ILLUMINATION LAYOUT OF INVERTER STATION (TYPICAL) - 8VSG592702-19009 - Rev A - CAT I - 12.12.2020

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

DOCUMENT SUBMISSION STATUS: FOR APPROVAL

Digitally signed by

Ramkumar RS Alireza Alireza


Aref
Sadraee

2020.12.02 20:51:14 Sadraee DN: cn=Alireza


Digitally signed by
Pankaj
Sadraee Aref,

+05'30' Aref ou=Normal


Date: 2020.12.03 Pankaj Kumar
23:21:32 +08'00'

DN: cn=Pankaj Kumar,


A 27 NOV 2020 FOR APPROVAL JNK/RSR ASA PK ou=Normal
Kumar Date: 2020.12.03
23:35:16 +08'00'

REV DATE DESCRIPTION PREPARED CHKD APPD

PROJECT TITLE

100 MW SOLAR (PV) POWER PLANT PROJECT

OWNER

ENERGON RENEWABLE BANGLADESH LIMITED

CONSULTANT

SUSTEN MAHINDRA

CONTRACTOR

 ABB PTE LTD, SINGAPORE

DOCUMENT TITLE:

ILLUMINATION LAYOUT OF INVERTER STATION [TYPICAL]

DOCUMENT NUMBER: 8VSG-5927-02-19009 PAGES: 01


DOCUMENT
CODE

1 Approved

2 Approved subject to incorporation of comment / modifications as noted

3 Not Approved. Resubmit revised drawings/documents after incorporating comment/modifications

For Information only with/without any comment and/or Resubmit revised drawings/documents after
4 incorporating comment/modifications
No comments received from customer within 5 days from 1st submission / 3 days from revised
submission shall be deemed as APPROVED

Review Date End User Name End User Signature


Y

FFL - FINISHED FLOOR LEVEL

49°
80X80X8MM THK NLDB - NORMAL LIGHTING DISTRIBUTION BOARD
PAD PLATE WELDED ELDB - EMERGENCY LIGHTING DISTRIBUTION BOARD
TO POLE FOR Z X NSB - NORMAL SWITCH BOX
80X80X8MM THK FIRST FLOOD LIGHT ESB - EMERGENCY SWITCH BOX
PAD PLATE WELDED CU - COPPER
TO POLE FOR GI - GALVANIZED IRON
SECOND FLOOD LIGHT FLOOD LIGHT
LED FIXTURE

01. OVERALL ARRAY LAYOUT - DWG NO. 20008-ED-ECD-001-00, REV-00.


ISA 65X65X6 02. ILLUMINATION DESIGN CALCULATION - DOC. NO. 8VSG-5926-02-19009, RA
WELDED TO 03. OUTLINE OVERALL DIMENSIONS [INVERTER
38MMØ GI PIPE
TRANSFORMER] - DWG. NO. 1LTN12456T0001, RA
DETAIL: 'B' 04. ICR EQUIPMENT LAYOUT - DWG. NO. 20008-EA-ECD-007-00, R0
38MMØ GI PIPE
300MM LENGTH WELDED
TO PAD PLATE 01. ALL DIMENSIONS ARE IN MILLIMETERS.
FLEXIBLE GI CONDUIT 02. LAYOUT SHOWN IS FOR GUIDANCE ONLY AND MAY BE REQUIRED TO BE
15626 3830 MODIFIEDTO SUIT SITE CONDITIONS IN CONSULTATION WITH SITE
1945 3900[TYP.] 978 1912 2RX1CX2.5SQ.MM ENGINEER.
ACDB01-C4-01 03. LIGHTING INSTALLATION SHALL BE CARRIED OUT ONLY AFTER ALL
PVC COPPER WIRE 80X80X8MM THK
ACDB01-C1-16 ACDB01-C1-15 ACDB01-C4-02 ACDB01-C1-14 CIVIL WORK IN THE PARTICULAR AREA HAVE BEEN COMPLETED.
6.0MTRS HEIGHT PAD PLATE WELDED 04. THE LIGHTING FIXTURE SHALL BE WIRED WITH PVC INSULATED 1CX2.5
POLE TO POLE SQ.MM STRANDED COPPER WIRES WHEREAS RECEPTACLES SHALL BE

670
WIRED WITH 1CX4.0 SQ.MM STRANDED COPPER WIRES.
ACDB01-C1-01 ACDB01-C1-03 ACDB01-C1-06 ACDB01-C1-09 38MMØ GI PIPE 05. ALL LIGHTING FIXTURES WILL BE EARTHED USING 12 SWG G.I WIRE
300MM LENGTH WELDED RUNNING ALONG THE ENTIRE LENGTH OF CONDUIT. ALL LIGHTING
ACDB01-C1-11 TO PAD PLATE PANEL WILL BE EARTHED THROUGH 25X6MM GS FLAT.

1190
INVERTERS AREA 06. WIRES OF DIFFERENT PHASES SHALL NOT RUN IN SAME CONDUIT.
07. MOUNTING HEIGHT'S OF LED FITTINGS, LIGHTING DISTRIBUTION
5275 5280
ACDB01-C1-04 ACDB01-C1-07 BOARDS, RECEPTACLES, SWITCH BOXES, ETC. ARE TABULATED AND
4040

SAME CAN REFERRED. MOUNTING HEIGHT'S ARE CONSIDERED FROM

2950
ACDB01-C1-12
3360

FFL AS REFERENCE.
ISA 65X65X6 08. LOADS ARE EQUALLY DISTRIBUTED ON ALL THREE PHASES AS FAR AS
WELDED TO POSSIBLE.
RMU, ACDB ROOM 38MMØ GI PIPE
2000

09. FOR EVERY CIRCUIT, ONE SEPARATE NEUTRAL WIRE WILL RUN IN THE
ACDB01-C1-02 ACDB01-C1-05 ACDB01-C1-08 ACDB01-C1-10 SAME CONDUIT OF RESPECTIVE PHASE.
ACDB01-C1-13 10. INSTALLATION WORK HAS TO BE DONE IN CLOSE CO-ORDINATION WITH
700

CIVIL CONTRACTOR.

XXDBXX-XX-XX
FITTING/SOCKET NUMBER
CIRCUIT NUMBER
SUPPLY DISTRIBUTION
BOARD TYPE & NUMBER

STIFFNER PLATES
120X100X8 MM THK.

125
SCADA+ACDB CABINET [ACDB01] 250 125 08-SWG GI WIRE
DETAIL: 'A'

2300
UPTO LIGHTING
LOCATION : INVERTER STATION [RMU, ACDB ROOM] L1
FIXTURES
JUNCTION L2
TOTAL LOAD: 1.840 KW L1

250
500
400V, 32A, 50Hz, 3PH, 4W, BOX

CU PVC WIRE
10kA, 1SEC, AL.BUS
100MMØ

2-2.5 SQmm
C001 C002 C003 C004
3.65MM THK. L2
4NO.S 22MMØ
11021

(TYP.)
500
MCB+ELCB, SPN HOLES
16A, 240V

6000
[TYP.] 150MMØ
5.00MM THK.
2RX1CX2.5SQMM PVC COPPER WIRE+
12SWG GI WIRE FOR EARTHING
6.0MTRS HEIGHT JUNCTION BOX
1RX3CX2.5SQMM COPPER CABLE [FOR FLOOD LIGHTS]+ EARTHING
12SWG GI WIRE FOR EARTHING GI POLE 20 SUPPLY
6.0MTRS HEIGHT TERMINAL
4500 TERMINALS [TYP.]

3700
POLE [TYP.] 2RX1CX4SQMM PVC COPPER WIRE+
[TYP.]
12SWG GI WIRE FOR EARTHING

120
08-SWG GI WIRE
ACDB01-C2-01 SYMBOL FIXTURE DESCRIPTION WATTS QTY C001 C002 C003 C004 08-SWG CONNECTED TO
X-AXIS ROTATION-49.1° GI WIRE

500
42W LINEAR LED 45 12 12 - - - NEAREST
OUTGOING MAIN EARTH FLAT
INCOMING

380
4595 ACDB01-C3-01 22W LINEAR LED 25 04 04 - - -
X-AXIS ROTATION-40.5°
- STIFFNER PLATES
3100

120W FLOOD LIGHT LED 125 04 02 02 - 1RX3CX2.5SQ.MM CU. PVC ARMOURED CABLE
120X100X8 MM THK.
SINGLE 5A, 3-PIN, 240V, SOCKET
200 01 - - - 01
WITH 5A SWITCH
BASE PLATE
SINGLE 15A, 3-PIN, 240V, SOCKET 500 01 - - - 01 500X500X20MM THK.
WITH 15A SWITCH

TOTAL WATTAGE CIRCUIT WISE 640 250 250 700


3858

TOTAL WATTAGE 1840 WATTS


3100

ACDB01-C3-02 INVERTER TRANSFORMER


X-AXIS ROTATION-49.1°
42W LINEAR LED 12 NO.S 144 NO.S 3.00 MTRS. CEILING MOUNTED
ACDB01-C2-02 22W LINEAR LED 04 NO.S 48 NO.S 3.00 MTRS. CEILING MOUNTED
X-AXIS ROTATION-40.1°
4900 120W FLOOD LIGHT LED 04 NO.S 48 NO.S 6.00 MTRS. POLE MOUNTED
A 27.NOV.2020 FOR APPROVAL JNK JNK/RSR ASA PK
SINGLE 5A, 3-PIN, 240V, SOCKET 01 NO. 12 NO.S 1.50 MTRS. WALL MOUNTED
WITH 5A SWITCH REV. DATE DESCRIPTION DRAWN DESIGN CHKD. APPD.
SINGLE 15A, 3-PIN, 240V, SOCKET 01 NO. 12 NO.S 1.50 MTRS. WALL MOUNTED Client :
WITH 15A SWITCH
ENERGON RENEWABLES (BD) LTD
6.0MTRS. HEIGHT GI POLE 150MMØ LOWER PART, 100MMØ UPPER PART, 02 NO.S 24 NO.S 6.00 MTRS. -
5MM THICK WITH BASE PLATE OF 500X500X20MM THK., STIFFNER PLATES
OF 120X100X8 MM THK. & ANCHOR GI BOLTS OF 20MMØ 500MM LONG Consultant : MAHINDRA RENEWABLES PRIVATE LTD
AFL House, Marol Maroshi Road, Marol, Andheri,
Mumbai 400059, India

Sub Contractor: Project Site Location:-


ABB PTE LTD. BAGERHAT, KHULNA,
2 AYER RAJAH CRESCENT BANGLADESH
SINGAPORE
Project:
100MW (AC) SOLAR PV PLANT

Drawing Title:
ILLUMINATION LAYOUT OF INVERTER STATION [TYPICAL]

Sheet Size:- A2 Scale:- NTS

FUNCTION DRAWN DESIGN CHECKED APPROVED


NAME JNK JNK/RSR ASA PK
X

DATE 27.NOV.2020 27.NOV.2020 27.NOV.2020 27.NOV.2020

Drawing No.: 8VSG-5927-02-19009 Sheet :- 01 OF 01 Rev: A

RELEASED FOR : TENDER INFORMATION APPROVAL CONSTRUCTION