0% found this document useful (0 votes)
87 views6 pages

DL-BCM Server: HMI Setting

This document provides guidelines for connecting HMI devices to a DL-BCM Server PLC, including recommended HMI settings, device addressing information, and wiring diagrams for RS-232 and RS-485 connections. The HMI settings section lists the recommended options for connecting via RS-232, including baud rate, data bits, parity, and stop bits. Device addressing specifies the ranges for bit, word, and register addresses. Wiring diagrams illustrate the pinouts for RS-232 and RS-485 connections between supported HMI models and the PLC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views6 pages

DL-BCM Server: HMI Setting

This document provides guidelines for connecting HMI devices to a DL-BCM Server PLC, including recommended HMI settings, device addressing information, and wiring diagrams for RS-232 and RS-485 connections. The HMI settings section lists the recommended options for connecting via RS-232, including baud rate, data bits, parity, and stop bits. Device addressing specifies the ranges for bit, word, and register addresses. Wiring diagrams illustrate the pinouts for RS-232 and RS-485 connections between supported HMI models and the PLC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

PLC Connection Guide

DL-BCM Server
Website: http://www.hzdelin.com

HMI Setting:
Parameters Recommended Options Notes
PLC type DL-BCM Server
PLC I/F RS232 RS232, RS485
Baud rate 9600 9600~115200
Data bits 8 8
Parity None Even, Odd, None
Stop bits 1 1
PLC sta. no. 0 0-31

Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998
W LW dddd 0 ~ 9998
W RW ddddd 0 ~ 55536

Wiring Diagram:
RS-232 9P D-Sub (Diagram 1 ~ Diagram 3)
Diagram 1
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103 / cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

MT-iE MT8073iE / MT8102iE

MT-XE MT8092XE

MT-iP MT6103iP / MT8102iP


PLC Connection Guide

HMI PLC
COM1 COM3 RS232
RS232 RS232 9P D-Sub
9P Female 9P Female Male
Rx 2 8 TX
Tx 3 7 RX
GND 5 5 GND
RTS
CTS

Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE /


MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8121XE / MT8150XE / MT8090XE

HMI PLC
COM1 RS232
RS232 9P D-Sub
9P Female Male
Rx 2 TX
Tx 3 RX
GND 5 GND
RTS
CTS
PLC Connection Guide

Diagram 3
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP / MT6071iP / MT8071iP

HMI PLC
COM1 RS232
RS232 9P D-Sub
9P Female Male
Rx 9 TX
Tx 6 RX
GND 5 GND
RTS
CTS

RS-485 2W 9P D-Sub (Diagram 4 ~ Diagram 9)


Diagram 4
cMT Series cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND
PLC Connection Guide

Diagram 5
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 7 4 8 Data-
Data+ 6 1 3 Data+
GND 5 5 5 GND

Diagram 6
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 9 5 GND
PLC Connection Guide

Diagram 7
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103

MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /


MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6103iP / MT8102iP

HMI PLC
COM2 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Male 9P Male Male
Data- 1 6 8 Data-
Data+ 2 9 3 Data+
GND 5 5 5 GND

Diagram 8
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP

HMI PLC
COM1 COM3 RS485 2W
RS485 2W RS485 2W 9P D-Sub
9P Female 9P Female Male
Data- 1 7 8 Data-
Data+ 2 8 3 Data+
GND 5 5 5 GND
PLC Connection Guide

Diagram 9
MT-iP MT6071iP / MT8071iP

HMI PLC
COM2 RS485 2W
RS485 2W 9P D-Sub
9P Female Male
Data- 1 8 Data-
Data+ 2 3 Data+
GND 5 5 GND