0% found this document useful (0 votes)
52 views46 pages

06 Differential Relay

Differential relays operate when the difference between electrical quantities such as currents or voltages on either side of a protected zone exceeds a predetermined threshold. They provide protection for internal faults while ignoring external faults. Differential relaying uses principles of voltage balance, current balance, and the restraining characteristic to distinguish between internal and external faults. Relay settings must account for factors like CT errors, transformer inrush, and zero sequence currents to prevent maloperation during normal conditions. Modern numerical relays simplify differential schemes by software compensation.

Uploaded by

gfdhdtfh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views46 pages

06 Differential Relay

Differential relays operate when the difference between electrical quantities such as currents or voltages on either side of a protected zone exceeds a predetermined threshold. They provide protection for internal faults while ignoring external faults. Differential relaying uses principles of voltage balance, current balance, and the restraining characteristic to distinguish between internal and external faults. Relay settings must account for factors like CT errors, transformer inrush, and zero sequence currents to prevent maloperation during normal conditions. Modern numerical relays simplify differential schemes by software compensation.

Uploaded by

gfdhdtfh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Differential Relay

Attia El-Fergany
Professor of EPS and Protection
Differential Protection
▪ Relay that operates when the vector difference of two or more
similar electrical quantities exceeds a predetermined value
▪ Almost any type of relay, when connected in a certain way,
can be made to operate as a differential relay
▪ Guard against faults arising only within the protected unit,
ignoring those occurring outside it.
Differential Relaying
▪ Voltage Balance

▪ Current Balance

▪ Low Impedance Schemes

▪ High Impedance Schemes


▪ The restraint characteristic

▪ Low Impedance Differential Settings


Principles of Differential Relaying

𝐾𝐶𝐿: ෍ 𝐼𝑖 = 0

𝐼𝑖𝑛 = 𝐼𝑜𝑢𝑡 𝐼𝑖𝑛 ≠ 𝐼𝑜𝑢𝑡


Voltage Balance
Voltage Balance
▪ Normal conditions, 𝐼1 = 𝐼2 as before.

▪ By virtue of CT connections 𝐼1 and 𝐼2


oppose each other and thus no CT
secondary current.

▪ Implies that CT s are effectively open-


circuited!

▪ Overcome by loading each CT with a


resistor.
Current Balance – Normal/External
faults
Current Balance – Internal Fault
High Z / unbiased differential protection
High Z / unbiased differential protection

▪ Stabilisation is achieved by means


of a stabilizing resistor, 𝑹𝒔 ,
intended to raise the operating
voltage of the system.

▪ Fault current through 𝑹𝒔 could


lead to dangerous overvoltages
voltage limiters are required.
High Z / unbiased differential protection

𝑽𝒔 = 𝑰𝑭 𝑹𝑪𝑻 + 𝟐𝑹𝑳

𝑽𝒔
𝑹𝒔 = − 𝑹𝒓𝒆𝒍𝒂𝒚
𝑰𝒔
Current transformer knee point requirements

▪ Current transformers must have sufficient output to


ensure fast operation of relay during internal fault
conditions

▪ Required 𝑉𝑘 > 2𝑉𝑠 (typically -depends on actual relay


type)
High Impedance Circuit Arrangement

𝑽 = 𝑪𝑰𝜷
▪ Suitable values of C & β chosen
based on :

▪ Max secondary current under fault


conditions

▪ Relay setting voltage


Principles of Differential Relaying

▪ In reality provision has to be made for nonzero


differential quantities under normal, healthy
conditions.

▪ These could result due to line charging current, CT


mismatching, the transformer tapchanger, etc.
Differential Protection Principle

CTR CTR
Protected
Equipment

Internal
Fault

87 IDIF > ISETTING

Relay Operates
Problem of Unequal CT Performance
CT CT
Protected
Equipment

87 IDIF  0

▪ False differential current can occur if a CT saturates during a


through-fault

▪ Use some measure of through-current to desensitize the relay


when high currents are present
Possible Scheme – Percentage Differential
Protection Principle
ĪSP ĪRP
CTR Protected CTR
Equipment

ĪS ĪR

Relay
(87)

Compares: IOP = I S + I R
| IS | + | IR |
k  I RT =k
2
Differential Protection Applications
▪ Bus protection,
▪ Transformer protection,
▪ Generator protection,
▪ Line protection,
▪ Large motor protection,
▪ Reactor protection,
▪ Capacitor bank protection,
▪ Compound equipment protection.
Principle of Bias Differential Protection Relay

 
  I1 + I 2
I Diff = I1 − I 2 I Bias =
2
Starting ratio (S)

▪ Differential current caused by CT


errors and tap-changer positions
grows at the same per sent ratio as
the load current increases

▪ setting range 10 - 50%


2nd turning point (turn point 2)

▪ CT saturation at high currents


passing through the
transformer
▪ Slope always 100% (45°)
▪ Setting range 1.0 - 3.0
– Trafo: 1.5 - 2.0
– Generators: 1.0 - 1.5
– Motors: 1.0
Magnetising Inrush

▪ The phenomenon of magnetising inrush is a

transient condition (It is not a fault condition),

▪ Protection must remain stable during the inrush

transient.

22
Typical magnetising characteristic
▪ To minimise material costs, weight and size, transformers are

generally operated near to the ‘knee point’ of the magnetising

characteristic.

23
Transformer energizing

Ie: inrush current envelope


τe: time constant

▪The waveform contains a substantial amount of 2nd harmonics.


▪This phenomenon is part of normal power system operation and should not be detected
as a fault by the protection units, which should let the peak energizing current through.
Transformer Magnetizing Inrush Current
Point(s)

25
Differential Protection Stabilisation
▪ Time Delay - delays operation of the relay in the event
of a fault occurring at switch-on, the method is no
longer used.
▪ Harmonic Restraint –
– the inrush current contains all harmonic orders, but
these are not all equally suitable for providing bias.
In practice, only the second harmonic is used.
– Normal fault currents do not contain second or other
even harmonics,

26
% winding protected during
an earth fault
% winding protected during an
earth fault
𝑉𝑠
𝐼𝐹 =
3𝑅𝑓
(Nominal fault SLGF at x=1)

@ any x%
𝑉𝑠
𝐼𝑆 = 𝑥. = 𝑥. 𝐼𝐹 → 𝐼𝑆 ∝ 𝑥
3𝑅𝑓

𝑁𝑠
𝐼𝑃 = 𝐼𝑆 . → Nominal TTR
𝑁𝑃

@ any x%

𝑥.𝑁𝑠
𝐼𝑃 = 𝑥. 𝐼𝐹 . → 𝐼𝑃 ∝ 𝑥 2
𝑁𝑃
Star-Connected Winding – Resistance Earthing

29
Star-Connected Winding – Solid Earthing
Derivation
𝑢𝑛𝑑𝑒𝑟 SLGF : 𝐼𝐿 (𝑆𝐿𝐺𝐹) = 𝐼𝑃

@ 20% setting of 𝐼𝐿 (nominal)


𝐼𝐿 (𝑆𝐿𝐺𝐹) ≥ 0.2𝐼𝐿 (nominal)

𝑥.𝑁𝑠 𝑁𝑠
𝑥. 𝐼𝐹 . ≥ 0.2. 3𝐼𝐹 .
𝑁𝑃 𝑁𝑃

𝑥 2 ≥ 0.2. 3 → 𝒙 ≥ 58.86%
i.e. 41.14% of secondary winding is protected.
Derivation
𝑥 2 ≥ 𝑠. 3

𝑥2
s≤
3

To protect 80% of winding i.e. 20% is unprotected.


Therefore, set relay at 2.3% (which is very difficult to
achieve)
Group No. 1 : Phase displacement = 0°
Group No. 2 : Phase displacement = 180°
Group No. 3 : Phase displacement = -30°
Group No. 4 : Phase displacement = +30°
Phase Correction
▪ Electromechanical and static relays use appropriate CT
connections to ensure that the primary and secondary
currents applied to the relay are in phase.
▪ For digital and numerical relays, it is common to use
star connected line CT’s on all windings of the
transformer and compensate for the winding phase
shift in software.

37
Percentage Differential Protection

38
Conventional Differential Relay Issues

▪ Need for interposing CTs,

▪ Matching Vector Groups,

▪ Elimination of the zero-sequence components.


Interposing CTs

▪ Matching the secondary


Currents
– Example: 115/20 kV, 75 MVA,

– CTs are 400/5 and 2500/5

– HV: In = 376A (relay has 4.7A)

– LV: In = 2165A (relay has 4.3A)


✓ Interposing CT required for matching the
secondary currents
Elimination of the zero-sequence components

▪ Neutral connected Y-
windings
– E/F current flows in the Star-side
only.

– Without elimination, the relay will


see this as a differential current!
Advantages of Numerical Relay

▪ Numerical computation of
– Vector group matching
– CT ratio corrections
– Zero sequence Elimination
▪ Eliminates the need of
interposing CTs (for two-
winding transformers).
Numerical Relays

43
Single, dual, and variable-slope percentage
differential characteristics
Selection of Slope Characteristic
Settings - 87
✓ Mismatch (0) - Digital

✓ Load Tap Changer (10%)

✓ No-Load Tap Changer (5%)

✓ Measuring Relay Error (<5%)

✓ CT Errors (1-10%)

✓ Transformer Excitation (3-4%)


END

Any Questions,
Please…

You might also like