NFS2-640/E: Fire Alarm Control Panel Installation Manual
NFS2-640/E: Fire Alarm Control Panel Installation Manual
NFS2-640/E: Fire Alarm Control Panel Installation Manual
NFS2-640/E
Installation Manual
This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for Class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
Section 4: Applications................................................................................................................................................... 44
4.1: Overview..........................................................................................................................................................................................................44
4.2: Devices Requiring External Power Supervision..............................................................................................................................................44
4.3: NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit) ......................................................................................44
4.4: Central Station Fire Alarm System Canadian Requirements...........................................................................................................................46
4.5: NFPA 72 Proprietary Fire Alarm Systems .......................................................................................................................................................47
4.6: Fire/Security Applications ..............................................................................................................................................................................47
4.6.1: General Operation.................................................................................................................................................................................47
4.6.2: Installing a Security Tamper Switch.....................................................................................................................................................47
4.6.3: Receiving Unit ......................................................................................................................................................................................48
4.6.4: Programming ........................................................................................................................................................................................48
4.6.5: Wiring for Proprietary Security Alarm Applications ...........................................................................................................................48
4.7: Releasing Applications ....................................................................................................................................................................................49
4.7.1: Overview...............................................................................................................................................................................................49
4.7.2: Programming ........................................................................................................................................................................................49
4.7.3: Connecting a Releasing Device to the Control Panel...........................................................................................................................49
4.7.4: Connecting a Releasing Device to the FCM-1 Module........................................................................................................................51
4.7.5: Connecting Releasing Devices to the FCM-1-REL Control Module...................................................................................................53
4.7.6: Connecting an NBG-12LRA Agent Release-Abort Station .................................................................................................................54
Section 5: Testing the System ...................................................................................................................................... 55
5.1: Acceptance Test ...............................................................................................................................................................................................55
5.2: Periodic Testing and Service............................................................................................................................................................................55
5.3: Operational Checks..........................................................................................................................................................................................55
5.4: Battery Checks and Maintenance ....................................................................................................................................................................55
Appendix A: Power Supply Calculations ...................................................................................................................... 57
A.1: Calculating AC Branch Circuit Current..........................................................................................................................................................57
A.2: Calculating the System Current Draws ..........................................................................................................................................................57
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw.............................................................................................59
A.3: Calculating the Battery Requirements ............................................................................................................................................................60
A.3.1: Calculating the Battery Capacity .........................................................................................................................................................60
A.3.2: Calculating the Battery Size ................................................................................................................................................................60
Appendix B: Electrical Specifications ........................................................................................................................... 61
B.1: Electrical Specifications..................................................................................................................................................................................61
B.2: Wire Requirements..........................................................................................................................................................................................62
Appendix C: Canadian Applications.............................................................................................................................. 64
C.1: Standalone Application ...................................................................................................................................................................................64
C.1.1: NFS2-640/E with KDM-R2 .................................................................................................................................................................64
C.1.2: NFS2-640/E with NCA-2.....................................................................................................................................................................64
C.2: Network Applications .....................................................................................................................................................................................64
C.3: Automatic Alarm Signal Silence .....................................................................................................................................................................64
C.4: Annunciator Applications................................................................................................................................................................................64
C.5: Releasing Devices ...........................................................................................................................................................................................64
C.6: Ancillary Devices ............................................................................................................................................................................................64
C.7: Isolating NACs with Audio Isolator Modules.................................................................................................................................................64
C.7.1: Description of Modules........................................................................................................................................................................64
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory. UL Product iQ:
https://iq.ulprospector.com/en/
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ONYXWorks™ Workstation Hardware & Software Application: Installation and Operation Manual 52342
ONYXWorks™ NFN Gateway (PC Platform) Installation & Operation Manual 52307
ONYXWorks™ NFN Gateway (Embedded Platform) Installation & Operation Manual 52306
NCS ONYX® Network Control Station Manual, Network Version 4.0 & Higher 51658
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
CAUTION:
! Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING:
! Indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of
programming data or personal injury.
NOTE: The CPS-24/E is an integral part of the CPU2-640/E and is not available separately.
2. One or more chassis. The NFS2-640/E chassis (included with the CPU) mounts the CPU2-640/CPU2-640E and peripherals. Mount
additional rows of equipment in a compatible chassis selected from Table 3.3 on page 25.
3. Optional: A primary display. Generally this is a KDM-R2 keypad/display behind a DP-DISP2 or ADP2-640 dress panel. For
information on using NCA-2 as primary display instead of KDM-R2, see Section 3.5.2 “Using XLS-NCA2 as Primary Display”
and the NCA-2 Manual.
4. A backbox and door:
SBB-A4 and DR-A4 (one row of equipment) or
SBB-B4 and DR-B4 (two rows of equipment) or
SBB-C4 and DR-C4 (three rows of equipment) or
SBB-D4 and DR-D4 (four rows of equipment)
(For a solid-metal door add “B” to the part number; for a red door add “R”.)
5. A battery dress panel BP2-4 is required.
6. Batteries (Refer to Appendix A.3 “Calculating the Battery Requirements” for system current-draw calculations; CAB-4 series
backboxes holds batteries up to 26 AH maximum.)
Refer to Section 2.4, “Compatible Equipment” for other peripherals listed for use with this FACP.
Displayed Behind
DP-DISP2
DP-DISP2.wmf
Mounted in NFS2-
640/E Chassis
(with no
peripherals)
CPU2-640-
Figure 2.1 NFS2-640/E Control Panel with Optional Keypad/Display Unit Installed
Non-resettable
(See Figure 3.16 on page 36) TB12 - EIA-232 Printer Connection (Figures 3.25 & 3.26)
TB12 - EIA-232 PC/Terminal Connection (CRT)
(Figure 3.27)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)
TB9 - NAC#1
TB7 - NAC#3
TB2 - Secondary Power Auxiliary Outputs
(power-limited)
TB6 - NAC#4
for larger images and more details. (Larger images are referenced on these drawings.)
TB5 -
Supervisory Relay
Security Relay
Alarm Relay
Trouble Relay
Output Relays - power-limited only if connected to a power-
limited source. (See Section 3.9 for details.) J7 - KDM-R2
Connection J5 - Security Tamper Switch
J6 - Auxiliary Trouble Input
and its power supply. Figure 2.2 shows wiring connections; Figure 2.3 shows jumpers, LEDs and switches. See Section 3 “Installation”
The following two figures illustrate the location of the various connections, switches, jumpers and LEDs on the CPU2-640/CPU2-640E
13
System Overview
14
JP1 - Ground Fault
Jumper (SLC#1)
System Overview
NAC
LEDs
For details on mounting options within the cabinet, see Section 3.4, “Laying Out Equipment in Cabinet and Chassis”.
B200S-LF-IV Low-Frequency Intelligent Programmable Sounder Base Ivory FCO-851 Fire/CO Detector
B200S-LF-WH Low-Frequency Intelligent Programmable Sounder Base White FCO-951(A) Carbon Monoxide Sensors
B200SA Intelligent Sounder Base FCO-951(A)-IV Carbon Monoxide Sensors Ivory
B200SA-IV Intelligent Sounder Base Ivory FCPS-24S6/S8 Field Charger/Power Supply
B200SA-WH Intelligent Sounder Base White FDM-1 Dual Monitor Module
B200SCOA Intelligent Programmable Sounder Base FDRM-1 Dual Monitor/Dual Relay
B200SCOA-IV Intelligent Programmable Sounder Base Ivory FDX-551 Intelligent Thermal Sensor
B200SCOA-WH Intelligent Programmable Sounder Base White FDX-551R Intelligent Thermal Rate-of-Rise Sensor
B200SR Intelligent Sounder Base FHS Fireman's Handset
B200SR-IV Intelligent Sounder Base Ivory FMM-1 Monitor Module
B200SR-WH Intelligent Sounder Base White FMM-101 Mini Monitor Module
B200SR-LF Low-Frequency Intelligent Sounder Base FMM-4-20 Monitor Module
B200SR-LF-IV Low-Frequency Intelligent Sounder Base Ivory FPC-951(A) Multi Criteria PHOTO/CO Detector
B200SR-LF-WH Low-Frequency Intelligent Sounder Base White FPJ Fireman's Phone Jack
B200SRA Intelligent Sounder Base FPTI-951(A) Multi-Criteria Photoelectric, Thermal and Infrared Sensor
B200SRA-IV Intelligent Sounder Base Ivory FPTI-951(A)-IV Multi-Criteria Photoelectric, Thermal and Infrared Sensor Ivory
B200SRA-WH Intelligent Sounder Base White FRM-1 Relay Module
B210LP Flange Mounted Base FSA-5000/A (FAAST XS) Intelligent Aspiration detector
B210LPA ULC Flange Mounted Base FSA-8000/A (FAAST XM) Intelligent Aspiration detector
B210LPBP Bulk Pack of B300-6. Package of 10 FSA-20000/A (FAAST XT) Intelligent Aspiration detector
B224BI Isolator Bases for Low-profile Detectors FSA-20000P (FAAST XT PRO) Intelligent Aspiration detector
B224BI-IV Isolator Bases for Low-profile detectors Ivory FSA-851A Intelligent Aspiration Detector - 06-NF10 Baffle for the FSA-851A
B224BI-WH Isolator Bases for Low-profile detectors White FSB-200S Single Ended Beam Smoke Detector With Sensitivity Testing
B224BIA Isolator Base for Low-profile detectors FSB-200 Single Ended Beam Smoke Detector
B224BIA-IV Isolator Base for Low-profile detectors Ivory FSC-851 IntelliQuad Multi-Criteria Smoke Detector
B224BIA-WH Isolator Base for Low-profile detectors White FSCO-951(A) Carbon Monoxide Sensor
B224RB Low-profile Relay Base FSD-751P/RP/PL Duct Detectors
B224RB-IV Low-profile Relay base Ivory FSH-751 HARSH™ Photo Detector
B224RB-WH Low-profile Relay base White FSI-751 Ion Detector
B224RBA Low-profile Relay base FSI-851 Ion Detector
B244RBA-IV Low-profile Relay base Ivory FSL-751 FlashScan VIEW® Laser Detector
B244RBA-WH Low-profile Relay base White FSM-101 Pull Station Monitor Module
B300-6 Intelligent Detector Base 6 Inch White FS-OSI-RI(A) Intelligent Single Ended Reflected Type Projected Imaging Beam
B300-6-IV Intelligent Detector Base 6 Inch Ivory Smoke Detector
B300A-6 Intelligent Detector Base 6 Inch White Canada FSP-751 Photo Detector
B300A-6-IV Intelligent Base 6 Inch Ivory Canada FSP-751T Photo/Thermal Detector
BX-501 Intelligent Detectors/Sensors Base FSP-851 Photo Detector, listed for use in ducts
B501 USA Intelligent Detector Base FSP-851T Photo/heat Detector, listed for use in ducts
B501A ULC Intelligent Detector Base FST-751 Thermal Detector
B501BH-2 Sounder Base FST-751R Thermal Rate-of-rise Detector
B501BHT-2 Temporal Sounder Base FST-851 Thermal Detector
B501-White Intelligent Detector Base White FST-851H High-temperature Thermal Detector
B501-BL Intelligent Detector Base Black FST-851R Thermal Rate-of-rise Detector
B501-IV Intelligent Detector Base Ivory FSP-951 Photo Detector
B710HD HARSH Detector Base FSP-951-IV Photo Detector/Dual Protocol Ivory
B710LP European Intelligent Detector Base FSP-951R Photo RAT
BAT-12120 Battery 12-volt, 12 amp-hour FSP-951R-IV Photo RAT/Dual Protocol Ivory
BAT-12180 Battery 12-volt, 18 amp-hour FSP-951P Photo/Thermal
BAT-12250 Battery 12-volt, 25 amp-hour FSP-951T-IV Photo/Thermal/Dual Protocol Ivory
BAT-12260 Battery 12-volt, 26 amp-hour FST-951 Programmable Heat
BAT-12550 Battery 12-volt, 55 amp-hour FST-951-IV Programmable Heat/Dual Protocol Ivory
BAT-12600 Battery 12-volt, 60 amp-hour
BDA-25V/75V Backup Amplifier FST-951R Heat Detector Rate of Rise
CK300 Color Kit White FST-951R-IV Heat Detector Rate of Rise/Dual Protocol Ivory
CK300-IR Color Kit White with IR Opening FST-951H Heat Detector High
CK300-IV Color Kit Ivory FST-951H-IV Heat Detector High/Dual Protocol Ivory
CK300-IR-IV Color Kit Ivory with IR Opening FSV-951(A) Intelligent High Sensitivity Photoelectric Smoke Detector
CK300-BL Color Kit Black FSV-951(A)-IV Intelligent High Sensitivity Photoelectric Smoke Detector Ivory
CK300-IR-BL Color Kit Black with IR Opening FSV-951RA Intelligent High Sensitivity Photoelectric Smoke Detector Retrofit
CMM-1 Communication converter Module FSV-951RA-IV Intelligent High Sensitivity Photoelectric Smoke Detector Retrofit
Ivory
CMX-1 Addressable Control Module
FTM-1 Telephone Module
CMX-2 Addressable Control Module
FW-MM Wireless Monitor Module
CPU2-640/E Control Panel Circuit Board
FW-RM Wireless Relay
CPX-551 Intelligent Ionization Smoke Detector
FWD-200ACCLIMATE Wireless Acclimate detector
CPX-751 Intelligent Ionization Smoke Detector
FWD-200P Wireless photo detector
CRT-2 Video Display Monitor With Keyboard
FWH-200FIX135 Wireless, fixed-temperature heat detector
DAA Series Digital Audio Amplifiers
FWH-200ROR135 Wireless, rate-of-rise heat detector
DAA2 Series Digital Audio Amplifier
FWSG Wireless Gateway
DAX Digital Audio Amplifier
FZM-1 Zone Module
DHX-501 Duct Detector
HPX-751 HARSH™ Hostile Environment Smoke Detector
DHX-502 Duct Detector
HS-NCM-MF High-Speed Network Communications Module (Multi-Mode Fiber)
DNR/W/A Intelligent Non-Relay Photoelectric Duct Detector
HS-NCM-MFSF High-Speed Network Communications Module (Multi-Mode
DPI-232 Direct Panel Interface Fiber to Single-Mode Fiber)
DS-AMP Audio Amplifier HS-NCM-SF High-Speed Network Communications Module (Single-Mode Fiber)
DS-BDA Backup Audio Amplifier HS-NCM-W High-Speed Network Communications Module (Wire)
DS-DB Digital Distribution Board HS-NCM-WMF High-Speed Network Communications Module (Wire to Multi-
DS-XF70V Transformer Mode Fiber)
DVC-AO Digital Voice Command Audio Output HS-NCM-WSF High-Speed Network Communications Module (Wire to Single-
DVC-EM Digital Voice Command Mode Fiber)
DVC-RPU DVC Remote Paging Unit HWF2A-COM IP Digital Alarm Communicator
FCM-1 NAC Module HWF2A-COM IP Digital Alarm Communicator
FCM-1-REL Control Module
ISO-X Loop Fault Isolator Module RA100Z Remote Annunciator with diode
ISO-6/A Six Fault Isolator Module RA400 Remote Annunciator
LCD-80 Liquid Crystal Display Module RPJ-1 Remote Phone Jack
LCD2-80 Liquid Crystal Display Module RPT-485SF EIA-485 Repeater (Fiber)
LDM-E32 Lamp Driver Module Ivory RPT-485W EIA-485 Repeater (Wire)
LDM-R32 Lamp Driver Module RPT-485WF EIA-485 Repeater (Wire/Fiber)
LDM-32 Lamp Driver Module RM-1 Remote Microphone
LEM-320 Loop Expander Module RM-1SA Remote Microphone
LDM-E32 Lamp Driver Module Ivory SCS-8, SCE-8 Smoke Control System
LDM-R32 Lamp Driver Module SDX-551 Intelligent Photoelectric Detector
LDM-32 Lamp Driver Module SDX-551TH Intelligent Photoelectric and Thermal Detector
LEM-320/A Loop Expander Module SDX-751 Intelligent Photoelectric Detector
MMX-1 Addressable Monitor Module SLC-IM Signaling Line Circuit Integration Module (FlashScan)
MMX-2 Addressable Monitor Module STS-1 Security Tamper Switch (Not ULC-listed)
MMX-101 Addressable Mini Monitor Module TM-4 Transmitter Module
MRD-1 Manual Releasing Disconnect Assembly TR300 Trim Ring White
N-ELR Assortment ELR Pack with Mounting Plate TR300-IV Trim Ring Ivory
NBG-12 Series Addressable Manual Pull Station UDACT/UDACT-2 Universal Digital Alarm Communicator Transmitter
NBG-12LRA - Agent Release Abort Station UZC-256 Universal Zone Coder
NBG-12LX Addressable Manual Pull Stations VEP-A00-P-NTF Addressable VESDA-E VEP with LEDs
NBG-12LXP Portuguese Labeled Addressable Pull Station VEP-A10-P-NTF Addressable VESDA-E VEP with 3.5"Display
NBG12LXSP Spanish Labeled Addressable Pull Station VEP-A00-1P-NTF Addressable VESDA-E VEP 1 Pipe with LEDs
NCA-2/C Network Communications Annunciator VEU-A00-NTF Addressable VESDA-E VEU with LEDs
NCD Network Control Display VEU-A10-NTF Addressable VESDA-E VEU with 3.5" Display
NCM-F Network Communications Module (Fiber) VEA-040-A00-NTF Addressable VESDA-E VEA-40 point with LEDs
NCM-W Network Communications Module (Wire) VEA-040-A10-NTF Addressable VESDA-E VEA-40 point with 3.5" Display
NCO-200 Carbon Monoxide Sensor XPIQ Quad Intelligent Audio Transponder (Audio Applications)
NCS Network Control Station XP10-M Ten Input Monitor Module
N-MPS MPS Series Pull Station XP6-C Supervised Control Module
NFV Notifier FireVoice 25/50 XP6-MA Six Zone Interface Module
NP-200C PHOTO/CO Detector XP6-R Six Relay Control Module
ONYXWorks® Workstation Network Monitoring Workstation
PRN-6 80-Column Printer System Sensor Devices
PRN-7 80-Column Printer A2143-00 End of Line Resistor Assembly
R-120 120 Ohm End-of-Line Resistor EOLR-1 End of Line Resistor Assembly
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470 470 End-of-Line Resistor
R-47K 47K End-of-Line Resistor
NOTE: The FWSG Wireless Gateway as part of the wireless network has been tested for compliance with the Federal Communications
Commission (FCC) requirements of the United States Government. This product has not been evaluated for use outside the USA. Use of
this system outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
CAUTION: Make sure to install system components in the sequence listed below. Failure to do so can damage the control
! panel and other system components.
WARNING: This system contains static-sensitive components. Always ground yourself with a proper wrist strap before
! handling any circuits. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
CAUTION: Unless you are familiar with the placement of components within this backbox, only use the knockout locations
! provided for conduit entry.
7. Install control panel and other components according to Section 3.5 “Installing the Control Panel” before installing hinges and door
according to CAB-3/CAB-4 Series Cabinet Installation Document.
CAB-4
Series
CAB-4
Backbox,
Series Keyholes
nfs640cabinetmountingholes.wmf
D-size
Backbox, 2 places
(four-row)
A-size (one-
row)
Mounting holes
2 places
NOTE: The BP2-4 is required for NFS2-640/E installations due to UL’s revised labeling requirements. If using NFS2-640/E
in retrofits, order BP2-4 to replace previous BP-4 battery dress panels.
If DP-DISP2 is not being used in the top row of the backbox, install VP-2B above the first row to cover the remaining space.
NOTE: When designing the cabinet layout, consider separation of power-limited and non-power-limited wiring as discussed in Section
3.11 “UL Power-limited Wiring Requirements.”
CHS2-M2iso.wmf
Also see Figure 3.3, “Top View of
NFS2-640/E Chassis Mounting
Chassis Keyhole
CPU
CPS-24/E
DP-DISP2
(or ADP2-640
if in lower row) Left Annunciator Primary Display KDM- Right Annunciator
(mounts to dress panel) R2 or NCA-2 (mounts (mounts to dress panel)
to chassis)
CHS2-
Option boards
Mounted on BMP-1
When installing the Network Control Display (NCD) into the NFS2-640 chassis, it can only be left mounted because of the position of
the grounding screw.
Backbox
CPS-24/E
NCDMounting1.w
Dress Panel
NCD
Option boards
Mounted on BMP-1
NCD Annunciators, which are connected to the Fire Alarm Control Panel
DVC • CA-1
• CA-2
DVC-RPU • CA-1
Analog audio amplifiers AA-30, AA-100, AA-120 • Mounts directly onto CAB-4 backbox
Option boards • NFS2-640/E chassis, CHS-4, CHS-4L, CHS-4N (shipped as part of kit CHS-4MB), or on BMP-
1 inside dress plate
• Note: Mount LEM-320 in front of CPU2-640 in the NFS2-640/E chassis.
• Note: Mount UDACT/UDACT-2 in second or lower row, or in
slot 4 of the NFS2-640/E chassis with nothing in front of it.
• Note: Mount fiber versions of the NCM and HS-NCM in the top row under knockouts, to avoid
excessive bend on the fiber-optic cable.
ACS series annunciators ACM-24AT, ACM-48A and • Dress Panel DP-DISP2, ADP2-640, or ADP-4B
expanders
NOTE: In retrofit applications, the CAB-e series backbox may be used, but order BP2-4 to replace previous BP-4 battery dress panels.
NFS2-640/E chassis Top row of backbox typical; lower rows also possible.
DPA-2 Dress Panel Mounts in front of CA-2 covering two rows of the backbox
DP-DISP2 Dress Panel Mounts in front of the NFS2-640/E chassis in top row of backbox
ADP2-640 Dress Panel Mounts in front of NFS2-640/E chassis in second or lower row of backbox
CAUTION: It is critical that all mounting holes of the NFS2-640/E are secured with a screw or standoff to insure continuity
! of Earth Ground.
2-640_assembly_3-2.wmf
Figure 3.7 Mounting KDM-R2
If the NFS2-640/E and NCA-2 are being used as a stand-alone pair, each device must be programmed using VeriFire Tools. Connect the
VeriFire Tools PC to NFS2-640/E using USB B Port J3 and program as described in VeriFire Tools on-line help.
For older PCs without USB connectors, NFS2-640/E and NCA-2 must be temporarily disconnected and separately programmed,
because VeriFire Tools also uses the network/service port. Follow VeriFire Tools instructions for off-line programming mode.
If the NFS2-640/E with NCA-2 is connected to a network, there are two additional options for programming: either connect the VeriFire
Tools programming PC to the network port on the NCM/HS-NCM board, or program the NFS2-640/E through another network node.
NOTE: This is the only NCA-2 application that does not require an NCM or HS-NCM connection to Noti•Fire•Net.
NOTE: Another option board can be mounted above a Loop Expander Module or Network Communications Module; for
ease of access, be sure to complete installation of those devices before mounting a second layer.
NOTE: If using the fourth (right-side) position of the NFS2-640/E chassis, the chassis needs to be installed on the backbox
before option boards or modules are installed in that position. These modules will block access to the keyhole opening.
2-640_assembly_3-4-2.wmf
Figure 3.8 Attaching Option Boards Behind KDM-R2
CHS-4L.wmf
two studs in any one of the
four positions on the chassis.
Chassis
CHS-4L
Slots
nfs640-
Insert tab of option board
into slot of chassis, and lay One option board Two option boards
the option board back in CHS-4L in CHS-4L
against standoffs.
tm4adp4.cdr
Single-space
blank plate
Figure 3.12 Mounting an Option Board onto a Dress Panel with BMP-1 (ADP-4B Shown)
NOTE: See the BMP-1 Product Installation Drawing for details if considering mounting the module behind blank module
plate in a dress plate or annunciator backbox. This dress plate is suitable for modules that do not need to be visible or
accessible when the door is closed.
CAUTION: For the SLC to function correctly, the stacker-connector must be installed as shown in Figure 3.14. Do not
! install other option modules on top of the LEM-320.
1 inch standoffs
LEM-320 CPU2-640
Stacker-connector
J4
J1
NOTE: See the Noti•Fire•Net Manual or the High-Speed Noti•Fire•Net Manual and NCM Installation Document or HS-NCM
Installation Document for wiring diagrams and system configuration information. See the BMP-1 Product Installation
Drawing if considering mounting the module behind blank module plate in a dress plate or annunciator backbox.
NOTE: Over-bending fiber-optic cable can damage it. Do not exceed a 3 inch (7.62 cm) minimum bend radius.
NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.
Network configurations require an associated NCA-2, and will support all Network Control-by-Event; each node (DVC, CPU-2 and
NCA-2) requires a network address/NCM port in network applications.
NOTE: The DVC Series consists of all the model versions listed in the bullets below this note. Individual part numbers are
used in this manual only when it is necessary to distinguish features or functions that differ. The term DVC is used in all other
cases.
• DVC-EM - Digital Voice Command, extended memory, wire version (standard)
• DVC-EMF - Digital Voice Command, extended memory, multi-mode fiber version
• DVC-EMSF - Digital Voice Command, extended memory, single-mode fiber version.
For information regarding audio storage for the DVC-EM Series models listed above, refer to the DVC Digital Voice Command Manual.
NOTE: The term DAA is used in this manual to refer to all DAA wire and fiber models. Individual part numbers are used only
when it is necessary to distinguish features or functions that differ.
Figure 3.15 gives simplified overview illustrations of typical applications for the DVC Series and its Digital Audio Loop (DAL).
Wire and fiber, or multi-mode and single-mode, can be mixed.
2-640DV1.wmf
Loop) not
compatible
with this
application.
2-640DV2.wmf
NCA-2
DVC-AO
WARNING:
! SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL. BEFORE SERVICING THE
CONTROL PANEL, DISCONNECT ALL SOURCES OF INPUT POWER INCLUDING THE BATTERY. WHILE ENERGIZED,
THE CONTROL PANEL AND ASSOCIATED EQUIPMENT CAN BE DAMAGED BY REMOVING AND/OR INSERTING
CARDS, MODULES, OR INTERCONNECTING CABLES.
3.7.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 5.0 A (with NFS2-640E use 240 VAC, 50/60 Hz, 2.5 A) from line voltage source.
Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use
12 AWG (3.31 mm2) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary
(battery) power is required to support the system during loss of primary power.
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and Annunciators.
• Auxiliary power source – 24 VDC power @ 0.5 A and 5 VDC power @ 0.15 A from TB2 on the CPS-24/E.
See Appendix B.1 “Electrical Specifications” for details and overall installation guidelines.
CAUTION:
! While checking AC power, make sure batteries are not connected.
Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 15.
Component Status
Control panel circuit board The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
Each option board The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This only applies to an
unconfigured system.)
Each auxiliary power The yellow Trouble indicator comes on because batteries are not connected.
supply
WARNING:
! DO NOT CONNECT THE BATTERY INTERCONNECT CABLES (P/N 75560 AND 75561) AT THIS TIME. MAKE THIS
CONNECTION AFTER INITIAL SYSTEM PRIMARY POWER UP. FOLLOW SEQUENCE OF STEPS IN SECTION 3.2
“INSTALLATION CHECKLIST”, TABLE 3.1; THIS IS STEP 16.
Batteries are installed in the control panel cabinet or in a separate battery cabinet
TB3 - Battery Connection
which can be mounted below the control panel or up to 20 feet (6.096 m) away
from the control panel, in conduit in the same room.
Battery (+) Battery (-)
Connect the battery as follows (see Figure 3.16 above):
1. Install batteries into bottom of cabinet or into separate battery cabinet.
CPS-24-DC.wmf
2. Connect the red cable from TB3(+) on the CPS-24/E power supply to the
positive (+) terminal of one battery.
+24V AUX COM COM +5V AUX
3. Connect the black cable from TB3(–) on the CPS-24/E power supply to the
negative (–) terminal of the other battery.
4. Connect the remaining cable between the negative (-) terminal on the first
battery to the positive (+) terminal on the second battery.
Non-resettable Resettable
Power Power
CPU2-640-
Figure 3.18 Power Supply DC Outputs - TB10
24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply provides a single 24 VDC filtered,
power-limited, resettable power circuit for devices that require resettable power (such as four-wire smoke detectors). This circuit is
power-limited, but must be supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as the Sys-
tem Sensor model EOLR-1) after the last device. Connect the power supervision relay normally open contact in series with an Initiating
Device Circuit (IDC). The four-wire power circuit energizes the power supervision relay. When you reset the system, the control panel
removes power from these terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB10 RESET(+) and (–) to provide up to 1.25 A of current for powering
four-wire smoke detectors. 1.5 A max for special applications.The total current drawn from the power supply by TB2, TB6 through TB9
and TB10 cannot exceed 3.0 A in standby or 6.0 A in an alarm condition. The Control Panel provides a total of 4.4 A of power in standby
and 7.4 A of power in alarm to be shared by all internal circuitry and external provisions (24 V
resettable and non-resettable). See Figure 3.18 above. TB2 (on CPS-24), TB10 and all 4 NACS share a maximum of 3.0 A in standby
and 6.0 A in alarm.
24 VDC Non-resettable Power Circuit The power supply provides one 24 VDC filtered, power-limited, non-resettable power output,
capable of up to 1.25 A. Use this circuit to power devices that require low-noise 24 VDC power (such as annunciator model ACM-24AT
or the transmitter module TM-4).
Connect external field wires to power supply terminals TB10 NONRESET(+)and(–) to provide up to 1.25 A of non-resettable current for
powering external devices such as annunciators. See Figure 3.18 above. TB2 (on CPS-24), TB10 and all 4 NACS share a maximum of
3.0 A in standby and 6.0 A in alarm.
CAUTION:
! DURING SYSTEM RESET, POWER REMAINS AT TERMINALS TB10 NONRESET(+)AND(–).
AMPS24_TB2access.wmf
COM - Black Wire
5V - Red Wire
TB9 - NAC #1
TB8 - NAC #2
TB6 - NAC #4
NOTE: Any NAC can be programmed as a releasing circuit, and the releasing circuit must be supervised; see Figure 4.8–Figure 4.10. For
more information, refer to Section 4 “Applications” in this manual and the NFS2-640/E Programming Manual. Refer to the Device
Compatibility Document for UL-listed compatible releasing devices. Sample connections for NAC terminals are shown in Figure 3.20. Follow
sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part of Step 6.
StatXMultiEOL.wmf
Stat-X
Stat-X
Stat-X
Figure 3.22 Wiring Diagram for Stat-X Devices
FAASTTermBlk.wmf
Installation Considerations:
The following installation factors should be taken into
consideration when installing the FSA-8000 FAAST
detector:
Programming Options:
The following programming options should be set when programming the NFS-320, NFS-320SYS, NFS2-640 and NFS2-
3030 with the FSA-8000:
CPU2-640-relays.wmf
ured as Alarm contacts. Follow instructions in the VeriFire Tools online help.
WARNING: DO NOT ENABLE THE BACKUP OPTION SWITCH FOR ANY OF THE FOUR NOTIFICATION APPLIANCE
! CIRCUITS (NACS) IF THEY ARE USED FOR RELEASING FUNCTIONS!
Backup alarm switches are provided that enable NACs and the alarm relay to activate
during a backup alarm condition. If the main board’s microcontroller fails and an alarm
is reported by any detector or a monitor module that has backup reporting enabled, the
NAC will turn on if the corresponding switch was enabled. The alarm will activate
during microcontroller failure regardless of the settings of switches SW1–SW4.
CPU2-640-
• SW1 - NAC#1
• SW2 - NAC#2
• SW3 - NAC#3
• SW4 - NAC#4
Figure 3.2 Backup Alarm Switches
So, for example, if SW1 and SW4 were enabled at the time of an alarm during micro-
controller failure, NAC#1 and NAC#4 would activate. Follow sequence of steps in Sec-
tion 3.2 “Installation Checklist”, Table 3.1; this is Step 7.
Power-
limited
circuits
Maintain vertical
separation where NPL
circuits appear to
“cross”
NPL
Nonpower-
320-2-640-PWRLMTWIR-
limited
circuits
To cabinet-mounted battery
(nonpower-limited)
NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35mm) between power-limited and non power-limited
circuit wiring. Install tie wraps and adhesive squares to secure the wiring. Use a power-limited source for relay output on terminals TB8-
TB11. Figure 2.2, “CPU2-640/CPU2-640E and Power-Supply: Wiring Connections” on page 13
NOTE: Drawing is not to scale. Proportions and angles are exaggerated to show wire-placement more clearly.
NOTE: If additional knockouts are added to the backbox, proper separation of power-limited and non power-limited wiring should be
maintained.
640tb200.wmf
cpu2-
Figure 3.4 EIA-485 Connections
NOTE: You can also use the EIA-232 printer interface with UL-listed information technology equipment, such as personal
computers, to monitor the control panel for supplementary purposes.
This section contains information on connecting a printer to the control panel and for setting the printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm system configuration (for example, a
Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power
source is not provided, use a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You may use
your building emergency power supply, so long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further
details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB12 terminal block on the control panel as shown in Figure 3.5.
2. Plug the DB-25 or DB-9 connector end of the custom cable into the EIA-232 port of the remote printer. Tighten securely.
DB-25 connector on PRN series printer (female socket shown) DB-9 Connector on PRN series Printer
DB9printer.
Terminate one end of
shield at backbox
CPU2-640-
Control Panel
Control Control
CPU2-640-
Panel Panel
DB-25 connector
on CRT-2
(female socket shown)
Control
nfs640-
Panel
NOTE: This section covers installation only; for information on how the CRT-2 functions as part of the fire alarm system, see
the NFS2-640/E Operations Manual.
NOTE: The CRT cannot be connected at the same time as the network
Note: For wire requirements, see Table B.1 in Appendix B.1 “Electrical Specifications”.
NOTE: To meet the ten-second response time required by UL 864, 9th edition, when SLC loops are configured to run in CLIP mode, all
input modules must be set to address 19 or lower on both loop one and 2. There are no limits to detectors or output modules.
Installation
This control panel supports one or two SLC loops; a second SLC loop is obtained by installing an LEM-320 module. SLC loop #1 con-
nects to TB13 on the control panel; SLC loop #2 connects to TB1 on the LEM-320. For details on designing, installing and configuring
SLC loops, see the SLC Wiring Manual.
SLC B SLC A
nfs640-slcloops.cdr, NFS2640-SLC-TB.wmf,
SLC B (output loop)
NOTE: Download operations that change the basic program of the control panel must be performed by responsible service personnel in
attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72.
Table 4.1
Municipal Box (Auxiliary)
Municipal Box applications require a TM-4 Transmitter module. Refer to the TM-4 Transmitter Module installation document for instal-
lation details.
Power Supervision
Relay (EOLR-1)
(Not required for
FlashScan type codes SLC from FACP
that provide built-in
power supervision.) –
+
Non-resettable 24 +
VDC Power from –
a listed source
Device to be 3030-external-power-
Supervised *If the SLC device
does not match the
N.C. Supervision one in this figure,
Relay Contact refer to the SLC
Part of EOLR-1 FCM-1
(Not required for
manual appendix,
FlashScan type codes which contains wir-
that provide built-in ing conversion
power supervision.) charts for type V and
4.3 NFPA 72 Central or Remote Station Fire Alarm System (Protected Premises Unit)
Figure 4.2 shows typical wiring diagram for a NFPA 72 Central Station Fire Alarm System (Protected Premises Unit) or a Remote Sta-
tion Fire Alarm System (Protected Premises Unit) using the Universal Digital Alarm Communicator/Transmitter (UDACT or UDACT-
2) and control panel. This provides typical wiring only; connect and program the UDACT or UDACT-2 according to the directions given
in the UDACT Instruction Manual or UDACT-2 Instruction Manual.
NOTE: An NFPA 72 Central Station or Remote Station requires 24 hours of standby power and 5 minutes in alarm.
NOTE: This application can also be done with the TM-4 Transmitter; refer to the TM-4 Transmitter Module installation
document for more details.
NOTE: For additional setup information for the UDACT-2, refer to the UDACT-2 Instruction Manual.
Ferrite cores
FACP Cabinet P/N 29090
24 VDC EIA-485
Nonresettable power (ACS Mode)
CPU2-640-
UDACT in ABS-8RB
(shown with cover removed)
Figure 4.2 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3 and 4 if this is the last or only device on EIA-
485 line.
UDACT-2
+24VDC REF ELR
+ 24V
_ {
LED 8
_
POWER
24
COMMON
LED 13
+
LED 14
LED2 LED1
LED 20
_
Rela EIA-+_{ Instruction Manual.
EIA- { • This illustration is show with the
INPUT 5
TRANS TEST POWER
INPUT 4
NCM-W. For other NCM or HS-
CLEAR REPORT RESET
LED4 SW6
NON-ISOLATED
ISOLATED
SW2 SW3 SW4
SW4
INPUT 3
Installation or HS-NCM
ENABLE
INPUT 2
SW3
LED3
TONE DETECT
LED21
TROUBLE SW5
1
INPUT 1
Installation documents.
1
SW1 ON
OPTION ON
SELECT
MR-101/C
FMM-1
EIA-485
_ + _
+
SLC
To
Previous
24V + EF B TERM B EF A TERM A
OFF
OFF
SW101
SW103
SW102
SW100
_
ON
ON
NFS2-640/E
LED101 LED100
J3 J2
A HI B HI
LED6 LED7
NUP2
NUP1
RCDA RCDB
LED4 LED2
STATA STATB
LED3 LED5
NCM-W
RECON PULSE1
LED1 LED8
LCM A
RESET POWER
LCM B
LCM TERM
A A
OFF
ON
SW1
SW2
To Next
EF B TERM B EF A TERM A
OFF
OFF
SW101
SW103
SW102
SW100
ON
ON
NCA-2
LED101 LED100
J3 J2
A HI B HI
LED6 LED7
NUP2
NUP1
RCDA RCDB
LED4 LED2
STATA STATB
LED3 LED5
RECON PULSE1
LED1 LED8
NCM-W
LCM A
RESET POWER
LCM B
LCMTERM
A A
OFF
ON
SW1
SW2
Figure 4.3 Central Station Canadian Requirements for Second Dial-Out Connection
UDACT or
UDACT-2
WARNING:
! Damage can result from incorrect wiring connections.
Connect to
J5 “Security Tamper”
LED7
LED6
LED5
LED4
LED3
LED2
LED1 J6 J5
4.6.4 Programming
The control panel can communicate with any number of security devices. To do so, program the points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code SECURITY.
NOTE: For detailed instruction on programming Type Codes, refer to the NFS2-640/E Programming Manual.
SLC
UL-listed 47K UL-listed, Channel
End-of-Line Resistor normally-open A or B
(provided with module) security switch
*If the SLC device
does not match the
one in this figure,
refer to the SLC
manual appendix,
CPU2-640-
WARNING:
! DO NOT ENABLE THE BACKUP OPTION SWITCH FOR ANY OF THE FOUR NOTIFICATION
APPLIANCE CIRCUITS (NACS) IF THEY ARE USED FOR RELEASING FUNCTIONS!
4.7.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a properly configured system with compati-
ble, listed actuating and initiating devices, this control panel complies with the following NFPA standards for installation in accordance
with the acceptable standard:
Standard Covers
4.7.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate Control Panel releasing outputs and
FCM-1 modules. Program the FCM-1 module for the appropriate type code according to the chart below:
CPU2-640-RELCONN1.wmf
Control
Panel
WARNING:
! DO NOT ENABLE THE BACKUP OPTION SWITCH FOR ANY OF THE FOUR NOTIFICATION
APPLIANCE CIRCUITS (NACS) IF THEY ARE USED FOR RELEASING FUNCTIONS!
1. The control panel provides four NAC/Releasing Circuits (Class A or Class B). Each circuit can provide 1.5 A. Total current drawn
from the power supply cannot exceed 7.4 A in an alarm condition (refer to Table A.2, “System Draw Current Calculations,” on
page 56). Use compatible UL-listed 24 VDC appliances only. For more information on compatible appliances, refer to the Device
Compatibility Document.
2. Refer to the Releasing Applications appendix in the NFS2-640/E Programming Manual for configuration details (such as setting
the Soak Timer).
3. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-2.2K) with control panel releasing circuits. Connect the End-of-Line device as
shown in Figure 4.7.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
4. For applications not requiring power-limited circuits –
a) If the application does not require supervising the releasing device against shorts, in-line supervisory devices (P/N REL-2.2K)
are not required.
b) In non-power-limited applications, program the releasing circuit for Type Code RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit device wiring and any power-limited
circuit wiring.)
5. The releasing circuit must be programmed with a releasing type code listed in the NFS2-640/E Programming Manual.
NOTE: As per UL 864 9th Edition, a supervisory signal must be indicated at the panel whenever a releasing
circuit is physically disconnected. Use a monitor module to monitor dry contacts off the switch. See 4.11.
IQActuatorsa.wmf
IQActuatorsb.wmf
Figure 4.9 Releasing Circuits (Option 2)
IQActuatorsc2010.w
Figure 4.10 Releasing Circuits (Option 3)
)
GasDisconnectMod.w
Monitor Module
Compatible UL-listed
24 VDC releasing device
–
Brow Red *If the SLC device
+ does not match the
one in this figure,
Relconn-
Figure 4.12 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module
Circuit Requirements When connecting a releasing device to the FCM-1 module, note the following:
1. Refer to the Releasing Applications appendix in the NFS2-640/E Programming Manual for configuration details (such as setting
the Soak Timer).
2. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the FCM-1 module. Connect the in-line supervisory device as shown in
Figure 4.12.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits:
a) In-line supervisory devices (P/N REL-47K) are not required; however, the releasing device circuit is not supervised against
shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit device wiring and any power-limited
circuit wiring.
WARNING:
! THE XP6-C IS NOT LISTED FOR RELEASING APPLICATIONS AND CANNOT BE SUBSTITUTED
FOR FCM-1
NOTE: As per UL 864 9th Edition, a supervisory signal must be indicated at the panel whenever a releasing
circuit is physically disconnected. Use a monitor module to monitor dry contacts off the switch. See 4.11.
(-)
(+)
SLC (-)
Module polarities are shown in alarm condition. SLC (+)
All wiring shown is supervised and power-limited.
Compatible UL-listed
24 VDC releasing device.
fcm-1-rel-
One (1) device maximum.
FCM-1-REL
SLC (-)
SLC (+)
Compatible UL-listed
fcm-1-1rel-
24 VDC releasing device.
One (1) device maximum.
FCM-1-REL
NOTE: With firmware version 12.0 or higher ALL new FlashScan Mode SLC releasing applications require the
FCM-1-REL control module. The V-type FCM-1 control module may be used in SLC releasing applications with
firmware version 14.0 or higher. H-type FCM-1 control modules do not support FlashScan Mode releasing
applications with firmware version 14.0 or higher. Use H-type FCM-1 for CLIP mode SLC releasing applications, with
firmware version 12.0 or higher.
Critical Requirements. When connecting a releasing device to the FCM-1-REL module, note the following:
1. See “Power Considerations” on page 52 for information on monitoring 24 VDC power.
2. Do not T-tap or branch a Class A or Class B circuit.
3. Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the
FCM-1-REL.
4. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections.
5. All applications using the FCM-1-REL are power-limited:
1. Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
2. Circuits are supervised against opens and shorts.
6. Refer to the NFS2-640/E Programming Manual for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the NFS2-640/E Programming Manual.
Violet Red
Red
C.
NFS640-
N.C. N.O.
System
Common (–)
Power Supervision
Relay (EOLR-1)
NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.7.3 “Connecting a Releasing Device
to the Control Panel” on page 49. If using FCM-1, see Circuit Requirements for Section 4.7.4, “Connecting a
Releasing Device to the FCM-1 Module”, on page 51. If using the FCM-1-REL, see Circuit Requirements for
Section 4.7.5, “Connecting Releasing Devices to the FCM-1-REL Control Module”, on page 53.
WARNING:
! Do not rely on disable/enable software settings to lockout releasing devices.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.
WARNING:
! Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.
• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes.
Water and household baking soda provides a good neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.
WARNING:
! Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.
No. of
Device Type Current (amps) Total Current
Devices
CPS-24 Power Supply [ 1 ] X 5.0 = 5.0
CPS-24/E Power Supply [ .. ] X 2.5A =
AA-30 [ ] X 1.00 =
AA-120 [ ] X 1.85 =
FCPS-24S6/S8 [ ] X 3.2 =
ACPS-2406 [ ] X 2.7* =
ACPS-610 [ ] X 5.0* =
ACPS-610/E [ ] X 2.5 =
APS-6R [ ] X 2.5 =
CHG-120 [ ] X 2.0 =
Sum column for AC Branch Current required=amps
AC Branch Circuit Installation: For guidelines on wiring the AC branch circuit current, see “Operating Power: AC Branch Circuit” on
page 72 in Appendix B.1 “Electrical Specifications”.
A.2.1 Calculating the Maximum Secondary Power Fire Alarm Current Draw
Use Table A.3 below to determine the maximum current requirements of secondary power source during fire alarm conditions. The
result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.4
to determine the size of the batteries needed for the fire alarm system.
Results taken from Table A.3 below assume that, while in a fire alarm condition, batteries must feed the main power supply (and
any additional supplies such as the APS-6R and AA-30) with the maximum rated power each supply can provide.
Current
Device Quantity Total Current/Type
(in amps)
Alarm Current, from Table A.2, col 2 =
*
APS-6R [ ] X 6 =
APS2-6R [ ] 6 =
AA-30† [ ] X 3 =
AA-120 [ ] X 7.3 =
Sum Column for Secondary Fire Alarm Load =
NOTE: If using an auxiliary power supply such as FCPS-24S6/S8, APS-6R, ACPS-2406, or ACPS-610, or
audio amplifiers, refer to the documentation for that equipment.
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum battery capacity for the CPS-24/E main
power supply is 200 AH. CAB-4 Series backboxes provide space for two 26 AH (or smaller) batteries. Use external battery boxes if the
installation requires larger capacity batteries; see Table A.5, “Selecting Battery and Battery Backbox,” on page 58.
The table below contains battery charger specifications.
Charger Description Specifications
CPS-24/E An internal battery charger for 18 Normal Charge: 27.6 VDC +/- 0.24 VDC
Main Power Supply AH to 200 AH Charging Current: 2.0 A or 5.7 A (Software selectable)
CHG-120 An external battery charger Dual Rate: High Charge: 28.1 VDC
Battery Charger designed to charge lead-acid Normal Charge: 27.6 VDC
batteries between 26 AH and 120 Charging Current: 4.5 A
AH
ACPS-610 An internal battery charger for Normal Charge: 27.6 VDC +/- 0.24 VDC
Addressable 12AH to 200AH Charging Current: 2A, 5A, or OFF (Software Selectable)
Charger/Power Supply
Output Relays
Output relays for Alarm and Trouble are common on TB4; Supervisory and Security are programmable on TB5. See Figure 3.21, “Form-
C Relay Connections” on page 39).
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB10 RESET (+) and (–) supply filtered, low-noise power for four-wire smoke detectors. Specifications are:
• Nominal voltage: 24 VDC special applications.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10, TB2, and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB10 NONRESET (+) and (–) supply one (1) power-limited circuit available to power external devices, such as
notification appliances and annunciators.
• Nominal voltage: 24 VDC regulated, special applications, 1.5 A max.
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
• TB10, TB2, and all 4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm.
Refer to the Device Compatibility Document for compatible devices and notification appliances.
NOTE: The Control Panel provides a total of 7.4 A of power in alarm (4.4 A in standby), shared
by all internal circuitry and external provisions (24 V resettable and non-resettable). TB10 and all
4 NACs share a maximum of 3.0 A in standby and 6.0 A in alarm. For power requirements, refer
to the power supply calculation tables in Appendix A.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the SpectrAlert, SpectrAlert Advanced
or MA/SS-24 Series) instead of more electronically noisy notification appliances (such as
electromechanical bells or horns).
Circuit Distance
Circuit Type Wire Requirements Typical Wire Type
Function (feet/meters)
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 12,500 ft. (3,810 m) 12 AWG (3.31 mm2)
(power limited) intelligent and (3.31 to 0.82 mm2). 50 ohms maximum per 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
addressable length of Class A & X loops. 50 ohms per 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
modules. branch maximum for Class B loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
Twisted, shielded pair 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 to
NOTE: 01.31 mm2)
• Shields must be isolated from ground. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
• Shields should be broken at each
device.
Untwisted, unshielded wire, in conduit or 5,000 ft. (1,524 m) 12 to 16 AWG (3.31 to
outside of conduit. 01.31 mm2)
3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
Note: Maximum total capacitance of all
SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 mircofarads.
EIA-485 Connects to Twisted-shielded pair with a characteristic 6,000/1829 16 AWG (1.31 mm2)
(power limited) FDU-80, ACS impedance of 120 ohms. 18 AWG (0.82 (max)
modules, LCD- mm2) minimum.
80, or TM-4
Transmitter
EIA-232 Connects to Twisted-shielded pair in conduit. 20 feet (6.1 m) 16 AWG (1.31 mm2)
(power limited) Printers, CRT, 18 AWG (0.82 mm2) minimum. (without modem)
or PC.
IDC FMM-1, 12-18 AWG (3.31 to 0.82 mm2). 12 to 18 AWG (3.31 to
Initiating Device FMM-101, Maximum circuit resistance is 20 ohms. 0.82 mm2)
Circuit FDM-1XP10-M,
XP6-MA
(power limited)
NAC FCM-1*, XP6-C 12-18 AWG (3.31 to 0.82 mm2). .To meet 1.2 V drop, 12 to 18 AWG (3.31 to
Notification (power limited) At alarm current level, no more than a 1.2 or sized to provide 0.82 mm2)
Appliance V drop at the end of the circuit, or sized to the minimum rated
Circuit provide the minimum rated operating operating voltage of
voltage of the appliances used. the appliances used.
Releasing FCM-1-REL 12-18 AWG (3.31 to 0.82 mm2). To meet 5 ohms 12 to 18 AWG (3.31 to
Module 5 ohms maximum per circuit for class A or maximum circuit 0.82 mm2)
B, or sized to provide the minimum rated resistance, or sized
operating voltage of the appliances used. to provide the
minimum rated
operating voltage of
the appliances used
24 VDC Power To TM-4 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 volt drop 12 to 18 AWG (3.31 to
Runs Transmitter, Size wire so that no more than 1.2 V drop 0.82 mm2)
(power-limited) Annunciator and across wire run from supply source to end
FCM-1 modules of any branch.
CHG-120 External battery 12 AWG (3.31 mm2) in conduit 20/6.1 (max) 12 AWG (3.31 mm2)
charger
Note: * FCM-1 cannot be used for synchronized strobe/sounder applications.
Stand-Off Lengths 23
Stat-X
Device Wiring 34
STS-1, also see Security Tamper Switch 48
Supervisory and Security Contacts
-Configuring as Alarm Contacts 35
Supervisory Relays, see Form-C Relays 35
Supplemental Documentation 8
Switches
Backup-Alarm 35
Switch Locations 13, 14
System
Description of Features 10
Limitations 10
Options 10
System Current Draws 57, 58, 59, 60
T
Terminal Block Locations 13, 14
Testing 55
TM-4, also see TM-4 Installation Document 28
Trouble Relays, see Form-C Relays 35
U
UL Non-Power-Limited Wiring Requirements 36
UL Requirements 36
V
VeriFire 43
W
Wiring
Proprietary Security Alarm Applications
48
Wire Requirements 62
Warn-HL-08-2009.fm