Record of Continuity and Insulation Resistance Test: A. Particulars of The Installation

This document provides instructions for testing the continuity and insulation resistance of electrical circuit wiring. It includes: 1. Details to record about the installation being tested, including the project name, wiring type, and test equipment used. 2. Procedures to test continuity of circuit protective conductors (CPC) in lighting and ring final circuits, which involve connecting conductors at different points and measuring resistance. 3. A procedure to confirm a ring final circuit is wired in a ring formation by cross-connecting conductors and comparing resistance readings. 4. Notes on interpreting resistance readings and diagrams illustrating the different test connections. The document provides guidance on properly testing and documenting the condition of circuit wiring.

Uploaded by

Syazrulazri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
80% found this document useful (5 votes)
4K views2 pages

Record of Continuity and Insulation Resistance Test: A. Particulars of The Installation

This document provides instructions for testing the continuity and insulation resistance of electrical circuit wiring. It includes: 1. Details to record about the installation being tested, including the project name, wiring type, and test equipment used. 2. Procedures to test continuity of circuit protective conductors (CPC) in lighting and ring final circuits, which involve connecting conductors at different points and measuring resistance. 3. A procedure to confirm a ring final circuit is wired in a ring formation by cross-connecting conductors and comparing resistance readings. 4. Notes on interpreting resistance readings and diagrams illustrating the different test connections. The document provides guidance on properly testing and documenting the condition of circuit wiring.

Uploaded by

Syazrulazri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CAWANGAN KEJURUTERAAN ELEKTRIK FORM NO : JKR.

C&I
JKR MALAYSIA Sheet of

Record of Continuity and Insulation Resistance Test


This Record Of Continuity and Insulation Resistance Test form shall be used for the reporting on the condition of
Final Circuit Wiring for New Installation prior to the installation of switches, sockets, electrical accessories, fittings and DB.

A. PARTICULARS OF THE INSTALLATION [Please tick (√ ) the relevant boxes]


Project Name
Drawing No./Installation Address
Block No./Floor
DB Designation Single phase, Phase R Y B Three phase

System of Wiring 'loop-in' system 'tee' system

B. TEST INSTRUMENT USED


Instrument Brand Model No. Serial No. Calibration Date
Insulation & Continuity Tester
Insulation Tester

C. TEST RESULTS (Please X where not applicable. Please refer to Page 2 for notes and test procedures)
Circuit No. 1 2 3 4 5 6 7 8 9 10 11 12
Type of Wiring [see note 2 ]
Circuit Reference [see note 3 ]
Numbers of Points
Phase (mm²)
Cable Size
CPC (mm²)
Neutral & CPC , or (ohms)
RADIAL CIRCUITS (R1+R2)
Phase & CPC (ohms)
C O N T I N U I T Y

(R1+R2)
Confirmation of CPC in a radial circuit is continuous
(Mark Y for yes and N for no)
Phase (ohms)
RING FINAL CIRCUITS
Neutral (ohms)
CPC (ohms)
Phase & Neutral (ohms)
Confirmation of
Ring final Circuit Is Phase & CPC (ohms)
Wired In A Ring
Mark Y for yes and N for no

Phase to Neutral (L-N)


(Mohms)
Phase to CPC (L-E)
INSULATION (Mohms)
RESISTANCE Neutral to CPC (N-E)
(Mohms)
Phase & Neutral to G.I Conduit/Trunking
(Mohms)

D. INSULATION E. REMARKS (If Any)


TEST VOLTAGE = Volts (d.c)

F. PENGAKUAN ORANG KOMPETEN G. PENGESAHAN JABATAN


( BAGI PIHAK KONTRAKTOR ELEKTRIK)

Diuji Oleh: Disaksi Oleh:


(Nama Pendawai) (Nama)

Tandatangan: Tandatangan:

No. Kekompetenan: Jawatan:

Tarikh Ujian: Tarikh:

Nama & Cop Kontraktor:

mri/ra/wan/johor/MAC2008
Page 1 of 2
FORM NO : JKR.C&I
Sheet of

Record of Continuity and Insulation Resistance Test


A. NOTES

1 FORM NO: JKR.C&I is for single phase points in a single phase DB or three phase DB
FORM NO: JKR.IR &C is for three phase points and submain cables
2 CODES FOR TYPE OF WIRING

A B C D E F G H (Others - please state)

PVC Cables in PVC Cables PVC Cables PVC Cables PVC Cables PVC/PVC Fire
surface GI in surface in concealed in concealed in trunking Cables Resistance
conduit UPVC conduit GI conduit UPVC conduit Cables

3 CIRCUIT REFERENCE

3 L S/Rg S/Rd A/C W/H K&E S Others - (Please state)


Socket - Socket - Keluar Sign
Lighting Air Cond. Water Heater Spare
Ring Cct Radial Cct EL

B. TEST PROCEDURES
It should be noted that the continuity and insulation resistance tests for lighting circuit describe below can only be applied to a

'loop-in' wiring system only

1.0 CONTINUITY OF CPC IN LIGHTING CIRCUIT

1.10 Test method 1 (CPC conductor terminated at the last point of the circuit and using the neutral conductor as a return lead)
1.11 Connect the neutral conductor to the CPC conductor at the last point of the circuit under test.
1.12 Test between neutral and earth of the circuit at the DB
1.13 Record the test result obtained.
1.14 The readings should be compared with the " Resistance of copper conductors " table for a particular
length and size.
1.15 See Fig. 1a for Test method connections.

1.20 Test method 2 ( CPC terminated at the switch panel and using the phase conductor as a return lead)
1.21 Connect the phase conductor (phase wire) to the CPC conductor at the switch panel
1.22 Test between the phase and earth of the circuit at the DB
1.23 Record the test result obtained.
1.24 The readings should be compared with the " Resistance of copper conductors " table for a particular
length and size.
1.25 See Fig. 1b for Test method connections.

2.0 CONTINUITY OF RING FINAL CIRCUIT CONDUCTORS

2.10 The phase, neutral and CPC conductors are identified and the end-to-end resistance of each conductor
is measured separately. Record the resistance readings.
2.20 A finite reading confirms that there is continuity on the ring conductors under test
2.30 See Fig 2 for Test method connections

3.0 CONFIRMATION OF RING FINAL CIRCUIT IS WIRED IN A RING (4 ends joined method)

3.10 Phase and neutral conductors cross-connected


3.11 Connect the outgoing phase (P1) conductor to the returning neutral (N2) conductor. (P1 to N2)
3.12 Connect the returning phase (P2) conductor to the outgoing neutral (N1) conductor. (P2 to N1)
3.13 Measure the resistance across (P1 to N2) and (P2 to N1) and record the reading
3.14 Measure the resistance at each socket on the ring between phase & neutral
3.15 If the readings obtained from those Sockets wired into the ring are all the same and equal to the
resistance accross (P1 to N2) and (P2 to N1) then the ring final circuit is confirmed.
3.16 If the readings are different, this will indicate the presence of a bridge or maybe due to incorrect
connections of the ends of the ring.
3.17 If they are connected P1 to N1 and P2 to N2 then the readings will increase or decrease as
sucessive measurements round the ring are taken.
3.18 See Fig 3a for Test method connections
3.20 Phase and CPC conductors cross-connected.
3.20 The above step is then repeated but with the phase and CPC conductor cross-connected.
3.21 See Fig 3b for Test method connections

4.0 INSULATION RESISTANCE IN LIGHTING CIRCUIT


4.1 A d.c voltage not less than twice (2x) the nominal voltage of the circuit concerned (r.m.s value for an a.c supply)
shall be applied for the measurement of insulation resistance, provided that the test voltage need not exceed 500 V
d.c for installations rated up to 500V.
4.2 Test method 1 (CPC conductor terminated at the last point of the circuit)
4.21 Test between the phase (join together all phase conductors at the switch panel) and the neutral at the DB
4.22 Repeat the test for phase to CPC
4.23 Test between the neutral and the CPC at the DB
4.24 Resistance readings should be not less than 2MΩ (for circuits tested individually)
4.25 See Fig. 4a for Test method connections
4.3 Test method 2 ( CPC terminated at the switch panel )
4.31 Repeat step 4.21 to 4.23
4.32 See Fig. 4b for Test method connections

mri/ra/wan/johor/MAC2008
Page 2 of 2