Wind Power Modeling Simulation Using Pscad
Wind Power Modeling Simulation Using Pscad
November 2016
Wind speed:
3.5 – 14 – 25 m/s
Main components
300
Station Z2
b1
CAP BANK 2
200
7500 pF
CCVT
LEGEND:
a a a a a b1
150 DS b1 b1 b1 b1 b1 b1
DS1 b1
BRK
100 BRK1
BAY A BAY B BAY C BAY D BAY E BAY F REACTOR 1
kV
50
50MVAr Reactor
0 50MVAr Cap.Bank
-100 b1
a1 a1 a1 a1 a1 a1 b1 b1
-150 b b b b b b
7500 pF
CCVT
REACTOR 2 REACTOR 3
time(s) 0.2450 0.2500 0.2550 0.2600 0.2650 0.2700 0.2750 0.2800 0.2850
50MVAr Reactor 50MVAr Reactor
Station X1 Station Y1 Station Z1
Transformer Energizing
• Core saturation
• Inrush current and harmonics
• Voltage dips
• Network characteristics - frequency scans
• Over voltages due to harmonic
resonance conditions Ia
7000 1.0
6000 380 Hz
5000
4000
240 Hz
|Z+|(ohms)
3000
2000
1000
0 0.0
0 100 200 300 400 500 600 700 800 900
Ia (kA) [6] 0.00628253
Frequency [Hz]
• ‘Traditional’ applications
Transients are initiated due to a change to the network topology • Transient solution
(connections) • Harmonics
• Switching Events • Non-linear effects
• Faults • Frequency dependent effects
• Lightning • Steady state solution
• Others • RMS Value
• Magnitude and phase
Grid
C
+ in Angle out slpang
- Resolver
rotor_angle D
- Stator flux
Id
Iq
Slip angle Rotor position
C
+ in Angle out slpang
- Resolver
rotor_angle D
• Solar PV, Type 3 and Type 4 renewable integration type use power
electronic inverters.
• Inverter performance depend on the fast and accurate measurement of
the Bus voltage phase angle
• This is a challenge in ‘weak’ system
Practical Examples
PSCAD/EMTDC feature
Wind Farm
• This example shows 12
Detailed Model Cluster_1
Windfarm_ENI:Cluster_1
Detailed PSCAD Wind farm
models connected to the
network through Electric
Wind Farm
Detailed Model
Cluster_2 Network Interface (ENI).
Windfarm_ENI:Cluster_2
ENI
• Each detailed model is
representing one or few
wind farm turbine
Wind Farm
Detailed Model
Cluster_12 generators.
Windfarm_ENI:Cluster_12
WGR Location
2.5 2.5
2
2
|Z1| (ohms)
|Z1| (ohms)
1.5
1.5 CTG007-Current_injection
CTG001_current_injection
CTG007-Harmonic_Scan
CTG001_Harm_Imp_Scan 1
1
0.5
0.5
0
0 0 10 20 30 40 50 60
0 10 20 30 40 50 60
Frequency (Hz)
Frequency (Hz)
Thank you