WP3082ADAM User's Manual

This document is the user manual for the WP3082ADAM 8-channel analog signal collector. It has the following key features: - Collects 8 single-ended analog inputs ranging from 0-20mA or 4-20mA using a 12-bit ADC chip. - Communicates via RS485 MODBUS RTU protocol to connect to configuration software, PLCs, and HMI panels. - Has dimensions of 125x73x35mm and can mount on a standard DIN rail or with screws. The manual provides details on the device specifications, interface pin definitions, analog input functionality, and MODBUS communication protocol for collecting input signals and configuring the device address and

Uploaded by

Oscar Santellano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views5 pages

WP3082ADAM User's Manual

This document is the user manual for the WP3082ADAM 8-channel analog signal collector. It has the following key features: - Collects 8 single-ended analog inputs ranging from 0-20mA or 4-20mA using a 12-bit ADC chip. - Communicates via RS485 MODBUS RTU protocol to connect to configuration software, PLCs, and HMI panels. - Has dimensions of 125x73x35mm and can mount on a standard DIN rail or with screws. The manual provides details on the device specifications, interface pin definitions, analog input functionality, and MODBUS communication protocol for collecting input signals and configuring the device address and

Uploaded by

Oscar Santellano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

https://www.wy-international.

com/
https://www.ebay.com/str/tiamofaye/
WP3082ADAM User’s Manual V1.42

WP3082ADAM

User’s Manual

Version 1.42
WP3082ADAM User’s Manual V1.42


1 Product description
8ch single-ended analog type:DC 0-20mA/4-20mA,using 12bit AD chip
Using RS485 MODBUS RTU communication standard. It can be netted with configuration software, PLC and industry
touch pad
Communication status LED
Communication circuit designed for lightening protection and interference immunity
Could be used for signal collection and control of Industrial field apparatus
3 Year’s quality assurance for normal use

2 、Specification
Analog iutput 8ch single-ended
Analog iutput range DC 0-20mA/4-20mA
Analog iutput accuracy ±0.02mA
Working Temperature ~ ℃
-20 70
External power supply ~
DC 9V 30V/2W
Isolation protect 1500VDC
Installation method Standard DIN slide rail or screw
Dimension 125×73×35mm

3 、Interface definition
AVcc External PSU positive terminal input
AGnd External PSU negative terminal input
AI_1+ positive terminal of the first analog input
Gnd signal ground,negative terminal of the first analog input
AI_2+ positive terminal of the second analog input
Gnd signal ground,negative terminal of the second analog input
AI_3+ positive terminal of the third analog input
Gnd signal ground,negative terminal of the third analog input
AI_4+ positive terminal of the fourth analog input
Gnd signal ground,negative terminal of the fourth analog input
AI_5+ positive terminal of the fifth analog input
Gnd signal ground,negative terminal of the fifth analog input
AI_6+ positive terminal of the sixth analog input
Gnd signal ground,negative terminal of the sixth analog input
AI_7+ positive terminal of the seventh analog input
Gnd signal ground,negative terminal of the seventh analog input
AI_8+ positive terminal of the eighth analog input
Gnd signal ground,negative terminal of the eighth analog input
485A RS485 signal A+
485B RS485 signal B-


4 Analog input work illustration
WP3082ADAM User’s Manual V1.42

5 、Communication Instruction
5.1 、Communication parameter (default setting): 9600,N,8,1
Parameter Description
9600 baud rate
N(no check) check bit
8 data bit
1 stop bit

5.2 、Command for collecting the input signal of analog quantity:


Send:01 03 00 00 00 08 44 0C (example/hexadecimal)
data byte data description remark
01 1 module address address range:01-FE
03 1 function code 03-read register
0000 2 register address (4x mode) 0000-analog input address of first register
0008 2 reading length 0008-read 8 registers
440C 2 CRC check code CRC check code for all data

Receive: 01 03 10 09 CE 00 00 00 00 00 00 00 00 00 00 00 00 00 00 6C 5B (
example/hexadecimal )
data byte data description remark
01 1 module address address range:01-FE
03 1 function code 03-read register
10 1 byte numbers 10-read 16 bytes
09CE 16 read data 09CE-read data from the first analog input
0000 0000-read data from the second analog input
0000 0000-read data from the third analog input
0000 0000-read data from the fourth analog input
0000 0000-read data from the fifth analog input
0000 0000-read data from the sixth analog input
0000 0000-read data from the seventh analog input
0000 0000-read data from the eighth analog input
6C5B 2 CRC check code CRC check code for all data

The recieved command means the data of the first analog input is “09CE”,and it is equal to 2510 in decimal,then substitute into
the fomula: I=(DATA*20)/4095=(2510*20)/4095≈12.26mA.The current in the other channel is 0mA.

5.3 、command for module address setting:


Send:00 06 00 64 00 01 08 04 (example/hexadecimal)
date byte data description remark
00 1 module address 00-group sending
06 1 function code 06-write single register
0064 2 register address (4x mode) 0064-modify module address
0001 2 data writing set new address for module, range 0001-00FE
0804 2 CRC check code CRC check code for all data


Receive 00 06 00 64 00 01 08 04 (example/hexadecimal)
This command means to send a code to a module, set the module address as 01, this setting could be saved when power off;
default address of module is 01,each module address could be assigned separately when using multiple modules for
network.Attentions is required that only one module could be used in 485 network when using multiple address sending,
otherwise all the modules will share the same address in 485 network. When module receives correct command, it will make
corresponding actions and send response back to the master. This is successful communication.

5.4 、Command for communication parameter setting:


Send:01 06 00 65 00 02 18 14 (example/hexadecimal)
data byte data description remark
01 1 module address address range:01-FE
06 1 function code 06-write single register
0065 2 register address (4x mode) 0065-modify communication parameter
0002 2 data writing 0001-set communication parameter 4800,N(no
check) ,8,1
0002-set communication parameter 9600,N(no
check) ,8,1
0003-set communication parameter 19200,N(no
WP3082ADAM User’s Manual V1.42

check) ,8,1
0004-set communication parameter 38400,N(no
check) ,8,1
0005-set communication parameter 4800,E(even
check) ,8,1
0006-set communication parameter 9600,E(even
check) ,8,1
0007-set communication parameter 19200,E(even
check) ,8,1
0008-set communication parameter 38400,E(even
check) ,8,1
1814 2 CRC check code CRC check code for all data


Receive 01 06 00 65 00 02 18 14 (example/hexadecimal)
This command means to send a code to the module and set the communication parameter as “9600, N (No check), 8, 1”.This
setting could be saved when power off. The default communication parameter is “9600, N (no check), 8, 1”. Attention is
required, when electing the correct communication parameter in communication setting and restarting the communication
terminal, setting will be done.Normally, the lower of baud rate, the lower of the transaction speed but the higher of transaction
stability. The opposite is also true.When module receives correct command, corresponding action will be taken and response
will be sent back to the master. This is successful communication.

6 、Indicator LED description


When module powered on, Led is green.
When module is under communication, LED is twinkling.
when module receive correct command, LED is green.
when module receive incorrect command or command for other modules, LED is red.


7 PC debugging instruction
This module provides software for parameter setting and function test. Please follow the steps below:
Connect the module and computer using RS485 converter.
Connect 12V or 24V power with module and power on. To avoid any unnecessary damage, please make sure the power
positive & negative terminals are correctly connected before power on.
Open the software, select the correct module number, you will see the window of function test or parameter setting.
Set correct parameter, open communication interface.
Select corresponding setting, collection and control items.
WP3082ADAM User’s Manual V1.42

8 、RS485 network diagram

https://www.wy-international.com/