Small
Footprint
Big Impact
Variable Refrigerant Flow Systems
Mini VRF Systems for New Construction
and Renovation Projects
MINI VRF
SYSTEMS

GO GREEN AND
SAVE SOME GREEN

Hitachi Mini VRF Systems are the energy-efficient A partnership of global leaders at your service
answer for buildings and properties with space
limitations. Hitachi Mini VRF Systems come to you from Johnson
Controls-Hitachi Air Conditioning, a global joint
The Mini VRF System delivers just the right amount venture of Johnson Controls, Hitachi, Ltd., and
of heating and cooling to every space using no more Hitachi Appliances, Inc.
energy than necessary.
When you partner with us, you benefit from proven
The small- footprint outdoor unit combined with VRF technologies backed by two of the industry’s
generous piping limits gives you flexibility to install most trusted companies. Johnson Controls-Hitachi
on rooftops or the ground. And the modular design Air Conditioning is the only North American-
makes indoor unit installation quick and easy with owned VRF equipment producer. We are uniquely
multiple options floor-by-floor and room-by-room. positioned to develop and deploy VRF systems
created without compromise to suit the climate
With both ducted and duct-free indoor units, the conditions, code requirements and technology
Mini VRF System is an excellent choice for both preferences shared by customers in North American
new and retrofit residential and light commercial countries.
applications.

Deliver savings and comfort


For owners and occupants, Mini VRF Systems offer
personalized comfort and exceptional energy
savings. Boasting impressive SEER ratings, the
system reduces operating costs with no compromise
in comfort. Multiple indoor unit options enable
individual comfort control of up to eight rooms/
zones, making it a great choice for residential and
light commercial applications with varied loads and
occupancy rates.

Hitachi Mini VRF Systems


MINI VRF
SYSTEMS –
TABLE OF CONTENTS
WHY VRF MINI VRF OUTDOOR UNITS
Enjoy A Better Tomorrow........................................................ 2-3 Mini VRF System Overview....................................................... 34
Everything You Need For Success........................................... 4-6 Mini VRF Systems-208/230V................................................ 35-36
Advantages For Your Entire Team........................................... 7-8
CONTROLLERS
INDOOR UNITS Controllers........................................................................... 38-43
Overview................................................................................ 9-11
OPTIONAL PARTS & ACCESSORIES
1-Way Cassette Unit................................................................. 13
2-Way Cassette Unit................................................................. 14 Optional Parts Accessories...................................................... 44
Mini Cassette Unit.................................................................... 15
4-Way Cassette Unit............................................................ 16-17
Ceiling Suspended Unit............................................................ 19
Wall-Mount Unit.................................................................. 20-21
Floor-Concealed Unit............................................................... 22
Floor-Exposed Unit................................................................... 23
Ducted High Static Unit....................................................... 24-25
Ducted Medium Static Unit................................................. 26-27 The information contained in this catalog is for illustration purposes only and is subject
Ducted Slim Unit...................................................................... 28 to change at the sole discretion of Johnson Controls. Statements, figures, calculations,
plans, images and representations are only examples. Johnson Controls encourages you,
EconoFresh Economizer Unit................................................... 29 as the purchaser, to analyze your HVAC requirements and to work with Johnson Controls to
Multi-Position Air Handler................................................... 31-33 determine the exact VRF System to fulfill your needs.

Hitachi Mini VRF Systems 1


MINI VRF
SYSTEMS

ENJOY A BETTER
TOMORROW

Mini VRF systems offer a host of benefits to you and Enjoy guilt-free comfort
your customers. These small-footprint, modular
systems offer tremendous design flexibility, enabling These compact systems are among the most energy-
you to solve multiple HVAC challenges. And your efficient HVAC options available today, so customers
customers will appreciate the exceptional energy never have to choose between comfort and savings.
savings and individualized comfort they provide.
Variable-speed compressors provide extremely
high part-load efficiency. And the systems
Design with freedom
essentially eliminate the energy loss that occurs in
A variety of standard modular components let you conventional, ducted central systems which may
customize and size equipment to meet specific account for as much as 30% of energy consumption.
project requirements. Because ductwork is generally In fact, these green technology systems can help
needed only for ventilation, ducts can be smaller, customers attain LEED® certification points for
reducing capital cost. Systems can easily be adapted resource efficiency.
as space is reconfigured. There is no need to
remove and replace the original unit or reconfigure Occupants will enjoy unparalleled comfort with
ductwork. Hitachi Mini VRF Systems. Temperature can be set
individually for multiple zones to suit different
Install with ease needs. And, once the temperature is set, the system’s
variable-speed compressors and precise modulation
Hitachi® Mini VRF systems are designed for quick help maintain it within a narrow range, ensuring
and simple installation. Piping from the outdoor consistent comfort. Occupants will also appreciate
units can be connected from the front, back, side, the system’s whisper-quiet operation.
or underneath. Indoor units are relatively small and
light and easy to transport and handle. Service is Plan on years of worry-free service
simple too: systems need little maintenance beyond
changing filters and cleaning coils. Removal of a Hitachi® Mini VRF Systems feature the Hitachi-
single panel provides easy access to all components: designed, high-efficiency scroll compressor. This
control boards, electrical connections, compressor exclusive technology is known for its excellent
and piping. reliability and efficiency and low noise level.

Hitachi Mini VRF Systems boast impressive efficiency ratings

SEER EER HSPF


Seasonal Energy Energy Heating Seasonal
Efficiency Ratio Efficiency Ratio Performance Factor
up to 23.1 up to 16.7 (HSPF) up to 12.1

2 Hitachi Mini VRF Systems


MINI VRF
SYSTEMS –
ENJOY A BETTER
TOMORROW Continued

You are in control


You set the level of control with options that range
from wired individual controllers to gateways for
building automation systems.

A selection of thermostats (controllers) are


available for indoor fan coil units from simple units
with on/off, setpoint, load and speed settings,
to programmable units that enable scheduling.
Wireless units are available to provide remote Industry certified
control of zone space conditions.
Hitachi VRF Systems are Intertek ETL
Central station controllers for larger projects
Listed (Canada & USA), signifying that
provide remote control and scheduling of the entire
they comply with the standard of
system from one or more control points.
Heating and Cooling Equipment (ANSI/
Adapters (gateways) enable control of large UL 1995 and CAN/CSA C22.2 No. 236-11,
buildings or campuses through building automation 4th Edition, October 14, 2011). Our Mini
systems such as Facility Explorer®. VRF products are tested under AHRI
210/240.
The ideal choice for multiple applications
The systems are also certified by the Air
The many advantages offered by the Hitachi Mini VRF Conditioning, Heating & Refrigeration
System make it the optimal choice for a wide range Institute.
of new construction and retrofit projects including:

• Buildings with multiple zones that have different


comfort needs such as hotels, schools, medical
office buildings and commercial office buildings

• Historical building renovations in which ducted


HVAC options are severely limited and the basic
building structure must not be disturbed

• Residential buildings including apartments,


townhomes, single-family homes and
condominiums

• Light commercial buildings such as small retail


shops and churches

Hitachi Mini VRF Systems 3


MINI VRF
SYSTEMS

EVERYTHING YOU
NEED FOR SUCCESS

Effective training, intuitive design and selection complete jobs accurately, on time and on budget.
software, advanced logistics and delivery and easily
accessible documentation form a powerful support • Service technicians maintain, troubleshoot and
package that adds substantial value to Hitachi Mini repair systems efficiently.
VRF Systems.
The training centers include a dedicated VRF
laboratory to provide hands-on experience with the
Expert instructors and various systems, components and controls. Videos
hands-on experience for your team and webinars supplement classroom learning on
specific subjects and refresh and enhance the skills
Comprehensive training programs provide
of your design, installation and service teams.
knowledge and skills necessary to effectively and
efficiently deploy Hitachi Mini VRF technology. Our Hitachi Mini VRF training programs help deliver
world-class training centers offer a full VRF course peace of mind that your staff is prepared to support
curriculum with specialized modules and topics that your business with the knowledge to compete in a
help: growing industry.
• D
 esigners select and configure the right
equipment easily and accurately.

• Installers learn the proper procedures and

4 Hitachi Mini VRF Systems


MINI VRF
SYSTEMS –
EVERYTHING YOU
NEED FOR SUCCESS Continued

Right-size systems • Accurately select systems using a System Sizing


with intuitive selection software Analysis. The process starts with the indoor fan
coil units so that outdoor units are optimally
The Hitachi® Mini VRF selection software intuitively sized. Proprietary algorithms figure the system
guides you step-by-step through equipment size using data input on the indoor units, load and
selection so you can quickly and accurately measurements, so your system does not include
choose an appropriate and cost-effective system capacity that will go unutilized.
configuration for each application.
• Use intuitively designed features and functionality
The web-based program allows access from any that make the design process easy, fast and
computer or tablet. The software helps you: accurate. You can select options and accessories
quickly, easily and accurately without the need for
• Design accurate final system drawings including additional information or calculations.
piping and wiring diagrams in an easy, quick, step-
by-step process.

Hitachi Mini VRF Systems 5


MINI VRF
SYSTEMS

EVERYTHING YOU
NEED FOR SUCCESS Continued

Expect the right equipment on site All information is available instantly via smartphone
and on time or tablet by scanning the Quick Reference (QR) code
on the product nameplate. The QR code also can be
Ample inventory and advanced order management used to make warranty registration even easier.
and logistics systems can help you complete
installations in a timely manner. Consistent service Let’s go to work – together
and predictable deliveries help you prevent delays
waiting for essential components and enable Hitachi Mini VRF Systems can be configured to meet
you to set a project timeline and schedule labor your project requirements and deliver exceptional
efficiently. Our state-of-the-art main distribution performance. Heat pump units with DC inverter-
center is located in Memphis, Tennessee where UPS driven compressors offer energy savings and the
and FedEx have hubs. This enables us to provide ability to scale to size. Indoor units for ducted or
fast, accurate deliveries and simplifies expedited non-ducted applications offer optional motion
shipments. sensing control for even greater energy savings.
Additional energy savings can be achieved with the
Find information you need 24/7 EconoFresh Economizer Indoor Unit which provides
free-cooling when conditions permit. A host of
Easy access to product information options, controls and accessories help ensure a
helps designers, contractors and custom fit for your project and years of comfort
service personnel work accurately for your customers.
and efficiently. Our secure web
portal, HVACNavigator.com, provides product Enjoy the advantages of working with our team
documentation, technical and service manuals, while bringing the many benefits of Hitachi Mini VRF
troubleshooting guides, brochures, videos, Systems to your customers.
technical support, contact information, and more.

6 Hitachi Mini VRF Systems


MINI VRF
SYSTEMS –
ADVANTAGES FOR Summary of features
YOUR ENTIRE TEAM and benefits

FEATURES ADVANTAGES BENEFITS

Compact footprint • Ideal for areas with strict lot-line codes • Expands options for positioning outdoor
units

• Simplifies design process


Modular components • Requires less indoor space than
conventional systems • Allows easy updates as space is
reconfigured or expanded
ARCHITECT / SYSTEM DESIGNER

• Ultimate in design flexibility • Reduces system costs


Non-ducted systems
• Reduces clearance between building floors • Ideal for historic renovations

• Accommodates retrofits by making use of


existing duct infrastructure
Ducted systems • Reduces overall construction costs
• Suits unique buildings that include ducted
and non-ducted areas

Heat pump VRF systems • Precisely heats or cools multiple zones • Provides extreme system design flexibility

Comprehensive training • Modules tailored to specific job functions • Enables effective equipment selection and
specification

Web-based system selection • Intuitive functionality that simplifies and


speeds designs • Allows confident selection and right-sizing
software of systems
• Accessible from any computer or tablet

FEATURES ADVANTAGES BENEFITS

Installation simplicity • Outdoor unit piping can be connected from • Reduces installation time and cost
front, side, back or underneath.

Comprehensive training • Modules tailored to specific job functions • Enables professional, high-quality, timely
installation
MECHANICAL CONTRACTOR / INSTALLER

Consistent, reliable product • Ensures correct components are delivered • Enhances installation efficiency
delivery to job sites on time • Allows efficient labor scheduling

Easy maintenance access • All components easily accessible • Speeds up time spent on maintenance,
repair, and troubleshooting

• All product information is available on


HVACNavigator.com
Easy access to product • Simplifies and speeds maintenance,
information • QR code on unit nameplate allows access troubleshooting and repairs
to all information on that unit, including
warranty registration.

Compact and lightweight


• Easy to handle • Reduces installation time and cost
outdoor units

Hitachi Mini VRF Systems 7


VRF
SYSTEMS

ADVANTAGES FOR
YOUR ENTIRE TEAM Continued
FEATURES ADVANTAGES BENEFITS

Single phase power • Flexibility in selection of buildings and • Mini VRF can be used in most light commercial
supply locations and residential applications

Designed for • SEER industry’s highest for VRF


systems • Saves energy
optimized efficiency

Optimum • Efficient heating or cooling


System

individualized • Up to 8 Indoor Units can be connected


to one Outdoor Unit • Set-temperatures per zone increases occupant
comfort comfort

• Extremely quiet (sound ratings as low as 44


Noise reduction dBA for outdoor units; 28 dBA for indoor units)
• Lets user choose from several noise
preference mode reduction levels • Ideal where outdoor units are positioned on
side of building or in locations where there
are noise restrictions

• Engineered to deliver the optimum • A leader in the Mini VRF system industry
DC inverter-driven
efficiency • Highest SEER
Compressor

scroll compressor at normal load conditions • Highest COP

Compressor • Smoothly delivers only the exact • Allows fine control for optimum comfort
amount of refrigerant needed for the
modulation load • Saves energy

• Limits electric demand charges


BUILDING OWNER

• Users can select several power-saving


Outdoor Units

Demand control levels • Limits equipment wear and tear


• Reduces noise

Compact and • Can be placed in tight areas such as


patios and balconies • Can save valuable space
lightweight

As high as .74 in. W.G.


static pressure in • Offers adjustable speeds to match the • Flexibility to accommodate long or short
Indoor Units

static pressure requirement ductwork runs


ducted systems

Optional motion and • Sets back temperature when space is


unoccupied, increasing efficiency even • Saves energy
radiant sensors further

• Controls multiple indoor and outdoor • Maximizes indoor comfort


units from one control point
H-Link II Protocol • Saves energy
• Adds versatility to connect various
central control options • Improves system management

• Adjusts in 1 degree Fahrenheit • Auto-adjusts for daylight saving time


Temperature control increments • Provides options to satisfy multiple projects/
Controls

• Adjustable fan speeds buildings

• Automatic data formatting reduces


• Enables control of VRF systems by way integration time and expense
of a building management system (e.g., • Full BMS capabilities enable superior control
VRF Smart Gateway Facility Explorer®) for almost unlimited of all system components
control in a building of campus • Wi-Fi accessibility enables 24/7 monitoring
enterprise. and control from laptops, tablets and
smartphones

8 Hitachi Mini VRF Systems


INDOOR
UNITS

Feel the
Difference
Indoor Units

The Mini VRF Outdoor Unit is compatible with all


Hitachi VRF indoor units. Hitachi VRF indoor units
operate quietly and are easy to install, service
and maintain. A wide variety of non-ducted and
ducted units are available in styles and capacities
to fit multiple applications. Units operate quietly
with sound ratings as low as 26 dBA.

Non-Ducted Units Ducted Units


1-Way Cassette Ducted High Static

2-Way Cassette Ducted Medium Static

4-Way Mini Cassette Ducted Slim

4-Way Cassette EconoFresh Economizer

Ceiling-Suspended Multi-Position Air Handler

Wall-Mount

Floor-Exposed

Floor-Concealed

Hitachi Mini VRF Systems 9


INDOOR
UNITS –
OVERVIEW Choose the style and size from
the wide selection of indoor units
to meet your requirements for
layout and design.

Non-Ducted indoor unit model numbers

1-Way Cassette 2-Way Cassette 4-Way Cassette Mini Cassette


HIC1006B21S HIC2018B21S HIC4008B21S HIC4024B21S HICM008B21S
HIC1008B21S HIC2024B21S HIC4012B21S HIC4030B21S HICM012B21S
HIC1012B21S HIC4015B21S HIC4036B21S HICM015B21S
HIC1015B21S HIC4018B21S HIC4048B21S HICM018B21S

Ceiling Suspended Wall Mount Floor Concealed Floor Exposed


HICS015B21S TIWM006B21S TIWM018B21S HIFC006B21S HIFE006B21S
HICS024B21S TIWM008B21S TIWM024B21S HIFC008B21S HIFE008B21S
HICS030B21S TIWM012B21S TIWM030B21S HIFC012B21S HIFE012B21S
HICS036B21S TIWM015B21S HIFC015B21S HIFE015B21S

Ducted indoor unit model numbers

Ducted High Static Ducted Medium Static Ducted Slim EconoFresh


HIDH015B22S HIDH030B22S HIDM006B22S HIDM027B22S HIDS006B21S HIDM030B21E
HIDH018B22S HIDH036B22S HIDM008B22S HIDM030B22S HIDS008B21S HIDM036B21E
HIDH024B22S HIDH048B22S HIDM012B22S HIDM036B22S HIDS012B21S HIDM048B21E
HIDH027B22S HIDH054B22S HIDM015B22S HIDM048B22S HIDS015B21S
HIDM018B22S HIDM054B22S HIDS018B21S
HIDM024B22S

Multi-Position Air Handler


HMAHP18B21S HMAHP48C21S
HMAHP24B21S HMAHP48D21S
HMAHP30B21S HMAHP60C21S
HMAHP36B21S HMAHP60D21S
HMAHP36C21S HMAHP60D22S

10 Hitachi Mini VRF Systems


INDOOR
UNITS –
SELECTION Choose from a wide array
of options

Tons 0.5 0.7 1.0 1.3 1.5 2.0 2.3 2.5 3.0 4.0 4.5 5.0

1-Way Cassette
Indoor Unit

2-Way Cassette
Indoor Unit

4-Way Mini
Cassette Indoor
Unit

4-Way Cassette
Indoor Unit

Ceiling Suspended
Indoor Unit

Wall Mount
Indoor Unit

Floor Concealed
Indoor Unit

Floor Exposed
Indoor Unit

Ducted High Static


Indoor Unit

Ducted Medium
Static Indoor Unit

Ducted Slim
Indoor Unit

EconoFresh
Economizer
Indoor Unit

Multi-Position
Air Handler Unit

Hitachi Mini VRF Systems 11


12 Hitachi Mini VRF Systems
INDOOR
UNITS

1-WAY CASSETTE Ceiling-mounted, one-way cassettes offer compact designs
and a choice of corner-mounted, one-way discharge, or
two-way discharge (from the front and downward).

Key Features
• Slim and stylish design
• Automatic swing louver distributes airflow evenly for
uniform temperature
• Optional energy saving motion and radiant heat sensor
for optimized airflow and temperature control in
response to room occupancy.
Capacities 6,000 to 15,000 Btu/hr

Tonnage 0.5 0.7 1.0 1.3


1-Way Cassette Indoor Unit Model HIC1006B21S HIC1008B21S HIC1012B21S HIC1015B21S
Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity * Btu / h (kW) 6000 (1.8) 8000 (2.3) 12000 (3.5) 15000 (4.4)

Nominal Heating Capacity * Btu / h (kW) 6700 (2.0) 9000 (2.6) 13500 (4.0) 17000 (5.0)

Sound Pressure Level dB


34-32-29-27 36-34-31-28 40-37-33-31 42-38-35-31
(Overall A Scale) (Hi2-Hi-Me-Lo)

Outer Dimensions Height in. (mm) 9-1/4 (235) 9-1/4 (235) 9-1/4 (235) 9-1/4 (235)

Width in. (mm) 35-7/16 (900) 35-7/16 (900) 35-7/16 (900) 35-7/16 (900)

Depth in. (mm) 27-15/16 (710) 27-15/16 (710) 27-15/16 (710) 27-15/16 (710)

Net Weight lbs. (kg) 55 (25) 55 (25) 57 (26) 57 (26)

Refrigerant R410A

Indoor Fan Air Flow Rate cfm 300-265-229-212 335-300-265-229 459-406-353-300 512-459-388-335

(Hi2-Hi-Me-Lo) (m3/min) (8.5-7.5-6.5-6) (9.5-8.5-7.5-6.5) (13-11.5-10-8.5) (14.5-13-11-9.5)

Motor Nominal Output W 50 50 50 50

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid LIne in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

Adjustable Panel Model Name P-AP36CNA P-AP56CNA

Applicable Indoor Unit Model HIC1006B21S and HIC1008B21S HIC1012B21S and HIC1015B21S

Color Neutral White

Dimension Height in. (mm) 1-3/8 (35)

Width in. (mm) 43-5/16 (1100)

Depth in. (mm) 31-1/2 (800)

Net Weight lbs. (kg) 10 (4.5)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
4.9 ft. (1.5m) beneath the units.
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS The above data was measured in an anechoic chamber so that reflected
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) sound should be taken into consideration in the field.
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Indoor Units

Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Piping Length: 24.6 ft. (7.5m)
Piping Lift: 0ft. (0m)

Hitachi Mini VRF Systems 13


INDOOR
UNITS

2-WAY CASSETTE With a sound level down to 33 dB(A), this unit is among the quietest
on the market. Individual louver control with auto-swing or fixed air
exhaust angles brings comfort to every space in the environment, no
matter the room layout.

Key Features
• Nominal capacity of 18 or • Standard integrated condensate
24 MBH DC drain pump with 33-7/16 inch
• Compact design - requires only lift height
Capacities 18,000 to 24,000 Btu/hr 11-3/4” height • Optional energy-saving motion
• Energy-efficient DC fan motor and radiant heat sensor
• Optional air filter box for optimized airflow and
temperature control in response
to room occupancy
Tonnage 1.5 2.0
2-Way Cassette Indoor Unit Model HIC2018B21S HIC2024B21S
Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity * Btu/h (kW) 18,000 (5.3) 24,000 (7.0)

Nominal Heating Capacity * Btu/h (kW) 20,000 (5.9) 27,000 (7.9)

Sound Pressure Level **


(Overall A Scale) dB 42-39-36-33 46-43-39-34
(Hi2-Hi-Me-Lo)

Height in. (mm) 11-3/4 (298) 11-3/4 (298)

Outer Dimensions Width in. (mm) 33-7/8 (860) 33-7/8 (860)

Depth in. (mm) 24-13/16 (630) 24-13/16 (630)

Net Weight lbs. (kg) 55.1 (25) 55.1 (25)

Refrigerant R410A

Air Flow Rate** cfm 653-582-512-441 777-688-582-459


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (18.5-16.5-14.5-12.5) (22-19.5-16.5-13)

Motor Nominal Output W 57 57

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25 VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32)

Adaptable Panel Model P-AP90DNA

Color Neutral White

Height in. (mm) 1-3/16 (30)

Outer Dimensions Width in. (mm) 43-5/16 (1,100)

Depth in. (mm) 27-15/16 (709)

Net Weight in. (mm) 16.5 (7.5)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
4.9 ft. (1.5m) beneath the units.
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS The above data was measured in an anechoic chamber so that
reflected sound should be taken into consideration in the field.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Piping Length: 24.6 ft. (7.5m)
Piping Lift: 0ft. (0m)

14 Hitachi Mini VRF Systems


INDOOR
UNITS

MINI-CASSETTE Mini-cassette indoor units are designed to meet a variety of building
requirements in energy efficient, quiet packages. Compact size
enables installation in tight spaces.

Key Features
• H
 igh-performance and high- • Optional energy-saving
efficiency heat exchanger motion and radiant heat
• Efficient turbo fan for low- sensor for optimized airflow
noise performance and temperature control in
• Wide range of air flow settings response to room occupancy.
Capacities 8,000 to 18,000 Btu/hr
• Motorized 2-, 3- or 4-channel
air flow louvers with louver kit

Tonnage 0.7 1.0 1.3 1.5


Mini-Cassette Indoor Unit Model HICM008B21S HICM012B21S HICM015B21S HICM018B21S
Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity* Btu / h (kW) 8,000 (2.3) 12,000 (3.5) 15,000 (4.4) 18,000 (5.3)

Nominal Heating Capacity* Btu / h (kW) 9,000 (2.6) 13,500 (4.0) 17,000 (5.0) 20,000 (5.9)

Sound Pressure Level **


dB 38-34-30-24.5 41-37-33-27.5 45-39-35-31 47-43-39-35
(Overall A Scale)

Height in. (mm) 11-1/4 (285) 11-1/4 (285) 11-1/4 (285) 11-1/4 (285)
Outer
Width in. (mm) 22-7/16 (570) 22-7/16 (570) 22-7/16 (570) 22-7/16 (570)
Dimensions
Depth in. (mm) 22-7/16 (570) 22-7/16 (570) 22-7/16 (570) 22-7/16 (570)

Net Weight lbs. (kg) 35 (16) 35 (16) 37 (17) 37 (17)

Refrigerant – R410A

Air Flow Rate cfm 424-353-300-212 459-388-335-247 530-424-353-282 565-494-424-353


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (12-10-8.5-6) (13-11-9.5-7) (15-12-10-8) (16-14-12-10)

Motor Nominal Output W 57 57 57 57

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

Adaptable Panel Model P-AP56NAM

Color Neutral White

Height in. (mm) 1-3/16 (30)


Outer Width in. (mm) 24-13/32 (620)
Dimensions
Depth in. (mm) 24-13/32 (620)

Net Weight lbs. (kg) 6 (3)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
4.9 ft. (1.5m) beneath the units.
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS The above data was measured in an anechoic chamber so that reflected
Indoor Units

Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) sound should be taken into consideration in the field.
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Piping Length: 24.6 ft. (7.5m)
Piping Lift: 0ft. (0m)

Hitachi Mini VRF Systems 15


INDOOR
UNITS

4-WAY CASSETTE Ceiling-mounted, 4-way cassettes measuring 33 x 33 inch
(84 x 84 cm) are offered with standard decorative panels.
Compact, thin, and lightweight, they are easy to install
even in tight spaces.

Capacities: 8,000 to 48,000 Btu/hr

Tonnage 0.7 1.0 1.3 1.5

4-Way Cassette Indoor Unit Model HIC4008B21S HIC4012B21S HIC4015B21S HIC4018B21S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 8,000 12,000 15,000 18,000


Nominal Cooling Capacity *
(kW) (2.3) (3.5) (4.4) (5.3)

Btu/h 9,000 13,500 17,000 20,000


Nominal Heating Capacity *
(kW) (2.6) (4.0) (5.0) (5.8)

Sound Pressure Level**


dB 33-30-28-27 35-31-30-27 37-32-30-27 42-36-32-28
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 9-3/4 (248) 9-3/4 (248) 9-3/4 (248) 9-3/4 (248)

Outer Dimensions Width in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)

Depth in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)

Net Weight lbs. (kg) 44 (20) 46 (21) 46 (21) 48 (22)

Refrigerant R410A

Air Flow Rate cfm 530-459-388-318 741-600-494-388 777-600-494-388 953-777-635-494


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (15-13-11-9) (21-17-14-11) (22-17-14-11) (27-22-18-14)

Motor Nominal Output W 57 57 57 57

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)

Condensate Drain VP25 VP25 VP25 VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
4.9 ft. (1.5m) beneath the units.
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS The above data was measured in an anechoic chamber so that reflected
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) sound should be taken into consideration in the field.
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)

 iping Length: 24.6 ft. (7.5m)


P
Piping Lift: 0ft. (0m)

16 Hitachi Mini VRF Systems


INDOOR
UNITS

4-WAY CASSETTE Key Features

(CONTINUED) • Optional energy-saving motion


and radiant heat sensor for
• 4-way airflow standard but can
be configured for 2-way or 3-way
optimized airflow and temperature • Integrated condensate pumps
control in response to room included in all units
occupancy • Uniform panel sizing
• Multiple fan speed settings • Motorized 2-, 3- or 4-channel air
• Air filter (polypropylene) included flow louvers with louver kit
• Optional fresh air kit available
• Four air volume settings including
Ultra Hi for higher ceilings
Tonnage 2.0 2.5 3.0 4.0

4-Way Cassette Indoor Unit Model HIC4024B21S HIC4030B21S HIC4036B21S HIC4048B21S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 24,000 30,000 36,000 48,000


Nominal Cooling Capacity *
(kW) (7.0) (8.8) (10.5) (14.1)

Btu/h 27,000 34,000 40,000 54,000


Nominal Heating Capacity *
(kW) (7.9) (10.0) (11.7) (15.8)

Sound Pressure Level **


dB 42-36-32-28 48-43-39-33 48-45-40-35 48-46-41-37
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 11-3/4 (298) 11-3/4 (298) 11-3/4 (298) 11-3/4 (298)

Outer Dimensions Width in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)

Depth in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)

Net Weight lbs. (kg) 57 (26) 57 (26) 57 (26) 57 (26)

Refrigerant 33-1/16

Air Flow Rate cfm 953-812-635-494 1306-1094-847-706 1306-1165-918-741 1306-1236-989-777


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (27-23-18-14) (37-31-24-20) (37-33-26-21) (37-35-28-22)

Motor Nominal Output W 57 127 127 127

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25 VP25 VP25 VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

P-AP160NA2 P-AP160NAE1
Adaptable Panel Model (applies to all models)
(without Motion and Radiant Heat Sensors) (with Motion and Radiant Heat Sensors)

Color Neutral White

Outer Dimensions Height in. (mm) 1-9/16 (40) 1-9/16 (40)

Width in. (mm) 37-3/8 (950) 37-3/8 (950)

Depth in. (mm) 37-3/8 (950) 37-3/8 (950)

Net Weight lbs(kg) 14 (6.5) 14 (6.5)


Indoor Units

See notes on page 16 for cooling operation and heating operation conditions.

Hitachi Mini VRF Systems 17


18 Hitachi Mini VRF Systems
INDOOR
UNITS

CEILING-SUSPENDED Ceiling-suspended indoor units have a stylized design and
color that make them among the most elegant units on the
market. Units are equipped with an automatic swing louver
to ensure even air distribution.

Key Features
• Optional energy-saving • New fan design for high
motion and radiant heat efficiency and low noise
sensor for optimized • Flexible installation for
airflow and temperature high ceilings
control in response to
Capacities 15,000 to 36,000 Btu/hr room occupancy

Tonnage 1.3 2.0 2.5 3.0

Ceiling Suspended Indoor Unit Model HICS015B21S HICS024B21S HICS030B21S HICS036B21S


Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity * Btu / h (kW) 15,000 (4.4) 24,000 (7.0) 30,000 (8.8) 36,000 (10.5)

Nominal Heating Capacity * Btu / h (kW) 17,000 (5.0) 27,000 (7.9) 34,000 (10.0) 40,000 (11.7)

Sound Pressure Level**


dB 38-35-31-28 43-40-36-31 44-42-37-32 48-45-41-35
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 9-1/4 (235) 9-1/4 (235) 9-1/4 (235) 9-1/4 (235)
Outer
Width in. (mm) 37-13/16 (960) 50 (1270) 62-3/16 (1580) 62-3/16 (1580)
Dimensions
Depth in. (mm) 27-3/16 (690) 27-3/16 (690) 27-3/16 (690) 27-3/16 (690)

Net Weight lbs. (kg) 59 (27) 77 (35) 90 (41) 90 (41)

Refrigerant R410A

Air Flow Rate cfm 530-459-388-318 847-741-635-512 1059-935-777-600 1236-1094-900-706


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (15-13-11-9) (24-21-18-14.5) (30-26.5-22-17) (35-31-25.5-20)

Motor Nominal Output W 50 80 160 160

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information.

COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS


Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)  iping Length: 24.6 ft. (7.5m)
P
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB) Piping Lift: 0ft. (0m)

** The sound pressure level is based on the following conditions:


4.9 ft. (1.5m) beneath the units.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
Indoor Units

Hitachi Mini VRF Systems 19


INDOOR
UNITS

WALL-MOUNT Wall-mount indoor units include wide-angle louvers that
distribute airflow comfortably. An auto-swing function
ensures efficient air distribution and uniform temperature
throughout the conditioned space. Drain piping can be
connected at the right, left or rear of the unit for ease of
installation.

Key Features
• Removable front panel for easy cleaning
• Built-in wireless sensor for use with optional wireless
Capacities: 6,000 to 30,000 Btu/hr zone controller
• Optional condensate pump

Tonnage 0.5 0.7 1.0

Wall-Mount Indoor Unit Model TIWM006B21S TIWM008B21S TIWM012B21S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 6,000 8,000 12,000


Nominal Cooling Capacity *
(kW) (1.8) (2.3) (3.5)

Btu/h 6,700 9,000 13,500


Nominal Heating Capacity *
(kW) (2.0) (2.6) (4.0)

Sound Pressure Level **


dB 39-35-32-30 39-35-32-30 46-40-36-33
(Overall A Scale) (Hi2-Hi-Me-Lo)
Height in. (mm) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300)

Outer Dimensions Width in. (mm) 31-1/8 (790) 31-1/8 (790) 35-7/16 (900)

Depth in. (mm) 9-1/16 (230) 9-1/16 (230) 9-1/16 (230)

Net Weight lbs.(kg) 22 (10) 22 (10) 24 (11)

Refrigerant R410A

Air Flow Rate cfm 353-282-247-229 353-282-247-229 494-388-318-265


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (10-8-7-6.5) (10-8-7-6.5) (14-11-9-7.5)

Motor Nominal Output W 38 38 38

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)

Condensate Drain VP16

OD in. (mm) 7/8 (22) 7/8 (22) 7/8 (22)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 3.3ft (1m) Front of the Unit and 3.3ft (1m) Below the Unit..
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that reflected
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)

Piping Length: 24.6 ft. (7.5m) Piping Lift: 0ft. (0m)

20 Hitachi Mini VRF Systems


INDOOR
UNITS

WALL-MOUNT
(CONTINUED)

Tonnage 1.3 1.5 2.0 2.5

Wall-Mount Indoor Unit Model TIWM015B21S TIWM018B21S TIWM024B21S TIWM030B21S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 15,000 18,000 24,000 30,000


Nominal Cooling Capacity *
(kW) (4.4) (5.3) (7.0) (8.8)

Btu/h 17,000 20,000 27,000 34,000


Nominal Heating Capacity *
(kW) (5.0) (5.8) (7.9) (10.0)

Sound Pressure Level **


dB 42-40-38-33 49-43-40-36 51-49-46-41 51-49-46-41
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 13-1/8 (333) 13-1/8 (333) 13-1/8 (333) 13-1/8 (333)

Outer Dimensions Width in. (mm) 45-1/4 (1150) 45-1/4 (1150) 45-1/4 (1150) 45-1/4 (1150)

Depth in. (mm) 9-5/8 (245) 9-5/8 (245) 9-5/8 (245) 9-5/8 (245)

Net Weight lbs.(kg) 35 (16) 37 (17) 37 (17) 37 (17)

Refrigerant R410A

Air Flow Rate cfm 530-494-459-353 671-600-494-424 777-671-600-530 777-671-600-530


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (15-14-13-10) (19-17-14-12) (22-19-17-15) (22-19-17-15)

Motor Nominal Output W 38 38 38 38

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP16

OD in. (mm) 7/8 (22) 7/8 (22) 7/8 (22) 7/8 (22)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 3.3ft (1m) Front of the Unit and 3.3ft (1m) Below the Unit..
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that reflected
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Indoor Units


Piping Length: 24.6 ft. (7.5m) Piping Lift: 0ft. (0m)

Hitachi Mini VRF Systems 21


INDOOR
UNITS

FLOOR-CONCEALED Floor-concealed indoor units are ideal for areas where space is at
a premium, such as hallways. These inconspicuous units provide
comfort without sacrificing space.

Key Features
• Compact design for limited spaces
• Provides compatibility with interior designs
• Ideal for perimeter zone air conditioning

Capacities 6,000 to 15,000 Btu/hr

Tonnage 0.5 0.7 1.0 1.3

Floor-Concealed Indoor Unit Model HIFC006B21S HIFC008B21S HIFC012B21S HIFC015B21S

Indoor Unit Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity * Btu / h (kW) 6,000 (1.8) 8,000 (2.3) 12,000 (3.5) 15,000 (4.4)

Nominal Heating Capacity * Btu / h (kW) 6,700 (2.0) 9,000 (2.6) 13,500 (4.0) 17,000 (5.0)

Sound Pressure Level **


dB 39-33-29 39-33-29 43-35-32 48-43-36
(Overall A Scale) (Hi-Me-Lo)

Height in. (mm) 24-7/16 (620) 24-7/16 (620) 24-7/16 (620) 24-7/16 (620)
Outer
Width in. (mm) 33-3/8 (848) 33-3/8 (848) 38-5/16 (973) 48-1/8 (1223)
Dimensions
Depth in. (mm) 8-11/16 (220) 8-11/16 (220) 8-11/16 (220) 8-11/16 (220)

Net Weight lbs. (kg) 52 (24) 52 (24) 57 (26) 68 (31)

Refrigerant R410A

Air Flow Rate cfm 300-247-212 300-247-212 424-353-318 565-494-388


Indoor Fan
(Hi-Me-Lo) (m3 /min) (8.5-7-6) (8.5-7-6) (12-10-9) (16-14-11)

Motor Nominal Output W 20 20 28 45

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 3.3 ft. (1m) Front of the Unit and 3.3 ft. (1m) above the floor level.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) reflected sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)

Piping Length: 24.6 ft. (7.5m)
Piping Lift: 0ft. (0m)

22 Hitachi Mini VRF Systems


INDOOR
UNITS

FLOOR-EXPOSED Floor-exposed indoor units have a slim-line design compatible
with the style of the room.

Key Features
• 8.7-inch (220 mm) depth preserves room space
• 24.8-inch height leaves ample window space
• Ideal for perimeter zone air conditioning

Capacities 6,000 to 15,000 Btu/hr

Tonnage 0.5 0.7 1.0 1.3

Floor-Exposed Indoor Unit Model HIFE006B21S HIFE008B21S HIFE012B21S HIFE015B21S

Indoor Unit Power Supply AC 1 Phase, 208/230V, 60Hz

Nominal Cooling Capacity * Btu / h (kW) 6,000 (1.8) 8,000 (2.3) 12,000 (3.5) 15,000 (4.4)

Nominal Heating Capacity * Btu / h (kW) 6,700 (2.0) 9,000 (2.6) 13,500 (4.0) 17,000 (5.0)

Sound Pressure Level **


dB 39-33-29 39-33-29 43-35-32 48-43-36
(Overall A Scale) (Hi-Me-Lo)

Height in. (mm) 24-13/16 (630) 24-13/16 (630) 24-13/16 (630) 24-13/16 (630)
Outer
Width in. (mm) 41-1/8 (1045) 41-1/8 (1045) 46-1/16 (1170) 55-7/8 (1420)
Dimensions
Depth in. (mm) 8-11/16 (220) 8-11/16 (220) 8-11/16 (220) 8-11/16 (220)

Net Weight lbs. (kg) 61 (28) 61 (28) 68 (31) 79 (36)

Refrigerant R410A

Air Flow Rate cfm 300-247-212 300-247-212 424-353-318 565-494-388


Indoor Fan
(Hi-Me-Lo) (m3 /min) (8.5-7-6) (8.5-7-6) (12-10-9) (16-14-11)

Motor Nominal Output W 20 20 28 45

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

NOTES:
* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 3.3 ft. (1m) Front of the Unit and 3.3 ft. (1m) above the floor level.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) reflected sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)

Piping Length: 24.6 ft. (7.5m)
Piping Lift: 0ft. (0m)
Indoor Units

Hitachi Mini VRF Systems 23


INDOOR
UNITS

DUCTED HIGH STATIC

Key Features
• High-efficiency AC fan motor
• Multiple fan speed settings
• Up to .74 in. W.G. static pressure
• Bottom access for easy service and troubleshooting
• Built-in condensate pump
Capacities: 15,000 to 54,000 Btu/hr

Tonnage 1.3 1.5 2.0 2.3

Ducted High Static Indoor Unit Model HIDH015B22S HIDH018B22S HIDH024B22S HIDH027B22S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 15,000 18,000 24,000 27,000


Nominal Cooling Capacity *
(kW) (4.4) (5.3) (7.0) (8.0)

Btu/h 17,000 20,000 27,000 30,000


Nominal Heating Capacity *
(kW) (5.0) (5.9) (7.9) (8.8)

Sound Pressure Level**


dB 41-38-35-32 37-35-32-30 40-37-34-32 40-37-34-32
(Overall A Scale) (208/230V) (Hi-Lo)

Height in. (mm) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300)

Outer Dimensions Width in. (mm) 27-9/16 (700) 41-5/16 (1050) 41-5/16 (1050) 41-5/16 (1050)

Depth in. (mm) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800)

Net Weight lbs.(kg) 64 (29) 84 (38) 84 (38) 84 (38)

Refrigerant R410A

Air Flow Rate** cfm 512-459-388-335 653-582-512-424 759-671-582-494 759-671-582-494


Indoor Fan
(Hi-Lo) (m3/min) (14.5-13-11-9.5) (18.5-16.5-14.5-12) (21.5-19-16.5-14) (21.5-19-16.5-14)

External Pressure High Pressure in. W.G. (Pa) 0.2 (0.4-0.8) 0.2 (0.4-0.8) 0.2 (0.4-0.8) 0.2 (0.4-0.8)
(208/230V)*** Standard in. W.G. (Pa) (50 (100-200)) (50 (100-200)) (50 (100-200)) (50 (100-200))

Motor Nominal Output W 157 190 190 190

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.7) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 4.9 ft. (1.5m) beneath the units.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that reflected
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
 *** The data for external pressure indicates Standard Pressure Setting (High
Piping Length: 24.6 ft. . (7.5 m) Pressure Setting 1 - High Pressure Setting 2) values when a filter is not used.
Piping Lift: 0 ft. (0 m) The sound pressure level is based on the Standard Pressure Setting.

24 Hitachi Mini VRF Systems


INDOOR
UNITS

DUCTED HIGH STATIC
(CONTINUED)

Tonnage 2.5 3.0 4.0 4.5

Ducted High Static Indoor Unit Model HIDH030B22S HIDH036B22S HIDH048B22S HIDH054B22S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 30,000 36,000 48,000 54,000


Nominal Cooling Capacity *
(kW) (8.8) (10.6) (14.1) (15.8)

Btu/h 34,000 40,000 54,000 60,000


Nominal Heating Capacity *
(kW) (10.0) (11.8) (15.8) (17.6)

Sound Pressure Level**


dB 40-37-34-32 42-39-36-33 44-40-37-34 44-40-37-34
(Overall A Scale) (208/230V) (Hi-Lo)

Height in. (mm) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300) 11-13/16 (300)

Outer Dimensions Width in. (mm) 55-1/8 (1400) 55-1/8 (1400) 55-1/8 (1400) 55-1/8 (1400)

Depth in. (mm) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800)

Net Weight lbs.(kg) 106 (48) 106 (48) 106 (48) 106 (48)

Refrigerant R410A

Air Flow Rate** cfm 1059-935-812-706 1183-1041-918-777 1271-1112-971-847 1271-1112-971-847


Indoor Fan
3
(Hi-Lo) (m /min) (30-26.5-23-20) (33.5-29.5-26-22) (36-31.5-27.5-24) (36-31.5-27.5-24)

External Pressure High Pressure in. W.G. (Pa) 0.2 (0.4-0.8) 0.2 (0.4-0.8) 0.2 (0.4-0.8) 0.2 (0.4-0.8)
(208/230V)*** Standard in. W.G. (Pa) (50 (100-200)) (50 (100-200)) (50 (100-200)) (50 (100-200))

Motor Nominal Output W 259 259 259 259

Connections

Refrigerant Piping

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 4.9 ft. (1.5m) beneath the units.
Indoor Units

Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that reflected
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
 *** The data for external pressure indicates Standard Pressure Setting (High
Piping Length: 24.6 ft. . (7.5 m) Pressure Setting 1 - High Pressure Setting 2) values when a filter is not used.
Piping Lift: 0 ft. (0 m) The sound pressure level is based on the Standard Pressure Setting.

Hitachi Mini VRF Systems 25


INDOOR
UNITS

DUCTED MEDIUM STATIC

Key Features
• High-efficiency AC fan motor
• Multiple fan speed settings
• Up to .74 in. W.G. static pressure
• Bottom access for easy service and troubleshooting
• Built-in condensate pump
Capacities: 6,000 to 54,000 Btu/hr

Tonnage 0.5 0.7 1.0 1.3 1.5

Ducted Medium Static Indoor Unit Model HIDM006B22S HIDM008B22S HIDM012B22S HIDM015B22S HIDM018B22S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 6,000 8,000 12,000 15,000 18,000


Nominal Cooling Capacity *
(kW) (1.8) (2.4) (3.6) (4.4) (5.3)

Btu/h 6,700 9,000 13,500 17,000 20,000


Nominal Heating Capacity *
(kW) (2.0) (2.7) (4.0) (5.0) (5.9)

Sound Pressure Level **


dB 32-30-28-27 33-31-29-28 38-35-32-30 40-37-34-31 37-35-33-31
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250)

Outer Dimensions Width in. (mm) 27-9/16 (700) 27-9/16 (700) 27-9/16 (700) 27-9/16 (700) 41-5/16 (1050)

Depth in. (mm) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800)

Net Weight lbs.(kg) 57 (26) 57 (26) 60 (27) 60 (27) 79 (36)

Refrigerant R410A

Air Flow Rate** cfm 300-265-229-194 335-300-265-229 459-406-353-300 512-459-388-335 653-582-494-424


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (8.5-7.5-6.5-5.5) (9.5-8.5-7.5-6.5) (13-11.5-10-8.5) (14.5-13-11-9.5) (18.5-16.5-14-12)

External Pressure*** in. W.G. 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6)
Std (Hi-Lo) (Pa) (50 (100-150)) (50 (100-150)) (50 (100-150)) (50 (100-150)) (50 (100-150))

Motor Nominal Output W 157 157 157 157 190

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 4.9 ft. (1.5m) beneath the units.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) reflected sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
*** The data for external pressure indicates Standard Pressure Setting
P
 iping Length: 24.6 ft. . (7.5 m) (High Pressure Setting 1 - High Pressure Setting 2) values when
Piping Lift: 0 ft. (0 m) a filter is not used. The sound pressure level is based on the
Standard Pressure Setting.

26 Hitachi Mini VRF Systems


INDOOR
UNITS

DUCTED MEDIUM
STATIC
(CONTINUED)

Tonnage 2.0 2.3 2.5 3.0 4.0 4.5

Ducted Medium Static Indoor Unit Model HIDM024B22S HIDM027B22S HIDM030B22S HIDM036B22S HIDM048B22S HIDM054B22S

Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 24,000 27,000 30,000 36,000 48,000 54,000


Nominal Cooling Capacity *
(kW) (7.0) (8.0) (8.8) (10.5) (14.1) (15.8)

Btu/h 27,000 30,000 34,000 40,000 54,000 60,000


Nominal Heating Capacity *
(kW) (7.9) (8.8) (10.0) (11.8) (15.8) (17.6)

Sound Pressure Level **


dB 39-37-34-32 39-37-34-32 40-38-35-32 42-39-36-34 43-40-37-34 43-40-37-34
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250) 9-13/16 (250)
Outer
Width in. (mm) 41-5/16 (1050) 41-5/16 (1050) 55-1/8 (1400) 55-1/8 (1400) 55-1/8 (1400) 55-1/8 (1400)
Dimensions
Depth in. (mm) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800)

Net Weight lbs.(kg) 79 (36) 79 (36) 97 (44) 97 (44) 97 (44) 97 (44)

Refrigerant R410A

Air Flow Rate** cfm 759-671-582-494 759-671-582-494 1059-935-812-706 1183-1041-918-777 1271-1112-971-847 1271-1112-971-847
Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (21.5-19-16.5-14) (21.5-19-16.5-14) (30-26.5-23-20) (33.5-29.5-26-22) (36-31.5-27.5-24) (36-31.5-27.5-24)

External Pressure*** in. W.G. 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6) 0.2 (0.4-0.6)
Std (Hi-Lo) (Pa) (50 (100-150)) (50 (100-150)) (50 (100-150)) (50 (100-150)) (50 (100-150)) (50 (100-150))

Motor Nominal Output W 190 190 259 259 259 259

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information. ** The sound pressure level is based on the following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS 4.9 ft. (1.5m) beneath the units.
Indoor Units

Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) The above data was measured in an anechoic chamber so that reflected
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
*** The data for external pressure indicates Standard Pressure Setting (High
P
 iping Length: 24.6 ft. . (7.5 m) Pressure Setting 1 - High Pressure Setting 2) values when a filter is not used.
Piping Lift: 0 ft. (0 m) The sound pressure level is based on the Standard Pressure Setting.

Hitachi Mini VRF Systems 27


INDOOR
UNITS

DUCTED SLIM
Key Features
• High-efficiency DC fan motor
• Multiple fan speed settings
• Up to .20 in. W.G. static pressure
• Bottom access for easy service and troubleshooting
• Built-in condensate pump
Capacities: 6,000 to 18,000 Btu/hr

Tonnage 0.5 0.7 1.0 1.3 1.5

Ducted Slim Indoor Unit Model HIDS006B21S HIDS008B21S HIDS012B21S HIDS015B21S HIDS018B21S
Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 6,000 8,000 12,000 15,000 18,000


Nominal Cooling Capacity *
(kW) (1.8) (2.3) (3.5) (4.4) (5.3)

Btu/h 6,700 9,000 13,500 17,000 20,000


Nominal Heating Capacity *
(kW) (2.0) (2.6) (4.0) (5.0) (5.9)

Sound Pressure Level **


dB 32-30-29-27 32-30-29-27 34-33.5-33-32 36-35-33-32 40-38-36-34
(Overall A Scale) (Hi2-Hi-Me-Lo)

Height in. (mm) 7-9/16 (192) 7-9/16 (192) 7-9/16 (192) 7-9/16 (192) 7-9/16 (192)

Outer Dimensions Width in. (mm) 35-3/4 (908) 35-3/4 (908) 35-3/4 (908) 46-3/8 (1178) 46-3/8 (1178)

Depth in. (mm) 17-19/32 (447) 17-19/32 (447) 17-19/32 (447) 17-19/32 (447) 17-19/32 (447)

Net Weight lbs.(kg) 44 (20) 44 (20) 46 (21) 57 (26) 57 (26)

Refrigerant R410A

Air Flow Rate** cfm 318-289-244-205 318-289-244-205 346-318-300-268 512-477-441-381 582-530-494-424


Indoor Fan
(Hi2-Hi-Me-Lo) (m3/min) (9-8-7-6) (9-8-7-6) (10-9-9-8) (15-14-13-11) (17-15-14-12)

External Pressure *** in. W.G. 0.04 (0.12-0.00) 0.04 (0.12-0.00) 0.04 (0.12-0.00) 0.04 (0.20-0.00) 0.04 (0.20-0.00)
Std (Hi-Lo) (Pa) (10 (30-0)) (10 (30-0)) (10 (30-0)) (10 (50-0)) (10 (50-0))

Motor Nominal Output W 40 40 40 60 60

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52)

Gas Line in. (mm) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)

Condensate Drain VP25 VP25 VP25 VP25 VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

NOTES:

* Nominal capacity condition is based on the following conditions. See www.ahrinet.org for more information.
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS ** The sound pressure level is based on the following conditions:
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) \4.9 ft. (1.5m) beneath the units.
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) The above data was measured in an anechoic chamber so that
reflected sound should be taken into consideration in the field.
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB)
Piping Length: 24.6 ft. . (7.5 m)
Piping Lift: 0ft. (0m) *** The data for external pressure indicates Standard Pressure Setting
(High Pressure Setting 1 - High Pressure Setting 2) values when a
filter is not used. The sound pressure level is based on the Standard
Pressure Setting.

28 Hitachi Mini VRF Systems


INDOOR
UNITS

ECONOFRESH The exclusive EconoFresh unit is a combination of a Ducted Medium Static
Unit paired with an Economizer Kit which contributes to energy savings to
ECONOMIZER provide outside air/free-cooling, up to 100%, when outside conditions are
favorable. Seamlessly integrating with the VRF system, the unit enhances
energy savings and improves air quality.

Key Features
• Excellent for applications with cooling demand during mid seasons
and winter
• Inputs for optional CO2 and enthalpy sensors are available for control
based on indoor air quality or humidity
The EconoFresh unit includes the Economizer Kit
and a Ducted Medium Static Unit in your choice of • A remote control switch allows control of the outside air damper
three capacities: 30,000, 36,000 or 48,000 Btu/hr. opening to ensure minimum outside airflow requirements are met

Tonnage 2.5 3.0 4.0

EconoFresh (Economizer Kit + a ducted


HIDM030B21E HIDM036B21E HIDM048B21E
medium static indoor unit) - Model
NOTES:
Power Supply AC 1 Phase, 208/230V, 60Hz * Nominal capacity condition is based on the following
conditions. See www.ahrinet.org for more information.
Btu/h 30,000 36,000 48,000
Nominal Cooling Capacity * COOLING OPERATION CONDITIONS
(kW) (8.8) (10.5) (14.1)
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB)
67°F WB (19.4°C WB)
Btu/h 34,000 40,000 54,000

Nominal Heating Capacity *
(kW) (10.0) (11.7) (15.8) Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)

Sound Pressure Level ** HEATING OPERATION CONDITIONS
dB 38-35-32 39-35-33 40-36-33
(Overall A Scale) (Hi-Me-Lo) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Height in. (mm) 10-7/8 (275) 10-7/8 (275) 10-7/8 (275) 43°F WB (6.1°C WB)

Outer Dimensions Width in. (mm) 58-1/16 (1474) 58-1/16 (1474) 58-1/16 (1474)
 Piping Length: 24.6 ft. (7.5m)
Depth in. (mm) 23-5/8 (600) 23-5/8 (600) 23-5/8 (600) Piping Lift: 0 ft. (0m)

Net Weight lbs.(kg) 106 (48) 106 (48) 106 (48)


** The sound pressure level is based on the following
Refrigerant R410A conditions:
4.9 ft. (1.5m) beneath the unit, connection with the
Air Flow
cfm 1059-953-847 1236-1094-988 1271-1130-1024 EconoFresh Kit, EconoFresh Pressure Mode Setting,
Indoor Fan Rate** damper opening is OA 50% and RA 50%, at rated airflow
volume and filter is not used. The above data was
(Hi-Me-Lo) (m3/min) (30-27-24) (35-31-28) (36-32-29)
measured in an anechoic chamber so that reflected sound
should be taken into consideration in the field.
External Pressure*** in. W.G. 0.17-0.12-0.10 0.16-0.11-0.10 0.12-0.10-0.08
Std (Hi-Me-Lo) (Pa) (43-30-25) (40-28-25) (30-25-20) *** The data for external pressure is based on a connection
with the pressure drop (damper opening at OA 100%),
Motor Nominal Output W 250 250 250 EconoFresh Pressure Mode Setting and filter is not used.

Connections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

Condensate Drain VP25 VP25 VP25

OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)

Adaptable EconoFresh Kit Model EF-456NE

Height in. (mm) 10 (254)

Width in. (mm) 55-1/2 (1410)


Indoor Units

Depth in. (mm) 12-3/16 (270)

Net Weight lbs. (kg) 28 (12.5)

Hitachi Mini VRF Systems 29


30 Hitachi Mini VRF Systems
INDOOR
UNITS

MULTI-POSITION AIR Key Features

HANDLER WITH DX-KIT • RC2 - Rigid Case


Construction interior
• Thermoset Drain Pan -
Positive slope for drainage
endoskeleton for structural to reduce potential for mold
support, flush side, and or contaminants.
locked-in insulation. • Factory Sealed - Achieves
• Powder-painted - G30 2% or less total airflow
galvanized steel case leakage rate at duct leakage
provides a coated edge that test conditions in positive
resists corrosion and rust and negative pressure for
creep. system airflow verification.
• MaxAlloy™ Coil - Long-life • Enhanced Filter Rack - All
aluminum coils built to models have integrated
deliver lasting performance, internal filter racks provided
efficiency, and reliability. for use with 1” thick,
• Quality Construction - standard-size filters.
Structural components are • Electric Heat Kits - Field-
made of Aluminum or G90 installed electric heat kits
galvanized steel to prevent are available for installation-
corrosion. friendly and easy service
• Improved Insulation applications.
Design - Single piece with • Blowers - All models use
no external screws to reduce direct-drive, multi-speed
thermal transmission paths motors.
to prevent sweating. Foil-
faced insulation for ease of
cleaning.
• Case Depth - These models
have a 20.5” casing which
Multi-Position Air Handler provides easy access in
Capacities: 18,000 to 60,000 Btu/hr
attics and tight applications.
Fully field installed integrated DX kit.

Indoor Units

Hitachi Mini VRF Systems 31


INDOOR
UNITS

MULTI-POSITION AIR
HANDLER WITH DX-KIT
Tonnage 1.5 2.0 2.5 3.0

Multi-Position Air Handler with DX-Kit HMAHP18B21S HMAHP24B21S HMAHP30B21S HMAHP36B21S HMAHP36C21S

Adaptable Air Handler Model AP18BX21 AP24BX21 AP30BX21 AP36BX21 AP36CX21

Indoor Unit Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 18,000 24,000 30,000 36,000 36,000


Nominal Cooling Capacity*
(kW) (5.3) (7.0) (8.8) (10.5) (10.5)

Btu/h 20,000 27,000 34,000 40,000 40,000


Nominal Heating Capacity*
(kW) (5.9) (7.9) (10.0) (11.7) (11.7)

Sound Pressure Level ***


Not Currently Available
(Overall A Scale)

Height in. (mm) 41 (1041) 41 (1041) 47-1/2 (1207) 47-1/2 (1207) 51-1/2 (1308)

Outer Dimensions Width in. (mm) 17-1/2 (445) 17-1/2 (445) 17-1/2 (445) 17-1/2 (445) 21 (533)

Depth in. (mm) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545)

Net Weight lbs (kg) 85 (39) 87 (40) 113 (51) 113 (51) 114 (52)

Refrigerant R410A

Air Flow Rate*2 cfm 576-382 / 687-500 713-457 / 778-605 843-677 / 917-769 1108-968 / 1178-1057 1110-877 / 1186-974
Indoor Fan (208/230V)
3
(Hi-Lo) (m /min) (16-11) / (19-14) (20-13) / (22-17) (24-19) / (26-22) (31-27) / (33-30) (31-25) / (34-28)

in. W.G. 0.4 0.7 0.7 0.7 0.7


External Pressure ***
(Pa) (99) (174) (174) (174) (174)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Refrigerant Piping
3
Gas Line * in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

OD in. (mm) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7)
Condensate Drain
ID in. (mm) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9)

Adaptable DX-Kit Model EXV-018E EXV-024E EXV-030E EXV-036E

Control Box Part

Power Supply AC 1 Phase, 208/230V, 60Hz

Height in. (mm) 3-3/16 (81.0) 3-3/16 (81.0) 3-3/16 (81.0) 3-3/16 (81.0)

Outer Dimensions Width in. (mm) 12-5/8 (320) 12-5/8 (320) 12-5/8 (320) 12-5/8 (320)

Depth in. (mm) 7-3/8 (187) 7-3/8 (187) 7-3/8 (187) 7-3/8 (187)

Net Weight lbs. (kg) 6.57 (2.98) 6.57 (2.98) 6.57 (2.98) 6.57 (2.98)

Expansion Valve Box Part

Power Supply DC 12V

Height in. (mm) 4-5/16 (109) 4-5/16 (109) 4-5/16 (109) 4-5/16 (109)

Outer Dimensions Width in. (mm) 17-1/16 (433) 17-1/16 (433) 17-1/16 (433) 17-1/16 (433)

Depth in. (mm) 5-5/16 (151) 5-5/16 (151) 5-5/16 (151) 5-5/16 (151)

Net Weight lbs. (kg) 8.84 (4.01) 8.84 (4.01) 8.84 (4.01) 8.84 (4.01)

Refrigerant R410A

Liquid Line In in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Refrigerant Piping
Liquid Line Out in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

NOTES:
* . Nominal capacity is based on combination with VRF system and following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS ** Sound pressure leavel is currently not available.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) *** Hi and Lo setting on the wired controller. (Hi = Air Handler's High tap and
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) Lo = Air Handler's Medium tap). Make sure both the external pressure and
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB) air flow rate match the specification.
 **** Gas connection piping diameter of the air handler is changed by using the
Piping Length: 24.6ft (7.5m) Piping Lift: 0ft. (0m) reducer (accessory of DX-Kit) to connect to VRF system.

32 Hitachi Mini VRF Systems


INDOOR
UNITS

MULTI-POSITION AIR
HANDLER WITH DX-KIT (CONTINUED)
Tonnage 4 5

Multi-Position Air Handler with DX-Kit HMAHP48C21S HMAHP48D21S HMAHP60C21S HMAHP60D21S HMAHP60D22S

Adaptable Air Handler Model AP48CX21 AP48DX21 AP60CX21 AP60DX21 AP60DX22

Indoor Unit Power Supply AC 1 Phase, 208/230V, 60Hz

Btu/h 48,000 48,000 60,000 60,000 60,000


Nominal Cooling
Capacity* (kW) (14.1) (14.1) (17.6) (17.6) (17.6)

Btu/h 54,000 54,000 64,000 64,000 64,000


Nominal Heating
Capacity* (kW) (15.8) (15.8) (18.8) (18.8) (18.8)

Sound Pressure Level


Not Currently Available
(Overall A Scale)

Height in. (mm) 51-1/2 (1308) 55-1/2 (1410) 55-3/4 (1416) 55-1/2 (1410) 55-1/2 (1410)

Outer Dimensions Width in. (mm) 21 (533) 24-1/2 (622) 21 (533) 24-1/2 (622) 24-1/2 (622)

Depth in. (mm) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545) 27-7/16 (545)

Net Weight lbs (kg) 150 (68) 153 (69) 146 (66) 170 (77) 170 (77)

Refrigerant R410A

Air Flow Rate*2 cfm 1062-971 / 1190-1059 1391-1139 / 1481-1258 1680-1562 / 1739-1659 1701-1590 / 1779-1694 1757-1639 / 1829-1735
Indoor Fan
(Hi-Lo) (m3/min) (30-28) / (34-30) (39-32) / (42-36) (48-44) / (49-47) (48-45) / (50-48) (50-46) / (52-49)

External Pressure in. W.G. 0.7 0.7 0.4 0.4 0.4


*** (Pa) (174) (174) (99) (99) (99)

Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Refrigerant Piping
Gas Line *3 in. (mm) 5/8 (15.88) 5/8 (15.88) 3/4 (19.05) 3/4 (19.05) 3/4 (19.05)

OD in. (mm) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7) 1-1/16 (26.7)
Condensate Drain
ID in. (mm) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9) 13/16 (20.9)

Adaptable DX-Kit Model EXV-048E EXV-060E

Control Box Part

Power Supply AC 1 Phase, 208/230V, 60Hz

Height in. (mm) 3-3/16 (81.0) 3-3/16 (81.0)

Outer Dimensions Width in. (mm) 12-5/8 (320) 12-5/8 (320)

Depth in. (mm) 7-3/8 (187) 7-3/8 (187)

Net Weight lbs. (kg) 6.57 (2.98) 6.57 (2.98)

Expansion Valve Box Part

Power Supply DC 12V

Height in. (mm) 4-5/16 (109) 4-5/16 (109)

Outer Dimensions Width in. (mm) 17-1/16 (433) 17-1/16 (433)

Depth in. (mm) 5-5/16 (151) 5-5/16 (151)

Net Weight lbs. (kg) 8.84 (4.01) 11.05 (5.01)

Refrigerant R410A

Liquid Line In in. (mm) 3/8 (9.52) 3/8 (9.52)


Refrigerant Piping
Indoor Units

Liquid Line Out in. (mm) 3/8 (9.52) 3/8 (9.52)

NOTES:
* . Nominal capacity is based on combination with VRF system and following conditions:
COOLING OPERATION CONDITIONS HEATING OPERATION CONDITIONS ** Sound pressure leavel is currently not available.
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) *** Hi and Lo setting on the wired controller. (Hi = Air Handler's High tap and
67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB) Lo = Air Handler's Medium tap). Make sure both the external pressure and
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB) air flow rate match the specification.
 **** Gas connection piping diameter of the air handler is changed by using the
Piping Length: 24.6ft (7.5m) Piping Lift: 0ft. (0m) reducer (accessory of DX-Kit) to connect to VRF system.

Hitachi Mini VRF Systems 33


OUTDOOR
UNITS

MINI VRF
OUTDOOR UNITS
SINGLE-PHASE 208/230V (HEAT PUMP)

Reliable, quiet Hitachi Mini VRF Outdoor Units are


available in capacities to fit multiple applications
and operate multiple indoor units. Heat pump units
provide flexibility of design for a variety of building
spaces and ambient conditions. Units operate quietly
with sound ratings as low as 51 dBA.

34 Hitachi Mini VRF Systems


OUTDOOR
UNITS

MINI VRF
OUTDOOR UNITS
Exceptionally efficient Hitachi Mini VRF systems provide design
versatility and flexibility and quiet personalized comfort. Single-
phase (208-230V) 3-, 4- and 5-ton heat pump systems with inverter
compressor technology provide cooling up to 118°F and heating
down to -4°F ambient. Multiple indoor unit options enable
individual comfort control of up to eight rooms/zones.

Mini VRF 208/230V HP Heat Pump Units 3 Ton 4 Ton 5 Ton

Mini VRF Outdoor Unit Model HVAHP036B21S HVAHP048B21S HVAHP060B21S

Rated Cooling Capacity (Btu/h) 36,000 48,000 60,000

Rated Heating Capacity (Btu/h) 40,000 54,000 64,000

Performance Operating Range* — Cooling (°F) 23 to 118

Operating Range* — Heating (°F) -4 to 59

Power Supply (V/ph/Hz) 208-230 / 1 / 60

Configurations Number Of Indoor Units 1 to 6 1 to 8 1 to 8

Maximum Piping Length (ft) 492

Maximum Total Piping Length (ft) 984

Maximum Vertical Distance, IU to OU —


Refrigerant Piping 164 / 131
OU above IU / OU below IU (ft)

Maximum Vertical Distance


49
Between Indoor Units (ft)

Dimensions H x W x D (in) 54 5/16 x 37 3/8 x 14 9/16

* For more details and limitations, please consult Hitachi sales team or refer to product manuals

Hitachi Mini VRF Outdoor Units All outdoor units feature:


Hitachi Mini VRF Heat Pump • Long refrigerant piping lengths – • P
 ower-saving demand control
units offer an extended operating up to 492 feet piping length for reduced peak load and energy-
temperature range: outdoor ambient • Advanced defrost cycle operation savings
temperature as low as 23°F (-5°C) in in the heating mode • Optional Low Sound Mode which
the cooling mode and as low as -4°F • Ability to operate up to 8 indoor reduces the standard low sound
(-20°C) in the heating mode. units on a single piping network level even further
Outdoor Units

Hitachi Mini VRF Systems 35


OUTDOOR
UNITS

MINI VRF HEAT PUMP OUTDOOR UNITS
208/230V HP | 3-, 4- & 5-Ton Systems
Type Mini VRF Outdoor Units
3, 4 & 5 Ton Systems
Tonnage 3 Ton 4 Ton 5 Ton
Model HVAHP036B21S HVAHP048B21S HVAHP060B21S
Power Supply 208/230V/ 1PH 60Hz 208/230V/ 1PH 60Hz 208/230V/ 1PH 60Hz
Capacity
Btu/h (kW) 36,000 (10.6) 48,000 (14.1) 60,000 (17.6)
(Nominal)
Cooling
Power input kW 2.53 3.78 5.05
Current input A 12.3 / 11.1 18.6 / 16.9 24.8 / 22.4
Capacity (Nominal) *
Capacity
Btu/h (kW) 40,000 11.7 54,000 15.8 64,000 18.7
(Nominal)
Heating
Power input kW 2.40 4.00 4.40
Current input A 11.8 / 10.6 19.6 / 17.7 21.7 / 19.6
Capacity (Rated) Btu/h 36,000 36,000 48,000 48,000 60,000 55,000
Cooling
(for Non-ducted EER Btu/Wh 16.70 13.80 16.70 13.10 12.20 9.70
and Ducted)
SEER Btu/Wh 23.50 18.70 24.10 18.40 16.80 15.90
Efficiency Ratings **
Rated Capacity Btu/h 40,000 40,000 54,000 54,000 64,000 64,000
Heating
(for Non-ducted COP W/W 5.12 / 3.90 4.56 / 3.86 3.90 / 3.30
and Ducted)
HSPF Btu/Wh 12.80 11.00 11.70 11.80 12.10 10.60
Cooling Operating Range*** Outdoor °F DB (°C DB) 23 (-5) ~ 118 (48) 23 (-5) ~ 118 (48) 23 (-5) ~ 118 (48)
Heating Operating Range*** Outdoor °F WB (°C WB) -4 (-20) ~ 59 (15) -4 (-20) ~ 59 (15) -4 (-20) ~ 59 (15)
Height in (mm) 54-5/16 (1380) 54-5/16 (1380) 54-5/16 (1380)
Outer Dimensions Width in (mm) 37-3/8 (950) 37-3/8 (950) 37-3/8 (950)
Depth in (mm) 14-9/16 (370) 14-9/16 (370) 14-9/16 (370)
Weight Net lbs (kg) 249 (113) 249 (113) 249 (113)
Total Indoor Unit Capacity % 60-130 60-130 60-105
Connection Ratio
Max. (Recommendation) indoor units/system 6 8 8
Type — HA36PHD-A1S2 HA36PHD-A1S2 A36PHD-A1S2
Motor Output (Pole) —/— 3PH / 6 3PH / 6 3PH / 6
Compressor
Operation Range % 10 ~ 100 10 ~ 100 10 ~ 100
Refrigeration Oil Type – FVC68D FVC68D FVC68D
Type – Propeller Fan Propeller Fan Propeller Fan
Motor Output W 58 + 58 58 + 58 58 + 58
Fan
Quantity Q'ty 2
Air Flow Rate cfm (m3/min) 3177 (90) 3530 (100) 3530 (100)
Min Circuit Amps A 31 31 31
Electrical
Max. Overcurrent Protective Device A 40

Sound Pressure Level Cooling (Night-Shift) dB(A) 51 (44) 52 (46) 53 (46)


***** Heating dB(A) 52 54 56
Type - R410A
Refrigerant
Charge amount lbs (kg) 7.9 (3.6) 7.9 (3.6) 7.9 (3.6)

Main Refrigerant Gas Line in (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Piping Liquid Line in (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
NOTES:
* Rating Conditions: ** Efficiency ratings are based on the AHRI 210/240 test standard.
COOLING Indoor Air Inlet Temperature: 80°F (26.7°C)DB
*** There are some exceptions and notes for cooling and cooling operation ranges.
67°F (19.4°C)WB For details, refer to Section 2.12 “Operation Range”.
Outdoor Air Inlet Temperature: 95°F (35.0°C)DB
**** Measurement Point: 3.3 ft. (1m) from the air outlet side, 4.9 ft. (1.5m) from floor level. The operation
HEATING Indoor Air Inlet Temperature: 70°F (21.1°C)DB sound is measured in an anechoic chamber. However, the actual operation sound may appear louder or
Outdoor Air Inlet Temperature: 47°F (8.3°C)DB with an echo because of surrounding environmental noise. Be sure to check environmental conditions
43°F (6.1°C)WB before installation. The sound of the air inlet side may be 3dB higher than that of the air outlet side.


Piping Length: 24.6in. (7.5m)
Piping Lift: 0ft. (0m)

36 Hitachi Mini VRF Systems


Hitachi Mini VRF Systems 37
CONTROLLERS

CONTROL YOUR SPACE
LIKE NEVER BEFORE
Controllers

Hitachi Mini VRF Systems offer a wide range of control Simplified Wired Zone Controller
systems to suit multiple applications including wired and Programmable Wired Zone Controller
wireless controllers that manage zones and central stations Wireless Zone Controller
for central control of the entire system. VRF Smart Gateway Centralized Controllers
(BACnet)® and LONWorks® Adapters provide control through VRF Smart Gateway (BACnet)
LONWorks® Adapter
building automation systems.

Computerized
Simplified Mini Large Central Web-Enabled VRF Smart
Project Requirements Wired Wired Wireless Central Central Controller Central Gateway LONWorks®
Controller Controller Controller Station Station (CCCS01/ Controller (BACnet)® Adapter
(CIS01) (CIW01) (CIR01) (CCM01) (CCL01) CCCA01) (CCWEB01) (CBN02) (CLW01)

Simple individual zone


control 4 4 4 4 4

Independent cool and heat


setpoints 4 4 4 4 4 4 4 n n

Individual zone control


with weekly programmable 4 4 4 4 4 n n
scheduling

Basic central point on/off


control of all units 4 4 4 4 4 4

Advanced multi-zone
control of small to medium 4 4 4 n n
size projects

Advanced multi-zone
control of large commercial 4 4 n n
projects

Automatic cooling/heating
changeover for heat pump 4 4 4 4 4 4 4 n n
systems

Single input batch


shutdown of all connected 4 4 4 4 4 4
units

Multiple tenant power


billing for shared condenser 4 n
applications*

Temperature set-point
range restrictions 4 4 4 4 4 4 n n

Graphical user interface


with floor plan layout 4 n n

Exposes more points n n


Exposes outdoor unit
points n n

Wi-Fi enabled n n

Easy integration n n

Easy commissioning n n

4 = Native application or feature of this device n = Dependent upon capabilities of a third party energy management system * = Additional metering hardware is required for consumption-based tenant billing

38 Hitachi Mini VRF Systems


CONTROLLERS

ZONE CONTROLLERS

ZONE CONTROLLERS
Energy-Saving Features

MODEL CIW01 Temperature range limit

Setback

Programmable Wired Zone Controller Occupancy-based operation


(Sensors available on select Indoor Units.)
• Standard wall controller
Set temperature auto reset
• Dual set point
• Controls temperature, mode, fan speed Off timer
• Seven-day schedule with multiple setpoints
Individual function lockout
• Control up to 16 indoor units (mode, temperature, fan speed)
• Built-in 23-hour timer
• Room name and service company name
programmable
• Help menus and error code diagnosis MODEL CIR01
• Large LCD display permits users to see the
operating conditions and settings. Wireless Zone Controller
• The timer can be set at half-hour intervals up to
23 hours. • Controls up to 16 indoor units
• Monitors the operating conditions in the system • Built-in 23-hour timer
and an alarm is issued if a problem occurs.
• Wireless receiver must be added for all
• A “self-diagnosis function” checks for problems indoor units except wall-mount models
on printed boards in indoor and outdoor units. (built in)

MODEL CIS01

Simplified Wired Zone Controller

• Small size for discreet applications


• Controls 1 to 16 indoor units (same settings)
• Error code diagnosis
• Adjustable fan speed
• Typically used in hotels, offices and
restaurants
Controllers

Hitachi Mini VRF Systems 39


CONTROLLERS

CENTRALIZED CONTROLLERS

Central Station
Mini and large systems are available.

• L arge version controls up to 64 groups of indoor units


(maximum 160 units).
• Mini version controls up to 32 groups of indoor units
(maximum 160 units).
• Easy-to-use touchscreen interface
• Records accumulated operations time for tenant billing
• Color-coded graphics for quick reference
• Set up to 10 on/off times per day Large: MODEL CCL01
• Up to 8 stations can be connected to the H-LINK II.
• In addition to basic control, such as settings for
operation/stop, the operation mode and temperature,
the air quantity and auto louver can be set. If a problem
occurs, an alarm code immediately shows the details of
the problem.
• An external input terminal is provided as standard.
External signals enable the following functions:
»» central operation/stop
»» demand control Mini: MODEL CCM01
»» emergency stop
»» central operation output
Mini: MODEL CCM01
»» central alarm output

Control up to
Compatible with the Control up to
H-LINK II 160 indoor units 32 64
or groups
Connect up to
8 stations
(model dependent)*

*See model details for specifics

40 Hitachi Mini VRF Systems


CONTROLLERS

CENTRALIZED CONTROLLERS

Web-Enabled Central Controller

The Web-Enabled Central Controller is a web-based interface Features


to control and monitor VRF systems with up to five (5) local • 24V AC powered
or remote Windows-based PCs and/or tablets.
• Built-in software for easy access with no need
for an optical drive for installation
• Advanced multi-zone control of large
commercial projects
MODEL
CCWEB01
• Scheduling
• Block and Group Control for scheduling, mode,
set point, prohibit RC functions
• Connect up to 8 Large (CCL01) and/or Mini (CCM01)
Central Controllers simultaneously in the same
H-LINK II segment
• Support for the following maximum device limits:
»» 64 Refrigerant Systems
»» 160 IDUs

Computerized Central Controller

Computerized central controllers can manage up to 2,048


groups of systems with a maximum 2,560 total indoor units
from a PC. This option increases management and setting
possibilities and allows instructions to be carried out from
any point on a local communication network.

Computerized Central Controller Software:


MODEL CCCS01

Computerized Central Computer Adapter:


MODEL CCCA01
Controllers

Hitachi Mini VRF Systems 41


CONTROLLERS

INTEGRATING HITACHI MINI VRF EQUIPMENT
WITH BUILDING MANAGEMENT SYSTEMS

Johnson Controls VRF Smart Gateway

The VRF Smart Gateway enables unprecedented control of Hitachi VRF System
components through fast, simple integration into the Facility Explorer® BAS.
Complete system data is available for all components in the system.
Enhanced Features
• Automatically structures and • B ACnet® compatible
organizes data for faster, easier • Information conforms to BAS
and less costly integration conventions for quick adoption
• Works over Ethernet to obtain • Wi-Fi accessibility enables
system data and make it accessible 24/7 monitoring and control of
through BAS equipment from laptops, tablets MODEL CBN02
• Brings all BMS capabilities to and smartphones
VRF components including
User Interface, Global Search,
schedules, reporting, and offline
configuration

LONWorks® Adapter

• Supports up to 64 Remote • Monitoring points include:


Control Groups Run/Stop Status, Operation
• Supports up to 160 Indoor Units Mode Status, Fan Speed Status,
with a variety of network variables Temperature Setpoint, Thermo
on a per indoor unit basis Status, Alarm Status
• Control points include:
Run/Stop, Operation Mode, Fan
Speed, Temperature Setpoint,
MODEL CLW01
Prohibit Zone Controller Functions

Features
• 24V AC powered • Support for the following maximum device limits:
• Connect up to 4 LonWorks Adapters (CLW01) • 64 Refrigerant Systems
simultaneously to the same H-LINK II segment • 160 Indoor Units
• Connect up to 8 Large (CCL01) and/or Mini (CCM01) • Total of 200 nodes:
Central Controllers and/or LONWorks Adapters (CLW01) A combination of up to 160 indoor units and
simultaneously to the same H-LINK II segment a maximum of 64 outdoor units, not to exceed
a total of 200.

42 Hitachi Mini VRF Systems


CONTROLLERS

H-LINK II NETWORK SYSTEMS

H-LINK II
H-LINK II System
H-LINK II is a unique communication system that can be used to control
multiple outdoor and indoor units from one control point. Its use assists Max. Number of Refrigerant
64
installers and service engineers by simplifying commissioning and service Groups / System
maintenance. For building owners and occupants, it provides great versatility
Address Setting Range of
to connect various types of central control options enabling better system Indoor Units / 0 to 63
management. Refrigerant Group
Max. Number of Indoor Units /
The H-LINK II communication system for connection between outdoor and System
160
indoor units provides an extended system configuration and improved
functions without sacrificing workability and flexibility. Total Number of Devices in the
200
same H-LINK II
Our proprietary high-performance communication system enables
connection of control wiring between indoor and outdoor units, and between Total Max. Wiring Length Total 3,281 ft
a centralized control system and indoor/outdoor units across two or more
refrigerant systems.

Flexible Wiring Routes


The H-LINK II allows for easy installation through a simple daisy-chain
configuration. Simply connect to the adjacent units or the terminal block of a
centralized control system.

Controllers

Hitachi Mini VRF Systems 43


ACCESSORIES

MINI VRF ACCESSORIES

Unit Type Accessory Description


Drain Kit For connection of field supplied drain pipe to drain pan

Air Flow Guide Louvers for directing outlet air

Wind Guard Protects outlet air from strong winds

Wind Prevention Tool Prevents the OU from tipping over


Outdoor Units
Snow Protection Hood Protects OU air outlet from snow

Toppling Prevention Tool Prevents OU from tipping over when Snow Protection Hood is in use

Protection Net Kit that protects OU heat exchanger

3-Pin Connector Cable Kit that provides remote start/stop capability for IU and operating status of IU functions

Kit (with 5 sets of 3P Connectors) that provides remote start/stop capability (binary input) to IU and operating status
3-Pin Connector Cable
(binary input) of IU functions

Relay and 3-Pin Connector Kit Relay and 3 Pin Connector Kit used for input/output signals (ON/OFF, mode, alarm) between central controller and IU
Ducted Indoor Units
Remote Temperature Sensor Remote air temperature sensor

Air Filter Washable air filter with mounting flange

Filter Box Mounting box for filter

Air Outlet Shutter Plate Plate for blocking of air outlet

Fresh Air Intake Kit Kit for connection of outside air to the IU

T-Tube Connecting Kit Kit for connection of outside air duct to the IU. Requires Fresh Air Intake Kit

Duct Adapter Kit for connection of outside air duct to the IU

Panel with Motion / Radiant


Air panel with motion and radiant heat sensor. Replaces standard panel
Sensors

Motion Sensor Kit Kit for detection of motion in the area

Grille for Front Discharge Grille used for front air outlet from IU

Strainer Kit For IU refrigerant circuit

IR Receiver Kit Kit for use with wireless controller CIR01

2-Pin Connector Printed Board Connector

Drain Pump Kit Drain pump kit

Remote Temperature Sensor Remote air temperature sensor

Drain pump (wall mount) Condensate Pump Kit Capacity - 2.9-3.2 GPH @ 0’ Head / 1.2-1.6 GPH @ 33’ Head

Kit (with 5 sets of 3P Connectors) that provides remote start/stop capability (binary input) to IU and operating status
3-Pin Connector Cable
(binary input) of IU functions

Relay and 3-Pin Connector Kit Relay and 3 Pin Connector Kit used for input/output signals (ON/OFF, mode, alarm) between central controller and IU

44 Hitachi Mini VRF Systems


NOTES
JOHNSON CONTROLS-HITACHI AIR CONDITIONING

CUSTOMER SERVICE CERTIFICATION
844-873-4445 Option 1
[email protected]

Industry certified
Hitachi VRF Systems are Intertek ETL Listed
(Canada & USA), signifying that they comply with the standard of Heating and Cooling
Equipment (ANSI/UL 1995 and CAN/CSA C22.2 No. 236-11, 4th Edition, October 14, 2011).
The systems are also certified by the Air Conditioning, Heating & Refrigeration Institute.

WARRANTY

For more details on terms, conditions, and limitations, please refer to the warranty certificate.
Contact your sales person or visit our warranty support center at [email protected] for
specific eligibility requirements.

The specifications of this catalog may change without prior notice to allow Hitachi Cooling &
Heating to incorporate the latest innovations for its customers. The information contained in
this catalog is merely informative. Hitachi Cooling & Heating declines any responsibility in the
broadest sense, for damage, direct or indirect, arising from the use and / or interpretation of the
recommendations in this brochure.