06 Differential Relay
06 Differential Relay
Attia El-Fergany
Professor of EPS and Protection
Differential Protection
▪ Relay that operates when the vector difference of two or more
similar electrical quantities exceeds a predetermined value
▪ Almost any type of relay, when connected in a certain way,
can be made to operate as a differential relay
▪ Guard against faults arising only within the protected unit,
ignoring those occurring outside it.
Differential Relaying
▪ Voltage Balance
▪ Current Balance
𝐾𝐶𝐿: 𝐼𝑖 = 0
𝑽𝒔 = 𝑰𝑭 𝑹𝑪𝑻 + 𝟐𝑹𝑳
𝑽𝒔
𝑹𝒔 = − 𝑹𝒓𝒆𝒍𝒂𝒚
𝑰𝒔
Current transformer knee point requirements
𝑽 = 𝑪𝑰𝜷
▪ Suitable values of C & β chosen
based on :
CTR CTR
Protected
Equipment
Internal
Fault
Relay Operates
Problem of Unequal CT Performance
CT CT
Protected
Equipment
87 IDIF 0
ĪS ĪR
Relay
(87)
Compares: IOP = I S + I R
| IS | + | IR |
k I RT =k
2
Differential Protection Applications
▪ Bus protection,
▪ Transformer protection,
▪ Generator protection,
▪ Line protection,
▪ Large motor protection,
▪ Reactor protection,
▪ Capacitor bank protection,
▪ Compound equipment protection.
Principle of Bias Differential Protection Relay
I1 + I 2
I Diff = I1 − I 2 I Bias =
2
Starting ratio (S)
transient.
22
Typical magnetising characteristic
▪ To minimise material costs, weight and size, transformers are
characteristic.
23
Transformer energizing
25
Differential Protection Stabilisation
▪ Time Delay - delays operation of the relay in the event
of a fault occurring at switch-on, the method is no
longer used.
▪ Harmonic Restraint –
– the inrush current contains all harmonic orders, but
these are not all equally suitable for providing bias.
In practice, only the second harmonic is used.
– Normal fault currents do not contain second or other
even harmonics,
26
% winding protected during
an earth fault
% winding protected during an
earth fault
𝑉𝑠
𝐼𝐹 =
3𝑅𝑓
(Nominal fault SLGF at x=1)
@ any x%
𝑉𝑠
𝐼𝑆 = 𝑥. = 𝑥. 𝐼𝐹 → 𝐼𝑆 ∝ 𝑥
3𝑅𝑓
𝑁𝑠
𝐼𝑃 = 𝐼𝑆 . → Nominal TTR
𝑁𝑃
@ any x%
𝑥.𝑁𝑠
𝐼𝑃 = 𝑥. 𝐼𝐹 . → 𝐼𝑃 ∝ 𝑥 2
𝑁𝑃
Star-Connected Winding – Resistance Earthing
29
Star-Connected Winding – Solid Earthing
Derivation
𝑢𝑛𝑑𝑒𝑟 SLGF : 𝐼𝐿 (𝑆𝐿𝐺𝐹) = 𝐼𝑃
𝑥.𝑁𝑠 𝑁𝑠
𝑥. 𝐼𝐹 . ≥ 0.2. 3𝐼𝐹 .
𝑁𝑃 𝑁𝑃
𝑥 2 ≥ 0.2. 3 → 𝒙 ≥ 58.86%
i.e. 41.14% of secondary winding is protected.
Derivation
𝑥 2 ≥ 𝑠. 3
𝑥2
s≤
3
37
Percentage Differential Protection
38
Conventional Differential Relay Issues
▪ Neutral connected Y-
windings
– E/F current flows in the Star-side
only.
▪ Numerical computation of
– Vector group matching
– CT ratio corrections
– Zero sequence Elimination
▪ Eliminates the need of
interposing CTs (for two-
winding transformers).
Numerical Relays
43
Single, dual, and variable-slope percentage
differential characteristics
Selection of Slope Characteristic
Settings - 87
✓ Mismatch (0) - Digital
✓ CT Errors (1-10%)
Any Questions,
Please…