DPX 250 Thermal Magnetic and Trip-Free Switches DPX - I 250: 87045 LIMOGES Cedex

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

87045 LIMOGES Cedex

Phone :+33 05 55 06 87 87 – Fax :+33 05 55 06 88 88

Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279
DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

CONTENTS PAGES
1. USE 1
2. RANGE 1
3. DIMENSIONS 1
4. OVERVIEW 2
5. ELECTRICAL AND MECHANICAL
CHARACTERISTICS 3
6. CONFORMITY 4
7. EQUIPMENTS AND ACCESSORIES 4
8. CURVES 6

1. USE 3. DIMENSIONS
DPX 3 "moulded case" circuit breaker offers optimal solutions to Fixed version
answer to protection requirements of tertiary and industrial
installations.

2. RANGE
Circuit breakers

25 kA 36 kA
In (A) 3P 4P 3P 4P
100 4 202 05 4 202 15 4 202 35 4 202 45
160 4 202 07 4 202 17 4 202 37 4 202 47
200 4 202 08 4 202 18 4 202 38 4 202 48
250 4 202 09 4 202 19 4 202 39 4 202 49
50 kA 70 kA
In (A) 3P 4P 3P 4P
100 4 202 65 4 202 75 4 206 05 4 206 15
160 4 202 67 4 202 77 4 206 07 4 206 17
200 4 202 68 4 202 78 4 206 08 4 206 18
250 4 202 69 4 202 79 4 206 09 4 206 19

Switches Fixed version, front terminals

In (A) 3P 4P
160 4 202 99 4 203 00

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011

1/1
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300
Fixed version, rear terminals Plug-in version

Fixed version, front motor operator

4. OVERVIEW
4.1 Supplied
Supplied with
 fixing screws
 connection plates for bars and cable lugs
 insulating shields (phase barrier)

4.2 Mounting possibilities


On plate:
• Vertical
• Horizontal
Fixed version, side motor operator • Supply invertor type

On DIN rail:
• Vertical
• Supply invertor type

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


2/2
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 5.2 Breaking capacity (kA)


5.1 Main parts constituting the circuit breaker Breaking capacity (kA) & Ics
3P‐4P 3P‐4P 3P‐4P 3P‐4P
Ue/Icu B F N H
Terminal
220/240 V AC 40 60 80 100
connectors
380/415 V AC 25 36 50 70
440/460 V AC 20 30 40 60
480/500 V AC 10 25 30 40
IEC 60947‐2
600 V AC 9 20 22 25
690V AC 8 16 18 20
Handle
Ics(% Icu) 100 100 100 100
Rated making capacity under short circuit Icm
Icm (kA) at 415V 52.5 75.6 105 154
Thermal and
magnetic 220/240 V AC 40 60 80 100
adjustment NEMA AB‐1 480/500 V AC 10 25 30 40
Housings for
690V AC 8 16 18 20
auxilliaries

Tripping button
5.3 Rated current (In) at 40°C / 50°C
Assigned current trip
thermal magnetic
3
DPX  250 (B/F/N/H)
In (A) L1‐L2‐L3 N L1‐L2‐L3 N
Circuit Breaker
(25kA, 36kA, 50kA, 70kA)  100 100 100 1000 1000
Rated current (A) 100, 160, 200, 250 160 160 160 1600 1600
Poles 3 ‐ 4 200 200 200 2000 2000
Rated insulation voltage Ui (V) 800 250 250 250 2500 2500
Rated operating voltage (50/60Hz) Ue (V) 690
Rated impulse withstand current Uimp (kV) 8
5.4 Power losses per pole under In
Rated frequency (Hz) 50 ‐ 60
Reference ambient temperature(°C) 40 ‐ 50 Circuit breaker
Operating temperature (°C) ‐25 ÷ 70
Mechanical endurance (cycles)  20000 Power losses per pole (W)
Mechanical endurance with motor control (cycles)  20000 In (A)
Electrical endurance at In (cycles)   8000
100 160 200 250
Electrical endurance at 0.5 In (cycles)  10000
Lugs 7.0 12.5 15.1 19.1
Utilization category  A
Suitable for isolation Yes
Type of protection Thermal‐magnetic Values in the table are referred to single phase and they are
Magnetic adjustment 5 ‐ 10 x In 
measured with cold breaker (with hot breaker, increase of
Thermal adjustment 0.8 ‐  1 x In
Neutral protection for 4P version (%Ith) 100 10% must be considered)
Dimensions (W x H x D) (mm) 3P 105 x 165 x 100 5.5 Load operations
Dimensions (W x H x D) (mm) 4P 140 x 165 x 100
Weight (kg) 1.9(3P) ‐ 2.4(4P)
Loads operation
Switch 3
DPX ‐I Rated current (A) In = 250A
Uninterrupted nominal current Iu (A) 250 Opening (N) 45
Short‐time resistive current Icw(kA) for 1s 3 Closing (N) 78
Rated short‐circuit making capacity Icm (kA) 4.5 Reset (N) 75
Isolated voltage Ui (V AC) 800
Maximum rated operating voltage Ue (V AC/DC) 690
Rated impulse withstand voltage Uimp (kV) 8
Utilisation category AC22‐23A
Rated frequency (Hz) 50‐60
Operating temperature (°C) ‐25 ÷ 70
Mechanical endurance (cycles)  20000
Mechanical endurance with motor control (cycles)  20000
Electrical endurance (cycles)  at In 8000
Electrical endurance (cycles) at 0.5 In 10000
Dimensions (W x H x D) (mm) 3P 105 x 165 x 100
Dimensions (W x H x D) (mm) 4P 140 x 165 x 100
Weight (kg) 1.9(3P) ‐ 2.4(4P)

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


3/3
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

5.6 Functioning in particular conditions 7. EQUIPMENTS AND ACCESSORIES


7.1 Releases
5.6.1 Temperature • Shunt releases
12 V ac/dc ref. 4 210 12
Temperature Ta (°C)
24 V ac/dc ref. 4 210 13
In (A) ‐25 ‐20 ‐10 ‐5 0 10 20 30 40 50 60 70
48 V ac/dc ref. 4 210 14
100 135 132 128 126 123 120 112 102 100 100 90 84 110-130 V ac ref. 4 210 15
160 216 211 205 201 197 192 179 163 160 160 143 134 200-277 V ac ref. 4 210 16
200 270 264 256 251 246 240 224 203 200 200 179 168 380-480 V ac ref. 4 210 17
250 338 330 320 314 308 300 280 254 250 250 224 210
Maximum power = 400 VA / W

• Undervoltage releases
5.6.2 Altitude 12 V ac/dc ref. 4 210 18
24 V ac/dc ref. 4 210 19
Altitude (m) 2000 3000 4000 5000
48 V ac/dc ref. 4 210 20
Ue (V) 690 590 520 460 110-130 V ac/dc ref. 4 210 21
In (A) (Ta = 40°C/50°C) In 0.98 x In 0.93 x In 0.9 x In 200-240 V ac ref. 4 210 22
277 V ac ref. 4 210 23
380-415 V ac ref. 4 210 24
5.6.3 Use at 400 Hz 440-480 V ac ref. 4 210 25

See table B. Maximum power = 4 VA


Circuit breaker opening time < 50 ms

6. CONFORMITY • Time-lag undervoltage releases (800ms)


DPX 3 range of product concerning circuit-breakers and switch- Time-lag modules with voltage:
230 V ac
disconnectors are in full compliance with the EN/IEC standard 60947-2 ref. 0 261 90
400 V ac ref. 0 261 91
and 60947-3 respectively.
The certificate are issued by LOVAG and/or by IECEE CB-scheme Release:
To be equipped with a time-lag module ref. 4 210 98
certification scheme.
All the product range are CE, CCC, EAC, ANCE marked. 7.2 Auxiliary contact
DMX3 are full in compliance with the Shipping Register of Lloyds, RINA, set of connectors for aux contacts ref. 4 210 44
aux contacts (1NC and 1 NO) for all rotary handles ref. 4 210 10
Bureau Veritas, Germanishe Lloyds, Norske Veritas and ABS. signalling contact plugged-in version ref. 4 210 48
Changeover switch 3A – 250 VAC ref. 4 210 11

" Tropical climate" : To show the state of the contacts or opening of the DPX3 on a fault:
• execution II (all climates) according to IEC 60947-1 Annex Q, Cat. F. Auxiliary contact (standard) OC
Fault signal CTR

6.1 Marking Auxiliary contact


Nominal voltage (Vn) V (AC or DC) 24 to 250
Circuit breaker :
Intensity (A) 24 V DC 5
48 V DC 1.7
110 V DC 0.5
230 V DC 0.25
110 V AC 4
230/250 V AC 3
Configurations:
DPX3 250 → 1 auxiliary contact + 1 fault signal

Switch:

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


4/4
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

7.3 Rotary handles 7.6 Plug-in version


Direct Bases
• front/rear terminals plug-in base 3P DPX3 250 ref. 4 210 42
• DPX3 direct rotary handle ref. 4 210 00 • front/rear terminals plug-in base 4P
• DPX3 emergency direct rotary handle ref. 4 210 02 (with or without earth leakage module) ref. 4 210 43

Vari-depth handle IP55 Locking accessories


• DPX3 vari depth rotary handle ref. 4 210 04 • Ronis type flat key (cod. ABA90GEL6149) for plug-in base
• DPX3 emergency vari depth rotary handle ref. 4 210 05 ref. 4 210 45
• Profalux type star key (cod. HBA90GPS6149) for plug-in base
Locking accessories ref. 4 210 46
• Ronis type flat key random for direct rotary handle • padlock accessory for plug-in base ref. 4 210 47
ref. 4 210 06
• Profalux type star key random for direct rotary handle
ref. 4 210 07
• Ronis type flat key random for vari-depth handle 7.7 Motor operator
ref. 4 210 08
• Profalux type star key random for vari-depth handle • side motor operator 24-230 Vac/dc ref. 4 210 60
ref. 4 210 09 • front motor operator 24-230 Vac/dc ref. 4 210 61
• Ronis type flat key (cod. EL43525) for direct rotary handle
ref. 4 228 00 Locking accessories for front motor operator
• Ronis type flat key (cod. EL43363) for direct rotary handle • Ronis type flat key (cod. ABA90GEL6149) for front motor operator
ref. 4 228 01 ref. 4 210 62
• Ronis type flat key (cod. EL43525) for vari-depth handle • Profalux type flat key (cod. HBA90GPS6149) for front motor
ref. 4 228 02 operator ref. 4 210 63
• Ronis type flat key (cod. EL43363) for vari-depth handle • padlock selector for front motor operator ref. 4 210 64
ref. 4 228 03
Locking accessories for side motor operator
• Ronis type flat key (cod. ABA90GEL6149) for side motor operator
7.4 Mechanical accessories ref. 4 210 65
Insulated shields (phase barriers) • Profalux type flat key (cod. HBA90GPS6149) for side motor
• Set of 36 ref. 4 210 70 operator ref. 4 210 66
• padlock selector for side motor operator ref. 4 210 67
Sealable terminal shields
• sealable terminal shield for rear terminals 3P ref. 4 210 52
• sealable terminal shield for rear terminals 4P ref. 4 210 53 7.8 Mounting on rail fixing plate
• sealable terminal shield for front spreaders 3P ref. 4 210 56
• sealable terminal shield for front spreaders 4P ref. 4 210 57
• DPX3 250 3P/4P without earth leakage module ref. 4 210 72
Padlocks • DPX3 160 3P/4P with side mounting motor operator
• DPX3 padlock accessory for handle (“open” position) ref. 4 210 49 ref. 4 210 69

Interlock 7.9 Spare parts


• DPX3 interlock for fixed version ref. 4 210 58
• DPX3 interlock for plug-in / draw-out version ref. 4 210 59 • Fixing screws (set of 4) for plate installation ref. 4 210 81
• Battery kit (batteries + extractor) for 1 breaker ref. 4 210 82
7.5 Connection accessories • Fixing screws (set of 12) for DIN installation ref. 4 210 84
Cage terminals
• terminals for Cu/Al cables kit (3P) - flex 1x120mm², rigid 1x150mm², • Mini USB cap (for 20 device) - light grey colour ref. 4 210 89
lugs 28.5 x 8 x 8.5mm ref. 4 210 30 • Plug-in base kit (for 1 breaker 3P or 4P) ref. 4 210 91

• terminals for Cu/Al cables kit (4P) - flex 1x120mm², rigid 1x150mm², • Compact terminal shields 4P (set of 2) ref. 4 210 97
lugs 28.5 x 8 x 8.5mm ref. 4 210 31 • Generic seals kit (for 4x seal kit) ref. 4 210 95
• screw terminals for bar connections (3P) ref. 4 210 79

• screw terminals for bar connections (4P) ref. 4 210 80

Front spreaders
• DPX3 front spreaders for 3P DPX3 250 (set of 3) ref. 4 210 34
• DPX3 front spreaders for 4P DPX3 250 (set of 4) ref. 4 210 35

Rear terminals
• DPX3 flat rear terminals for 3P DPX3 250 (set of 3) ref. 4 210 38
• DPX3 flat rear terminals for 4P DPX3 250 (set of 4) ref. 4 210 39

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


5/5
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

8. CURVES
9.3 Courbe de limitation en courant DPX125 1P
8.1 Thermal magnetic tripping curve

Icu = 25-36-50-70 kA Imax = 250A 3-4 P Ue = 415Vac

Value Description
t time
I current
In rated current
Ir long time setting current
curve 1 characteristic with cold start
curve 2 characteristic with hot start

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


6/6
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

8.2 Pass-through specific energy characteristic curve

Icu = 25-36-50-70 kA Imax = 250A 3-4 P Ue = 415Vac

Value Description
Icc short circuit current
2
I²t (A s) pass‐through specific energy

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


7/7
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

8.3 Cut-off peak current characteristic curve (kA)

Icu = 25-36-50-70 kA Imax = 250A 3-4 P Ue = 415Vac

Value Description
Icc estimated short circuit symmetrical current (RMS value)
Ip maximum short circuit peak current
maximum prospective short circuit peak current
corresponding at the power factor
maximum real peak short circuit current

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


8/8
Reference(s) : 420 205/ 207/ 208/ 209/ 215/ 217/ 218/ 219
DPX3 250 420 235/ 237/ 238/ 239/ 245/ 247/ 248/ 249
Thermal magnetic and trip-free switches 420 265/ 267/ 268/ 269/ 275/ 277/ 278/ 279

DPX3-I 250 420 605/ 607/ 608/ 609/ 615/ 617/ 618/ 619
420 299/ 300

A) Derating Temperature and configurations

Ambient temperature
30 °C 40 °C 50 °C 60 °C 70 °C
Fixed version Imax  (A) Ir / In Imax (A) Ir / In Imax (A) Ir  / In Imax  (A) Ir / In Imax  (A) Ir / In
Cage terminals, flexible cable 263 1,05 250 1 250 1 225 0,9 213 0,85
Cage terminals, flexible cable + sealable terminal shields 0 0 0 0 0 0 0 0 0 0
Cage terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
DPX  250 fixed ‐ 
vertical installation

Lugs, flexible cable 250 1 250 1 250 1 238 0,95 225 0,9


Lugs, rigid cable 0 0 0 0 0 0 0 0 0 0
Spreaders, flexible cables 250 1 250 1 250 1 238 0,95 225 0,9
Spreaders, rigid cable 0 0 0 0 0 0 0 0 0 0
3

Rear flat staggered terminals, flexible cableelds 0 0 0 0 0 0 0 0 0 0
Rear flat staggered terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
Lugs, flexible cable + sealable terminal shields 250 1 250 1 250 1 238 0,95 225 0,9
Rear flat staggered term., flex. cable + sealable term. shields 250 1 250 1 250 1 238 0,95 225 0,9
Cage terminals, flexible cable 0 0 0 0 0 0 0 0 0 0
Cage terminals, flexible cable + sealable terminal shields 0 0 0 0 0 0 0 0 0 0
Cage terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
horizontal installation
DPX  250 fixed ‐ 

Lugs, flexible cable 250 1 250 1 250 1 238 0,95 225 0,9


Lugs, rigid cable 0 0 0 0 0 0 0 0 0 0
Spreaders, flexible cables 250 1 250 1 250 1 238 0,95 225 0,9
Spreaders, rigid cable 0 0 0 0 0 0 0 0 0 0
3

Rear flat staggered terminals, flexible cableelds 0 0 0 0 0 0 0 0 0 0
Rear flat staggered terminals, rigid cable 0 0 0 0 0 0 0 0 0 0
Lugs, flexible cable + sealable terminal shields 250 1 250 1 250 1 238 0,95 225 0,9
Rear flat staggered term., flex. cable + sealable term. shields 250 1 250 1 250 1 238 0,95 225 0,9

B) Correct factor for adjustment for use at 400 Hz

Thermal adjustment Magnetic adjustment
In (A) at 50 Hz Correction factor In (A) at 400Hz Correction factor Im (A) MIN at 400Hz Im (A) MAX at 400Hz
100 0.95 95 2 1000 2000
160 0.9 144 2 1600 3200
200 0.85 170 2 2000 4000
250 0.85 213 2 2500 5000

Technical sheet: F01364EN/02 Update: 24/06/2017 Creation: 25/05/2011


9/9