Modul 10 - Fundamental Principles of Earthquake Resistant Design
Modul 10 - Fundamental Principles of Earthquake Resistant Design
Modul 10
Fundamental Principles of
Earthquake Resistant
Design
Patria Kusumaningrum, ST, PhD
SI 3213 Dinamika Struktur
Fakultas Teknik Sipil dan Lingkungan & Rekayasa Gempa
2
Materi Term 2
Mg. Topik Sub Topik
General Dynamic Loading Response of SDOF system excited by impulsive loading. Numerical
9
and the Numerical Evaluation solution including Duhamel’s & step by step integration method
Earthquake Resistant General concept of earthquake resistant buildings and the
10 importance of ductility factor
Building
11 Response Spectrum Analysis Concept and application of Response Spectrum (RS) analysis
Assembling of mass and stiffnes matrix, eigen vectors, eigen
12 MDOF values
MDOF: Modal Superposition
General concept of using modal superposition analysis to
13 Analysis and Normalization determine the responses of MDOF system
Mode of Vibration
General concept of using CQC and SRSS method, to determine the
14 MDOF: Maximum Response responses of MDOF system
General concept and application of Spectrum Response analysis
15 MDOF: RSA and ELF and Equivalent Lateral Force (ELF) procedure.
16 UAS
3
What is risk?
4 Risk?
Disaster
Seismic Risk
Seismic risk directly depends
Risk
upon Seismic Hazard, Seismic
Vulnerability, and Exposure of
elements at risk.
Seismic Risk
The applied forces are “attracted to” and concentrated at the stiffer
elements of the building.
Thus, the engineer must calculate the stiffness of the resisting elements
to ascertain the forces that they must accommodate.
If two elements (two frames, walls, braces, or any combination) are
forced to deflect the same amount, and if one is stiffer, that one will take
more of the load.
11
In the figure the columns have the same cross-section, but the short
column is half the length of the long one.
Mathematically, the stiffness of a column
varies approximately as the cube of its
length. Therefore, the short column will be
eight times stiffer (23) instead of twice as 450 lb
stiff and will be subject to eight times the
horizontal load of the long column. Stress
is concentrated in the short column, while
the long column is subject to nominal
forces.
13
Assignment
10 k 10 k
8 ft
10 ft 15 ft 10 ft 15 ft
Fig. 1 Fig. 2
10 ft 8 ft
15 ft
Fig. 3
Torsional Forces
The center of mass, or center of gravity, of an object is the point at which it could
be exactly balanced without any rotation resulting.
If the mass (or weight) of a building is uniformly distributed (in plan), the result is
that the plan's geometric center (centroid) will coincide with the center of mass.
In a building, the main lateral force is contributed by the weight of the floors,
walls, and roof, and this force is exerted through the center of mass, usually the
geometric center of the floor (in plan).
If the mass within a floor is uniformly distributed, then the resultant force of the
horizontal acceleration of all its particles is exerted through the floor's geometric
center
16
Torsional Forces
Centre of mass and rigidity
Centre of rigidity
Torsional forces.
17
Torsional Forces
Engineers refer to this as eccentricity between the center of mass and the
center of rigidity, C.R. (or centre of stiffness), which makes a building
subjected to ground motion rotate around its center of rigidity, creating torsion
- a twisting action in plan, which results in undesirable and possibly
dangerous concentrations of stress
18
Torsional Forces
(typical of a symmetrical building with uniform floor, wall and column masses)
In practice, some degree of torsion is always present, and the building code
Five configuration conditions (three vertical and two in plane) that originate in
the architectural design and that have the potential to seriously impact seismic
performance are:
Re-entrant corners
Discontinuous shear walls
28
Soft Stories/
Flexible Stories
29
Tabel 14
Ketidakberaturan Tipe 1
30
Soft-storey effect
The soft first story is the most common
feature of soft story irregularity. It usually
is present in modern frame buildings when
a large number of nonstructural rigid
components, such as masonry walls, are
attached to the columns of the upper
floors of a reinforced concrete frame
structure while the first story is left empty
of walls or with a reduced number of walls
in comparison to the upper floors. The
rigid nonstructural components limit the
ability to deform of the columns,
modifying the structural performance of
the building to horizontal forces. In a
regular building, the earthquake shear
forces increase towards the first story.
© Guevara-Perez, 2012
31
Soft-storey effect
In a regular building (Fig. a), the total disp
(∆ T) induced by an earthquake tend to
distribute homogeneously in each floor
throughout the height of the building.
Deformation in each floor (∆ n) would be
similar. When a more flexible portion of the
lower part of the building (Fig. b) supports
a rigid and more massive portion, the bulk
of the energy will be absorbed by the
lower-significantly more flexible-story
while the small remainder of energy will be
distributed amongst the upper more rigid
stories, producing on the most flexible
floor, larger relative displacement between
the lower and the upper slab of the soft
story (interstorey drift) and therefore, the
columns of this floor will be subjected to
large deformations.
© Guevara-Perez, 2012
32
Soft-storey effect
The most prominent of the problems caused by severe stress concentration is
that of the “soft” story.
Solutions
Solutions
Solutions
Fig A Fig B
This apartment house appears to have a soft first story (Figure A), but the
lateral force-resisting system is a strong internal shear wall box (Figure B).
41
Weak Story
42
Tabel 14
Ketidakberaturan Tipe 5
43
Weak-storey effect
Weak story configuration is often generated in
hotel and hospital buildings, in which not only
the first floor is designed less walls than the
other floors, but generally, due to its
importance, it also has a greater height than
the rest of the floors. Weak story can be
generated by:
(1) elimination or weakening of seismic
resistant components at the first floor;
(2) mixed systems: frames and structural
walls, with wall interruption at the second
floor or at intermediate floors
44
Avoid weak-storey
Solutions
Solutions
When shear walls form the main lateral resistant elements of a structure, and
there is not a continuous load path through the walls from roof to foundation,
the result can be serious overstressing at the points of discontinuity. This
discontinuous shear wall condition represents a special, but common, case of
the “soft” first-story problem.
Long section, Olive View Hospital. Note that the shear walls stop at the third floor.
Solutions
If the decision is made to use shear walls, then their presence must be
recognized from the beginning of schematic design, and their size and
location made the subject of careful architectural and engineering
coordination early.
52
Variations in Perimeter
Strength & Stiffness
53
If there is wide variation in strength and stiffness around the perimeter, the
center of mass will not coincide with the center of rigidity, and torsional forces
will tend to cause the building to rotate around the center of rigidity.
55
The figure shows an apartment house in Viña del Mar, Chile, following the
earthquake of 1985. The apartment, designed with open frontage, had only
three apartments per floor, with the service areas and elevator concentrated
to the rear and surrounded by reinforced concrete walls that provided the
seismic resistance. The lack of balance in resistance was such that the
building rotated around its center of rigidity, tilted sharply, and nearly
collapsed. The building was subsequently demolished.
56
A common instance of an
unbalanced perimeter is that
of open-front design in
buildings, such as fire
stations and motor
maintenance shops in which Centre of rigidity
it is necessary to provide
large doors for the passage
of vehicles.
CE-412: MODULE
Unbalanced perimeter2 resistance:
( Fall 2015) storefronts and “wedges.”
57
Solutions
The solution to this problem is to reduce the possibility of torsion by
endeavoring to balance the resistance around the perimeter.
Solutions
The opaque portion of the perimeter can be constructed of nonstructural
cladding, designed so that it does not affect the seismic performance of the
frame. This can be done either by using lightweight cladding or by ensuring
that heavy materials, such as concrete or masonry, are isolated from the
frame (Figure A)
60
Solutions
Solutions
Re-Entrant Corners
63
Re-entrant Corners
shapes
Re-entrant Corners
There are two problems created by these shapes.
The first is that they tend to produce differential motions between different
wings of the building that, because of stiff elements that tend to be located in
this region, result in local stress concentrations at the re-entrant corner.
The second problem of this form is torsion. Which is caused because the
center of mass and the center of rigidity in this form cannot geometrically
coincide for all possible earthquake directions. The result is rotation. The
resulting forces are very difficult to analyze and predict.
65
Re-entrant Corners
Re-entrant corner
Centre of rigidity
66
Re-entrant Corners
Re-entrant Corners
68
Re-entrant Corners
There are two basic alternative approaches to the problem of re-entrant corner
forms: structurally to separate the building into simpler shapes, or to tie the
building together more strongly with elements positioned to provide a more
balanced resistance (see figure ). The latter solution applies only to smaller
buildings
Solutions
Shall be avoided ?
70
1. Short Column
72
Structural Redundancy
A redundant or indeterminate structure has more structure than is absolutely
necessary. So, if some part of the structure is damaged or removed, the
structure will not necessarily fail or collapse, as another part can bear the
load of the damaged or missing piece. A non redundant structure is dependent
on every piece of the structure.
Redundancy in the structural system permits redistribution of internal forces
in the event of failure of key elements.
After experience in many earthquakes and much study and discussion, the
engineering profession has generally concluded that more than a single
system is the ideal solution for successful seismic resistance.
77
Provide Redundancy
The Hanshin Expressway after the 1995, Kobe Earthquake , Japan. Columnsin the
partially collapsed portion failed due to inadequate shear reinforcement. Existing
soil conditions and lack of redundancy aggravated the situation
78
Provide Redundancy
Provide Redundancy
Building must have sufficient separation to ensure they do not pound together
and damage each other in an earthquake. Generally if framed buildings are
separated by at least 0.01 H, pounding will not be a problem. (e.g. two 6-metre
tall buildings should be separated by 60mm.)
86
Improper
anchorage of
architectural
Components
@Mataram
University,
Lombok
Earthquake
2018
Base Isolation
Response of a building with no base isolation is shown in Figure a. Response of the
building with base isolation can be simulated by Figure b, where the rollers move
during ground shaking but the building above does not move, and no force is
transferred to the building due to shaking.
(a) (b)
100
Base Isolation
An LRB is made from layers of rubber sandwiched together with layers of steel.
In the middle of the bearing is a solid lead "plug." On top and bottom, the bearing
is fitted with steel plates which are used to attach the bearing to the building and
foundation. The bearing is very stiff and strong in the vertical direction, but
Lead-Rubber Bearing
Lead-Rubber Bearing
Building base
isolated with LRB
(lower
Building resting displacement and
directly on acc. in building)
ground (large
displacements
and acc. in
building)
105
The force needed to move the building upwards limits the horizontal or lateral
forces (Transformation of K.E into P.E & vice versa) which would otherwise
cause building deformations.
It should be noted that base isolation is not suitable for tall high rise
buildings or buildings located on soft soil.
Base isolation is most effective for short to medium rise buildings located on
hard soil.
107
Under a simple harmonic load, one can show that the main mass can be kept
completely stationary when the natural time period (of the attached absorber is
chosen to be (or tuned to) the time period of excitation .
During an earthquake or wind , TMD will move against the direction of main
structural vibration and an inertia force will be acted on the structure to
reduce the response of the structure .
TMD are effective in controlling wind induced excessive vibration in high rise
buildings due to one specific value of time period of tuned mass. However,
multiple tuned mass dampers have also been devised to control vibration
during earthquake corresponding to important modes
108
Assignment
1. Can we reduce the seismic risk of an existing building? Support your answer
with argument(s)
2. What will be your strategy as a design engineer to avoid soft story effect at a
floor (other than ground floor) without providing any wall?
3. How you will cope, as a design engineer, where you cannot avoid short
columns?
4. How will you handle a situation as a design engineer where you cannot
change the x-sectional dimensions of a very stiff beam connected to a
flexible column?
5. Suggest at least two methods of bracing the boundary walls.
111