Instruments Functional Loop Check Execution Procedure
Instruments Functional Loop Check Execution Procedure
Contents
1 FOREWORD ............................................................................................................................................................................................... 3
2 MAIN ISSUES ............................................................................................................................................................................................. 4
2.1 REFERENCE DOCUMENTS................................................................................................................................................................ 4
2.2 REQUIRED INSTRUMENTS................................................................................................................................................................ 4
3 FUNCTIONAL CHECKS .......................................................................................................................................................................... 5
3.1 FUNCTIONAL CHECK OF SERVO VALVES & LVDT CONTROL LOOPS (with MKVI Control System) .................. 5
3.2 FUNCTIONAL CHECK OF 4÷20 mA PRESSURE TRANSMITTERS (including differential PT) ............................. 10
3.3 FUNCTIONAL CHECK OF TEMPERATURE LOOPS: 4÷20 mA TRANSMITTERS,
THERMOCOUPLES and RTD’s...................................................................................................................................................... 11
3.4 FUNCTIONAL CHECK OF 4÷20 mA LEVEL/FLOWMETER TRANSMITTERS ............................................................... 12
3.5 FUNCTIONAL CHECK OF ACCELEROMETER / VELOCIMETER SEISMIC PROBE ...................................................... 13
3.6 FUNCTIONAL CHECK OF DIGITAL INPUT ............................................................................................................................... 16
3.7 FUNCTIONAL CHECK OF ANALOG OUTPUT ......................................................................................................................... 18
3.8 FUNCTIONAL CHECK OF DIGITAL OUTPUT ........................................................................................................................... 19
1 FOREWORD
This documents aims to provide general directions for the functional loop test of the instruments / devices
installed on GE/NP equipments and the relevant control system(s).
o Instrument, that is a transducer that converts a physical process variable into an electrical analog
signal (4-20 mA), or digital (open/closed contact). This may also be an output device, such as an
actuator, a solenoid, etc converting an electric signal into a physical process variable.
o Control software
These loops shall be checked including, as much as possible, all the above components, meaning that the preferred
test method implies to simulate the physical process variable, verifying the reading on the animated display AND
the actions caused by the control software, such as alarms, trips, sequencing, etc.
Sometime, the entire loop may not be tested due to limited or impossible access to some portion of the loop itself,
for instance when an instrument is installed inside a sealed or assembled part of machinery. In this case, only the
portion that is available can be checked, injecting an electrical signal, equivalent to the instrument output, at the
first terminal board, closest to the instrument. The inaccessible portion of the loop must have been checked and
certified in the factory, at assembly. The correct functionality can also be confirmed at site comparing the output
of the instrument with the process variable measured elsewhere, using a verified loop.
The simulation of the instrument output can be also recommended when the process physical variable cannot be
changed or simulated or measured, or when this is unrealistic at site.
Loops including “Smart” instruments can be checked using a “Hart communicator”, when the physical variable cannot
be simulated.
Warning: In case a fully tested loop is altered in any way and for any reason, the loop check validity is void and it
shall be repeated, signing off again the relevant SQCL line. <2>
2 MAIN ISSUES
3 FUNCTIONAL CHECKS
All installation requirements have been successfully completed, witnessed and signed-off, and the documents are
readily available for review if needed. It is also required that all instruments are loop-checked prior to each
functional test.
3.1 FUNCTIONAL CHECK OF SERVO VALVES & LVDT CONTROL LOOPS (with MKVI Control System)
System pre-commissioning
1) Lube oil (L.O.) and hydraulic oil (H.O.) pressure available.
2) Continuity/ground check from TSVO to servo’s and LVDT.
Servo coil resistance should be 1 Kohm
Colors are: Red/White – Yellow/Green – Orange/Blue
LVDT resistance should be few tenths ohm
Colours are: Extc. Red/Black+Blu or Yellow
Fdbk Orange/Yellow or Blue
Open circuit to ground for all terminals.
3) Test the Trip Solenoid Valves (i.e. 20HD-1, 20FG-1, 20TV-1, etc.)
4) Keep the Trip Solenoid Valves energized.
5) With everything disconnected and both L.O. and H.O. in pressure, verify the devices moves to their
safety position:
SRV closed
GCV closed
IGV closed
TSNZ open
Note: If the device moves to the wrong direction, check the Moog valve Model number, the tubing connection and
the installation position (P is the inlet H.O. port). Otherwise is a mech. Bias problem (refer to Mech. Bias adjusting
procedure).
9) In calibration mode give a Manual command of 50% (the feedback will be different).
10) On the servovalve adjust the Mechanical Bias screw, located on the side of the body:
- put the allen-key to hold the screw, then loose the nut
- adjust the screw to align the feedback to the 50% command
- tight the nut, keeping the screw, and verify the feedback remains at 50%.
Note: the screw is rotate
11) Move the Device up and down to verify that the difference between Command and Feedback remains
almost zero.
Note: if this procedure doesn’t fix the problem, replace the Moog valve.
Acceptance criteria:
The max deviation between reference and actual position shall not exceed the value indicated in the Control
Specification (if existing). For reference, the acceptable limits may be +/- 1%, for linear strokes (SRV & GCV) and
+/- 1 Deg for angular positions (IGV and Nozzles).