Model: C1500 D6 Frequency: 60 HZ Fuel Type: Diesel: Generator Set Data Sheet
Model: C1500 D6 Frequency: 60 HZ Fuel Type: Diesel: Generator Set Data Sheet
Model: C1500 D6 Frequency: 60 HZ Fuel Type: Diesel: Generator Set Data Sheet
Model: C1500 D6
Frequency: 60 Hz
Fuel type: Diesel
Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 1545 (1931) 1286 (1608)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 32.8 54.9 77.7 103.6 29.2 47.6 68.0 87.3
L/hr 124 206 294 392 111 180 257 330
Fuel flow
Maximum fuel flow, L/hr 693
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2017 Cummins Inc. | DS85-CPGK (10/17)
Air Standby rating Prime rating
Combustion air, m3/min 125 116
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 301.5 271.8
Exhaust gas temperature, °C 515 470
Maximum exhaust back pressure, kPa 6.7
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2017 Cummins Inc. | DS85-CPGK (10/17)
Alternator data
Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS85-CPGK (10/17)