DPX 250 Thermal Magnetic and Trip-Free Switches DPX - I 250: 87045 LIMOGES Cedex
DPX 250 Thermal Magnetic and Trip-Free Switches DPX - I 250: 87045 LIMOGES Cedex
DPX 250 Thermal Magnetic and Trip-Free Switches DPX - I 250: 87045 LIMOGES Cedex
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
CONTENTS PAGES
1. USE 1
2. RANGE 1
3. DIMENSIONS 1
4. OVERVIEW 2
5. ELECTRICAL AND MECHANICAL
CHARACTERISTICS 3
6. CONFORMITY 4
7. EQUIPMENTS AND ACCESSORIES 4
8. CURVES 6
1. USE 3. DIMENSIONS
DPX 3 "moulded case" circuit breaker offers optimal solutions to Fixed version
answer to protection requirements of tertiary and industrial
installations.
2. RANGE
Circuit breakers
25 kA 36 kA
In (A) 3P 4P 3P 4P
100 4 202 05 4 202 15 4 202 35 4 202 45
160 4 202 07 4 202 17 4 202 37 4 202 47
200 4 202 08 4 202 18 4 202 38 4 202 48
250 4 202 09 4 202 19 4 202 39 4 202 49
50 kA 70 kA
In (A) 3P 4P 3P 4P
100 4 202 65 4 202 75 4 206 05 4 206 15
160 4 202 67 4 202 77 4 206 07 4 206 17
200 4 202 68 4 202 78 4 206 08 4 206 18
250 4 202 69 4 202 79 4 206 09 4 206 19
In (A) 3P 4P
160 4 202 99 4 203 00
1/1
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Fixed version, rear terminals Plug-in version
4. OVERVIEW
4.1 Supplied
Supplied with
fixing screws
connection plates for bars and cable lugs
insulating shields (phase barrier)
On DIN rail:
• Vertical
• Supply invertor type
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Tripping button
5.3 Rated current (In) at 40°C / 50°C
Assigned current trip
thermal magnetic
3
DPX 250 (B/F/N/H)
In (A) L1‐L2‐L3 N L1‐L2‐L3 N
Circuit Breaker
(25kA, 36kA, 50kA, 70kA) 100 100 100 1000 1000
Rated current (A) 100, 160, 200, 250 160 160 160 1600 1600
Poles 3 ‐ 4 200 200 200 2000 2000
Rated insulation voltage Ui (V) 800 250 250 250 2500 2500
Rated operating voltage (50/60Hz) Ue (V) 690
Rated impulse withstand current Uimp (kV) 8
5.4 Power losses per pole under In
Rated frequency (Hz) 50 ‐ 60
Reference ambient temperature(°C) 40 ‐ 50 Circuit breaker
Operating temperature (°C) ‐25 ÷ 70
Mechanical endurance (cycles) 20000 Power losses per pole (W)
Mechanical endurance with motor control (cycles) 20000 In (A)
Electrical endurance at In (cycles) 8000
100 160 200 250
Electrical endurance at 0.5 In (cycles) 10000
Lugs 7.0 12.5 15.1 19.1
Utilization category A
Suitable for isolation Yes
Type of protection Thermal‐magnetic Values in the table are referred to single phase and they are
Magnetic adjustment 5 ‐ 10 x In
measured with cold breaker (with hot breaker, increase of
Thermal adjustment 0.8 ‐ 1 x In
Neutral protection for 4P version (%Ith) 100 10% must be considered)
Dimensions (W x H x D) (mm) 3P 105 x 165 x 100 5.5 Load operations
Dimensions (W x H x D) (mm) 4P 140 x 165 x 100
Weight (kg) 1.9(3P) ‐ 2.4(4P)
Loads operation
Switch 3
DPX ‐I Rated current (A) In = 250A
Uninterrupted nominal current Iu (A) 250 Opening (N) 45
Short‐time resistive current Icw(kA) for 1s 3 Closing (N) 78
Rated short‐circuit making capacity Icm (kA) 4.5 Reset (N) 75
Isolated voltage Ui (V AC) 800
Maximum rated operating voltage Ue (V AC/DC) 690
Rated impulse withstand voltage Uimp (kV) 8
Utilisation category AC22‐23A
Rated frequency (Hz) 50‐60
Operating temperature (°C) ‐25 ÷ 70
Mechanical endurance (cycles) 20000
Mechanical endurance with motor control (cycles) 20000
Electrical endurance (cycles) at In 8000
Electrical endurance (cycles) at 0.5 In 10000
Dimensions (W x H x D) (mm) 3P 105 x 165 x 100
Dimensions (W x H x D) (mm) 4P 140 x 165 x 100
Weight (kg) 1.9(3P) ‐ 2.4(4P)
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
• Undervoltage releases
5.6.2 Altitude 12 V ac/dc ref. 4 210 18
24 V ac/dc ref. 4 210 19
Altitude (m) 2000 3000 4000 5000
48 V ac/dc ref. 4 210 20
Ue (V) 690 590 520 460 110-130 V ac/dc ref. 4 210 21
In (A) (Ta = 40°C/50°C) In 0.98 x In 0.93 x In 0.9 x In 200-240 V ac ref. 4 210 22
277 V ac ref. 4 210 23
380-415 V ac ref. 4 210 24
5.6.3 Use at 400 Hz 440-480 V ac ref. 4 210 25
" Tropical climate" : To show the state of the contacts or opening of the DPX3 on a fault:
• execution II (all climates) according to IEC 60947-1 Annex Q, Cat. F. Auxiliary contact (standard) OC
Fault signal CTR
Switch:
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
• terminals for Cu/Al cables kit (4P) - flex 1x120mm², rigid 1x150mm², • Compact terminal shields 4P (set of 2) ref. 4 210 97
lugs 28.5 x 8 x 8.5mm ref. 4 210 31 • Generic seals kit (for 4x seal kit) ref. 4 210 95
• screw terminals for bar connections (3P) ref. 4 210 79
Front spreaders
• DPX3 front spreaders for 3P DPX3 250 (set of 3) ref. 4 210 34
• DPX3 front spreaders for 4P DPX3 250 (set of 4) ref. 4 210 35
Rear terminals
• DPX3 flat rear terminals for 3P DPX3 250 (set of 3) ref. 4 210 38
• DPX3 flat rear terminals for 4P DPX3 250 (set of 4) ref. 4 210 39
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
8. CURVES
9.3 Courbe de limitation en courant DPX125 1P
8.1 Thermal magnetic tripping curve
Value Description
t time
I current
In rated current
Ir long time setting current
curve 1 characteristic with cold start
curve 2 characteristic with hot start
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Value Description
Icc short circuit current
2
I²t (A s) pass‐through specific energy
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Value Description
Icc estimated short circuit symmetrical current (RMS value)
Ip maximum short circuit peak current
maximum prospective short circuit peak current
corresponding at the power factor
maximum real peak short circuit current
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Ambient temperature
30 °C 40 °C 50 °C 60 °C 70 °C
Fixed version Imax (A) Ir / In Imax (A) Ir / In Imax (A) Ir / In Imax (A) Ir / In Imax (A) Ir / In
Cage terminals, flexible cable 263 1,05 250 1 250 1 225 0,9 213 0,85
Cage terminals, flexible cable + sealable terminal shields 0 0 0 0 0 0 0 0 0 0
Cage terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
DPX 250 fixed ‐
vertical installation
Rear flat staggered terminals, flexible cableelds 0 0 0 0 0 0 0 0 0 0
Rear flat staggered terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
Lugs, flexible cable + sealable terminal shields 250 1 250 1 250 1 238 0,95 225 0,9
Rear flat staggered term., flex. cable + sealable term. shields 250 1 250 1 250 1 238 0,95 225 0,9
Cage terminals, flexible cable 0 0 0 0 0 0 0 0 0 0
Cage terminals, flexible cable + sealable terminal shields 0 0 0 0 0 0 0 0 0 0
Cage terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
horizontal installation
DPX 250 fixed ‐
Rear flat staggered terminals, flexible cableelds 0 0 0 0 0 0 0 0 0 0
Rear flat staggered terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
Lugs, flexible cable + sealable terminal shields 250 1 250 1 250 1 238 0,95 225 0,9
Rear flat staggered term., flex. cable + sealable term. shields 250 1 250 1 250 1 238 0,95 225 0,9
Thermal adjustment Magnetic adjustment
In (A) at 50 Hz Correction factor In (A) at 400Hz Correction factor Im (A) MIN at 400Hz Im (A) MAX at 400Hz
100 0.95 95 2 1000 2000
160 0.9 144 2 1600 3200
200 0.85 170 2 2000 4000
250 0.85 213 2 2500 5000