 1.47 LY
Element:
Client: ABC
WIND LOAD-CAL
Project: ABC Doc. No.: SAMPLE-CAL Location/ Grids:
Rev. Ppd. by Date Chd. by Date ---
Project: ABC,HYD 2 - - - - Designation:
Structure: PEB 1 - - - - WIND LOAD-CAL
Type: GABLE-FRAME 0 - - . - - Sht. 05 of 05
FORM NO : ECE-E0001