DPB - Tech Evaluation1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

For Technical Evaluation of DPS Panel Board's

Sl No Description Agree Disagree Remarks if any


Panel Enclosure mainframe, doors, partitions should be
of 2mm CRCA without Powder Coating and Powder
Coating of minimum 80 micron. Base Channel
1 Yes No
75x5 for main panel

Panel should be fully compartmentalised(Cubicle type)


including all individual Capacitors feeders
2 Yes No

Cable Gland Plate - ACB chamber - 3mm , All other


chambers 2mm with Rubber Gasket
3 Yes No

Fan Filters with Louvers for all Chambers in all Panels .


Heater with Thermostat for ACB chambers
4 Yes No

All Busbars including Drop Busbars shall be Electrolytic


Aluminium of 99% purity with colour sleeved.
The current density shall be 0.8
Neutral =100% as of Phase. APFC main Busbar should
5 be of 1200A Rating as there will be number of holes. Yes No
Flexible copper wire wherever used should follow the
same rule.

All panels should have Al Earth Bars of 50 % of Neutral


current
6

MFM should show V, A, F,PF,


KVA,KW,KwH,KVAH,KVARH
7 Yes No

All CTs should be Moulded CT of Metering Class of Class


1 Accuracy with 7.5VA Burden. Tape wound CTs are not
8 allowed. Yes No

U/V and O/V Relay should be Digital microcontroller


based LCD display and site selectable U/V & O/V
settings range and settable Trip Time delay and Fault
9 Indications Yes No
All MCCBs should be Adjustable Thermal and
Adjustable Short Circuit of rated fault level. Handle,
Spreader, Shunt Trip Auxiliary and Trip Contact should
10 Yes No
be provided

All Earth Leakage Relay flush mounting type should be


microcontroller based LCD Display with continuously
showing Leakage Current as well as set current.
The leakage current should be adjustable 30 to 300Milli
Ampere. It
should have Test & Reset Facility.
11 There should be inbuilt Trip Circuit Monitoring and Yes No
indication to detect the failure of the ELR to trip the
MCCB during fault.
Prefered Make : Prok DvsMPEL 02, Elmeasure
iELR400D.
(Please submit the Technical Catalogue)

The Core Balance Current Transformer CBCT should be


Resin Cast of 250mm Dia for 630A, 150mm for 250A
MCCB as we have 240Sq mm cable available with us
12 and for all other feeders 100mm Dia Resin Cast. Tape Yes No
wound or Moulded CBCTs are not allowed. Cast resin
CT prefered for avoiding moisture related tripping

Overall Dimensions of each panels should be


mentioned to evaluate the space as we have to
13 Yes No
accommodate the cables as per the spare cable
available with us and ease of maintenance.
You should agree to provide commissioning support for
each and every panel during installation.
Each and every Earth Leakage Relay with Resin Cast
CBCT is to be Tested at site for trpping at 30 mA
14 sensitivity with portable Test Kit. Yes No
You should also ensure that >0.99 PF is maintained in
DPS monthly Energy Bill.

Cubicle Space with wiring should be provided for


800KVA Transformer Fixed Compensation capacitors

15 Yes No

All Capacitors are to be Heavy Duty Box Type, 440V AC .


APFC Relay should be only Beluk with Dual Auto
Selection of CESU and DG mode.
16 APFC should have Auto/ Manual and OFF mode. Yes No
(CESU pf & DG 0.9 pf)