Model: C1500 D6 Frequency: 60 HZ Fuel Type: Diesel: Generator Set Data Sheet

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 3

Generator set data sheet

Model: C1500 D6
Frequency: 60 Hz
Fuel type: Diesel

Spec sheet: SS16-CPGK


Noise data sheet (open/enclosed): ND60-OSHHP/ND50-CSHHP
Airflow data sheet: AF60-HHP
Derate data sheet (open/enclosed): DD60-OSHHP/DD60-CSHHP
Transient data sheet: RTF

Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 1545 (1931) 1286 (1608)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 32.8 54.9 77.7 103.6 29.2 47.6 68.0 87.3
L/hr 124 206 294 392 111 180 257 330

Engine Standby rating Prime rating


Engine manufacturer Cummins
Engine model KTA50-G9
Configuration Cast iron, 60 º V16 cylinder
Aspiration Turbocharged and after-cooled
Gross engine power output, kWm 1656 1384
BMEP at set rated load, kPa 2221 1835
Bore, mm 159
Stroke, mm 159
Rated speed, rpm 1800
Piston speed, m/s 9.5
Compression ratio 13.9:1
Lube oil capacity, L 152
Overspeed limit, rpm 2070 ±50
Regenerative power, kW 168
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 693
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins.com
©2017 Cummins Inc. | DS85-CPGK (10/17)
Air Standby rating Prime rating
Combustion air, m3/min 125 116
Maximum air cleaner restriction, kPa 6.2

Exhaust
Exhaust gas flow at set rated load, m3/min 301.5 271.8
Exhaust gas temperature, °C 515 470
Maximum exhaust back pressure, kPa 6.7

Standard set-mounted radiator cooling


Ambient design, °C 40
Fan load, kWm 33
Coolant capacity (with radiator), L 501
Cooling system air flow, m3/sec @ 12.7 mm H2O 22.7
Total heat rejection, Btu/min 61830 52220
Maximum cooling air flow static restriction mm H2O 12.7

Weights* Open Enclosed


Unit dry weight kgs 10348 18199
Unit wet weight kgs 10967 18818
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions mm 5811 2033 2330
Enclosed set standard dimensions (with exhaust stack)
12192 2438 2896 (3233)
mm

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

power.cummins.com
©2017 Cummins Inc. | DS85-CPGK (10/17)
Alternator data

Connection Temp rise ºC Duty Alternator Voltage


Wye, 3-phase 150/125 S/P PI734D 380 - 416 V
Wye, 3-phase 125/163 S/P PI734C,D 416 - 480 V
Wye, 3-phase 150/125 S/P PI734D 480 V
Wye, 3-phase 125/105 S/P MVSI804R 4160 V
Wye, 3-phase 125/105 S/P HVSI804R 6600 V
Wye, 3-phase 125/105 S/P HVSI804R 13200 - 13800 V

Ratings definitions

Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS85-CPGK (10/17)

You might also like