HD30 Inversor
HD30 Inversor
Thank you for purchasing HD30 series vector control inverter manufactured by
Shenzhen Hpmont Technology Co., Ltd.
This User Manual describes how to use HD30 series inverters and their installation
wiring, parameter setting, troubleshooting and daily maintenance etc. Before using
the product, please read through this User Manual carefully. In addition, please do
not use this product until you have fully understood safety precautions.
Note:
Preserve this Manual for future use.
If you need the User Manual due to damage, loss or other reasons, please contact
the regional distributor of our company or directly contact our company Technical
Service Center.
If you still have some problems during use, please contact our company Technical
Service Center.
Due to product upgrade or specification change, and for the purpose of
improving convenience and accuracy of this manual, this manual’s contents may
be modified.
Email address: [email protected]
Connection with peripheral devices
MCCB
Contactor
AC input reactor
(accessory)
EMI filter
Braking resistor
(accessory)
HD30 DC reactor
(accessory)
EMI filter
AC output reactor
(accessory)
Motor
Quick Start for HD30 Operation
Note:
Some parameters have been set (factory setting) so that you could not set for the initial use.
2. Control the start/stop and set the running frequency via using the keypad
1. Power on. Using the keypad can set motor parameters (see the motor nameplate parameter),
running frequency and Acc. / Dec. time. See the following table.
Ref. Code Function Setting Meaning
F00.10 Frequency setting source selection 0 (factory setting) Set by keypad
F00.11 Command setting source selection 0 (factory setting) Keypad running command channel
Running frequency, adjust according
F00.13 Starting frequency digital setting -
to actual requirement
Acc. time, adjust according to actual
F03.01 Acc. time 1 -
requirement
Dec. time, adjust according to actual
F03.02 Dec. time 1 -
requirement
2. Pressing panel’s key can start the inverter, pressing / button increase / decrease set
frequency, and pressing key can stop the inverter outputting.
3. Control the start/stop via terminals and set the running frequency via keypad
1. The terminal DI1 is forward running signal input, and DI2 is reverse running signal input, their
wirings are as following figure.
K1 Output indicating
Forward DO1
DI1 signal at running
K2 R1C
Reverse
DI2
R1B
Fault indicating
COM
R1A
2. After power on, set the functional parameters in accordance with wirings, as following table.
Ref. Code Function Setting Meaning
F00.10 Frequency setting source selection 0 (factory setting) Set by keypad
F00.11 Command setting source selection 1 Terminal running command source
Running frequency, adjust according
F00.13 Starting frequency digital setting -
to actual requirement
Acc. time, adjust according to actual
F03.01 Acc. time 1 -
requirement
Dec. time, adjust according to actual
F03.02 Dec. time 1 -
requirement
Forward running function (terminal
F15.00 DI1 function 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 function 3 (factory setting)
rervese signal input)
3. When the K1 is closed in the wiring diagram, the motor is running forward; when K1 is turned off,
the motor stops running. When the K2 is closed, the motor is running reverse; when K2 is turned off,
the motor stops running. K1, K2 are closed or disconnected at the same time, the motor stop running.
You can increase / decrease the set frequency by changing F00.13 or pressing the / key on the
control keypad.
Close the K1 of the wiring diagram, the motor will run forward; close K2, run reverse; simultaneously
close or disconnect, the motor will stop.
4. Control the start/stop via terminals and set the running frequency via analogue
1. The terminal DI1 is forward running signal input, and DI2 is reverse running signal input, their
wirings are as following figure.
K1
Forward
DI1
K2 DO1 Output indicating
Reverse DI2 signal at running
COM R1C
+10 R1B
Analogue input AI1 Fault indicating
R1A
GND
2. After power on, set the functional parameters in accordance with wirings, as following table.
Ref. Code Function Setting Meaning
F00.10 Frequency setting source selection 3 Analogue setting
F00.11 Command setting source selection 1 Terminal running command source
Acc. time, adjust according to actual
F03.01 Acc. time 1 -
requirement
Dec. time, adjust according to actual
F03.02 Dec. time 1 -
requirement
Forward running function (terminal
F15.00 DI1 function 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 function 3 (factory setting)
rervese signal input)
F16.01 AI1 function 2 (factory setting) Frequency setting source (set by AI1)
K1
Forward Output indicating
DI1 DO1
K2 signal at running
Reverse DI2
R1C
COM
R1B
MODBUS Fault indicating
R1A
2. After power on, set the functional parameters in accordance with wirings, as following table.
Ref. Code Function Setting Meaning
F00.10 Frequency setting source selection 2 SCI communication setting
F00.11 Command setting source selection 1 Terminal running command source
Acc. time, adjust according to actual
F03.01 Acc. time 1 -
requirement
Dec. time, adjust according to actual
F03.02 Dec. time 1 -
requirement
Forward running function (terminal
F15.00 DI1 function 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 function 3 (factory setting)
rervese signal input)
F15.18 DO1 function 2 (factory setting) Inverter is running
F17.00 Data format 0 (factory setting) 1-8-2 format, no parity, RTU
F17.01 Baud rate 3 (factory setting) 9600bps
F17.02 Local address 2 (factory setting)
3. Close the K1 of the wiring diagram, the motor will run forward; close K2, run reverse; simultaneously
close or disconnect, the motor will stop.
4. Modify the running frequency via SCI communication function code 0X06 writing register 0x3201.
Such as: modify the local address two of slave with running frequency of 45.00Hz, as following table.
Command Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E
Response Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E
6. Control the start/stop and set the running frequency via using communication
1. The communication wirings are as following figure.
Output indicating
DO1
signal at running
MODBUS R1C
R1B
Fault indicating
R1A
2. After power on, set the functional parameters in accordance with wirings, as following table.
Ref. Code Function Setting Meaning
F00.10 Frequency setting source selection 2 SCI communication setting
SCI communication running
F00.11 Command setting source selection 2
command source
Acc. time, adjust according to actual
F03.01 Acc. time 1 -
requirement
Dec. time, adjust according to actual
F03.02 Dec. time 1 -
requirement
F17.00 Data format 0 (factory setting) 1-8-2 format, no parity, RTU
F17.01 Baud rate 3 (factory setting) 9600bps
F17.02 Local address 2 (factory setting)
3. Start and stop the local address 2 of inverter via SCI communication function code 0x06 writing
register 0x3200, such as forward start command, as following table.
Command Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x00 0x10 0x01 0x4B 0x41
Response Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x00 0x10 0x01 0x4B 0x41
4. Modify the running frequency via SCI communication function code 0X06 writing register 0x3201.
Such as: modify the local address two of slave with running frequency of 45.00Hz, as following table.
Command Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E
Response Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E
7. Motor parameter auto-tuning
1. Motor parameter auto-tuning can be only done in keypad mode.
2. Correct wiring.
3. Power on, set motor parameter (F08.00 - F08.04) by keypad.
4. Parameter auto-tuning, available auto-tuning methods for different control mode are shown as
below table.
Control Mode Auto-tuning Method (Recommanded)
Manual torque boost Automatic torque boost
V/f control
Use static, rotary, stator resistance self-tuning Use still, rotate self-tuning
Vector control Use Rotation Auto Tuning
Static self-tuning:
F08.06 = 1 (static auto-tuning), press key to the stop parameter display state, press key to
start the auto-tuning. Auto-refresh F08.07 - F08.09 after auto-tuning.
Ref. Code Function Ref. Code Function
F08.07 Motor 1 Stator resistance F08.09 Motor 1 Leakage inductance
F08.08 Motor 1 rotor resistance
Rotation Auto-Tuning:
Before turning the auto-tuning, first disconnect the motor from the load.
Then set F08.06 = 2 (Rotate Auto Tuning), press key to go to the stop parameter display state,
press key to start auto tuning.
In the motor rotation process, there may be shock or even overcurrent, this time should immediately
press key to stop the parameter tuning, and adjust the Acc. and Dec. time and F09.15, F09.16
(suppression shock coefficient) to mitigate possible shocks.
After auto tuning, auto refresh F08.04, F08.07 - F08.16.
Ref. Code Function Ref. Code Function
F08.04 Motor 1 rated Rpm F08.12 Motor 1 Core saturation coefficient 1
F08.07 Motor 1stator resistance F08.13 Motor 1 Core saturation coefficient 2
F08.08 Motor 1rotor resistance F08.14 Motor 1 Core saturation coefficient 3
F08.09 Motor 1 leakage inductance F08.15 Motor 1 Core saturation coefficient 4
F08.10 Motor 1 Mutual resistance F08.16 Motor 1 Core saturation coefficient 5
F08.11 Motor 1 No-load excitation current
Product Information 2
Mechanical Installation 3
Electrical Installation 4
Operation Instructions 5
Function Introduction 6
Options 8
Parameters B
Communication Protocol C
Shenzhen Hpmont Technology Co., Ltd. Chapter 1 Safety Information and Precautions
1
Danger
Danger: A Danger contains information which is critical for avoiding safety hazard.
Warning
Warning: A Warning contains information which is essential for avoiding a risk of damage to products or other
equipements.
Note
Note: A Note contains information which helps to ensure correct operation of the product.
Altitude
1000m 4000m
Figure 1-1 Derating curve of rated current and altitude
Voltage Rating
200 - 240VAC = 2
380 - 460VAC = 4
2
Phase
Single-phase / Three-phase input = D
Three-phase input = T
Power
Product Type
General = G
Fan and pump = P
Special Feature
2.2 Nameplate
HZ A V RPM %
Middle enclosure
Keypad
Bottom enclosure
Upper cover
Certification
Danger
• Do not install if HD30 is incomplete or impaired.
• Please see the controller size and weight to take appropriate tools for handing, avoid harming from sharp edges or
injured by a dropped controller.
• Make sure that HD30 is far from the explosive and flammable things.
• Do not do wiring operation until power supply is cut off for more than 10 minutes, the internal charge indicator of
HD30 is off and the voltage between (+) and (-) of the main circuit terminals is below 36V.
3
Warning
• It is required not only carry the keypad and the cover but also the inverter bottom enclosure.
• Do not play metal into the inverter when installing.
Note:
1. It needs derating use running temperature exceeds 40℃. The derating value of the output current of
HD30 shall be 2% for each degree centigrade. Max. allowed temperature is 50℃.
2. Keep ambient temperature between -10 - +40℃. It can improve the running performance if install at
location with good ventilation or cooling devices.
More than one inverter with the installation of the upper and
lower, the middle should be installed with diversion partitions,
installation space size see Table 3-2. a
Table 3-2 Multi-inverters changer installation space dimension
HD30 power ≤55kW ≥75kW
A ≥50mm ≥100mm
B ≥50mm ≥100mm
≥50mm ≥100mm b
C
a ≥50mm ≥100mm c
b ≥50mm ≥100mm
C
c ≥50mm ≥100mm B
123
H1
H2
H
3
Size F1 - F4
W
W1 D
4-Ød
H2
H1
H
Size F5 - F6
W D
W1
4-Ød
H2
H1
H
Frame 7 - Frame 10
W
W1 4-Ød
D1
D
H
3
Figure 3–2 Install keypad
There are two steps in Figure 3–3.
First, press the hook of the keypad according to direction 1. Second, take out of the keypad according
to direction 2.
1
2
(a)
(b)
(c)
Figure 3-4 Dismantle of the plastic cover
Danger
• Only qualified electrical engineer can perform wiring job.
• Only when the power supply switch is completely off can you do the wiring job.
• You can’t open the inverter cover to do wiring operation until the power is cut-off 10 minutes later. Do not wire or
detach the inverter internal devices at power-on situation.
• Do not do wiring operation until the internal charge indicator of the inverter is off and the voltage between (+)
and (-) of the main circuit terminals is below 36V.
• Check the wiring carefully before connecting emergency stop or safety circuit.
• The earth terminal PE of the inverters must be reliable earthing. It must use two separate earth wire due to the
leakage current from the inverter to ground.
• It must use Type B mode when utilize earth leakage protection devices (ELCB/RCD).
• Do not touch the wire terminals of the inverter when it is live. The main circuit terminals is neither allowed
4
connecting to the enclosure nor short-circuiting.
Warning
• Do not do dielectric strength test on the inverter.
• Do wiring connection of the braking resistor or the braking unit according to the wiring figure.
• Make sure the terminals are fixed tightly.
• Do not connect the AC supply cable to the output terminals U, V, W of the inverter.
• Do not connect the phase-shifting capacitors to the output circuit.
• Be sure the inverter has ceased output before switching motor or change-over switches.
• The inverter DC bus terminals must not be short-circuited.
Danger
• The bare portions of the power cables must be bound with insulation tapes.
Warning
• Ensure that AC supply voltage is the same as rated input voltage of HD30.
PE L1 L2 L3 (+) (-)
POWER
PE U V W
MOTOR
L1 L2 L3 (+) (-) BR U V W PE
EMI filter
Braking
Frame 1 - Frame 2 AC reactor resistor
Supply
ground
MCCB
Contactor
Mains supply
L1 L2 L3 P1 (+) (-) BR U V W PE
EMI filter
Contactor
Mains supply
PE L1 L2 L3 P1 (+) (-) PE U V W
Braking
EMI filter resistor
Contactor
Mains supply
PE L1 L2 L3 (+) (-) PE U V W
Braking
EMI filter resistor
Danger
4
• The control circuit is basically isolated with the power circuit. Do not touch HD30 after it is powered.
Warning
• If the control circuit is connected to external devices with live touchable port, it should increase an additional
isolating barrier to ensure that voltage classification of external devices not be changed.
• If connect the communication terminal of the control circuit to the PC, choose the RS485/232 isolating converter
which meets the safety requirement.
• Only connect the relay terminal to AC 220V voltage signal. Other control terminals are strictly forbiden for this
connection.
Control Board
Terminal
+10 AI1 AI2 DI1 DI2 DI3 DI4 DI5 DI6 COM COM R1A
GND GND AO1 AO2 P24 SEL COM CME DO1 DO2 R1B R1C
Figure 4-1 Control board terminal
Note:
Limit the current within 3A if the relay terminal is to connect to AC 220V voltage signal.
RJ45 2 485+
1 8
4,5,6 GND
RJ45
7 485-
8 Unused
AI1
CN7
AI2
AO1 Analogue output 1
1
AI2
CN6
1
CN8
GND GND
3
PE
Figure 4-3 HD30 control board connection
SEL SEL
Dry contact +
DC - Dry contact
Current Using internal Using external
power supply 12 - 30V
Current power supply
K K
DI1...DI6 DI1...DI6
COM COM
Figure 4-4 Dry contact connection
+
-
12 - 30V
SEL
DC SEL
+ 12 - 30V
-
COM
1
DI1
External controller
1
External controller
DI1
Source Drain
Using external Using external
power supply power supply
6
DI6
6
DI6
COM
Figure 4-5 Source / Drain connection when using external power
4
Using internal 24V power supply of HD30, it is NPN / PNP connection in which external controller is
common emitter output, as shown in Figure 4-6. (For PNP, remove the connector between SEL and
P24)
+24V +24V
P24 P24
SEL SEL
COM
1 1
DI1 DI1
External controller
External controller
NPN PNP
Using internal Using internal
power supply power supply
6
DI6 6
DI6
COM
Figure 4-6 NPN (source) / PNP (drain) connection when using internal power supply
AI1
AI1 Filter capacitor
0.022uF/50V
GND GND
PE
Figure 4-7 AI1 connection
Note:
1. To reduce the interference and attenuation of control signal, length of control cable should limit within
50 m, and the shield should be reliably grounded.
2. In serious interference occasions, the analogue input signal should add filter capacitor and ferrite core,
as shown in Figure 4-7.
AI2 are selected as voltage input and the range is -10 - +10V. When selecting internal +10V of HD30,
refer to Figure 4-7; selecting +/-10V external supply, refer to Figure 4-8.
AI2 are selected as current input and the range is 0 - 20mA, refer to Figure 4-8.
External power supply
+10V
AI2
AI2
-10V
P24 P24
Relay
coil
DO1 DO1 +
Relay - DC
coil 12 - 30V
CME CME
COM COM
Figure 4-9 DO1 connection
DO2 is open collective output, refer to Figure 4-9.
DO2 is pulse frequency output; DO2 can use internal 24V power supply of inverter or external power
supply. The connection is shown in Figure 4-10.
+24V +24V
Using external power supply
Area E
Power supply control cabinet
Area A: transformers of control power
Area A Area C supply, control devices and sensor etc.
AC reactor Area B: interfaces of signal and control
cables, correct immunity is required.
Area C: noise sources such as AC reactor,
Control device (the EMI filter controller, braking unit and contactor.
host PC, PLC etc.) Area D: output EMI filter and its cable connection.
Area F
Mechanical system Motor
Manufacture machines
Figure 4-11 System wiring
• All areas should be isolated in space to achieve electromagnetic decoupling effect.
• The minimum distance between areas should be 20cm, and use grounding bars for decoupling
among areas, the cables from different area should be placed in different tubes.
• EMI filters should be installed at the interfaces between different areas if necessary.
• Bus cable (such as RS485) and signal cable must be shielded.
HD30 >30 cm
Motor cable
>20 cm >50 cm
Power supply cable Motor cable
PE PE
The cross sectional area (CSA) of controller cables should refer to Table 4-2, on page 18.
The controller should be derated if motor cables are too long or their CSA is too large. The current
should be decreased by 5% when per level of CSA is increased. If the CSA increase, so do the current to
ground and capacitance.
4.5.7 Reactor
AC input reactor
The purpose of installing an AC input reactor: to increase the input power factor; to dramatically
reduce the harmonics on the input side at the high voltage point of common coupling and prevent
input current unbalance which can be caused by the phase-to-phase unbalance of the power supply.
DC reactor
The installation of a DC reactor can increase the input power factor, improve the overall efficiency and
thermal stability of controller, substantially eliminate the upper harmonics influence on performance
of inverter, and decrease the conducted and radiated electromagnetic emissions from the inverter.
AC output reactor
When the length of cable between inverter and motor is more than 100m, it will cause leakage current
and controller tripping. It is suggested that user should consider installing an AC output reactor.
Danger
• Only when the terminal cover of HD30 has been fitted can you switch on AC power source. Do not remove the
cover after power is switched on.
• Ensure the motor and the mechnical device are in the use application before HD30 starts.
• To change the MCB, correctly set the parameters before operating.
Warning
• Do not check or detect the signal during HD30 running.
• Do not randomly change HD30 parameter setting.
• Please thoroughly complete all control debugging and testing, make all adjustments and conduct a full safety
assessment before switching the run command source of HD30.
• Do not touch the energy-depletion braking resistor due to the high temperature.
0 A J U
1 b L u
2 C n y
3 c o -
4 d P Point
5 E q Full display
6 F r No display
Flash
7 H S
modifiable
8 h T
9 i t
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
Copy para. to MCB Copy para. to keypad Failed to copy para Reset
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
PRG
Hz A V RPM % Hz A V RPM %
Parameter setting
For example: To modify the setting value of the F02.14 from 000.00Hz to 012.00Hz, refer to Figure 5-6.
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
Hz A V RPM % Hz A V RPM %
5
Shift to tens Modify value
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
PRG
Hz A V RPM % Hz A V RPM %
PRG PRG
1.5s later
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
1.5s later
1.5s later
Hz A V RPM % Hz A V RPM %
Hz A V RPM %
Copied to keypad
Figure 5-11 Parameter copied to keypad
Parameters are copied from the operator panel to the control board:
When F01.02 = 2/3 or F01.02 = 5/6, the keypad will display “dnLd”. When the download is finished, the
keypad will jump to display F01.03.
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
Hz A V RPM % Hz A V RPM %
Inverter
2: Start after speed tracking. If the result of speed tracking is smaller than F02.02, it will start from the
starting DWELL frequency.
• The inverter automatically searches and catches the motor’s running direction and speed, and starts
the rotating motor smoothly without impact. As the right figure. 6
• This mode is enabled only in the process from stop status to running status. But it is disabled in the
process of direction switch.
Motor free rotaiton
Motor rotation
Rotation setting
0
Recognize motor speed
Inverter running and direction
command
Frequency setting
Inverter running
frequency
Inverter running Positive direction
direciton
Oppositive direction
F02.01 Starting delay time 0.00 - 10.00 [0.00s]
When the inverter receives the run command, it will wait for the delay time set by F02.01 and then start
running.
F02.14
• Only when F02.13 = 0 will it be enabled. Time
• Set F02.14 or F02.15 as 0, DWELL frequency at stop is
disabled. F02.15
F02.16 DC braking initial frequency at stop 0.00 - 50.00 [0.50Hz]
F02.17 DC braking waiting time at stop 0.00 - 10.00 [0.00s]
F02.18 DC braking time at stop 0.00 - 60.00 [0.50s]
F02.17 is the interval from A to B in the right Out frequency
figure during Dec. stop process.
Running frequency
• The inverter has no output during the
waiting time. By F02.17 setting the waiting
time, the current overshoot in the initial F02.16 A Time
stage (point B in the figure ) of braking can
be reduced when the inverter drives a high Out voltage
power motor. (effective value)
• By F02.04 setting the DC braking current at
stop. DC braking value
A B
F02.18 = 0.00s, there is no DC braking process at Time
stop.
F02.17F02.18
• Only when F02.13 = 2 will F02.16 - F02.18 be
Run command 6
enabled.
F02.19 Jog control mode 00 - 11 [10]
Units:
0: The jog functions of start and stop mode etc are invalid.
• In jog running, start mode set by F02.00 and stop mode set by F02.13 are invalid. When the jog
command is valid, the inverter starts up and running. When the jog command is invalid, the inverter
will decelerate and stop.
1: The jog functions of start and stop mode etc are enabled.
• In jog running, inverter will run in start mode set by F02.00 and stop mode set by F02.13.
Tens:
0: Terminal jog is not preferred.
• Terminal control operation does not respond to terminal jog command.
1: Terminal jog priority.
F02.20 Pre-excitation time 0.00 - 0.50 [0.50s]
Pre-excitation effect: Before the motor rotation, establish the motor flux, in order to obtain faster Acc.
performance.
• This function only takes effect in open loop vector control mode. It is recommended that F02.20 value be
not less than 0.10s.
• F02.20 = 0.00s, the pre-excitation function is disabled.
F05.02 F05.04
F05.06 P/A(setting) F05.08 P/A(setting)
F05.01 F05.03 F05.01 F05.03
F05.05 F05.07 F05.05 F05.07
Positive and negative characteristic of polyline
Setting corresponding value Setting corresponding value
F05.10 F05.16
Inflection point 2
F05.12 F05.14 Inflection point 1
F05.14 F05.12 Inflection point 2
Inflection point 1
F05.16 P/A(setting) F05.10 P/A(setting)
F07.02
Jump frequency = Fw x F07.05
Time
Stop command
6
Ref. Code Function Description Setting Range [Default]
F07.00 Wobble operation selection 0,1 [0]
0: Disabled.
1: Enabled.
F07.01 Wobble operation mode 0000 - 1111 [0000]
Units: Start mode of wobble operation.
• 0: Auto start. The inverter will first operate at the preset frequency of wobble operation (F07.02) for
certain time (F07.03), and then enter wobble mode automatically.
• 1: Manual start. If the multi-function terminal is set as No.36 function (set as wobble start function) and
the signal is enabled, the inverter will enter wobble mode. If the terminal is disabled, the inverter will end
wobble operation and operate at the preset frequency of wobble operation (F07.02).
Tens: Wobble operation amplitude. Refer to parameter F07.04.
• 0: Relative to the wobble central frequency.
• 1: Relative to the maximum output frequency.
Hundreds: Restart mode of wobble operation.
• 0: The inverter restarts the wobble operation as per the recorded frequency and direction when it stops
last time.
• 1: The inverter restarts the wobble operation from 0Hz.
Thousands: Save the wobble operation parameters at power outage
• 0: Saved. When the hundreds of F07.01 is set as 0, the wobble operation parameters will be saved when
power outage occurs.
• 1: Not be saved.
I1 I2
1-S
U1 S R2
Io
Lm
Central frequency
After limiting
amplitude
Time
Out signal
limitation of upper/lower limits
of wobble frequency
15: Simple PLC operating status indication.
• The indicating signal will be output when the inverter is at simple PLC operating.
16: Simple PLC pausing indication.
• The indicating signal will be output if the simple PLC operation is suspended by external terminals.
Output
DO
Time
Zero-frequency
running output
Time
Zero-frequency output
Time
DO
6
Time
DO1
DO2
F15.39 Ananlogue input over-limitation selection 0000 - 1133 [0000]
If the corresponding analog > F15.40 or analog < F15.41, and continued F15.42 time, the overrun check.
After the limit detection, when F15.41 ≤ analog ≤ F15.40, according to thousands to determine whether the
automatic operation of the inverter.
Unit: action drive when the input exceeds the limit Hundreds: Analog overrun detection conditions
• 0: Free stop. • 0: Always detected.
• 1: Emergency shutdown. • 1: Run command is detected.
• 2: Deceleration stop. Thousands : Automatical selection when analog
• 3: No action. overrun is detected
Ten: Select the analog input port • 0: Do not allow automatic operation.
• 0: No analog port. • 1: Allows automatic operation.
• 1: Operation panel potentiometer. Note: Thousands are valid only in terminal two-wire
• 2: AI1 port. mode.
• 3: AI2 port.
F15.40 Analog input overrun upper limit F15.41 - 100.0 [100.0%]
F15.41 Analog input overrun down limit 0.0 - F15.40 [0.0%]
F15.42 Analog overrun detection time 0.00 - 50.00 [5.00s]
F15.43 Terminal output delay 0.0 - 100.0[0.0s]
F15.44 Start analog overrun detection time 0.00 - 50.00 [15.00s]
Pre-treatment
Keypad Storing in power failure
Initial value
Auxiliary set frequency
F19.04
setting channel
Communicaiton Digital
F19.00
Process PID
Yes
Fcmd>Fmin
No Handle by
F19.11 setting
F19.11=1
Yes
Keep stop 6
No
Yes Fcmd=F19.11
Confirmed frequency
No
Fcmd>Fstart
Yes
H=Fstart
Reach No
F2.03 or
no
Yes
H=Fcmd
Frequency
0: This function is disabled. Setting
1: This function is enabled. And low-voltage
frequency
Given
compensation is activated. frequency Time
This Group is used to realize fixed length stop function. As the right figure:
The inverter inputs the count pulse from the terminal
(multi-function terminal is set as No. 52 function) and gets Measuring
speed shaft
the count length according to the measuring number of
pulses per revolution (F19.31) and shaft diameter (F19.30).
Then modify the count length and obtain the actual length
(F19.27) via length ratio (F19.28) and length checking Inverter Motor
coefficient (F19.29) too. 6
The formula is as follows:
F19.27 = Counted length × F19.28 ÷ F19.29
Counted length = Counted pulse number ÷ F19.31 × F19.30 × π
If F19.27 ≥ F19.26, the inverter will automatically send the stop command. Before running again, it
need clear F19.27 or changed to F19.27 < F19.26. Otherwise the inverter can’t be started.
Ref. Code Function Description Setting Range [Default]
F19.26 Preset length 0 - 65535 [0m]
F19.27 Actual length 0 - 65535 [0m]
F19.28 Length ratio 0.001 - 30.000 [1.000]
F19.29 Length checking coefficient 0.001 - 1.000 [1.000]
F19.30 Measuring shaft diameter 1.00 - 100.00 [10.00cm]
F19.31 Number of pulses per revolution 1 - 9999 [1]
F19.32 Length arrive and output function selection 0,1 [0]
0: Output level signal.
1: Output 500ms pulse.
F19.33 Record of length disposal after length arrive 0,1 [0]
F19.34 Record of length disposal at stop 0,1 [0]
0: Auto-clear.
1: No change.
Faulted auto reset function and faulted relay action (F20.18 - F20.20)
Auto reset function enables the inverter to reset the fault as per the preset F20.18 and F20.19.
During the reset interval, the inverter stops output and it will automatically restarts with flying start 6
mode.
The following faults do not have the auto reset function:
E0008: Power modular fault E0021: Control board EEPROM read/write fault
E0010: Braking unit fault E0023: Parameter setting fault
E0013: Contactor isn’t closed at power on E0024: Peripheral device fault
E0014: Current detection circuit fault
Ref. Code Function Description Setting Range [Default]
F20.18 Auto reset times 0 - 100 [0]
F20.19 Auto reset interval 0.01 - 200.00 [5.00s/time]
When F20.19 = 0, it means “auto reset” is disabled and the protective device will be activated in case of fault.
• If no other fault is detected within 5 minutes, the auto reset times will be automatically cleared.
• On condition of external fault reset, auto reset time will be cleared.
F20.20 Faulted relay action selection 00 - 11 [00]
Units: In auto reset process Tens: In the undervoltage process
• 0: Faulted relay doesn’t act. • 0: Faulted relay doesn’t act.
• 1: Faulted relay acts. • 1: Faulted relay acts.
Note: It need preset the relay function as No. 31 function.
• The carrier frequency will affect the operating noise of the motor. The higher the carrier frequency, the
lower the noise made by the motor. Please properly set the carrier frequency.
• When the value is higher than the factory setting, the inverter should be derated by 5% when per 1kHz is
increased compared to the factory setting.
F23.01 Carrier frequency is automatically adjusted 0 - 2 [1]
0: The carrier frequency is disabled automatically.
1: Carrier frequency auto adjustment 1.
2: Carrier frequency automatic adjustment 2.
• When the carrier frequency is automatically adjusted, the inverter automatically adjusts the carrier
frequency according to the output frequency and the radiator temperature.
• Invalid carrier frequency auto adjustment during torque control.
F23.02 PWM overshoot enable 0,1 [1]
0: Disabled.
1: Enabled.
F23.03 PWM modulation mode 0 - 2 [0]
0: Two-phase modulation or three-phase modulation.
1: Three-phase modulation.
2: Two-phase modulation.
F23.04 PWM Modulation mode switching point1 0.00 - 50.00Hz
F23.05 PWM Modulation mode switching point2 [Dependent on HD30]
PWM modulation mode switching only applies to working conditions of V/f control and carrier frequency >
3kHz; open loop vector or carrier frequency ≤ 3kHz, the inverter automatically selects the three-phase
modulation.
• F23.04 sets the switching frequency of two-phase modulation → three-phase modulation.
• 2.2kW and below models (380V and 220V) factory value 10.00Hz, the lower limit of 10.00Hz.
• Other models, factory default 5.00Hz, lower limit 5.00Hz.
• F23.05 sets the switching frequency of three-phase modulation → two-phase modulation.
• 2.2kW and below models (380V and 220V) factory value 15.00Hz.
• Other models, factory value 10.00Hz.
Note: F23.04 setting value is F23.05 - 2.00Hz, F23.05 lower limit is F23.04 + 2.00Hz.
F23.09 Random carrier frequency coefficient K1 0 - 2000 [2]
F23.10 Random carrier frequency coefficient K2 0 - 2000 [3]
7.2 Maintenance
Factors such as ambient temperature, humidity, PH, dust, oscillation, internal component aging, wear
and tear will give rise to the occurrence of potential faults. Therefore, it is necessary to conduct daily
maintenance to the controller.
• If HD30 has been transported for a long distance, check whether the components of HD30 are
complete and the screws are well tightened.
• Periodically clean the dust inside HD30 and check whether the screws are loose.
Danger
• Only a trained and qualified professional person can maintain the controller.
• Maintenance personnel should take off all metal jewellery before carrying out maintenance or internal
measurements in the controller. Suitable clothes and tools must be used.
• High voltage exists when the controller is powered up or running.
• Checking and maintaining can only be done after AC power of HD30 is cut off and wait for at least 10 minutes. The
cover maintenance can only be done after ensured that the charge indicator inside HD30 and the indicators on
the keypad are off and the voltage between power terminals (+) and (-) is below 36V.
Warning
• For HD30 with more than 2 years storage, please use voltage regulator to increase the input voltage gradually.
• Do not leave metal parts like screws or pads inside HD30.
• Do not make modification on the inside of controller without instruction from the supplier.
• There are IC components inside the controller, which are sensitive to stationary electricity. Directly touch the
components on the PCB board is forbidden.
Periodical Maintenance
Customer should check the inverter in short time or every 3 to 6 months according to the actual
environment so as to avoid hidden problems and make sure the inverter runs well for a long time.
General Inspection:
• Check whether the screws of control terminals are loose. If so, tighten them with a screw driver;
• Check whether the main circuit terminals are properly connected; whether the copper bar and
mains cables are overheated;
• Check whether the power cables and control cables are damaged, check especially for any wear on
7
the cable tube;
• Check whether the insulating tapes around the cable lugs are stripped, and for signs of overheating
near terminations;
• Clean the dust on PCBs and air ducts with a vacuum cleaner.
Note:
1. Dielectric strength test of the controller has already been conducted in the factory. Do not do the test
again. Otherwise, the controller might be damaged.
2. If insulation test to the motor is necessary, it should be done after the input terminals U/V/W of motor
have been detached from HD30. Otherwise, HD30 will be damaged.
3. For controllers that have been stored for a long time, they must be powered up every 2 years. When
supplying AC power to the controller, use a voltage regulator to gradually raise the input voltage to rated
input voltage at least 5 hours.
Chapter 8 Options
8.1 HD30-EIO
HD30 series inverters using with HD30-EIO can achieve the extension of analogue input, digital input
and relay contact output.
Terminal Description
HD30-EIO
Terminal Terminal
AI3 AI4+ DI7 DI8 DI9 R2A R3A R3B R4A
GND AI4- P24 SEL COM R2B R2C R3C R4B R4C
Figure 8-1 HD30-EIO terminal
Table 8-1 Terminal description
Terminal Description
Input voltage / current are selectable
AI3 Analogue input • Input voltage range: -10V - 10V (input impedance 32kΩ)
• Input current range: 0 - 20mA (input impedance 500Ω)
Note:
Limit the current within 3A if the relay terminal is to connect to AC 220V voltage signal.
HD30-EIO
CN3 CN2 CN4
Terminal Wiring
Digital Input Connection (DI)
DI7 - DI9 have the same connection with control board digital input terminals (DI1 - DI6), please refer
to section 4.4.4 Control Terminal Wiring.
Analogue Input Connection (AI)
AI3 with the AI2 of control terminal has same wiring, see analog input terminal of the section 4.4.4
Control Terminal Wiring, shown as Figure 4-8.
When AI4 is used as setting analogue input terminal, the connection is shown as Figure 8-3. (The AI4+
= analogue signal input)
Analogue input
AI4+ -10 - +10V/0 - 20mA
AI4-
GND
PE
Figure 8-3 AI4 connection (AI4 = analogue input terminal)
Thermistor
10k AI4+ CN2 CN3
1 1
V V
AI4-
I R
GND 3 3
PE
Figure 8-4 AI4 connection (AI4 = overheat detection signal input)
8.2 HD30-PIO
HD30 series inverters can use plastic interface card (HD30-PIO), HD30-PIO is specific development for
injection molding machine industry, mainly provide two way isolated selectable sampling 0 - 24V
voltage, 0 - 1A current signal analogue input channels.
Terminal Description
HD30-PIO
Jumper
HD30-PIO
CN2 CN3
134.5±0.2
142
Extension Cable
The keypad extension cable is an accessory. If needed, please order goods.
The models are as follows:
• 1m extension cable to keypad: HD-CAB-1M
• 2m extension cable to keypad: HD-CAB-2M
• 3m extension cable to keypad: HD-CAB-3M
• 6m extension cable to keypad: HD-CAB-6M
Note:
1. Please select braking resistor based on the above table.
Bigger resistor can protect the braking system in fault condition, but oversized resistor may bring a
capacity decrease, lead to over voltage protection.
2. The braking resistor should be mounted in a ventilated metal housing to prevent inadevertent contact
during it works, for the temperature is high.
U00.00 User menu map of setting 1 00.13 00.00 - 23.03, 99.99 [Factory setting]
If set as 99.99, there is no parameter map
U00.02 User menu map of setting 2 03.01 function
U00.01 The setting value of map 1 Without setting
U00.03 The setting value of map 2 Without setting
After finish setting, modifying the setting value of map (U00.01 and U00.03) can change value of
F00.13 and F03.01 automatically.
Factory setting
The user menu Group U can set up to 16 parameters, of which there are 14 parameters have been set. A
Ref. Code Setting Ref. Code Setting
U00.00 00.01 (control mode selection) U00.14 03.01 (Acc. time 1)
U00.02 00.06 (inverter maximum output frequency) U00.16 03.02 (Dec. time 1)
U00.04 00.08 (upper limit of operation frequency) U00.18 08.00 (motor rated power)
U00.06 00.13 (starting frequency digital setting) U00.20 08.01 (motor rated voltage)
U00.08 00.10 (frequency setting sources selection) U00.22 08.02 (motor rated current)
U00.10 00.11 (command setting source selection) U00.24 08.03 (motor rated frequency)
U00.12 02.13 (stop mode selection) U00.26 08.04 (motor rated RPM)
Appendix B Parameters
Attributes are changed:
”*”: It denotes that the value of this parameter is the actual value which cannot be modified.
“×”: It denotes that the setting of this parameter cannot be modified when the inverter is in run status.
”○”: It denotes that the setting of this parameter can be modified when the inverter is in run status.
“-”: The same as the mapping functional parameter.
Ref. Code Function Setting Range Default Unit Attribute Setting
d00: Status Display Parameters (refer to pages 44 - 47)
d00.00 Series of the inverter 0x10 - 0x50 *
Software version of the
d00.01 00.00 - 99.99 *
control board
Special software version of
d00.03 00.00 - 99.99 *
the control board
Software version of the
d00.05 00.00 - 99.99 *
keypad
d00.06 Custom series No. 0 - 9999 *
Units: Display the current
driving motor
0: Motor 1
1: Motor 2
d00.07 Motor and control mode *
Tens:
Bit1&Bit0: Acc. / Dec. / constant
Bit3: DC braking (including start
d00.10 Inverter status and stop DC braking) *
Hundreds:
Bit0: Parameter auto-tuning
Bit2: Speed limiting value
Bit3: Control mode
Thousands:
Bit0: Stall overvoltage
Bit1: Current limiting
Hundreds: Communication
setting frequency storage
selection
0: Not stored when power down
1: Storage when power down
0: Enabled
F00.20 Key enable of optional keypad 0 1 ○
1: Disabled
0: Disabled
F00.21 Dormant function selection 0 1 ×
1: Enabled
F00.22 Dormancy wake up time 0.0 - 6000.0s 1.0s 0.1s ○
F00.24 Sleep delay time 0.0 - 6000.0s 1.0s 0.1s ○
F00.25 Sleep frequency 0.00Hz - upper limit 0.00Hz 0.01Hz ○
Unit: When running is controlled
by V/f, action selection of zero
frequency
0: No treatment
1: Inverter lock output
2: Inverter run in DC brake
Action selection for inverter
F00.26 111 1 ×
running at zero frequency Ten: Zero frequency action
selection in open loop vector
running
Hundreds: Zero frequency
action selection in torque
control
0: No treatment
0: No binding
Command source binding 1: Keypa digital setting
F00.27 ×
frequency source selection
2: Terminal digital setting
3: SCI communicaiton setting
5: Terminal pulse setting
7 - 9: AI1 - AI3 setting
A: AI4 setting
b: Keypad potentiometer
setting
C: PIDsetting
d: Multi-speed setting
0: Only valid in control of
Functions selection of button
F00.28 keypad 0 1 ○
STOP
1: Valid in all control mode
F01: Protection of Parameters ( refer to pages 50 - 53)
F01.00 User’s password 00000 - 65535 0 1 ○
Units:
0: Full menu mode
1: Checking menu mode (Only
different from factory setting
parameters can be displayed)
Tens:
0: Does not lock the parameter
mapping relationship of Group
U and Group F
F01.01 Menu mode selection 010 1 ○
1: Lock the parameter mapping
relationship of Group U and B
Group F
Hundred:
0: After password protection,
Group F and U parameters can
be read
1: After password protection,
Group F and U parameters are
Tens:
0: Terminal jog is not preferred
1: Terminal jog priority
F02.20 Pre-excitatio n time 0.00 - 0.50s 0.50s 0.01s ×
F03: Acc. / Dec. Parameters (refer to pages 56 - 57)
Unit: Mode selection of Acc. and
Dec.
0: Linear Acc. or Dec.
1: S-curve Acc. or Dec.
F03.00 Acc. / Dec. mode selection 00 1 ○
Ten: Acc. / Dec. time reference
frequency adjustment
0: Maximum frequency (F00.06)
1: Set frequency
F03.01 Acc. time 1 0.1 - 6000.0s 15kW or 0.1s ○
below
F03.02 Dec. time 1 0.1 - 6000.0s 0.1s ○
models:
F03.03 Acc. time 2 0.1 - 6000.0s 10.0s 0.1s ○
55 - 132kW
0.0 - 30.0%
F09.07 Torque boost of motor 1 inverter: 0.1% ×
0.0: Auto torque boost
1.0%
160kW and
above:
0.5%
Cut-off point used for manual
F09.08 0.0 - 50.0% (F08.03) 25.0% 0.1% ○
torque boost of motor 1
Slip compensation gain of
F09.09 0.0 - 300.0% 00.0% 0.1% ○
motor 1
Slip compensation filter time
F09.10 0.01 - 10.00s 0.10s 0.01s ○
of motor 1
Slip compensation limitation
F09.11 0.0 - 250.0% 200.0% 0.1% ×
of motor 1
Compensation constant of
F09.12 0.1 - 25.0s 2.0s 0.1s ×
motor 1
0: Disabled
F09.14 AVR function of motor 1 1: Enabled all the time 1 1 ○
2: Disabled in Dec. process
Motor 1 low frequency
F09.15 0 - 200 50 1 ○
suppression shock coefficient
Motor 1 high frequency
F09.16 0 - 200 20 1 ○
suppression shock coefficient
0: Energy saving control invalid
Motor 1 energy saving control
F09.17 3: Energy saving according to 0 1 ×
select
output current
F09.18 Motor 1 energy saving factor 0.0 - 100.0% 5.0% 0.1% ○
Motor 1 energy start
F09.19 0.00 - 50.00Hz 25.00Hz 0.01Hz ○
frequency
Motor 1 energy switching
F09.20 0.0 - 100.0% 100.0% 0.1% ○
point B
Motor 1 energy saving
F09.21 0 - 5000 times 10 times 1 times ○
detecting times
Motor 1 energy voltage
F09.22 40 - 4000ms 100ms 1ms ○
recovery time
Motor 1 energy voltage
F09.23 40 - 4000ms 100ms 1ms ○
decreasing time
F10: Motor 1 Vector Control Speed-loop Parameters (refer to pages 70 - 71)
0: Number limit
1: Analog input limit
2: Terminal pulse limit
3 - 6: AI1 - AI4 limit
7: Keypad potentiometer is
limited
Motor torque limitation when 0.0 - 200.0% (motor rated
F10.11 180.0% 0.1% ○
motor 1 is forward current)
Motor torque limitation when 0.0 - 200.0% (motor rated
F10.12 180.0% 0.1% ○
motor 1 is reverse current)
Recreated torque limitation 0.0 - 200.0% (motor rated
F10.13 180.0% 0.1% ○
when motor 1 is forward current)
Recreated torque limitation 0.0 - 200.0% (motor rated
F10.14 180.0% 0.1% ○
when motor 1 is reverse current)
F11: Motor 1 Vector Control Current Loop Parameter (refer to pages 71 -72)
55 - 132
0.0 - 30.0% kW
F13.23 Torque boost of motor 2 0.1% ×
0.0: Auto torque boost inverter:
1.0%
160kW and
above:
0.5%
Cut-off point used for manual
F13.24 0.0 - 50.0% (F13.04) 30.0% 0.1% ○
torque boost of motor 2
0: Number limit
1: Analog input limit
2: Terminal pulse limit
3 - 6: AI1 - AI4 limit
7: Keypad potentiometer is
limited
Motor torque limitation when 0.0 - 200.0% (motor rated
F13.46 180.0% 0.1% ○
motor 2 is forward current)
Motor torque limitation when 0.0 - 200.0% (motor rated
F13.47 180.0% 0.1% ○
motor 2 is reverse current)
Recreated torque limitation 0.0 - 200.0% (motor rated
F13.48 180.0% 0.1% ○
when motor 2 is forward current)
Recreated torque limitation 0.0 - 200.0% (motor rated
F13.49 180.0% 0.1% ○
when motor 2 is reverse current)
F13.50 Motor 2 current loop KP 1 - 2000 400 1 ○
F13.51 Motor 2 current loop KI 1 - 1000 200 1 ○
Motor 2 current loop output
F13.52 0 - 31 3 1 ○
filter times
Motor 2 core saturation
F13.53 0.00 - 1.00 1.00 0.01 ×
coefficient 4
Motor 2 core saturation
F13.54 0.00 - 1.00 1.00 0.01 ×
coefficient 5
Motor 2 current loop 0: Feedforward is prohibited
F13.55 1 1 ×
feedforward enabled 1: Enable feedforward
Motor 2 excitation boost
F13.56 0.0 - 30.0% 0.0% 0.1% ×
setting
Unit: Field orientation angle
correction enable
0: Field orientation correction is
forbidden
1: Enables magnetic field
orientation correction
Motor 2 field orientation
F13.57 00 1 ×
optimization setting
Ten: Mutual inductance
projections enabled
0: Disable mutual inductance
based on flux calculation
1: Enable mutual inductance
based on flux calculation
Motor 2 energy start
F13.58 0.00 - 50.00Hz 25.00Hz 0.01Hz ○
frequency
F13.59 Motor 2 energy switching 0.0 - 100.0% 100.0% 0.1% ○
0: Unused
Set the display parameter 1 1: Inverter’s rated current
F18.02 8 1 ○
during operation 3: Inverter status
4: Master setting frequency
source
Set the display parameter 2 5: Master setting frequency
F18.03 7 1 ○
during operation 6: Auxiliary setting frequency
7: Setting frequency
8: Reference frequency (after
Acc. / Dec.)
Set the display parameter 3
F18.04 9: Output frequency 9 1 ○
during operation
10: Setting speed
11: Running speed
13: Output voltage
Set the display parameter 4 14: Output current
F18.05 13 1 ○
during operation
15: Torque given
16: Output torque
17: Output power
Set the display parameter 5 18: DC bus voltage
F18.06 14 1 ○
during operation 19: Potentiometer input voltage
20: AI1 input voltage
21: AI1 input voltage (after
disposal)
Set the display parameter 6
F18.07 22: AI2 input voltage 18 1 ○
during operation
23: AI2 input voltage (after
disposal)
24: AI3 input voltage
Set the display parameter 1 at
F18.08 25: AI3 input voltage (after 7 1 ○
stop
disposal)
26: AI4 input voltage B
27: AI4 input voltage (after
Set the display parameter 2 at disposal)
F18.09 18 1 ○
stop 28: DI6 terminal pulse input
frequency
29: AO1 output
Set the display parameter 3 at 30: AO2 output
F18.10 20 1 ○
stop 31: High-speed output pulse
frequency
0: Integer
1: One decimal
F18.16 Line speed display accuracy 0 1 ○
2: Two decimal
3: Three decimal
F19: Function-boost Parameters (refer to pages 93 - 101)
0: No auxiliary source
1: Digital setting 1 (the initial
value is set by F19.03 and
adjusted by and keys
on the keypad)
2: Digital setting 2 (the initial
value is set by F19.03 and
Auxiliary frequency setting adjusted by terminals UP/DN)
F19.00 0 1 ○
source selection 3: Digital setting 3 (the initial
value = 0, set by SCI direct
communication
4: AI analogue setting
5: Terminal pulse setting
6: Process PID output
7 - 10: AI1 - AI4
11: Keypad potentiometer
Units: Main and auxiliary
operations
Master/Auxiliary setting 0: Master setting + auxiliary
F19.01 10 1 ○
calculation setting
1: Master setting - auxiliary
setting
Network Mode
Frame head (at least Slave Function Frame head (at least
Data Checking
3.5 character spacing) address code 3.5 character spacing)
MODBUS adopts “Big Endian” encoding mode, higher byte prior to lower byte at sending.
In the RTU mode
• The idle time of frame head and frame tail passing bus should be not less than 3.5 bytes.
• Slave address=0, it means broadcast address.
• Data checking relies on CRC-16. The whole information need be checked. The concrete CRC
checking is referred to the page 172.
For example: To read the slave internal register F00.08 = 50.00Hz of No. 1 address:
Command Address Parameter Register Address Read char no. Checksum
frame 0x01 0x03 0x00 0x08 0x00 0x01 0x05 0xC8
Response Address Parameter Response Byte Content of register Checksum
frame 0x01 0x03 0x02 0x13 0x88 0xB5 0x12
3. Protocol Function
Supported function
MODBUS protocol supports the below parameter operation:
Supported function Code Instructions
To read function parameters and status parameter 0x03
To rewrite single function parameter or control 0x06 Saving or not is set by F17.09 in power failure
parameter 0x41 Not saved at power off
To rewrite numbers of function parameters or control 0x10 Saving or not is set by F17.09 in power failure
parameters 0x43 Saved at power off
Response CRC/LRC
Address Code Read byte no. Register content
frame checking
Data frame
1 1 1 2* no. of registers 2/1
bytes
Value or range 1 - 247 0x03 2* no. of registers
Response CRC/LRC
Address Code Register address Register content
frame checking
Data frame
1 1 2 2 2/1
bytes
Value or range 1 - 247 0x06, 0x41 0x0000 - 0xFFFF 0x0000 - 0xFFFF
This command rewrites the contents of continuous data unit from starting register address where is
mapped as function parameter and control parameter of controller, etc.
The inverter will start to save from low address to high address of the register when it continuously
saves many register parameters. The saving will return from the firstly failed address if the saving
process isn’t completely successful.
Fault and exception code
If the operation command fails, the response is fault code. The fault code is+0x80. Below is the
instruction for the exception codes.
Exception code Instructions
0x01 Illegal function parameters.
0x02 Illegal register address.
0x03 Data fault. Data is exceeded the upper/lower limit.
0x04 Slave operation fails (including fault caused by data invalid).
Unsupported operation (unsupported to read the attributes, factory default and upper / lower
0x16
limit for the control parameter and status parameter).
0x17 The register number of command frame is fault.
0x18 Incorrect information frame, including incorrect information length and incorrect checking.
0x20 Parameters cannot be modified.
0x21 Parameters are unchangeable when the controller is in running status.
0x22 Parameters are protected by password.
For instance: The register address of function parameter F03.02 is 0x0302, and that of function
parameter F16.01 is 0x1001.
Control parameter (0x32) address mapping
The users can realize the inverter’s starting, stopping and running speed setting through the control
parameter, and obtain the inverter’s running frequency, output current, etc. through indexing the
inverter’s status parameters.
The status parameters (0x32) are mapped as higher bytes of the register address, and the inter Group
indexes are as following:
Register address Parameter name Retained or not at power loss
0x3200 Control command character No
Saving or not is set by hundreds bit
0x3201 Running frequency setting
of F00.14 in power failure
0x3202 Auxiliary running frequency setting No
0x3204 Virtual terminal control setting No
The contents of the register can be defined as control commands as shown in the table below, ie the
control command word bit logic combination.
Register content Control command Register address Parameter name
0x1001 Forward running 0x1020 Stop due to external fault
0x1003 Reverse running 0x1040 Forward jog
0x1004 Decelerate to stop 0x1080 Reverse jog
0x1008 Emergency to stop 0x1100 Fault reset
0x1010 Coast to stop
5. Special Instruction
1. Group F08 (Asynchronous motor 1 parameter setting), Group F12 (Unused), F13.00 - F13.15
(Asynchronous motor 2 parameter setting) and Group F17 (SCI communication parameters) are the
inverter parameter which can be read but cannot be modified by the host computer.
2. F01.00 (user password) cannot be set and adjusted through communication as well, but the user can
verify the user password by writing F01.00 and get access to adjust inverter function parameters on
C
the host. After adjustment, the user can close the permission by writing invalid password to F01.00.
3. If many multi-function input terminals are set the same function, it may cause dysfunction. Therefore,
the user should avoid this case when modify the multi-function terminal function via the MODBUS.
7. Application Case
Remarks: Please verify all the hardware equipments are connected well before controlling the inverter
via communication. In addition, please preset the communication data format, baud rate and
communication address.
1. To read the command frame of the maximum output frequency of slave 2 (to read F00.06), answer
50.00Hz.
Command Address Code Register address Word no. of read Checksum
frame 0x02 0x03 0x00 0x06 0x00 0x01 0x64 0x38
Response Address Code Answer byte Register content Checksum
frame 0x02 0x03 0x02 0x13 0x88 0XF1 0x12
2. To read the DC bus voltage of slave 2 (to read status parameter), answer 537V.
Command Address Code Register address Word no. of read Checksum
frame 0x02 0x03 0x33 0x19 0x00 0x01 0x5A 0xBA
Response Address Code Answer byte Register content Checksum
frame 0x02 0x03 0x02 0x02 0x19 0x3C 0xEE
4. When the frequency setting source F00.10 = 2, set the frequency value to 45.00Hz by writing the
register content 0x11, 0x94.
Command Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E
Response Address Code Register address Register content Checksum
frame 0x02 0x06 0x32 0x01 0x11 0x94 0xDB 0x7E