Generator Grounding
Generator Grounding
Contents:
Theory
Introduction
Objective of Generator Grounding
Generator Grounding Types
High-impedance grounding
Low resistance grounding
Reactance grounding
Grounding transformer grounding
Examples
High Resistance Grounding
2
Electrical power system
•
M
G
3
Grounding System
4
GENERATOR GROUNDING
NEUTRAL
POINT
11kV
Grounding
Method ? 3.3kV
400V
5
GENERATOR GROUNDING
6
Grounding Method
1. Ungrounded
2. High-resistance grounded
3. Low-resistance grounded
4. Low-inductance grounded
5. Effectively grounded
7
OBJECTIVES OF GENERATOR GROUNDING
8
Minimizing Damage for Internal Ground Faults
9
Ground fault current depend on Grounding Method
1. Resonant grounded
low
2 Ungrounded
3 High-resistance grounded
4 Low-resistance grounded
5 Low-inductance grounded
Increase fault
6 Effectively grounded current direction
10
Effects of Arc Burning on Stator Core Laminations
11
Allowable damage criteria for copper or aluminum
12
OBJECTIVES OF GENERATOR GROUNDING
13
Limiting Mechanical Stress in the Generator for External Ground Faults
X0 < X1
The sufficient neutral impedance is used to make the phase-to-
ground fault current less than or equal to the 3-phase fault
current with the machine isolated from the system, the winding
currents for any fault will be less than or equal to the winding
current for a 3-phase fault
14
OBJECTIVES OF GENERATOR GROUNDING
15
Limiting Overvoltages on Generator Insulation
1 Effectively grounded
2 Low-inductance grounded
3 Low-resistance grounded Increase
Temporary
4 Resonant grounded overvoltage
5 High-resistance grounded direction
6 Ungrounded
16
Limiting Overvoltages on Generator Insulation
Cg = capacitance of all
phase to ground , (3 C0)
Xcg =1/2 π f Cg
Rn = effective neutral
resistance
17
OBJECTIVES OF GENERATOR GROUNDING
18
Providing a Means of Generator System Ground-Fault Protection
19
OBJECTIVES OF GENERATOR GROUNDING
20
Coordinating with the Other Apparatus at Generator Voltage Level
Overvoltage control
21
Generator grounding
Winding configurations
22
Winding Configuration
23
Generator Grounding Method
¾ Neutral Grounding
¾ No Neutral Grounding
24
GUIDE OF THE APPLICATION
OF
25
Grounding Method
Reactance Grounding
26
Generator Grounding Method
28
Grounding Method
Reactance Grounding
29
Generator Grounding Method
High- Resistance Grounding
Two Methods of Neutral High-Resistance Grounding:
30
Generator Grounding Method –Resistor directly connected to ground
Standard Application
32
Generator Grounding Method-Distribution transformer and resistor combination
Advantage:
Low- Ohmic value Load Resistor
Primary current 3 – 15 A
Rugged construction
More details, to be added
and Example to calculate R
Standard Application
33
Generator Grounding Method-Distribution transformer and resistor combination
ZA
or B
UGen
V n UR
3
UR
Voltage Relay
35
Generator Grounding Method-Distribution transformer and resistor combination
37
EXAMPLE : TYPICAL HIGH -RESISTANCE NEUTRAL GROUNDING
High- Resistance Grounding
38
Generator Grounding Method
To power
system
X 1 = X 2 = 4%
Gen. VT's X 0 = 12%
Power transformer 100 MVA
surge 160 MVA
160 MVA 345 kV
Distribution capacitors 18: 345 kV
18 kV
transformer 15 %
Xd = X 2 = .21pu Unit
auxiliaries
transformer
15 MVA
18: 2.4 kV
R V0
0R Unit auxiliaries
service
bus
39
Generator Grounding Method
40
Generator Grounding Method
41
Generator Grounding Method
Low-Resistance Grounding
This method permits coordination with other equipment connected
to the system and is generally used where:
42
Generator Grounding Method
Low-Resistance Grounding
43
Generator Grounding Method- Ungrounded system
Zig-Zag
GROUNDING
TRANSFORMER
44
Generator Grounding Method
45
Generator Grounding Method
Reactor Grounding
46
Generator Grounding Method No Neutral Grounding
(Ungrounded )
47
Generator Grounding Method
No Neutral Grounding
48
BASIC GROUNDING
Voltages without ground fault Voltages at the point of ground fault at phase A
VCG=VCA
VLG voltage decreases in the faulty phase
(min -> 0)
N
VAG= 0 VLG voltage in both healthy phases are
increase (max -> Line to Line voltage)
49
Generator Ground Fault Current (Single Line to Ground)
Model
A
B
C
Ib Ic
VCG
1
XCg = ω = 2π f
ωCg
Vf = 3V0 N
VAG= 0
XCg = Three phase capacitance reactance to ground
Ib Ic
VBG
If
50
Correlation from Earth fault location
Displacement voltage V0 (U0) and earth current IE (3I0) as function of the fault
location of an earth fault in the machine winding.
V0 Z0
VAG VBG
VAG VBG
V0 V0
V0
IE = 3
Z0
At faults close to the star-point the displacement voltage and the earth
currents become small.
51
Elimination of the Disturbance High Voltage Ground Fault
Problem: grid earth faults cause disturbances Solution: attenuation by means of
due to the coupling capacitance between the a load resistor
two transformer windings Ck
CG CL R Prim CTr
R= 2
⎛ Q TR ⎞
⎜ ⎟
⎝ 3 ⎠ UGen 100 500
QTR = V V UN
3 3 3 UEO
Note: 3
Earthing At solidly earthed
(Limb transformation ratio)
transformer
transformer the U is
UR
appr. 80% of UN/√3
(Safety margin, if solidly
earthing is open)
52
Unit Connection – Influence on the Coupling Capacitance
R prim
U R ,prim ≈ U EO
1 220kV
R prim +
jω C K C K = 10 nF U EO =
CK 3
UR,Prim CE Rprim UEO Example: U N ,G = 10 .5 kV R = 5 Ω
uTr = 36 .4
2
⎛ u ⎞
R Prim = R. ⎜ Tr ⎟ = 735 Ω
⎝ 3 ⎠
CG+CL+CTr neglected ⇒ U R ,prim = 293V
UEO displacement voltage on the high voltage side
CK three phase coupling capacitance ⇒ U R ,sek ≈ 24V
Rprim primary load resistor
24V
üTr earthing transformer ratio ⇒ ⇒ 4 .83 % disturbance
500V
influence
53
Unit Connection with Neutral Transformer
UGen
n= UR
3
UR
R
Rsek = prim
Design of Rprim so that the fault current is < 10A
n
54
Fault Current : High-Resistance Grounding (Distribution Transformer)
X0
Xcg =
3
Rn = Xcg
Rn = effective neutral resistance
Rn
R= 2
n C0 = total of capacitance to ground/ phase
Network
L1
L2
L3
CE
Earthing
IC + IR transformer
3U0
Ohmic current
3i0 √3u0 boost
• DFT √3U0 >, 3I0 > UL1 UL2
•Direction
(√3U0 , 3I0)
3I0
IR
ICL2
IC
ICL1
56
Fault Currents – Direct Connection
G1
IMess
G2
IMess
57
Fault Currents – Direct Connection with Earthing Transformer
G1
IMess
G2 Earthing transformer
Ohmic current
RB
IMess
58
Directional Stator Earth Fault Protection - Characteristic
59