Commissioning Service Department Commissioning Standard Test Formats Description: Rxma2 Aux. Relay Test

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Commissioning Service Department

Commissioning Standard Test Formats

Description: RXMA2 AUX. RELAY TEST Record No.:


Bay no.: Drawing ref.: Sheet: 1 of 2
Contractor: Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:

Bay No. : ________________ Rated Voltage Ur: 110 – 125V DC

Bay Name : ________________ Function. : ______________

Manufacturer : ________________ Type No. : RK211 185-AN

Draw. & Sh. No. : ________________ Conn. Diag. No. : ______________

No. of contacts : 10 C/O

2. MECHANICAL CHECKS AND VISUAL INSPECTION :

ITEM DESCRIPTION CHECKED


1 Inspect for physical damage / defects.
2 Verify connections as per approved drawings.
3 Check tightness of all connections.
4 Check Ferrules.
5 Check apparatus lists.

3. ELECTRICAL TESTS :

a) FUNCTION TEST :

ITEM DESCRIPTION CHECKED


1 All contacts checked.
2 All output contacts resistance measured.

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: RXMA2 AUX. RELAY TEST Record No.:


Bay no.: Drawing ref.: Sheet: 2 of 2
Contractor: Contract no.: Substation No :

b) PICK-UP AND DROP OFF TEST :

Pick up Value Drop off Value


Volts Current Volts Current

Limits:
Pick-up voltage : < 80% Ur Drop-off voltage: > 0.25 Ur
(Table 1of Buyer’s Guide 1MRK 508 015-BEN)

c) OPERATING AND DROP OFF TIME TEST (AT 125V DC) :

Pickup (ms) Contacts Drop off (ms) Contacts

Limits:
Pick-up Time: 30/20 ms Drop-off Time: 5/10 ms
(Table 1of Buyer’s Guide 1MRK 508 015-BEN)

d) RELAY BURDEN TEST :

Voltage Current Watts

Limits:
Watts: 2 – 2.5 (at Ur)
(Table 1of Buyer’s Guide 1MRK 508 015-BEN)

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: