Docs-Literature-New-Chilled Beam 2013

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Chilled Beam Solutions

ADVANCING THE SCIENCE OF AIR DISTRIBUTION

k-12 education woodgrains dual-function energy solutions

Redefine your comfort zone. ™ | www.titus-hvac.com


Redefine your comfort zone. ™ table of contents

The CBAL-24 is a linear active chilled beam that mounts into the ceiling. It features
either a one- or two-way air distribution pattern and is used for heating and/or
cooling applications. This model can contribute toward achieving LEED EA Credit 1:
Optimize Energy Performance; IEQp1: Minimum IAQ Performance.

03 Overview 11 TAO Heating/Cooling Operating Modes

04 Products 12 Introducing the CBAL Product Line

07 Titus’ Chilled Beam 13 Air Patterns

08 Introducing the TAO

10 Perimeter Heating/Cooling

02
Chilled Beam Solutions | www.titus-hvac.com
Overview - Chilled Beams
NEW OPTIONS FOR A NEW GENERATION

The Titus chilled ceiling product line is comprised of chilled beams, are available in 1, 2, and 4-way throw patterns. There is even a model
both active and passive, radiant ceiling panels, and radiant sails. These for high sidewall applications. In addition to the variety of product
products offer optimized performance and provide high levels of thermal solutions available, the appearance of the units can be customized
comfort for the occupant. In addition to increased occupancy comfort, through standard options, which enables seamless integration into any
use of the chilled ceiling products reduce the amount of energy required architectural style, traditional or contemporary.
to heat and cool a building.

The chilled ceiling products provide sensible cooling and heating to the
space by utilizing the more efficient heat transfer capacity of water, as
opposed to air. This decouples the latent and sensible loads, reducing
the energy cost of sensible cooling. With passive beams and radiant
products, an additional system is necessary to meet the ventilation
and latent cooling needs of the space. The Titus active chilled beams
integrate the supply of ventilation air creating an active diffuser. Using
the ventilation air to pressurize a plenum with aerodynamically designed
nozzles, high velocity jets of air are created forcing induction of room air
over the water coils integral to the units. Forced induction dramatically
improves the heating and cooling capacity over passive beams and
radiant products. Titus active chilled beams harness the energy of the
supply air to further reduce total energy consumption.

Titus offers a chilled ceiling product to meet the requirements of any


design or installation. Just a single model of passive beam accommodates
both exposed and recessed mounting applications. Active chilled beams

03
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ chilled beam products

linear active chilled beams

The CBAL-24 is a ceiling mounted, linear active chilled beam


capable of being mounted either Tegular or Lay-In into the ceiling.
It has a 1-way or 2-way air distribution pattern and is used for
heating and/or cooling applications. It is available in lengths from
2 to 10 ft.
CBAL-24

The CBAL-12 is a ceiling mounted, linear active chilled beam


capable of being mounted either Tegular or Lay-In into the ceiling.
It has a 1-way or 2-way air distribution pattern and is used for
heating and/or cooling applications. It is available in lengths from
2 to 10 ft.
CBAL-12

The DISA V is a sidewall chilled beam diffuser with a 2-pipe or


4-pipe system with a horizontal throw pattern. It is used for heating
and/or cooling applications.

DISA V

04
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ chilled beam products

All Titus Chilled Beam products can contribute toward achieving


floor mounted - under the sill LEED EA Credit 1: Optimize Energy Performance; IEQc2: Increased
Ventilation; and IEQc7.1: Thermal Comfort - Design.

The TAO is an under the sill active chilled beam that provides the
right proportion of heating/cooling to the perimeter wall, while
maintaining the necessary displacement ventilation, humidity
control, and temperature level of the room within the desirable
acoustic levels that are expected in classrooms or theaters.
TAO
linear passive chilled beams

The SPB is a passive chilled beam diffuser that can be mounted


flush with the ceiling or suspended below the ceiling for exposed
applications.

SPB
radiant ceiling products

The ALPETY FKL is a water-driven radiant ceiling system that creates


a high degree of thermal comfort through draft free cooling and
even temperature distribution in the space. The system operates
with low energy consumption and low noise levels.

ALPETY FKL

05
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ chilled beam products

The ALPETY HKL is a water-driven radiant ceiling system that


creates a high degree of thermal comfort through draft free
cooling and even temperature distribution in the space. The system
operates with low energy consumption and low noise levels.

ALPETY HKL

The ALPETY SKS is a water-driven radiant ceiling system that


creates a high degree of thermal comfort through draft free
cooling and even temperature distribution in the space. The system
operates with low energy consumption and low noise levels.

ALPETY SKS

06
Chilled Beam Solutions | www.titus-hvac.com
Benefits of Titus’ Chilled Beam Products
REDUCE COSTS. IMPROVE COMFORT. SAVE ENERGY.

BENEFITS OF CHILLED CEILING SYSTEMS


Chilled Ceiling Systems are designed to provide superior occupancy • When supplied with primary air from a dedicated outside air system
comfort. These systems require less energy to operate, and reduces (DOAS), 100% fresh air is supplied to the space
maintenance cost in comparison to conventional all air systems. • Dry-coil sensible cooling, eliminates bacterial, fungal, or mold
growth associated with fan coils and other unitary products with
Tempered and dehumidified air is supplied to the space to meet condensing coils
ventilation requirements and handle the latent load. The majority of the • Constant primary air volume ensures ventilation requirements are
sensible load is addressed with the chilled ceiling products. Decoupling met and helps maintain relative humidity levels in the space
the latent and sensible loads takes advantage of the superior volumetric
heat capacity of water. The reduced volume of air that must be delivered ENERGY EFFICIENCY AND OPERATIONAL BENEFITS:
to the space results in reduced air handler capacity and size, smaller • Utilizing the heat transfer capacity of water also takes advantage of
duct sizes, and overall energy savings. A higher supply temperature the superior operational efficiency of pumps as compared to fans.
contributes to increased occupancy comfort. "" A 1” diameter pipe can deliver the same cooling/heating capacity as
an 18” x 18” duct
FIRST COST BENEFITS: "" Reduction of fan energy by a factor of 7 to deliver the same cooling
• Shallow unit profiles allow for reduced ceiling space requirements; to the space
they typically require 60% less vertical space than conventional all • Higher supply water temperatures compared to conventional
air systems systems allow for use of water side economizers
"" Reduced slab-to-slab spacing, reducing material costs per floor "" Increased opportunities for free-cooling
"" Easily integrated into retrofit applications where space is limited • Significant reduction in maintenance costs and labor as compared
• Low volume of supply air required for active beams enables to conventional all air systems
reduction of the total amount of air processed at the air-handler by "" No moving parts - no blowers, motors, damper actuators to replace
an all air system up to 50% "" Dry-coil operation - does not require regular cleaning and disinfecting
"" Reduced air-handler size/capacity, and duct work size of condensate pans
"" Recommended cleaning of coils once every 4 to 5 years, more
COMFORT AND IAQ BENEFITS: frequently in hospitality rooms where linens are frequently changed
• Active beams typically supply a constant volume of primary air, (i.e. hospital patient rooms and hotel rooms)
decreasing occurrences of dumping and changes to the air motion
in the space - issues common to typical VAV systems

07
Chilled Beam Solutions | www.titus-hvac.com
Introducing the TAO - Temperature Ambient Optimizer
UNDER THE SILL ACTIVE CHILLED BEAM

Titus, TAO Temperature Ambient Optimizer, targets educational facilities


in climate zones with heat loads > 200 BTUH per foot. The unit can
help find the path to a balanced and healthy system by providing the
right proportion of heating or cooling to the perimeter wall to take
care of the majority of the room load, while maintaining the necessary
displacement ventilation, humidity control, and temperature level of
the room within the desirable acoustic levels that are expected to be in
classrooms or theaters.

• Allows the supply of 100% outside air


• Operates at near-minimum ventilation rate for the classroom
• Conforms to ANSI Standard S12.60 sound levels, acceptable to education
facilities pool of fresh air spreading over the entire floor. The convection from the
• Reduces energy consumption occupants and other heat sources causes the fresh air to rise and create
• Features customizable cabinets in a variety of wood finishes and colors very comfortable conditions in the occupied zone.

According to BOMA, energy averages 60% of a building’s total operating By redirecting a portion of the treated supply air at very low velocity
costs. With oil and electricity prices on the rise, it is no surprise that towards the cold, outside wall or window, it neutralizes the heat load
there is an increased focus on renewable energy, green products, and and creates a thermal curtain. This reduces the convention and radiation
LEED certified buildings, resulting in a greater demand for a product that from the cold wall or window, providing a more uniform temperature
combines comfort, indoor air quality, and energy efficiency. The TAO, a distribution and comfortable environment.
combination chilled beam/displacement unit and radiator, is the perfect
solution to help address these issues. Since there are no blowers and motors operating within the TAO unit,
the sound levels are further reduced and the overall energy consumption
The TAO is an excellent choice for schools and theaters where air quality of the system can be improved.
is a concern. The required ventilation air for the classrooms is already
pretreated before it is brought into the unit. With the TAO unit, part This revolutionary product takes advantage of all LEED certification
of the supply air is discharged into the space, with low air velocity, as requirements to obtain energy credits. In addition, the stricter ASHRAE
close to the floor as possible. This provides a very low and slow moving Standards of thermal comfort (Std. 55), energy savings and perimeter

08
Chilled Beam Solutions | www.titus-hvac.com
heating (Std.90.1) can be easily achieved with the addition of this Classroom latent loads as high as 200 BTUH per linear foot of exposure
product. can be satisfied while operating with chilled water temperatures high
enough to avoid condensation on the integral terminal cooling coil.
DESCRIPTION OF OPERATION Higher latent loads may require that some degree of condensation
TAO – A hybrid unit that takes advantage of the displacement, chilled be employed as a means of removing moisture from the recirculated
beams and radiation principles. room air. Although the units are furnished with a condensate pan, Titus
suggests that all latent loads are handled by the primary air.
The unit does not have any moving parts; instead it has two sets of
coils and two sets of nozzles to neutralize the two major loads within This revolutionary new product is specifically designed for the high
the zone. ventilation loads that are normally required in all the educational
facilities, theaters and long hallways with perimeter walls or windows.
The units are provided with a constant volume flow of conditioned
outside air between 55 to 66°F supply air temperature. This primary • TAO takes advantage of the new, non-condensing, low temperature, high-
supply air pressurizes the induction plenum of the TAO terminal unit efficiency boilers that operates at 140 deg. F instead of 180 degrees, thus
reducing energy consumption
and major portion of it will flow through the primary set of nozzles
• Allows for the reduction of the fresh air guidelines per ASHRAE 62.1,
located in the lower part of the unit and displaced into the room. As the making its air exchange effectiveness the highest among all HVAC systems
conditioned air leaves the nozzle it will also induce room air through the and ensures the correct quantity of outdoor air is provided to the space
water coil to heat or cool the return air. Here it is reconditioned, mixed • Achieves high indoor air quality by using the displacement ventilation
with primary air, and delivered to the room, at a discharge temperature strategy so there is no mixing of contaminants which keeps the CO2 levels
of 64 to 72°F, providing the necessary ventilation/air displacement for a in the classroom at minimum
very comfortable occupied zone. • Helps meet fan power limitations prescribed by ASHRAE 90.1
• Provides individual zone control and satisfies both heating and cooling
The other portion of the primary supply air is discharged through a loads in one single unit with no moving parts
secondary set of nozzles directed towards the outside wall/window to • Available to take full advantage of cooling-water side economizer offering
energy savings when mechanical cooling is not needed
neutralize the perimeter load. The secondary set of nozzles induces room
air through the secondary coil to increase the temperature of the supply
Opportunities for the contractor who understand DOAS
air during the heating mode. The hot air will rise along the perimeter
• Easier to coordinate
walls and windows to neutralize the thermal load by creating a warm
• Higher labor productivity
air curtain.
• Takes advantage of prefabrication and modularization
Comfort (temperature and air movement) is met by optimizing the air
Two unit sizes can be chosen and very well suited to fit under the
path where the two major loads are located. At the same time the unit
windowsill adjacent to the perimeter wall. Customized cabinets in a
meets minimum ventilation requirements.
variety of aesthetically-pleasing wood finishes and colors.

09
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ perimeter heating / cooling operating mode

A rendering of the TAO in a classroom environment providing the right


proportion of heating/cooling to the perimeter wall while taking care of
the room load.

The number of and size of units required is determined by the heating


requirements of the environment in which they are operating. Only the
minimum amount of terminals required to satisfy the space heating load
should be fitted. This maximum amount of supply air will continue to
discharge in a displacement fashion.

10
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ perimeter heating / cooling operating mode

HEATING MODE Primary air continues to be delivered cooler temperature than the
ambient air in the classroom. It is discharged through induction nozzles
inducing room air through the integral heat transfer coil. This air is cooled
in accordance with space thermostat demands prior to mixing with the
primary air. The resultant air delivery to the space is a displacement type
mixture of primary and recirculated air at 62 to 68°F.

Supply Airflow
(85to 90ºF)

Room Air 900


Primary Airflow 450 CFM CFM
(62 to 66ºF)
(70 to 72ºF)

COOLING MODE Primary air is delivered through the induction nozzles. The velocity of
the nozzles induces room air through the integral heat transfer coil
which is then cooled in accordance with space thermostat demands
prior to mixing with the primary air. The use of room air induction and
reconditioning allows the use of 100% outside air as the primary air
source. The space thermostat regulates the amount of induced air
reconditioning in accordance with the room cooling requirements,
resulting in a constant volume, variable temperature (61 to 68ºF)
discharge to the classroom.

Supply Airflow
(62 to 66 ºF)

Primary Airflow Room Air


(55 to 58ºF) (75 to 78ºF)

Chilled Water

Supply Airflow
(65 to 72ºF)

11
Chilled Beam Solutions | www.titus-hvac.com
Introducing the CBAL Product Line
THE NEXT STEP FOR TITUS CHILLED BEAM PRODUCTS

Chilled Beam is growing in popularity as engineers and design FEATURES


professionals are seeking to follow the statutory green products to meet • 1 way and 2 way air pattern
the minimum LEED or CHPS certification levels. To address the market • 2 to 10 foot chilled beam length in 1 foot increment
and our representative’s needs, Titus is introducing a USA built Active • 2 and 4 pipe coil configurations
Chilled Beam product line which will give us the competitive edge that • Cooling and/or heating coils
we have been lacking until now. • Left or right hand pipe configurations
• ½” SWT or MNPT water connections
Titus Ceiling mounted Active Beam, CBAL are designed to meet the • Air vent
room’s heating and cooling load demands, maximize room comfort while • Multiple nozzle sizes are available to vary the primary
air supply and chilled beam performance
simultaneously supplying fresh air to the occupied area. The whisper-
quiet air conditioning for almost any application can be installed in • Perforated round or linear bar return grille facing
suspended ceilings or T-bar ceilings and is available in various widths • Hinged access return grille panel for easy room side access to the coil
• Heavy gauge, galvanized steel casing
and lengths.
• Top or side air inlet; several diameters available
• Contributing sound levels below NC30
CBAL-12 AND CBAL-24 LINEAR ACTIVE CHILLED BEAM
• Adjustable mounting brackets
Titus chilled beams features the aerodynamic properties of Titus ceiling
• Internally painted surface
diffusers with the extra benefits of using hydronic coils and induced
• Pressure port for air-side balancing and flow verification
air to reduce the high sensible thermal loads. The primary air from the
• Polyester painted white (RAL 9010)
DOAS is supplied to the CBAL and is discharged through a series of
nozzles located along the length of the beam. This causes room air to
be induced through one or two coils and then mixes with the primary
supply air. This mixture of air is then discharged into the space through
the ceiling slot diffusers providing high cooling outputs with low
amounts of primary air. The CBAL’s are offered in 12” and 24” and can
be easily integrated into suspended and drywall ceilings.

12
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ air patterns

CBAL-24 2-WAY

CBAL-24 1-WAY

CBAL-12 2-WAY

CBAL-12 1-WAY

13
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ notes

14
Chilled Beam Solutions | www.titus-hvac.com
Redefine your comfort zone. ™ notes

15