XPSBCE is replaced by XPSUS
XPSBCE XPSUS
Commercial Reference Commercial Reference
XPSBCE3110C XPSUS12AC
XPSBCE3110P XPSUS12AP
XPSBCE is replaced by XPSUS
XPSBCE XPSUS
Wiring Two-Hand Control* (24VAC/DC) diagram XPSBCE & XPSUS
XPSBCE XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the connected
equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
* Wiring example for two hand control type IIIC
Safety FUNCTION position 4.
START function positions 1.
Refer to Start Functions under your user guide, page 74 for details
Note: With appropriated input and output devices, XPSUS can reach up to PLe, Cat.4, SILCL3
XPSBCE is replaced by XPSUS
XPSBCE XPSUS
Commercial Reference Commercial Reference
XPSBCE3410C XPSUS32AC
XPSBCE3410P XPSUS32AP
XPSBCE3710C XPSUS32AC
XPSBCE3710P XPSUS32AP
XPSBCE is replaced by XPSUS
XPSBCE XPSUS
Wiring Two-Hand Control* (115/230VAC) diagram XPSBCE & XPSUS
XPSBCE XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the connected
equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
* Wiring example for two hand control type IIIC
Safety FUNCTION position 4.
START function positions 1.
Refer to Start Functions under your user guide, page 74 for details
Note: With appropriated input and output devices, XPSUS can reach up to PLe, Cat.4, SILCL3
XPSBF is replaced by XPSUS
XPSBF XPSUS
Commercial Reference Commercial Reference
XPSBF1132 XPSUS12AP
XPSBF1132P XPSUS12AP
XPSBF is replaced by XPSUS
XPSBF XPSUS
Wiring Two-Hand Control* (24VDC) diagram XPSBF & XPSUS
XPSBF XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the
connected equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
* Wiring example for two hand control type IIIC
Safety FUNCTION position 4.
START function positions 1.
Refer to Start Functions under your user guide, page 74 for details
Note: With appropriated input and output devices, XPSUS can reach up to PLe, Cat.4, SILCL3
XPSVC is replaced by XPSUS
XPSVC XPSUS
Commercial Reference Commercial Reference
XPSVC1132 XPSUS12AP
XPSVC1132P XPSUS12AP
XPSVC is replaced by XPSUS
XPSVC XPSUS
Wiring Enabling Switch diagram XPSVC & XPSUS
XPSVC XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the
connected equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
Safety FUNCTION position 6.
START function positions 1.
Refer to Start Functions under your user guide, page 74 for details
Note: With appropriated input and output devices, XPSUS can reach up to PLe, Cat.4, SILCL3
XPSDMB is replaced by XPSUS
XPSDMB XPSUS
Commercial Reference Commercial Reference
XPSDMB1132 XPSUS12AP
XPSDMB1132P XPSUS12AP
XPSDMB is replaced by XPSUS
XPSDMB XPSUS
Wiring Coded Magnetic Switches diagram XPSDMB & XPSUS
XPSDMB XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the
connected equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
Safety FUNCTION position 5.
START function position 1
(refer to Start Functions under your user guide, page 74 for details)
Note: With appropriated input and output devices, XPSUS can reach up to PLe, Cat.4, SILCL3
Wiring Coded Magnetic Switches* diagram XPSDMB & XPSUS
XPSDMB XPSUS
Wiring Coded Magnetic Switches* diagram XPSDMB & XPSUS
XPSUS
Y1- Control output (DC+) of start input
Y2- Input channel (CH+) of start input
Z1- Pulsed output for diagnostics (see User Guide page 89), not safety- related
B2- Terminal for common reference potential for 24Vdc signals. The power supplier of the connected equipment must have a common reference potential to be connected to this terminal.
EXT- Side connector for output extension module XPSUEP
Safety FUNCTION position 5.
START function position 1
(refer to Start Functions under your user guide, page 74 for details)
* NOTE:
The number of Coded Magnetic Switches (SRP/CSa), to be used in series at the same Safety-Related input must follow the below technical data:
• Maximum resistance at each of the Safety-Related input (including wires/cables): 500Ω (Ohms)
• Minimum Voltage at each of the Safety-Related input: 15VDC
In this application, with appropriated input and output devices, XPSUS can reach up to PLd, Cat.3, SILCL2