You are on page 1of 56
At a glance
Powered by AI
The document provides contact information for various Terasaki company locations around the world and also includes a sample order form for circuit breakers.

Company locations are listed for the UK, Italy, Spain, Sweden, Singapore, Malaysia, Brazil, China and Japan.

The order form requests information about circuit breaker type, voltage, mounting type, over-current release, accessories, testing and more.

TERASAKI (EUROPE) LTD.

 
   
80 Beardmore Way, Clydebank Industrial Estate, Clydebank
Glasgow G81 4HT SCOTLAND (UK)
Telephone: +44 (0) 141 941 9140 / Fax: +44 (0) 141 952 9246
E-mail: [email protected] / http://www.terasaki.com

TERASAKI ITALIA s.r.l.


Via Campania 4/6, 20090 Segrate, Milano, ITALY
Telephone: 39-02-2137574 / Fax: 39-02-26922931
E-mail: [email protected] / http://www.terasaki.it

TERASAKI ESPANA,S.A.U.
Roma Street, s/n 08400 Granollers, Bacelona, SPAIN
Telephone: 34-93-879-60-50 / Fax: 34-93-870-39-05
E-mail: [email protected] / http://www.terasaki.es

TERASAKI SKANDINAVISKA AB
Frasarvagan 32, 14250 Skogas,SWEDEN
Telephone: 46-8-556-282-30 / Fax: 46-8-556-282-39
E-mail: [email protected] / http://www.terasaki.se

TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.


9 Toh Guan Road East 03-01 Alliance Building, SINGAPORE 608604
Telephone: 65-6744-9752 / Fax: 65-6748-7592
E-mail: [email protected]

TERASAKI ELECTRIC (M) SDN, BHD.


Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul Ehsan, MALAYSIA
Telephone: 60-3-5549-3820 / Fax: 60-3-5549-3960
E-mail: [email protected]

TERASAKI DO BRASIL LTDA.


Rua Cordovil, 259-Parada De Lucas, 21250-450 Rio De Janeiro-R.J. BRAZIL
Telephone: 55-213301-9898 / Fax: 55-21-3301-9861
E-mail: [email protected] / http://www.terasaki.com.br

TERASAKI ELECTRIC (CHINA) LIMITED


72 Pacific Industrial Park, Xingtang Zengcheng, Guangzhou 511340,CHINA

ACB
Telephone: +44 (0) 141 941 9140 / Fax: +44 (0) 141 952 9246
E-mail: [email protected]

ELECTRIC CO. LTD.


Head Office: 7-2-10 Hannancho, Abenoku, Osaka, JAPAN
Circuit Breaker Division: 7-2-10 Kamihigashi, Hiranoku, Osaka, JAPAN
Telephone: 81-6-6791-9323 / Fax: 81-6-6791-9274
E-mail: [email protected] / http://www,terasaki.co.jp
- for your PROTECTION
Sept 2003 Ref No. 03-I55E
Ratings and specifications in this catalogue may be subject to change without notice
;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@


@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
World Class Air Circuit Breakers

@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
Terasaki’s TemPower2 Contents
A.C.B is the result of
1. Features ...................................................2
an intensive market
2. Appearance and Internal Construction ...11
r e s e a rch p ro g r a m 3. Ratings ...................................................12

@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
which took into ac- 4. Specifications .........................................14
count the require- zTypes of Mounting ...............................15
xAccessories for Draw-out Type ...........16
ments of switchboard
cSpring Charged Operation ..................18
builders, consultants

@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
vAccessories for Spring
and end users. Charged Operation .............................20
TemPower2 Air Circuit bTrip Devices ........................................21
Breaker is one of the nOver-current Releases ........................23
mOther Accessories ..............................38

@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
smallest in the market
,Operation Environments .....................45
with a 1 second rating 5. Outline Dimensions ................................46
(Icw). 6. Circuit Diagram .......................................56
öBased Standards
JIS C8372 ................................................. Japanese Industrial Standard 7. Technical Data ........................................60
(New JIS C8201-2 is

@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;
8. Order Forms ...........................................62
also supported)
IEC60947-2 ............................................... International Electrotechnical Commission
EN60947-2 ................................................ European Standard
AS 3947-2 ................................................. Australian Standard
NEMA PUB NO.SG3 ................................. National Electrical Manufacturers Association
ANSI C37.13 ............................................. American National Standard Institute

öCertification and
Authorization
ASTA, UK .................................................. ASTA Certification Services
NK, Japan ................................................. Nippon Kaiji Kyokai
LR, UK ...................................................... Lloyd's Register of Shipping
ABS, USA ................................................. American Bureau of Shipping
GL, Germany ............................................ Germanischer Lloyd
BV, France ................................................. Bureau Veritas

1
1 Features
The ultimate in compactness and operational capability
Geared toward the smallest depth in the world
TemPower2
Direct connection of the
isolating main contacts to TemPower
the hinges of the fixed
main contacts eliminates
the need for intermediate
conductors. Allowing the

Saved space
TemPower2 ACBs have
the world’s smallest depth
resulting in space saving
in switchboards.

More than twenty design


patents have been regis-
tered for the TemPower2
ACB.

345
458

The height and depth dimensions are identical in all sizes to 3200A. There are two common widths or frame
size, from 800-2000A and from 2500-3200A for the standard series. The panel cutout size is the same for all
types of TemPower2, which makes it easy to arrange the ACBs in switchboards.
Maximum power from minimum volume was central to the design specification. With a depth of 290mm for
the fixed type and 345mm for draw-out, it is one of the smallest ACBs in the world.
ACBs with front connections are available off-the-shelf.
Front connections are especially suitable for smaller-depth switchboards.

H: 460

D: 345 D: 375

W: 354 W: 460 W: 631


Standard series 800-2000A 2500-3200A 4000A
High fault series 1250-2000A 1600-3200A

2
Increased accessibility from the front
It enhances ease of installation, operation, and maintenance.

Connection to the main circuit


(for front connections)
Connection to the control circuit

Replacement of internal parts


(Removing the front cover enables
replacement of internal parts.)

The double insulated design Manual operation


ensures that most accesso-
ries can be safely and easily,
installed by the user. Control,
auxiliary and position switch
terminals are mounted at the
front on the ACB body for easy
access. Horizontal, vertical Breaker fixing bolt
and front terminal connec- (optional)
tions, can also be changed by
the user for any last minute
alterations. Due to the in-
creased level of harmonics
within the distribution network, Draw-out operation
the neutral phase is fully rated
as standard.

No extra arc space required, Replacement of


vertical stacking permitted the main contacts
The fixed and moving main contacts can
No extra arc space required
easily be replaced in the field, thus prolong-
ing the life on the circuit breaker. Changing
The TemPower2 ACB dissi- each pole takes around 15 minutes.
pates all arc energy within
its unique “DoubleBreak”
arc chamber. The internal
energy dissipation within the
ACB allows the clearance
distance of the ACB to
nearby earthed metal to be
zero. This will assist in mini-
mizing switchboard height
and costs.

3
1 Features
A high performance and reliability
Very fast interruption by
“DoubleBreak” system
The unique “DoubleBreak” main contact sys-
tem ensures extremely fast interruption of
short circuit currents and substantially re-
duces main contact wear. The internally sym-
metrical “DoubleBreak” structure allows re-
verse power connection.

No clamp screws used


Isolating main contact
for the main circuit
contact units
There are no clamp screws or flexible leads
in the main circuit contact units. Fixed main contact
This substantially enhances the durability of
the main circuit contact units and improves
Moving main contact
the reliability in ON-OFF operation.

Main circuit contact units

Contactless closing/tripping operation circuitry using the AGR2.


When the AGR2 OCR is used, the closing/tripping operation circuits of the TemPower2 series are
contactless and free of the possibility of poor conduction or contact, thereby
remarkably increasing the reliability in operation.

4
Enhanced selectivity L Long time delay
S Short time delay
I Instantaneous

At Terasaki we are so con-


cerned about selectivity that all
our protection relays have ‘LSI’
characteristics as standard.

This provides an adjustable time


delay on overload (L) and also the
l2t ramp characteristic (S).

As shown, these are essential to


provide selectivity when grading
with other protective devices such
as downstream fuses and up-
stream relays.

The standard ‘LSI’ curve provides


more than five million combinations of unique time current characteristics.
Zone selective interlocking is available to provide zero time delay selectivity.

As the rated breaking capacity is identical to the rated short-time withstand current full selectivity can be
achieved. Type and rated current AR208S 800A AR212H 1250A AR325S 2500A AR316H 1600A AR440S 4000A
AR212S 1250A AR216H 1600A AR332S 3200A AR320H 2000A
AR216S 1600A AR220H 2000A AR325H 2500A
Performance AR220S 2000A AR332H 3200A
Rated breaking With INST trip function
current
(at AC440V) With ST delay trip function 65kA 80kA 85kA 100kA 100kA
(Without INST trip/MCR functions)

Rated short-time withstand current (for 1 sec.)

A substantial improvement in life cycles


The TemPower2 series achieved very high life cycles compared with our existing series.
More than
30,000 cycles
More than
25,000 cycles
More than
20,000 cycles
More than
15,000 cycles
800A
More than
2000A 2500A 10,000 cycles
1600A
More than
3200A 5,000 cycles
4000A 630A
2500A 3200A
4000A
Exsisting series
Note: aboves are the mechanical endurance with maintenance. For details please refer to pages 12 & 13.

5
1 Features
TemPower2 provides positive protection for electric power systems. For general feeder circuits (L-characteristic)
For general feeder circuits (R-characteristic)
The TemPower2 series is equipped with an RMS sensing over-current
For generator protection (S-characteristic)
release (OCR) having a wide range of protection functions and capabilities.

Two channel pre-trip alarm Advanced L.C.D. display, Over


function (S-characteristic) ¶1 Current Relay: type AGR-22
This function can be used to monitor and switch on additional The AGR-22 OCR comes standard with an LCD display. It can
power backup to feed critical circuits. For example, the function monitor and indicate phase currents, voltages, power, energy,
can be set so that when a pre-trip alarm is activated, an emer- power factor, frequency, and more. Fault Analysis and mainte-
gency generator starts to ensure a constant supply. This fea- nance information can also be displayed. For features refer page
ture is only available on some AGR21/22 OCR models with a 27.
generator “S” characteristic - refer features table pages 28-29.

Remote Communications
N-phase protection Protocols (optional) ¶1
function (optional) This function supports LONTALK® and Modbus protocol. Also
In 3-phase, 4-wire systems that contain harmonic distortion, we can cope with PROFIBUS, DeviceNet and the other open
the 3rd harmonic may cause large currents to flow through the network. (LONTALK® is a registered trademark of the Echelon
neutral conductor. The N-phase protection function prevents Corporation)
the neutral conductor from sustaining damage or burnout due Energy Measurement
to these large currents. Available in all OCRs except for gen- I, V, kW, MWh, kVar, cosø, frequency
erator “S” characteristic types. Intelligent Fault Analysis
Status, fault type, fault size, tripping time, fault history
Maintenance Information
Trip circuit supervision, protection relay supervision, contact
Earth leakage trip
temperature measurement.
function (L/R-characteristic) ¶1 For details please refer to page 10.
Used in conjunction with an externally mounted Zero phase For other protocols please contact terasaki.
Current Transformer (ZCT), this function provides protection
against leakage to earth of very small levels of current. Trip or
Standard OCR with adjustment Enhanced OCR with adjustment Enhanced OCR with L.C.D.
dial Type AGR-11. dial Type AGR-21. display Type AGR-22.
alarm indication, and contact output is available to enhance Contact temperature
the level of system protection. Available using general purpose
monitoring function (optional) ¶2
L / R -characteristic AGR21/22 OCRs - refer features tables
pages 28-29. This function monitors the temperature of the ACBs main con-

Overload protection Reverse power trip function tacts. An alarm indicates when the temperature exceeds 155°C.
Continuous monitoring of the contact temperature provides
(S-characteristic) ¶1

(The first-ever feature for ACBs) Adjustable undervoltage valuable input for preventative and predictive maintenance pro-
Adjustable from 40–100% of rated current. True r.m.s detec- grams.
tion up to the 19th harmonic, a distant vision for the competi- This feature provides additional protection when paralleling
trip function UVT ¶1
¶1: Not available for standard OCRs, type AGR-11.
tion who rarely see past the 7th. Neutral protection for all those generators. The AGR21/22 OCR for generator protection with Available as a fixed type, or with adjustable voltage pick up and ¶2: Available for type AGR-21 OCR only.
Triple-N harmonics, such as 3rd, 9th and 15th. Also in case we the reverse power trip function, negates the need for installa- an adjustable time delay. 3 Phase, Phase failure protection is
forgot to mention, a “thermal memory” as standard! tion and wiring in an external reverse power relay. This feature also available. AGR11/21/22 OCR’s - refer features table pages
is available using an AGR2 OCR with a generator “S” type char- 28-29.
acteristic only.

6 7
1 Features
Optimum protective
coordination
Why use a separate panel mounted protection relay when
you can have all the benefits of I.D.M.T. protection integral to
the ACB?

TemPower2 is available with a choice of flexible protection curves


to assist in selectivity applications.

I0.02t
S.I. Standard Inverse
It
V.I. Very Inverse
E.I. Extremely Inverse I2t = S.I.

I3t = V.I.
All these curves are user definable and comply with IEC 60255-3.
Standard transformer and generator protection characteristics are I4t = E.I.
also available.

Inverse Definite Minimum Time (I.D.M.T.)


AGR-L Industrial & transformer protection
AGR-S Generator protection
AGR-R Characteristics to IEC 60255-3

Operation panel
available for centralised
indication and control
The TemPower2 operation panel provides a lower
cost alternative to the P.C. based system.

Incorporating a dual LED display, the informa-


tion gathered by the AGR-21 intelligent protec-
tion relay can be displayed.

The operation panel can also provide the op-


tion of remote closing and opening ACB opera-
tion.

Up to eight TemPower2 ACBs can be connected


to one operation panel.

(See page 38 for details).

8
Meeting customer
requirements
TemPower2 provides solutions to satisfy customer needs.

SWITCHBOARD BUILDER
• Compact size for high packing density
• No extra arc space required for clearance
• Low temperature dissipation
• Built in trip supervision circuit
• Fully rated neutral as standard
• Terminal connections and accessories are field changeable
• Uniform panel cut out size

CONSULTANT
• Time Current Characteristics to IEC 60255-3
• Standard, Very and Extremely Inverse curves available
• Restricted and Unrestricted ground fault protection in one relay
• LSI characteristic curves as standard
• True r.m.s. protection
• Sophisticated undervoltage/phase failure protection
• Integral reverse power protection and load shedding relay

END USER
• Self checking protection relay and tripping coil
• Built in relay tester - can check on line without tripping ACB
• Percentage contact wear indicator
• Contact temperature monitoring
• Fault diagnosis - type of fault, magnitude, tripping time & trip
history
• High making capacity for operator safety
• Communication via B.M.S. or S.C.A.D.A. system
• Main contacts can be changed within around 15 minutes per
pole

9
1 Features
Communication facility
added to TemPower2
TemPower2 is equipped with a communication interface
unit that allows data exchange with a host PC via a
Modbus or LONWORKS® open network. Data communi-
cated includes measurements, fault log, maintenance in-
formation, ON/OFF status, settings, and control (ON/
OFF/RESET) signals.

Fault log
Cause Whichever trip functions, LTD, STD, INST,
or GF is activated is then transmitted. Communication interface unit
Fault current The fault current at which the breaker tripped
open is transmitted.
Trip pickup time The trip pickup time is transmitted. Data measurement
Phase current The phase current I1, I2, I3, IN, IG and max
current Imax are measured and transmitted.
Maintenance information Line-to-line voltage V12, V23 and V31 are measured.
Tripping circuit The tripping coil is always monitored for Active power The three-phase power, reverse power and max
monitoring disconnection. If the breaker is not open within power are measured.
approx. 300 ms of a trip signal delivered from
Reactive power The reactive power is measured.
the OCR, an alarm signal is generated.
Effective electric energy The three-phase electric energy is measured.
Overcurrent release A self-diagnostic function always monitors the
(OCR) monitoring CPU and peripheral circuits for normal Power factor The circuit power factor is measured.
operation. Frequency The frequency is measured.

Network interface I/O specifications


Item Modbus LONWORKS®
Transmission standard RS-485 Echelon FTT-10A
Transmission method Two-wire half-duplex, Four-wire full-duplex Two-wire half-duplex
Topology Multi-drop bus Free topology
Transmission rate 115.2 kbps max 78.1 kbps
Transmission distance 1.2 km max (at 57.6 kbps) 500 m max, 400 m max between nodes
Data format Modbus-RTU or ASCII Conforming to LONTALK® protocol
Max number of nodes 1 - 247 (provided that a repeater is used every 32 nodes) Service pushbutton switch used (32,768 nodes max)

Communication network

Host PC

On-screen PC monitor
Host network
Power Monitoring

Next page

TR 3ø750kVA
Print
6600/460V Commercial gateway or PLC
Fault cause OCR status Long time-delay
Short time-delay ACB No.1 ON FTT-10A
Instantaneous I1 729 A
Ground fault V12 455 V
Fault current A
Power factor 95 % RS485
Power 546 kW
ACB Tripping time sec. Electric energy 1041 kWh

ON ON ON OFF ON

320 A 206 A 180 A 0 A 23 A


418 KWh 364 KWh 235 KWh 13 KWh 11 KWh

Power supply No. 1 Power supply No. 2 Power supply No. 3 Pump Conveyer
Modbus LONWORKS®
Up to 31 units can be Up to 60 units can be
connected per system connected per system

10
2 Appearance and
Internal Construction
Appearance
Position switch terminals
Auxiliary switch terminals
Control circuit terminals
ON-OFF Cycle Counter Draw-out cradle

ON-OFF indicator

Spring charge indicator


Over-current release

OFF button Spring charging handle

Breaker fixing bolts ON button

Key lock location


Draw-out handle insertion hole

Position padlock Position indicator

Internal Construction

Control circuit terminals


Main circuit terminal
Charging motor
Isolating main contact
Closing coil

Fixed main contact

Moving main contact


Closing spring

Measuring CT
Arc chamber

Closing mechanism

Moulded insulating cover Power CT

Draw-out arm

11
3 Ratings
Standard Series
AMPERE RATING(A) 800 1250 1600 2000 2500 3200 4000
TYPE AR208S AR212S AR216S AR220S AR325S AR332S AR440S
RATED CURRENT (max) [In](A) IEC, EN, AS 800 1250 1600 2000 2500 3200 4000
q w JIS 800 1250 1600 2000 2500 3200 3700
NEMA, ANSI 800 1250 1540 2000 2500 3200 3700
Marine 800 1250 1600 2000 2500 3200 4000
NEUTRAL POLE AMPERES FRAME (A) 800 1250 1600 2000 2500 3200 4000
NUMBER OF POLES e r 3 4 3 4 3 43 4 3 4 3 4 3 4
RATED PRIMARY CURRENT OF OVER–CURRENT 200 400 400 400 2500 3200 4000
RELEASE [ICT](A) 400 800 800 800
• for general feeder circuit use 800 1250 1250 1250
1600 1600
2000
RATED CURRENT OF OVER–CURRENT RELEASE (A) 100ÖInÖ200 200ÖInÖ400 200ÖInÖ400 200ÖInÖ400 1250ÖInÖ2500 1600ÖInÖ3200 2000ÖInÖ4000
• for generator protection use 200ÉInÖ400 400ÉInÖ800 400ÉInÖ800 400ÉInÖ800
[In] is generator rated current. 400ÉInÖ800 630ÉInÖ1250 630ÉInÖ1250 630ÉInÖ1250
800ÉInÖ1600 800ÉInÖ1600
1000ÉInÖ2000
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) t 1000 1000 1000 1000 1000 1000 1000
RATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) y 690 690 690 690 690 690 690
AC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]
IEC,EN,AS AC 690V u 50/105 50/105 50/105 50/105 65/143 65/143 75/165
[Ics = Icu] 440V 65/143 i 65/143 i 65/143 i 65/143 i 85/187 i 85/187 i 100/220
NEMA AC 600V 42/96.6 42/96.6 42/96.6 42/96.6 50/115 50/115 65/149.5
ANSI 480V 50/115 50/115 50/115 50/115 65/149.5 65/149.5 75/172.5
240V 65/149.5 65/149.5 65/149.5 65/149.5 85/195.5 85/195.5 100/230
JIS AC 550V 50/105 50/105 50/105 50/105 65/143 65/143 75/165
460V 65/143 65/143 65/143 65/143 85/195.5 85/195.5 100/230
220V 65/143 65/143 65/143 65/143 85/195.5 85/195.5 100/230
o DC 600V !0 40/40 40/40 40/40 40/40 40/40 40/40 40/40
250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40
NK !2 AC 690V 50/115 50/115 50/115 50/115 65/153 65/153 75/179
450V 65/153 i 65/153 i 65/153 i 65/153 i 85/201 i 85/201 i 100/245
LR, AB, !2 AC 690V 50/115 50/115 50/115 50/115 65/153 65/153 75/179
GL, BV 450V 65/153 i 65/153 i 65/153 i 65/153 i 85/201 i 85/201 i 100/245

RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV) 12 12 12 12 12 12 12


RATED SHORT TIME WITHSTAND 1s 65 65 65 65 85 85 100
CURRENT[Icw][kA rms] 3s 50 50 50 50 65 65 85
LATCHING CURRENT (kA) 65 65 65 65 85 85 100
TOTAL BREAKING TIME (s) 0.03 0.03 0.03 0.03 0.03 0.03 0.03
CLOSING OPERATION TIME
SPRING CHARGING TIME (s) max. 10 10 10 10 10 10 10
CLOSE TIME (s) max. 0.08 0.08 0.08 0.08 0.08 0.08 0.08
No. of operating cycles
Mechanical life with maintenance 30000 30000 30000 25000 20000 20000 15000
without maintenance 15000 15000 15000 12000 10000 10000 8000
Electrical life without maintenance AC460V 12000 12000 12000 10000 7000 7000 5000
AC690V 10000 10000 10000 7000 5000 5000 2500
WEIGHT (kg) draw-out type 73 86 73 86 76 90 79 94 105 125 105 125 139 176
OUTLINE DIMENSION (mm)
FIXED TYPE a 360 445 360 445 360 445 360 445 466 586 466 586 — —
b b 460 460 460 460 460 460 —
c 290 290 290 290 290 290 —
a c d d 75 75 75 75 75 75 —
DRAW-OUT a 354 439 354 439 354 439 354 439 460 580 460 580 631 801
TYPE !3 b b 460 460 460 460 460 460 460
c 345 345 345 345 345 345 375
a c d d 40 40 40 40 40 40 53

q : Values in open air at 40°C (45°C for marine applications). y : Rated operational voltage depends on applied standard: 690V
w : Values of AR208S ~ 216S for draw-out type with horizontal terminals, according to IEC 60947-2 and JIS C8201-2.
Values of AR220S ~ 440S for draw-out type with vertical terminals. u : Cannot apply IT earthing system, ie, insulated from earth.
e : For 2poles use both opposite ends poles of 3poles ACBs. i : For 500V AC.
r : 4poles ACBs without Neutral phase protection can not be applied to o : Please contact TERASAKI for DC application.
IT earthing systems. !0 : 3poles in series should be applied for 600V DC.
t : Rated insulation voltage depends on applied standard: 1000V AC !2 : Applicable to only 3poles ACBs.
according to IEC 60947-2 and JIS C8201-2. !3 : For vertical terminals or horizontal terminals.

¶1 : Please refer to catalogue No. I52E for 5000 & 6300 amperes frame ACB’s.

12
High Fault Series
AMPERE RATING(A) 1250 1600 2000 1600 2000 2500 3200
TYPE AR212H AR216H AR220H
AR316H AR320H AR325H AR332H
RATED CURRENT (max) [In](A) IEC, EN, AS 1250 1600 2000 1600 2000 2500 3200
q w JIS 1250 1600 2000 1600 2000 2500 3200
NEMA, ANSI 1250 1600 2000 1600 2000 2500 3200
Marine 1250 1600 2000 1600 2000 2500 3200
NEUTRAL POLE AMPERES FRAME (A) 1250 1600 2000 1600 2000 2500 3200
NUMBER OF POLES e r 3 4 3 4 3 3 4 4 3 4 3 4 3 4
RATED PRIMARY CURRENT OF OVER–CURRENT 200 1600 2000 200 2000 2500 3200
RELEASE [ICT](A) 400 400
• for general feeder circuit use 800 800
1250 1250
1600
RATED CURRENT OF OVER–CURRENT RELEASE (A) 100ÖInÖ200 800ÖInÖ1600 1000ÖInÖ2000 100ÖInÖ200 1000ÖInÖ2000 1250ÖInÖ2500 1600ÖInÖ3200
• for generator protection use 200ÉInÖ400 200ÉInÖ400
[In] is generator rated current. 400ÉInÖ800 400ÉInÖ800
630ÉInÖ1250 630ÉInÖ1250
800ÉInÖ1600
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) t 1000 1000 1000 1000 1000 1000 1000
RATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) y 690 690 690 690 690 690 690
AC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]¶2
IEC,EN,AS AC 690V u 55/121 55/121 55/121 85/187 85/187 85/187 85/187
[Ics = Icu] 440V 80/176 80/176 80/176 100/220 100/220 100/220 100/220
NEMA AC 600V 42/96.6 42/96.6 42/96.6 50/115 50/115 50/115 50/115
ANSI 480V 65/149.5 65/149.5 65/149.5 80/184 80/184 80/184 80/184
240V 80/184 80/184 80/184 100/230 100/230 100/230 100/230
JIS AC 550V 55/121 55/121 55/121 85/196 85/196 85/196 85/196
460V 80/176 80/176 80/176 100/230 100/230 100/230 100/230
220V 80/176 80/176 80/176 100/230 100/230 100/230 100/230
o DC 600V !0 40/40 40/40 40/40 40/40 40/40 40/40 40/40
250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40
NK !1 !2 AC 690V 55/128 55/128 55/128 85/201 85/201 85/201 85/201
450V 80/186 80/186 80/186 100/233 100/233 100/233 100/233
LR, AB, !1 !2 AC 690V 55/128 55/128 55/128 85/201 85/201 85/201 85/201
GL, BV 450V 80/186 80/186 80/186 100/233 100/233 100/233 100/233

RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV) 12 12 12 12 12 12 12


RATED SHORT TIME WITHSTAND 1s 80 80 80 100 100 100 100
CURRENT[Icw][kA rms] 3s 55 55 55 75 75 75 75
LATCHING CURRENT (kA) 65 65 65 85 85 85 85
TOTAL BREAKING TIME (s) 0.03 0.03 0.03 0.03 0.03 0.03 0.03
CLOSING OPERATION TIME
SPRING CHARGING TIME (s) max. 10 10 10 10 10 10 10
CLOSE TIME (s) max. 0.08 0.08 0.08 0.08 0.08 0.08 0.08
No. of operating cycles
Mechanical life with maintenance 30000 30000 30000 25000 20000 20000 20000
without maintenance 15000 15000 15000 12000 10000 10000 10000
Electrical life without maintenance AC460V 12000 12000 12000 10000 7000 7000 7000
AC690V 10000 10000 10000 7000 5000 5000 5000
WEIGHT (kg) draw-out type 79 94 79 94 79 94 105 125 105 125 105 125 105 125
OUTLINE DIMENSION (mm)
DRAW-OUT a 354 439 354 439 354 439 460 580 460 580 460 580 460 580
TYPE !3 b b 460 460 460 460 460 460 460
c 345 345 345 345 345 345 345
a c d d 40 40 40 40 40 40 40

q : Values in open air at 40°C (45°C for marine applications). y : Rated operational voltage depends on applied standard: 690V
w : Values for draw-out type with vertical terminals. according to IEC 60947-2 and JIS C8201-2.
e : For 2poles use both opposite ends poles of 3poles ACBs. u : Contact TERASAKI for details.
r : 4poles ACBs without Neutral phase protection can not be applied to o : Please contact TERASAKI for DC application.
IT earthing systems. !0 : 3poles in series should be applied for 600V DC.
t : Rated insulation voltage depends on applied standard: 1000V AC !1 : Will apply soon.
according to IEC 60947-2 and JIS C8201-2. !2 : Applicable to only 3poles ACBs.
!3 : For vertical terminals.

¶1 : Please refer to catalogue No. I52E for 5000 & 6300 amperes frame ACB’s.
¶2 : When the ACB is used without Instantaneous trip function MCR should be set to work. The rated breaking capacity will reduce to the level of the latching current
without MCR function.

13
4 Specifications
TemPower2 series ACBs have an extensive range of accessories available,
enabling the ACBs to be “custom built” to suit every application.
ACB type Standard Series AR208S AR212S AR216S AR220S AR325S AR332S AR440S
High fault Series AR212H AR216H AR220H AR316H AR320H AR325H AR332H

3-poles 4-poles Main circuit safety shutters (See P. 16)


Control circuit safety shutter (See P. 16)
Position switches (See P. 17)
Test jumper (See P. 16)
Type of mounting (Note 5) Fixed type Draw-out type
Mal-insertion prevention device (See P.16)
Breaker fixing bolts (See P. 16)
Door interlock (See P. 17)
(Note 6) Vertical terminals Horizontal terminals Front connections Lifting plate (See P.43)
Inter-pole barrier (Note 1) (See P. 44)
Control circuit tab terminals Control circuit screw terminals Automatic closing
spring release (See P. 20)
Earthing device (See P. 44)

Spring charged operation Manual charging Motor charging

Over-current release (OCR) For general feeder circuit (L, R) For generator protection (S)

Enhanced O.C.R. Type AGR-21,22 Standard O.C.R. Type AGR-11


With Long time-delay, Short time-delay, INST/MCR trip

Pre-trip alarm, 1-channel (See P. 24) Pre-trip alarm, 1-channel (See P. 24)
Pre-trip alarm, 2-channel (See P. 24) Ground fault trip (See P. 24)
Ground fault trip (See P. 24) Spring charge indicator (See P. 20)
Operation indication Operation indication
Earth leakage trip (See P. 24) Trip indicator (See P.26)
(via individual contacts) (via single contact)
Reverse power trip (See P. 24) Field test N-phase protection (Note2) (See P.24)
Adjustable type Under voltage trip (See P. 25) Fixed type Under voltage trip (See P. 22)
Spring charge indicator (See P. 20) CT for neutral line (Note 3) (See P. 39)
Trip indicator (See P. 26) OCR checker (See P. 39)
N-phase protection (Note2) (See P. 24)
Contact temperature monitoring function (See P.25)
Operation panel (See P. 38)
Auxiliary switches with 4c contacts arrangement (standard) Auxiliary switch assembly (Max.10c)
Communication function ¶ (See P. 10) (Note 4) (See P. 40)
CT for neutral line (Note 3) (See P. 39) Door flange (See P. 43) Mechanical interlock ¶(See P. 42)
OCR checker (See P. 39) Key lock (See P. 41) ON-OFF cycle counter (See P. 40)
Manual reset device ¶ (See P. 40) Key interlock (See P. 41) Control circuit terminal cover (See P. 43)
Continuous-rated shunt trip device (See P. 21) IP cover (See P. 44)
Capacitor trip device (See P. 21)
OFF Padlock (See P. 44)
Tropicalization (See P. 45)
Normal environment Special environment Cold climate treatment (See P. 45)
Anti-corrosion treatment (See P. 45)

TemPower2 suited to your application


Note 1: Not applicable to ACBs equipped with front connections or Note 4: Microload switch assembly with 3c arrangement available.
reverse power trip device. Note 5: Fixed type is not available for High fault series.
Note 2: Applicable to 4-pole ACBs. Note 6: Vertical terminal is standard and horizontal terminal is optional for High
Note 3: Required for ground fault protection for 3-poles ACB on 3-phase, fault series. Front connection is not available for High fault series.
4-wire systems. ¶: Contact Terasaki for details.

14
1 Types of Mounting
Draw-out type Fixed type (standard series only)
This type of ACB consists of a breaker body and a draw-out This type of ACB has no draw-out cradle and is designed to be
cradle. The breaker body can be moved within or removed directly mounted in the switchboard.
from the draw-out cradle that is fixed in the switchboard.
There are four breaker body positions: CONNECTED, TEST, Connection methods
ISOLATED, and WITHDRAWN. The switchboard panel door °Main circuit terminals
can be kept closed in the CONNECTED, TEST, and ISOLATED
Three(3) types of main circuit terminal arrangements are avail-
positions (“shut-in three positions”).
able: vertical terminals, horizontal terminals, and front connec-
tions. Different types of terminal arrangements can be speci-
fied for the line and load sides. Unless otherwise specified by
the user, horizontal terminals are given to types AR208S,
z CONNECTED position
AR212S and AR216S ACBs on both the line and load sides,
and vertical terminals to AR220S, AR235S, AR332S and AR
Position indicator
TEST
440S. For AR440S, only vertical terminals available. For High
ISOLATED CONN RELEASE
BUTTON
fault series, vertical terminals are standard and horizontal ter-
minals are optional, and front connections are not available.

Both the main and control circuits are connected for


normal service.

x TEST position

Position indicator
£Horizontal terminals
ISOLATED TEST CONN RELEASE
BUTTON

The main circuit is isolated and the control circuits are


connected. This position permits operation tests without the
need for opening the switchboard panel door. £Front connections

c ISOLATED position
£Vertical terminals

Position indicator °Control circuit terminals


ISOLATED TEST CONN RELEASE
BUTTON
Control circuit terminals are front located to allow easy wiring/
access.
• The terminal blocks (for auxiliary switches, position switches,
and control circuits) are positioned on the top of the ACB front
Both the main and control circuits are isolated. panel and can be accessed from the front for wiring.
The switchboard panel door does not need to be opened.
• 0.5 mm-thick tab terminals (#187) are used. Receptacle ter-
v WITHDRAWN position minals fully insulated with #187 insulation sleeve are required.
M4 screw terminals are also available.

The breaker body is fully withdrawn from the draw-out


cradle.
£Tab terminals £Screw terminals

15
4 Specifications
2 Accessories for Draw-out Type ¶: Standard equipment

Main circuit safety shutters Control circuit safety shutter Breaker fixing bolts
The main circuit safety shutters auto- The control circuit safety shutter covers The breaker fixing bolts hold the breaker
matically conceal the main circuit con- the control circuit contacts, ensuring body securely to the draw-out cradle in
tacts on the draw-out cradle when the safety. position. Use them if the ACB is subject
ACB is drawn out. to strong vibration.
• The top and bottom shutters operate
independently and can be separately
padlocked in the closed position.
• Up to three padlocks (with ø6 hasp)
can be installed on each side using
padlocking unit. (Padlock not supplied)
• In the closed position, the shutters are
locked to the extent that they cannot Test jumper Position padlock lever ¶
be easily unlocked by hand. They can
be unlocked and held open if required The test jumper is a plug-in type, and Using the position padlock lever pre-
for the purpose of inspection or main- allows ON-OFF tests on all the vents the breaker body from inadvert-
tenance. TemPower2 series ACBs with the breaker ently being drawn out. The position pad-
body drawn out from the draw-out lock lever in the pulled-out position locks
cradle. the breaker body in the CONNECTED,
The standard jumper cable is 5 m long. TEST, or ISOLATED position. Up to
three padlocks (with ø6 hasp) can be in-
stalled.

Lifter Mal-insertion prevention device

A special lifter is available to allow easy Interchangeability exists within the


and safe transportation or installation of TemPower2 series of ACBs. Because of
the ACB. A drop prevention mechanism this feature, there is a possibility for an
ACB
is standard. ACB of a different specification being
Loader
placed into the draw-out cradle. Using
2300

the mal-insertion prevention device


ACB mounting position
¶190Max.
eliminates such a possibility.
ACB front panel
Grip This device is capable of distinguishing
nine different breaker bodies.
Winch handle
Please specify the Code 1A, 1B, 1C, 2A,
2B, 2C, 3A, 3B, 3C for each ACB.
95

927
W

Contact Terasaki for products with CE marking.

Type of Weight W Applicable


Switchboard panel door Lifter (kg) (mm) ACBs
¶: If 190 mm is exceeded, contact Terasaki. AWR-1 110 700 AR2, AR3
AWR-2 120 890 AR2, AR3, AR4

16
Position switches
The position switches operate to give indication of breaker positions: CONNECTED, TEST, ISOLATED, and INSERT.
There are two contact arrangements: 2c and 4c.
Connections to the switches are made via tab or screw type terminals.
The following table lists the available types of the switches.

Number of Contact arrangement


Type contacts INSERT ISOLATED TEST CONN
ALR-0110P 0 1 1 0 Position switch operation sequence
ALR-0101P 0 1 0 1
ALR-0011P 0 0 1 1 ISOLATED TEST CONNECTED
2c
ALR-0200P 0 2 0 0
CONNECTED position switch a- contact ON
ALR-0020P 0 0 2 0
ALR-0002P 0 0 0 2 a- contact ON
TEST position switch
ALR-1111P 1 1 1 1 a- contact ON
ISOLATED position switch
ALR-1210P 1 2 1 0
a- contact ON
ALR-1201P 1 2 0 1 INSERT position switch

ALR-0211P 0 2 1 1
ALR-1120P 1 1 2 0 INSERT position means the breaker body is in any position
ALR-1021P 1 0 2 1 between ISOLATED and CONNECTED.
ALR-0121P 0 1 2 1
ALR-1102P 1 1 0 2
ALR-1012P 1 0 1 2 Position switch ratings
ALR-0112P 0 1 1 2
ALR-0220P 4c 0 2 2 0 Inductive load (A)
ALR-0202P 0 2 0 2 Voltage Resistive load (A) (COS ø = 0.6, L/R = 0.07)
ALR-0022P 0 0 2 2 AC 100-250V 11 6
ALR-1030P 1 0 3 0 DC 250V 0.3 0.3
ALR-0130P 0 1 3 0 DC 125V 0.6 0.6
ALR-0031P 0 0 3 1 DC 30V 6 5
ALR-1003P 1 0 0 3 DC 8V 10 6
ALR-0103P 0 1 0 3
ALR-0013P 0 0 1 3
ALR-0040P 0 0 4 0
ALR-0004P 0 0 0 4

Door interlock
The door interlock prevents the switchboard door from being opened unless the breaker body is in the ISOLATED position.
When the draw-out handle¶ is removed while the ACB is in the ISOLATED position, the interlock is released and the switchboard
door can be opened.
The breaker body cannot be inserted unless the switchboard door is closed.
Contact Terasaki for details.

Note 1: When a Door interlock is specified, a storage draw-out handle is supplied.


Note 2: Door interlock can not be specified with Door flange.
Note 3: Contact TERASAKI for the details for fitting Door Interlock with IP55 cover.

17
4 Specifications
3 Spring Charged Operation
Manual charging type
For this type of ACB, the closing springs are charged by means of the spring charging handle. ON/OFF operation of the ACB is
performed by means of ON/OFF buttons on the ACB.

°Charging the closing springs


Pumping the spring charging handle by hand charges the closing springs.

°Closing the ACB


Pressing the ON button on the ACB closes the ACB.

°Opening the ACB


Pressing the OFF button on the ACB opens the ACB.
The ACB cannot be closed as long as the OFF button is pressed.

Motor charging type


For this type of ACB, the closing springs are charged by means of a motor. ON/OFF operation of the ACB can be performed
remotely.
The control circuits provide optimum control to the spring charging and ACB ON/OFF operation.
A manual charging mechanism is also fitted to facilitate inspection or maintenance work.

°Charging the closing springs


A motor is used to charge the closing springs.
When the closing springs are released to close the ACB, they are automatically charged again by the motor for the next ON
operation.

°Closing the ACB


Turning on “remote” ON switch enables the ACB to be remotely closed.
• Anti-pumping mechanism
Even if the ON switch is kept on, ACB closing operation is performed only once.
To close the ACB again, remove the ON signal to reset the anti-pumping mechanism and then reapply the ON signal.
• If ON and OFF signals are simultaneously given to the ACB, the ON signal is ignored.

°Opening the ACB


(1) With AGR-11 OCR or without OCR.
For opening the ACB remotely, specify the shunt trip device (See P. 21) or the undervoltage trip (See P. 22).

(2) With AGR-21 or AGR-22 OCR.


Turning on an external OFF switch excites the tripping coil TC , thus enabling the ACB to be remotely opened.
The tripping coil TC is equipped as standard.

18
°Operation power supply
(1) With AGR-11 OCR or without OCR.
Applicable voltage range (V) Operation power supply ratings
Rated voltage
(V) CHARGE/ OFF operation Motor inrush Motor steady-state Closing command
ON operation (Note1) current (peak) (A) current (A) current (peak) (A)
AC 100 85-110 6 0.8 0.48
AC 110 94-121 6 0.8 0.39
AC 120 102-132 6 0.8 0.37
AC 200 170-220 8 0.7 0.24
AC 220 187-242 8 0.7 0.19
AC 240 204-264 8 0.7 0.18
DC 24 20-26 12 3.5 1.65
DC 48 41-53 9 1.4 0.86
DC 100 85-110 5 0.7 0.39
DC 110 94-121 5 0.7 0.37
DC 125 106-138 5 0.7 0.31
DC 200 170-220 6 0.5 0.19
DC 220 187-242 6 0.5 0.18
Note 1: For the ratings refer to the shunt trip device of page 21.

(2) With AGR-21 or AGR-22 OCR


Applicable voltage range (V) Operation power supply ratings
Rated voltage
(V) CHARGE/ Motor inrush Motor steady-state Closing command
OFF operation
ON operation current (peak) (A) current (A) current (peak) (A)
AC 100-120 085-132 070-132 6 0.8 3.0
AC 200-240 170-264 140-264 8 0.7 3.5
DC 24 18-26 17-26 12 3.5 7
DC 48 36-53 34-53 15 3 9
DC 100-125 075-138 070-138 5 0.7 2.5
DC 200-250 150-275 140-275 6 0.5 3

Step-down transformer (external)


The maximum rated control voltage applicable to 62 58 50
M4
the operation power supply is AC240V. If far higher 33
voltages, a step-down transformer is needed.
The following step-down transformers are available
as options.
91
Earth
terminal
Rated control Transformer
4-6U
voltage Type Capacity Voltage ratio
AC410-470V TSE-30M 300VA 450/220V 70 93
AC350-395V TSE-30M 300VA 380/220V 105 105

19
4 Specifications
4 Accessories for Spring Charged Operation
Automatic closing spring release Spring charge indicator
This device allows the charged closing springs to be automati- This switch can be used to indicate that the closing springs
cally released when the ACB is drawn out from the ISOLATED have been fully charged.
position to the REMOVED position.
ANSI or NEMA-compliant ACBs require this option.

(1) With AGR-11 OCR or without OCR


Voltage Switch contact ratings (A)
(V) Resistive load Inductive load
AC 250 6 3
250 0.1 0.1
DC 125 0.5 0.5
30 3 2

(2) With AGR-21 or AGR-22 OCR


Voltage Switch contact ratings (A)
(V) Resistive load Inductive load
AC 250 0.5 0.2
250 0.27 0.04
DC 125 0.5 0.2
30 2 0.7

20
5 Trip Devices
Continuously-rated shunt trip device
The continuous-rated shunt trip device allows the ACB to be Shunt Trip Rating (Continuously rated type)
opened when an external protection relay against overcurrent Rated Operational Peak excitation Steady–state Opening time
Type voltage voltage current current (max.)
or reverse power is activated. (V) (V) (A) (A) (ms)
AC100 AC70–110 0.48 0.32
Because of its continuous rating, the device can also be used
AC110 AC77–121 0.39 0.26
to provide an electrical interlock to the ACB. AC120 AC84–132 0.37 0.24
When an AGR-11 OCR is fitted or no OCR is fitted continu- AC200 AC140–220 0.24 0.16
AC220 AC154–242 0.19 0.13
ously rated shunt trip and fixed type undervoltage trip can not AC240 AC168–264 0.18 0.12
be fitted to the same ACB. However, Instantaneously rated AVR–1C DC24 DC16.8–26.4 1.65 1.1 40
shunt trip can be used together with fixed type undervoltage DC48 DC33.6–52.8 0.86 0.57
DC100 DC70–110 0.39 0.26
trip with special specification. DC110 DC77–121 0.37 0.25
DC125 DC87.5–137.5 0.31 0.21
DC200 DC140–220 0.19 0.13
DC220 DC154–242 0.18 0.12

Capacitor trip device


In conjunction with the continuously-rated shunt trip device, Type AQR-1
the capacitor trip device can be used to trip the ACB within a Rated Voltage AC100-120V
Operational Voltage Rated Voltage X 70 to 110%
limited period of 30 sec if large voltage drop occurs due to an Rated frequecy 50/60Hz
ac power failure or short-circuit. Rated Voltage of Shunt Trip Used DC48V
Power Consumption 100VA
When the continuously-rated shunt trip device is used with ca-
pacitor trip device, “a” contact of auxiliary switch of ACB should
be inserted in series, otherwise, the internal damage may oc-
cur.

PB (OPEN) or
• Control Circuit • Outline Dimensions
OCRy etc.

2–ø6.5Mtg.holes

10

1
1 2 NP
2 3
100
120
140

4
3 NEON LAMP POWER SWITCH
SHT
AVR–IC
B A 4
POWER SUPPLY
AC100V~120V

CAPACITOR TRIP
70 95

76.5
20

¶1
Auxiliary Switch

User Wiring
¶1: Use Auxiliary Switch for capacitor trip

21
4 Specifications
Fixed type Undervoltage Trip (UVT) (With AGR-11 or Without OCR)

The undervoltage trip (UVT) automatically trips the ACB when AC Undervoltage Trip Control Circuit
¶2 PB(OPEN) or OCRy etc.
the control power voltage drops below a pre-determined value. ¶3 AUX.SW

AC SOURCE
When the control voltage is restored to a value equal to or
08 18 28 24
greater than the pick-up value, the ACB can be closed.
G
The UVT consists of a trip control device and a tripping mecha-
A UVT
nism. ENERGIZED
“ON”
B R
Two types of UVT are available. AUR-1BS (instantaneous trip C
C R
type) and AUR-1BD (500ms time delay type). R C
¶1
UVT
Remote opening of the circuit breaker by the UVT is possible R
UVT
by connection of a normally open push button across termi- ENERGIZED
“OFF”

nals ¤4 and ‹0. D


Ry

09 30

¶1 For AUR-1BD only


¶2 For tripping command apply minimum 50ms
¶3 “a” contact of auxiliary switch of ACB to be used.

• Rating
Type of UVT Rated Control Opening Pick-up Coil Excitation Power Consumption (VA)
Control Device Voltage (V), 50/60Hz Voltage (V) Voltage (V) Current (A) Normal Reset
AUR-1BS AC 100 35 – 70 85
AUR-1BD 110 38.5 – 77 93.5
120 42 – 84 102
200 70 – 140 170
220 77 – 154 187 0.3 30 50
240 84 – 168 204
380 133 – 266 323
415 145 – 290 352
440 154 – 308 374
¶24V DC UVT also available as special specification.
Outline Dimension for separate type
UVT control device can be installed separate from the UVT control device
ACB body. Drilling plan
190 170±0.3
2 m lead wire is provided to connect the UVT control 4-ø7 or M6
170
device with the ACB. 4-ø6.5
250±0.3
227
250

UVT CONTROL DEVICE


94.2

22
6 Over-current Releases (OCRs)
The AGR series of over-current releases (OCRs) featuring high reliability and multiple protection capabilities is available for TemPower2.
Controlled by an internal 8-bit microprocessor, the OCR provides reliable protection against overcurrent.
The OCR range is divided into three groups: L-characteristic, R-characteristic (both for general feeder) and S-characteristic (for
generator protection).
Each group consists of,:
Type AGR-11: Standard OCR with adjustment dial
Type AGR-21: Enhanced OCR with adjustment dial
Type AGR-22: Enhanced OCR with L.C.D. display
Optional protection functions of the OCR include those against ground fault, earth leakage, undervoltage and reverse power.
Pre-trip alarm function can also be installed.

Protective functions
qAdjustable long time-delay trip function LT wAdjustable short time-delay trip function ST

RMS sensing is used to accurately read through distorted wave- The ST delay trip function has a “definite time delay character-
forms. istic” and a “ramp characteristic”. These characteristics are
In addition to the standard L and S-characteristics, the R-char- switch-selectable.
acteristic is available in five types for long time-delay trip. The ramp characteristic provides close selectivity with down-
The R-characteristic can be used to give selectivity with e.g., stream circuit breakers or fuses.
fuses. (See P. 8). The group AGR-21L and AGR-21R OCRs come in operation
with the definite time characteristic when the load current
°HOT start mode (applicable to L-characteristic) reaches 1000% or more of the rated current [In] (500% or more
HOT or COLD start mode is user-selectable. of the rated current [In] for AGR-21S).
In HOT start mode, the OCR operates faster than in COLD The ST trip function is factory set to the definite time character-
start mode in response to an overload. The HOT start mode istic.
gives protection, taking account of the behavior of loads under Ramp characteristic curve
heat stress. (“L” or “R” characteristic)
Isd
Operating time

HOT start mode

2.5

0.1 tsd
COLD start curve
Operating time

200% 1000%
q  Current
w  HOT start curves
e  eAdjustable instantaneous trip function INST/MCR
Current
qWhen the OCR is set to start operation at 50% of the rated current, its The INST trip function trips the ACB when the short circuit cur-
operating time in HOT start mode is approx. 80% of that in COLD start mode.
wWhen the OCR is set to start operation at 75% of the rated current, rent exceeds the pickup current setting, irrespective of the state
its operating time in HOT start mode is approx. 60% of that in COLD start mode. of the ACB.
eWhen the OCR is set to start operation at 100% of the rated current, its The making current release (MCR) trips the ACB when the
operating time in HOT start mode is approx. 20% of that in COLD start mode.
short circuit current exceeds the pickup current setting during
closing operation. After the ACB is closed, the MCR is locked
and kept inoperative.
The INST and MCR are switch-selectable.
Note) The MCR needs the control power. If the control power
is lost, the MCR provides the INST trip function only.

23
4 Specifications
rAdjustable pre-trip alarm function PTA yEarth leakage trip function ELT
(For AGR-21 and AGR-22 only.)
The pre-trip alarm function provides an alarm signal via the
alarm contact (1a-contact) when the load current exceeding a In conjunction with an external Zero phase Current Transformer
predetermined value lasts for a predetermined time. A 2-chan-
(ZCT), the ELT function provides protection against earth leak-
nel pre-trip alarm function is available for S-characteristic. This
age.
function can be used to adjust feeding to loads according to
The ELT pickup current can be set at 0.2, 0.3, 0.5 and 1A
their priority.
(Medium sensitivity) or 3 and 5A (Low sensitivity).
The pre-trip alarm is automatically reset when the load current
drops to the predetermined value. This function needs the control power.
Note that this function needs the control power. Note 1: For details on specifications of the external ZCT, con-
tact Terasaki.
tGround fault trip function GF Note 2: The ELT function comes usually with operation indica-
tions (LED and contact output). If you need nothing
The peak value sensing is used (the residual current of each but earth leakage indications without earth leakage trip-
phase is detected). ping operation, specify at the time of ordering.
The GF pickup current can be set between 10% and 100% of Note 3: The ELT function is available up to 3200A rated current
the CT rated primary current [ICT]. [In]

<Ramp characteristic is added> uReverse power trip function RPT


The ramp and definite time characteristics are switch select- (For AGR-21 and AGR-22 only.)
able. The GF trip function comes into operation with the defi-
nite time characteristic when the load current reaches 100% or The RPT function protects 3-phase generators running in par-
more of the CT rated primary current [ICT]. allel against reverse power. The RPT pickup current can be
The GF trip function is factory set to the definite time charac- set in seven levels: 4% thru 10% of the generator rated power.
teristic. The applicable rated voltages are AC100 - 120V, AC200 - 240V,
and AC380 - 460V.
When using a 3-pole ACB in a 3-phase, 4-wire system, be sure The RPT function comes usually with operation indications (LED
to use an optional CT for neutral line (see P. 39). and contact output).
Note 1: The GF trip function comes usually with operation indi- Note 1: CT for RPT is provided as standard when you specify
cations (LED and contact output). If you need nothing RPT for AR2 and AR3 Draw-out type. However, CT for
but ground fault indication without a ground fault trip- RPT for AR440S should be provided by you as
ping operation, specify at the time of ordering. TERASAKI do not supply.
Note 2: Applicable ACBs depend on the connection method of
main terminals. For the details please contact
TERASAKI.

iN-phase protection function NP

This NP function is available on 4-pole ACBs and prevents the


neutral conductor from suffering damage or burnout due to
overcurrent.
The NP trip pickup current can be set between 40% and 100%
of the OCR rated primary current for L and R-characteristics or
of the generator rated current for S-characteristic.
It is factory set to a value specified at the time of ordering.
Note 1: The NP trip function comes usually with operation indi-
cations (LED and contact output). The NP trip pickup
current setting is shared by the LT trip function.
Note 2: The HOT start mode is available. The operating time
for the NP trip function is linked to that for the LT trip
function.
24
oAdjustable type undervoltage trip function UVT !0Contact temperature monitoring function (HEAT)
(For AGR-21 and AGR-22 only.) (For AGR-21 only.)

The applicable rated voltages are AC100 - 120V, AC200 - 240V, The HEAT function prevents the ACB from suffering damage
and AC380 - 460V. due to overheat.
The UVT function trips the ACB when the UVT control voltage It monitors the temperature of the ACB main contacts, and gives
drops to a value equal to 65% of the rated value. an alarm via an LED indicator and an output signal via the
The operating time can be set in ten levels: “instantaneous” alarm contact (1a-contact) when the temperature exceeds
thru 1 sec. 155°C.
The ACB can be closed 2 sec. after the UVT control voltage The alarm can be manually reset when the temperature drops
has returned to the pick-up voltage. to a normal temperature.
Phase failure protection is available by connecting R,S and If you want to set the threshold temperature to a lower value,
T-phase. contact Terasaki.
Note 1: The UVT control power is shared by the reverse power This function needs the control power.
trip function (if fitted).
Note 2: The UVT function comes usually with operation indica-
tions (LED and contact output).
Note 3: The UVT function trips the ACB when any phase is lost
in case 3 phases are detected.
Note 4: For the fixed type undervoltage trip device for AGR-11
or no OCR, See page 22.

NON setting and fail-safe feature

zNON setting xFail-safe feature


Setting a trip pickup current setting dial to the NON position The OCR has a fail-safe mechanism in case setting dials are
allows you to render the corresponding protection function in- improperly set to the NON position.
operative. • If the ST and INST trip pickup current setting dials are both
Dials having the NON position include LT, ST, INST/MCR, and set to NON, the fail-safe mechanism will activate the INST
GF. trip function to trip the ACB when a fault current equal to or
Appropriate NON setting will be a useful means for optimum more than 16 times the rated current [In] flows through the
selectivity. ACB.
• If the ST and MCR trip pickup current setting dials are both
set to NON, the fail safe mechanism will activate the ST de-
lay trip function to trip the ACB when a fault current equal to
or more than 10 times (5 times for generator protection) the
rated current [In] flows through the ACB.

25
4 Specifications
Field test facility
The field test facility allows simple field testing on the LT, ST and INST trip functions.
This facility needs control power.

Operation indication function

z Indication via single contact x Indication via individual contacts and LED indicators
When the LT, ST, INST/MCR, or GF trip function is activated, When the LT trip, ST trip, INST/MCR trip, GF trip, ELT, RPT,
an output is generated via 1a-contact. UVT, pre-trip alarm, or contact temperature overheat alarm func-
The 1a-contact will turn off after 40 ms or more. tion is activated, the corresponding LED indicator turns on and
A self-hold circuit is needed. output is generated via the corresponding contact.
The OCR also has a self-diagnostic feature that monitors the
internal tripping circuits and electronic circuits. If detecting any
fault in these circuits, this feature turns on the system alarm
Contact ratings for operation indications (for AGR-11, 21, 22) LED indicator. The control power is needed.
Current (A) Operation indications
Voltage
zSingle contact xIndividual contacts õ: Self-hold (Note 1)
(V) ~: Auto-reset
Resistive load Inductive load Resistive load Inductive load |: Not applicable
AC 250 8 3 0.5 0.2 Protection characteristic L/R-characteristic S-characteristic
250 0.3 0.15 0.27 0.04 Function LED Contact LED Contact
LT • NP õ õ õ ~ (Note 2)
DC 125 0.5 0.25 0.5 0.2
ST õ õ
30 5 3 2 0.7 õ ~ (Note 2)
INST/MCR õ õ
GF or ELT õ õ | |
~ (Note 2)(UVT)
UVT or Trip indicator õ õ õ
õ (Trip ind.)
RPT | | õ ~ (Note 2)
PTA ~ ~ ~ ~
PTA2 or spring
~ ~ ~ ~
charge indicator
Contact temperature
õ õ õ õ
monitoring
System alarm õ õ õ õ

Note 1: To reset indicators for AGR-11, press the reset button or disconnect the
control supply. To reset indicators for AGR-21 and 22, press the reset
button or bridge operation circuit terminals ⁄2 and ¤3.
The ACB can be closed without reset of the indicators.
Note 2: The contact will turn off after 500 ms or more. A self-hold circuit is needed.

c Contact ratings of Trip indicator for use with AGR-11 or without OCR
Voltage Switch contact ratings (A)
(V) Resistive load Inductive load
AC 250 6 3
250 0.1 0.1
DC 125 0.5 0.5
30 3 3

26
OCR with L.C.D. display, type AGR-22 (Contact TERASAKI for details)

zMonitoring various data on L.C.D.


OCR can monitor,
• Phase current (A) of I1, I2, I3, IN, IG and their max. peak
current
• Line voltage (V) of V12, V23, V31 and their max. peak voltage
(or, Phase voltage (V) of V1N, V2N, V3N and their peak volt- LED indicators
age)
• Active power max. (kW)
• Reactive power max. (kVar)
• Power factor (cos ø)
• Electric energy (MWh)
• Frequency
• Trip history
Fault current is monitored, and the operation cause is indi-
cated via individual contacts and LED indicators. Liquid Crystal Display

x Gives the system alarm with LED indication and


output contact for the following abnormal Membrane switchies
function.
• Abnormal analog circuit
• UVT reset fail
• Trip function fail
• MHT circuit break
• Abnormal closing time
• Abnormal opening time
• Abnormal charging time

27
4 Specifications
OCR Specifications
Protection function Operation indication
Over-current release
Protection
(OCR) Long Short Instantaneous Pre-trip alarm Ground Earth Reverse Adjustable Single contact Individual Spring Field test
Control
characteristic or Making type Under Trip power
Type time-delay time-delay current release 1-channel pre-trip alarm 2-channel pre-trip alarm fault Leakage power voltage and LED contacts and charge
LT ST indicator
INST/MCR (PTA) (PTA + PTA2) (Note 2) GFq ELTw RPT UVT indicators LED indicators indicator
AGR–11L–AL ú — — — — — y ú(Note1) — õ õ — Not required
AGR–11L–GL ú — — ú(Note3) — — y ú(Note1) — õ õ — Not required
AGR–11L–PS ú ú — — — — y — ú õ õ ú Required
For general feeder circuits

AGR–11L–PG ú ú — ú — — y — ú õ õ ú Required
AGR–21L–PS ú ú — — — — — — ú ú ú ú Required
AGR–21L–PG ú ú — ú — — — — ú ú ú ú Required
AGR–21L–PGU e — — — — —u Required
Dial adjustment type

ú ú ú ú ú ú ú
AGR–21L–PE–L i ú ú — — úr — — — ú ú ú ú Required
AGR–21L–PE–M i ú ú — — út — — — ú ú ú ú Required
AGR–11R–AL ú — — — — — y ú(Note1) — õ õ — Not required
AGR–11R–GL ú — — ú(Note3) — — y ú(Note1) — õ õ — Not required
AGR–11R–PS ú ú — — — — y — ú õ õ ú Required
AGR–11R–PG ú ú — ú — — y — ú õ õ ú Required
AGR–21R–PGU e ú ú — ú — — ú — ú ú —u ú Required
AGR–11S–AL ú — — — — — y ú(Note1) — õ õ — Not required
For generator

AGR–11S–PS — — — — y — Required
protection

ú ú ú õ õ ú
AGR–21S–PSU e ú ú — — — — ú — ú ú —u ú Required
AGR–21S–PRU e ú ú — — — ú ú — ú ú —u ú Required
AGR–21S–TRU e ú — ú — — ú ú — ú — —u ú Required
AGR–22L–PS e ú ú — — — — — — ú ú ú ú Required
For general feeder circuits

AGR–22L–PG e ú ú — ú — — — — ú ú ú ú Required
AGR–22L–PGU e ú ú — ú — — ú — ú ú —u ú Required
L.C.D. display type i

AGR–22L–PE–L e ú ú — — úr — — — ú ú ú ú Required
AGR–22L–PE–M e ú ú — — út — — — ú ú ú ú Required
AGR–22R–PS e ú ú — — — — — — ú ú ú ú Required
AGR–22R–PG e ú ú — ú — — — — ú ú ú ú Required
AGR–22R–PGU e ú ú — ú — — ú — ú ú —u ú Required
AGR–22S–PS e — — — — — — Required
For generator

ú ú ú ú ú ú
protection

AGR–22S–PSU e ú ú — — — — ú — ú ú —u ú Required
AGR–22S–PRU e ú ú — — — ú ú — ú ú —u ú Required
AGR–22S–TRU e ú — ú — — ú ú — ú — —u ú Required

ú : Available as standard If the control power is not supplied or is lost, each function operates as follows:
õ : Available as option LT, ST, INST, RPT, UVT Operates normally.
\ : Not available GF Operates normally
When the CT rated primary current [ICT] is less than
q : Not available if CT rated primary current [ICT] is 200A Note1: When a protection function of OCRs with single-contact indica-
800 A and the GF pick-up current is set to 10 %, the
or less. tion is activated, the corresponding operation LED indicator is
GF becomes inoperative.
w : Available up to 3,200A rated current [In]. ON momentarily or OFF.
MCR Operates as INST.
e : For over AC 460V, a step down PT is required. But the LED indicator is kept ON when the protection function is
PTA 1-channel PTA Is inoperative.
r : 3–5A Adjustable pick-up current (Low sensitivity). checked with the optional OCR checker.
2-channel PTA
t : 0.2–0.3–0.5–1A Adjustable pick-up current (Medium Note2: The use of the optional 2-channel pre-trip alarm function may
ELT Is inoperative.
sensitivity). cause the OCR to be subject to some functional constraints.
LED indicator on OCRs with single-contact indication Is on momentarily or off.
y : Fixed type UVT with UVT controller can be selected as Contact Terasaki for details.
Contact output from OCRs with single-contact indication Turns off after 40 ms or more.
option. See P. 22. Note3: If the CT rated primary current [ICT] is less than 800A and the GF
LED indicator on OCRs with individual-contact indication Is kept off.
u : Trip indicator can be selected as option in place of UVT pick-up current is set to 10 %, control power is required, and specify
Contact output from OCRs with individual contact indication Is inoperative.
indication. the control voltage at the time of ordering.
Spring charge indicator Is inoperative. (For AGR-21,22)
i : Contact TERASAKI for details.
Field test facility Is inoperative.

28 29
4 Specifications
Optional functions
Protection function Operation indication
Over-current release
Protection (OCR) Communication
Type N-phase protection Contact temperature monitoring Fixed type Under Voltage Trip Operation panel
characteristic i o

Note 4 N O P C
AGR–11L–AL õ — õ — —
AGR–11L–GL õ — õ — —
AGR–11L–PS õ — õ — —
For general feeder circuits

AGR–11L–PG õ — õ — —
AGR–21L–PS õ õ — — —
AGR–21L–PG õ õ — õ õ
AGR–21L–PGU —
Dial adjustment type

õ õ õ õ
AGR–21L–PE–L õ õ — õ õ
AGR–21L–PE–M õ õ — õ õ
AGR–11R–AL õ — õ — —
AGR–11R–GL õ — õ — —
AGR–11R–PS õ — õ — —
AGR–11R–PG õ — õ — —
AGR–21R–PGU õ õ — õ õ
AGR–11S–AL — — õ — —
For generator

AGR–11S–PS — — — —
protection

õ
AGR–21S–PSU — õ — õ õ
AGR–21S–PRU — õ — õ õ
AGR–21S–TRU — õ — õ õ
AGR–22L–PS õ — — — —
For general feeder circuits

AGR–22L–PG õ — — — õ
AGR–22L–PGU õ — — — õ
L.C.D. display type

AGR–22L–PE–L õ — — — õ
AGR–22L–PE–M õ — — — õ
AGR–22R–PS õ — — — —
AGR–22R–PG õ — — — õ
AGR–22R–PGU õ — — — õ
AGR–22S–PS — — — — —
For generator
protection

AGR–22S–PSU — — — — õ
AGR–22S–PRU — — — — õ
AGR–22S–TRU — — — — õ

õ : Available as option
\ : Not available
i : Contact TERASAKI for details.
o : Communication function can not be applied together with Operation panel.
Note4: When optional functions are required please specify the OCR type designation
by adding one or more of the abbreviated letters at the end of the code.
Ex. AGR–21L–PSNO

Contact temperature monitoring


N-phase protection

30 31
4 Specifications
L-characteristic for general feeder circuits (Type AGR-11L, 21L, 22L)
Setting range of protection functions

Protection functions Setting range


°Adjustable long time-delay trip characteristics
LT
Pick-up current [IR] (A) [In]~(0.8 – 0.85 – 0.9 – 0.95 – 1.0 – NON) ; 6 graduations
• Non tripping when load current Ö ([IR]~1.05). • Tripping when ([IR]~1.05) É load current Ö ([IR]~1.2)
Time-delay [tR] (s) (0.5 – 1.25 – 2.5 – 5 – 10 – 15 – 20 – 25 – 30) at 600% of [IR]; 9 graduations
Time-delay setting tolerance (%) ±15% +150ms – 0ms
°Adjustable short time-delay trip characteristics
ST
Pick-up current [Isd] (A) [In]~(1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) ; 10 graduations
Current setting tolerance (%) ±15%
Time-delay [tsd] (ms) Relay time 50 100 200 400 600 800 ; 6 graduations
Resettable time (ms) 25 75 175 375 575 775
Max. total clearing time (ms) 120 170 270 470 670 870
°Adjustable instantaneous trip characteristics
INST or MCR
Pick-up current [I i] (A) [In]~(2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) ; 9 graduations
Current setting tolerance (%) ±20%
°Adjustable pre-trip alarm characteristics
PTA
Pick-up current [IP1] (A) [In]~(0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0) ; 6 graduations
Current setting tolerance (%) ±7.5%
Time-delay [tP1] (s) (5 – 10 – 15 – 20 – 40 – 60 – 80 – 120 – 160 – 200) at [I P1] or more; 10 graduations
Time-delay setting tolerance (%) ±15% +100ms – 0ms
°Adjustable ground fault trip characteristics
GF Note: Set [Ig] to 1200A or less.
Pick-up current [Ig] (A) [ICT]~(0.1 – 0.2 – 0.3 – 0.4 – 0.6 – 0.8 – 1.0 – NON) ; 8 graduations
Current setting tolerance (%) ±20%
Time-delay [tg] (ms) Relay time 100 200 300 500 1000 2000 ; 6 graduations
Resettable time (ms) 75 175 275 475 975 1975
Max. total clearing time (ms) 170 270 370 570 1070 2070
°N-phase protection characteristics
NP
Pick-up current [IN] (A) [ICT]~(0.4 – 0.5 – 0.63 – 0.8 – 1.0) ; Factory set to a user-specified value.
• Non tripping when load current Ö ([IN]~1.05). • Tripping when ([IN]~1.05) É load current Ö ([IN]~1.2)
Time-delay [tN] (s) Tripping at 600% of [IN] with LT time-delay [tR]
Current setting tolerance (%) ±15% +150ms – 0ms
°Adjustable earth leakage trip characteristics
ELT (AGR-21,22 only)
Pick-up current [I∆R] (A) 0.2 – 0.3 – 0.5 – 1 (Medium sensitivity) or 3 – 5 (Low sensitivity)
Current setting tolerance Non operate below 50% of [I R ], Operate between 50% and 100% of [I R ].
Time-delay [t∆R] (ms) Relay time 100 200 300 500 1000 2000 ; 6 graduations
Resettable time (ms) 50 150 250 450 950 1950
Max. total clearing time (ms) 250 350 450 600 1150 2150
°Undervoltage trip characteristics
UVT (AGR-21,22 only)
Pick-up voltage (V) UVT rated supply voltage [Uc]~(0.8 – 0.85 – 0.9 – 0.95) ; 4 graduations
Time-delay [time] (s) 0 – 0.1 – 0.2 – 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 1.0 ; 10 graduations
°Control power AC100 – 120V  DC100 – 125V  DC24V 
Common Common Common
AC200 – 240V  DC200 – 250V  DC48V 
Power consumption: 5 VA
__ : Default setting

Type Applicable Rated current [In](A)


°Values of [ICT] and [In] [ICT] [ICT] [ICT] [ICT] [ICT]
Type Applicable Rated current [In](A) Type Applicable Rated current [In](A) (A) ~0.5 ~0.63 ~0.8 ~1.0
[ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] AR212H 200 100 125 160 200
(A) ~0.5 ~0.63 ~0.8 ~1.0 (A) ~0.5 ~0.63 ~0.8 ~1.0 400 200 250 320 400
AR208S 200 100 125 160 200 AR220S 400 200 250 320 400 800 400 500 630 800
400 200 250 320 400 800 400 500 630 800 1250 630 800 1000 1250
800 400 500 630 800 1250 630 800 1000 1250 AR216H 1600 800 1000 1250 1600
AR212S 400 200 250 320 400 1600 800 1000 1250 1600 AR220H 2000 1000 1250 1600 2000
800 400 500 630 800 2000 1000 1250 1600 2000 AR316H 200 100 125 160 200
1250 630 800 1000 1250 AR325S 2500 1250 1600 2000 2500 400 200 250 320 400
AR216S 400 200 250 320 400 AR332S 3200 1600 2000 2500 3200 800 400 500 630 800
800 400 500 630 800 AR440S 4000 2000 2500 3200 4000 1250 630 800 1000 1250
1250 630 800 1000 1250 1600 800 1000 1250 1600
1600 800 1000 1250 1600 AR320H 2000 1000 1250 1600 2000
AR325H 2500 1250 1600 2000 2500
AR332H 3200 1600 2000 2500 3200
32
Front face of over-current release (OCR)

Operation LED indicator


System alarm LED indicator
Undervoltage trip LED indicator

Field test buttons Reset button

Rated current setting dial


Long time-delay trip
Long time-delay trip pickup current setting dial
time-delay setting dial

Short time-delay trip pickup current setting dial Short time-delay trip time-delay setting dial
INST or MCR selector switches
Instantaneous trip pickup current setting dial
ST/GF ramp characteristic selector switch

Ground fault trip pickup current setting dial Ground fault trip time-delay setting dial

Pre-trip alarm pickup current setting dial Pre-trip alarm time-delay setting dial

Undervoltage trip pick-up voltage setting dial Undervoltage trip time-delay setting dial

Protection
3
characteristics LT current setting range
hour

2 N-phase protection
current setting range
PTA current setting range
1
40
ST current setting range
20
GF current setting range
INST current setting range
minute

10

6
4

1
40
Operating time

20
Max
10

6
4

2
second

1
800ms

0.6
0.4 400ms

Min. The ST trip characteristic


0.2 shown in the figure applies
when the ramp characteristic
100ms
0.1 select switch is in the
OFF position.
0.06
0.04

0.02

0.01

0.006
60
70
80
90
100

125
150

200
250
300

400

500
600
700
800
900
1000

1500

2000
2500
3000
7
8
9
10

15

20

30

40

50
60
70
80
90
100

150

200

% of OCR rated primary current [ICT ] % o f r a t e d c u r r e n t [ In ]

33
4 Specifications
R-characteristic for general feeder circuits (Type AGR-11R, 21R, 22R)
Setting range of protection functions

Protection functions Setting range


°Adjustable long time-delay trip characteristics Select one from among I0.02t, It, I2t, I3t, and I4t by selector switch.
LT
Pick-up current [IR] (A) [In]~(0.8 – 0.85 – 0.9 – 0.95 – 1.0 – NON) ; 6 graduations
• Non tripping when load current Ö ([IR]~1.05). • Tripping when ([IR]~1.05) É load current Ö ([IR]~1.2)
Time-delay [tR] (s) (1 – 2 – 3 – 4 – 5 – 6 – 7 – 8 – 10 – 13) at 300% of [IR]; 10 graduations
Time-delay setting tolerance (%) ±20% +150ms – 0ms
°Adjustable short time-delay trip characteristics
ST
Pick-up current [Isd] (A) [In]~(1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) ; 10 graduations
Current setting tolerance (%) ±15%
Time-delay [tsd] (ms) Relay time 50 100 200 400 600 800 ; 6 graduations
Resettable time (ms) 25 75 175 375 575 775
Max. total clearing time (ms) 120 170 270 470 670 870
°Adjustable instantaneous trip characteristics
INST or MCR
Pick-up current [I i] (A) [In]~(2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) ; 9 graduations
Current setting tolerance (%) ±20%
°Adjustable pre-trip alarm characteristics
PTA
Pick-up current [IP1] (A) [In]~(0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0) ; 6 graduations
Current setting tolerance (%) ±7.5%
Time-delay [tP1] (s) (5 – 10 – 15 – 20 – 40 – 60 – 80 – 120 – 160 – 200) at [I P1] or more; 10 graduations
Time-delay setting tolerance (%) ±15% +100ms – 0ms
°Adjustable ground fault trip characteristics
GF Note: Set [Ig] to 1200A or less.
Pick-up current [Ig] (A) [ICT]~(0.1 – 0.2 – 0.3 – 0.4 – 0.6 – 0.8 – 1.0 – NON) ; 8 graduations
Current setting tolerance (%) ±20%
Time-delay [tg] (ms) Relay time 100 200 300 500 1000 2000 ; 6 graduations
Resettable time (ms) 75 175 275 475 975 1975
Max. total clearing time (ms) 170 270 370 570 1070 2070
°N-phase protection characteristics
NP
Pick-up current [IN] (A) [ICT]~(0.4 – 0.5 – 0.63 – 0.8 – 1.0) ; Factory set to a user-specified value.
• Non tripping when load current Ö ([IN]~1.05). • Tripping when ([IN]~1.05) É load current Ö ([IN]~1.2)
Time-delay [tN] (s) Tripping at 300% of [IN] with LT time-delay [tR]
Current setting tolerance (%) ±20% +150ms – 0ms
°Undervoltage trip characteristics
UVT (AGR-21,22 only)
Pick-up voltage (V) UVT rated supply voltage [Uc]~(0.8 – 0.85 – 0.9 – 0.95) ; 4 graduations
Time-delay [time] (s) 0 – 0.1 – 0.2 – 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 1.0 ; 10 graduations
°Control power AC100 – 120V  DC100 – 125V  DC24V
Common Common Common
AC200 – 240V  DC200 – 250V  DC48V
Power consumption: 5 VA
__ : Default setting

°Values of [ICT] and [In]


Type Applicable Rated current [In](A) Type Applicable Rated current [In](A) Type Applicable Rated current [In](A)
[ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT]
(A) ~0.5 ~0.63 ~0.8 ~1.0 (A) ~0.5 ~0.63 ~0.8 ~1.0 (A) ~0.5 ~0.63 ~0.8 ~1.0
AR208S 200 100 125 160 200 AR220S 400 200 250 320 400 AR212H 200 100 125 160 200
400 200 250 320 400 800 400 500 630 800 400 200 250 320 400
800 400 500 630 800 1250 630 800 1000 1250 800 400 500 630 800
AR212S 400 200 250 320 400 1600 800 1000 1250 1600 1250 630 800 1000 1250
800 400 500 630 800 2000 1000 1250 1600 2000 AR216H 1600 800 1000 1250 1600
1250 630 800 1000 1250 AR325S 2500 1250 1600 2000 2500 AR220H 2000 1000 1250 1600 2000
AR216S 400 200 250 320 400 AR332S 3200 1600 2000 2500 3200 AR316H 200 100 125 160 200
800 400 500 630 800 AR440S 4000 2000 2500 3200 4000 400 200 250 320 400
1250 630 800 1000 1250 800 400 500 630 800
1600 800 1000 1250 1600 1250 630 800 1000 1250
1600 800 1000 1250 1600
AR320H 2000 1000 1250 1600 2000
AR325H 2500 1250 1600 2000 2500
AR332H 3200 1600 2000 2500 3200

34
Front face of over-current release (OCR)

Operation LED indicator


System alarm LED indicator
Undervoltage trip LED indicator

Field test buttons Reset button

Rated current setting dial Selection of curve

Long time-delay trip


Long time-delay trip pickup current setting dial
time-delay setting dial

Short time-delay trip pickup current setting dial Short time-delay trip time-delay setting dial
INST or MCR selector switches
Instantaneous trip pickup current setting dial
ST/GF ramp characteristic selector switch

Ground fault trip pickup current setting dial Ground fault trip time-delay setting dial

Pre-trip alarm pickup current setting dial Pre-trip alarm time-delay setting dial

Undervoltage trip pick-up voltage setting dial Undervoltage trip time-delay setting dial

Protection
3
characteristics LT current setting range
hour

2 N-phase protection
current setting range
PTA current setting range
1
40
ST current setting range
20
GF current setting range
INST current setting range
minute

10

6
4

I4t
2 I4t
I3t I3t
1
Operating time

40 I0.02t

20
I0.02t
10

6
4

2
second

1
800ms

0.6
0.4 400ms

The ST trip characteristic


0.2 shown in the figure applies
when the ramp characteristic
100ms
0.1 select switch is in the
OFF position.
0.06
0.04

0.02

0.01

0.006
60
70
80
90
100

125
150

200
250
300

400

500
600
700
800
900
1000

1500

2000
2500
3000
7
8
9
10

15

20

30

40

50
60
70
80
90
100

150

200

% of OCR rated primary current [ ICT ] % o f r a t e d c u r r e n t [ In ]

35
4 Specifications
S-characteristic for generator protection (Type AGR-11S, 21S, 22S)
Setting range of protection functions

Protection functions Setting range


°Adjustable long time-delay trip characteristics
LT
Pick-up current [IR] (A) [In]~(0.8 – 1.0 – 1.05 – 1.1 – 1.15 – NON) ; 6 graduations
Current setting tolerance (%) ±5%
Time-delay [tR] (s) (15 – 20 – 25 – 30 – 40 – 50 – 60) at 120% of [IR]; 7 graduations
Time-delay setting tolerance (%) ±15% +150ms – 0ms
°Adjustable short time-delay trip characteristics
ST
Pick-up current [Isd] (A) [In]~(2 – 2.5 – 2.7 – 3 – 3.5 – 4 – 4.5 – 5 – NON) ; 9 graduations
Current setting tolerance (%) ±10%
Time-delay [tsd] (ms) Relay time 100 200 300 400 600 800 ; 6 graduations
Resettable time (ms) 75 175 275 375 575 775
Max. total clearing time (ms) 170 270 370 470 670 870
°Adjustable instantaneous trip characteristics
INST or MCR
Pick-up current [I i] (A) [In]~(2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) ; 9 graduations
Current setting tolerance (%) ±20%
°Adjustable pre-trip alarm characteristics
PTA
Pick-up current [IP1] (A) [In]~(0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05) ; 7 graduations
Current setting tolerance (%) ±5%
Time-delay [tP1] (s) (10 – 15 – 20 – 25 – 30) at 120% of [IP1]; 5 graduations
Time-delay setting tolerance (%) ±15% +100ms – 0ms
PTA 2 (AGR-21,22 only)
Pick-up current [IP2] (A) [In]~(0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05) ; 7 graduations
Current setting tolerance (%) ±5%
Time-delay [tP2] (s) 1.5 [tP1] at 120% of [IP2]
Time-delay setting tolerance (%) ±15% +100ms – 0ms
°Adjustable reverse power trip characteristics
RPT (AGR-21,22 only)
Pick-up power [PR] (kW) Rated power [Pn]~(0.04 – 0.05 – 0.06 – 0.07 – 0.08 – 0.09 – 0.1 – NON) ; 8 graduations
Power setting tolerance (%) +0 – 20%
Time-delay [time] (s) (2.5 – 5 – 7.5 – 10 – 12.5 – 15 – 17.5 – 20) at 100% of [PR]; 8 graduations
Time-delay setting tolerance (%) ±20%
°Undervoltage trip characteristics
UVT (AGR-21,22 only)
Pick-up voltage (V) UVT and RPT rated supply voltage [Uc]~(0.8 – 0.85 – 0.9 – 0.95) ; 4 graduations
Time-delay [time] (s) 0 – 0.1 – 0.2 – 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 1.0 ; 10 graduations
°Control power AC100 – 120V  DC100 – 125V  DC24V 
Common Common Common
AC200 – 240V  DC200 – 250V  DC48V 
Power consumption: 5 VA
__ : Default setting

Applicable range of generator rated current [In]


Type OCR rated primary Applicable range of generator Type OCR rated primary Applicable range of generator
current [ICT](A) rated current [In] (A) current [ICT](A) rated current [In] (A)
AR208S 200 100Ö[In]Ö200 AR212H 200 100Ö[In]Ö200
400 200É[In]Ö400 400 200É[In]Ö400
800 400É[In]Ö800 800 400É[In]Ö800
AR212S 400 200Ö[In]Ö400 1250 630É[In]Ö1250
800 400É[In]Ö800 AR216H 1600 800Ö[In]Ö1600
1250 630É[In]Ö1250 AR220H 2000 1000Ö[In]Ö2000
AR216S 400 200Ö[In]Ö400 AR316H 200 100Ö[In]Ö200
800 400É[In]Ö800 400 200É[In]Ö400
1250 630É[In]Ö1250 800 400É[In]Ö800
1600 800Ö[In]Ö1600 1250 630É[In]Ö1250
AR220S 400 200Ö[In]Ö400 1600 800É[In]Ö1600
800 400É[In]Ö800 AR320H 2000 1000Ö[In]Ö2000
1250 630É[In]Ö1250 AR325H 2500 1250Ö[In]Ö2500
1600 800Ö[In]Ö1600 AR332H 3200 1600Ö[In]Ö3200
2000 1250Ö[In]Ö2000
AR325S 2500 1250Ö[In]Ö2500
AR332S 3200 1600Ö[In]Ö3200
AR440S 4000 2000Ö[In]Ö4000

36
Front face of over-current release (OCR)

Operation LED indicator


System alarm LED indicator
Undervoltage trip LED indicator
Reverse power trip LED indicator

Field test buttons


Reset button

Long time-delay trip pickup current setting dial Long time-delay trip time-delay setting dial

Short time-delay trip pickup current setting dial Short time-delay trip time-delay setting dial
INST or MCR selector switches
Instantaneous trip pickup current setting dial
ST ramp characteristic selector switch
1st stage pre-trip alarm pickup 1st stage pre-trip alarm
current setting dial time-delay setting dial
2nd stage pre-trip alarm pickup
current setting dial

Undervoltage trip pick-up voltage setting dial Undervoltage trip time-delay setting dial

Reverse power trip pickup power setting dial Reverse power trip time-delay setting dial

Protection
3
characteristics
hour

2 LT current setting range

1 PTA current setting range

40

20
minute

10

6
4
ST current setting range

2 INST current setting range


Max. Max.

1
40
Operating time

20

10 PTA2
Min.
6
4 Min.

2 PTA
second

1
800ms

0.6
0.4 400ms

The ST trip characteristic


0.2 shown in the figure applies
when the ramp characteristic
100ms
0.1 select switch is in the
OFF position.
0.06
0.04

0.02

0.01

0.006
7
8
9
10

15

20

30

40
50
60
70
80
90
100

125
150

200
250
300

400

500
600
700
800
900
1000

1500

2000
2500
3000

% o f g e n e r a t o r r a t e d c u r r e n t [ In ]

37
4 Specifications
7 Other Accessories
Operation panel, type APR-1P (For AGR-21 only)

The operation panel, which is an


integrated monitoring and control
tool, has functions and capabili-
ties of watt-hour meters, wattme-
ters, voltmeters, ammeters,
switches, and indicators, allowing
the operator to remotely monitor
and control up to eight ACBs via
serial communications.
Two large LED monitors on the
panel can read two kinds of data
simultaneously in real time.
The operation panel can be in-
stalled up to 50 m away from the
ACBs.

Specifications and functions


• Power supply:
237
;
;25
Switchboard panel

;
DC12V (supplied from ACB)
• Dimensions (in mm):

;
202 (H) ~ 237 (W) ~ 25 (D)
• Weight: 1.65 kg

;
• Operation:
Selecting an ACB, turning it ON/OFF, resetting
202

;
OCR indications, etc. are allowed from a remote
site.

;
• Monitoring:
Items monitored include the present or demand
values of the following: 4-ø4.5
M4 mounting screws
Line voltage (V12, V23, V31) not supplied
Active power (kW) and reactive power (kvar)
16

Power factor 20 58
55

Active electric energy (MWh) 50


Phase current (I1, I2, I3, IN) and ground fault
16
170

current (IG) 13 35 Clearance for connectors

Frequency
84

ACB main contact temperature (°C)


ACB main contact wear (%)
• Fault indication:
210
Fault trip current
System alarm Panel cutout
(front view)
38
OCR checker, type ANU-1
The OCR checker allows easy checking of the long time-delay trip,
short time-delay trip, instantaneous trip, ground fault trip functions
and the pre-trip alarm function of the OCR in the field.

¡Ratings and specifications


Power supply • AC100–110V, 50/60Hz
or
AC100–240V, 50/60Hz with type C plug
• 4~AA alkaline cells
Power consumption 7VA
Dimensions 101 (W) ~ 195 (H) ~ 44 (D) mm
Weight 400 g

Current transformer for neutral line (separate type)


When using a 3-pole ACB with the ground fault protection function to protect a 3-phase, 4-wire system against ground fault, install
an appropriate current transformer (CT) to the neutral line of the system.
TERASAKI can provide this neutral line CT as an option.
For the 4-pole ACB, a measuring CT instead of the neutral line CT is already built into the neutral phase of the ACB when the
ground fault protection is fitted.

• Outline dimension of CT for neutral line


AR208S, AR212S, AR216S AR220S, AR325S, AR332S, AR440S
AR212H, AR216H, AR316H AR220H, AR320H, AR325H, AR332H
M5 50
60 M5
k r
kr
L L K K L
K 4-M5 Tap
for fixing
secondary
150

wiring
30
80

ø160
255
70

125

4-ø7
4-ø10
30 80
70 100
80 160 120
125 235 150

Type CW80-40LS Type EC160-40LS


Rated 200 1250 Rated 1600 3200
Primary 400 1600 Primary 2000 4000
Current (A) 800 Current (A) 2500
Rated secondary current is 5A Rated secondary current is 5A

39
4 Specifications
ON–OFF cycle counter
The ON-OFF cycle counter is a mechanical 5-digit readout that
shows the number of ON-OFF cycles of the ACB.
Counter readings serve as a guide for maintenance or inspec-
tion.

Auxiliary switches
The auxiliary switches operate during the ACB ON/OFF op-
eration. Type For general service For microload ¶¶
Connections to the switches are made via tab terminals. Screw ¶AXR-004 4c —
AXR-007 7c —
terminal type is available as an option.
AXR-304 4c 3c
The auxiliary switches for draw-out type ACBs operate in the
AXR-010 10c —
CONNECTED and TEST positions.
AXR-307 7c 3c
The auxiliary switches for ACBs conforming to classification
society’s rules operate in the CONNECTED position only. ¶The standard contact arrangement of the auxiliary switches is 4c.
The auxiliary switches have change-over contacts and are avail- (Form c: Change-over, single gap, three terminals)
able for general service and for microload. ¶¶Suited to electronic circuits

Auxiliary switch ratings


Category For general service For microload ¶¶
Resistive Inductive AC: cos øÜ 0.3 Resistive Inductive AC: cos øÜ 0.6 Min. applicable
Voltage
load (A) load (A) DC: L/R Ö 0.01 load (A) load (A) DC: L/R Ö 0.007 load
AC100-250V 5 5 0.1 0.1
AC251-500V 5 5 — —
DC5V 1mA
DC30V 1 1 0.1 0.1
DC125-250V 1 1 — —

Note 1: The chattering of b-contacts due to ON-OFF operation of the ACB lasts for less than 20 ms.
Note 2: Do not supply different voltages to contacts of a switch.

Manual reset device (Contact TERASAKI for details)

The manual reset device holds the ACB open that was tripped
by the OCR, and provides a mechanical indication that the ACB
is in the tripped state.
To close the ACB again, the operator needs to manually reset
the indication after making sure the cause of tripping has been
removed.

Note 1: The manual reset device is not applicable when AGR-


11 OCR is equipped.
Note 2: The manual reset device is not applicable when the
OCR is equipped with the UVT function.
Note 3: When the OCR is equipped with the manual reset de-
vice, a continuous-rated shunt trip device is necessary
for remote OFF operation of the ACB.

40
Key lock Key interlock
The key lock is available in two types: The key interlock is a system of interlocking between ACBs, each fitted with a key lock
the lock-in ON type that locks the ACB of lock-in OFF type.
in the closed position, and the lock-in • A key must be inserted to release the lock before the ACB can be closed.
OFF type that locks the ACB in the open • The ACB must be opened and locked in the OFF position before the key can be
position. removed.
When the ACB is fitted with a key lock, By utilizing the lock-in OFF type key lock feature, and then a limited number of keys by
the operator cannot operate the ACB un- default provides an effective and reliable interlock system.
less using a matched key. Using the same keys also allows interlocking between an ACB and other devices
(such as a switchboard door).
ACBs are supplied with a cylinder lock or with a provision for type FS-2 Castell lock
(with angular movement 90° clockwise to trap key).
The Castell lock is not supplied.

Example: Interlock for prevention of parallel feeding from two sources


ACB 3 cannot be closed ACB 2 cannot be closed ACB 1 cannot be closed
Source 1 Source 2 Source 1 Source 2 Source 1 Source 2
ACB 1 ACB 2 ACB 1 ACB 2 ACB 1 ACB 2

ACB 3 ACB 3 ACB 3


(bus-tie breaker) (bus-tie breaker) (bus-tie breaker)

Load 1 Load 2 Load 1 Load 2 Load 1 Load 2

41
4 Specifications
Mechanical interlock (Contact TERASAKI for details)

Mechanical interlocks for interlocking 2 or 3 ACBs in either horizontal (Draw-out type and Fixed type) or vertical (Draw-out type
only) arrangements are available.
Interlocking is possible between any frame size within the TemPower2 range.
In conjunction with an electrical interlock, it will enhance safety and reliability of power distribution systems.

zHorizontal type
This table shows the standard pitch between left side ACB A and right side ACB B,
or between left side ACB B and right side ACB c.

Cable

Pitch of ACB P (mm)


(PC line to PC line) Min. R300mm
Right ACB AR208S`AR220SAR325S`AR332S
AR440S
AR212H`AR220H AR316H`AR332H
Left ACB 3P, 4P 3P, 4P 3P, 4P
AR208S` 3P 500, 600, 700 600, 700, 800 500, 600, 700
AR220S N N N
AR212H`
AR220H 4P 600, 700, 800 700, 800, 900 600, 700, 800

AR325S` 3P 600, 700, 800 700, 800, 900 600, 700, 800
AR332S
AR316H`
AR332H 4P 700, 800, 900 800, 900, 1000 700, 800, 900
A P1
B P2
C
3P 800, 900, 1000 900, 1000, 1100 800, 900, 1000
AR440S
4P 1000, 1100, 1200 1000, 1100, 1200 1000, 1100, 1200

For the ordering, select the required pitch for P1 and P2 from the above table, and specify the type and
Number of poles for ACB A, ACB B and ACB C if exists.

Example,

P1: 700 mm
P2: 800 mm
ACB A: Type AR212H 3 poles
ACB B: Type AR332H 3 poles
ACB C: Type AR216H 3 poles

xVertical Type
Minimum pitch (550mm) is possible.
Specify the reguired pitch when order.
Maximum is 1200mm.
Contact TERASAKI for the details of vertical type with 3 ACBs.
Rod

N
Min 550 mm

42
Lifting plate Control circuit terminal cover
Lifting plates are detachable tools that A control circuit terminal cover protects
can be used to lift a breaker body out of the terminal blocks for auxiliary switches,
a draw-out cradle. position switches, and control circuits
from being accidentally touched, thus
enhancing safety.

Door flange
A door flange can be used as a
decoration panel that covers the cutout
on the switchboard panel, and provides
ON-OFF button cover ¶
IP20 protection. For IP31 protection
¶: Standard equipment
please specify the door flange with a
An ON-OFF button cover prevents
gasket.
inadvertent or unauthorized operation of
Note: Door flange can not be specified
the ON or OFF button. It can be locked
with Door interlock.
with up to three padlocks with ø6 hasp.
Padlocks are not supplied.

¶ : Mount IP20 door flange through 6 mounting holes and IP31 door flange
through 10 mounting holes.

43
4 Specifications
OFF padlock Inter-pole barrier
Permits the ACB to be padlocked in the An inter-pole barrier prevents a possible
OFF position. Max. three padlocks with short-circuit due to foreign objects
ø6 hasp can be fitted. Padlocking is pos- entering between the poles of the main
sible only when ON-OFF indicator shows circuit terminals or between the line and
OFF. When the ACB is padlocked in the load ends, thus enhancing operational
OFF position both manual and electrial reliability of the ACB.
closing become inoperative, but the This barrier cannot be applied to ACBs
charging of the closing spring by manual that are supplied with front connections
or motor is still possible. or a reverse power trip function.
Note1: OFF padlock facility cannot be
fitted with key lock or key interlock.

Earthing device
There is a growing demand in L.V. distribution for greater pro- This converts the ACB from a normal service device to an
tection against electric shock particularly during periods when earthing device.
maintenance work is being carried out on the main busbars or When the ACB is converted to the earthing device mode, the
cables. A safe and economical way to meet this requirement is over-current release and the other electrical tripping devices
to apply system earthing via the normal service breaker. are automatically disabled to prevent the remote opening of
Earthing devices on TemPower2 ACBs comprises; Permanent the ACB.
parts which are factory fitted by Terasaki and are mounted on It is recommended that the ON-OFF operating buttons be pad-
the ACB chassis and body to enable the ACB to receive the locked to prevent manual opening of the ACB when used in the
portable parts. Portable parts are supplied in loose kit form earthing mode.
and are fitted on to the ACB body by the customer’s engineer. UVT function can not be applied to the earthing device.
For further information contact Terasaki for details.

IP cover
An IP cover provides an IP55 grade of
protection as defined in IEC 60529.
Even if the breaker body is on the 97
Hinge Panel
ISOLATED position, IP cover can still (ø6 Padlocking) 6-ø6.5
84
Hook
be fitted on the ACB.
365
340
375

335
10
30

Panel
325 250
Domed Floor level
286 for ACB
cap nut Panel Cutout
266 Gasket
Bushing Hexagon socket
head bolt
Insert gasket and bushing
when the IP cover is fixed.

44
8 Operation Environments
Standard environment Special environment
The standard environment for ACBs is as follows: Tropicalization (Fungus and moisture treatment)
Specify this treatment when the ACB is used under high-tem-
Ambient temperature –5°C to +40°C perature and high-humidity conditions.
The average temperature for 24 Conditions: Max. permissible ambient temperature 60°C
hours must not exceed 35°C. Max. permissible humidity 95% rel.
No condensation
Relative humidity 45% to 85%

Attitude Below 2000 m Cold climate treatment


Atmosphere Excessive water vapor, oil vapor, Specify this treatment when the ACB is used in cold areas.
smoke, dust, or corrosive gases must Conditions: Min. permissible storage temperature –40°C
not exist. Min. permissible operating temperature –25°C
Sudden change in temperature, con- No condensation
densation, or icing must not occur.
Anti-corrosion treatment
Specify this treatment when the ACB is used in a corrosive
atmosphere.
Contact Terasaki for details.

Recommendation for Busbars connection


The busbars to the ACB should be firmly supported near the ACB terminal. Fault current flow through the busbars develops a large
electromagnetic force between the busbars, and the support must be strong enough to withstand such forces. The ACB should not
be relied on as a single support.

Busbar support

Busbar Busbar

ACB Busbar support ACB

L L

The maximum distance of the connection point of ACB to the first busbar support

Short-circuit current (kA) 30 50 65 80 100


Distance Type AR2 300 250 150 150 —
L (mm) Type AR3,AR4 350 300 250 150 150

45
5 Outline Dimensions P
C

conductor overlap. max


N
85 85 85
¡Type AR208S, AR212S, AR216S, AR220S,

15
35
AR212H, AR216H, AR220H Draw-out type
P
C : Front panel centre line • With reverse power trip function, the length of the line side
main terminals become 55 mm longer, and the applicable ACBs
35
depend on the connection method of main terminals. Front connection
Terminal size

515
Type t1 t2 t3 W Type Front connection Vertical terminal Horizontal terminal
AR208S 10 10 15 17.5 AR208S õ õ õ
AR212S 10 10 15 17.5 AR212S õ õ õ
AR216S 20 15 25 22.5 AR216S — õ õ

conductor overlap. max


AR220S 20 15 25 —— AR220S — õ õ
AR212H 20 15 —— —— AR212H õ õ

65
AR216H 20 15 —— —— AR216H õ õ

35
AR220H 20 15 —— —— AR220H õ õ

15
t3
õ : Available 318 25
— : Not available 380 50
2-ø11

CP CONNECTED position
TEST position Control circuit terminal cover
(optional)
ISOLATED position
Maintenance 2-ø20 AR208S AR212H
rear panel cut 158.5 81 space AR212S AR216H
14 21 Lifting
AR216S AR220S,H N
hole 35 35 conductor overlap. max 85 85 85
front panel cut 17 194
CP

18
15 15

78
ON-OFF button cover

15.5
30 2-ø11

25 25
N
12

25
Vertical terminal 42.5

232

14.5 14.5
W
9 32

149
335 ¶3
400

329

460

490

500

W
M8 screw

25

25 25
R earth terminal
11 140
6

150.5
W

32
15.5
50

40
42.5 7
33

3-ø11
25

30

27
250 94 141 110 21 t2
With UVT
238 Controller ¶1 9 345 40 29
164 164(3P) 265 385 140(3P) ¶2
249(4P)
177 177(3P) draw-out handle 225(4P)
For fitted with breaker fixing bolts 262(4P) 35 conductor overlap. max
204 204(3P) 15
panel cut-out Maintenance
289(4P)
Maintenance N

52
25
space 240 240(3P) space 85 85 85
325(4P)

2-ø11
94

t1
141

¶1: UVT controller is required when fixed type undervoltage


trip is fitted with AGR-11 OCR or Without OCR.

174
UVT controller can be mounted externally if required. Horizontal terminal
If externally mounted controller is required please specify
on order.
¶2: Conductors including connecting bolts should be
separated min-7mm from Draw-out arm.

138
4-ø14
¶3: Panel cut should be 339 mm not 335 mm when the door 120 120(3P)
flange is used. Refer to page 43. 205(4P)
• N represents the neutral pole of 4-pole ACBs. Draw-out arm
• For High fault series vertical terminal is standard and 385 (comes out when breaker is drawn out)
horizontal terminal is optional, and front connection is not
available. Mounting holes

46 47
5 Outline Dimensions
CP
¡Types: AR208S, AR212S, AR216S, AR220S Fixed type

Conductor overlap max.


N
85 85 85
P CP
C : Front panel centre line

15

35
Mounting
hole 2-ø11
(Note 1)

N Front connections

430
515

220
220
85

150
85
35
185

65
165 165(3P) t3 M8 screw 25
250(4P) earth terminal 50
41
180 180(3P)
265(4P) 82 250
CP 165(3P) 165
CP 175(3P) 250(4P)
240 240(3P) 175
260(4P) 102 165
325(4P)
17 194 Control circuit terminal cover (optional)
Lifting Conductor overlap max. Conductor overlap max.

18
hole 35 35
Front panel cut ON-OFF 15 15
81 button cover N
85 85 85

15.5 25 25 14.5 14.5 25 25 15.5


W
N 140
12

550 (Arc space)

25
Vertical terminals
550

W
460

490

149
335 ¶2

232
329

25 W
t2

150.5
W
76

6
33

20(max)
30

238
100

250 3-ø11
With UVT Controller ¶1 82 165 118 2-ø11
180 180(3P) M8 screw
9 365 earth terminal
265(4P) Mounting holes (Note 1)
Maintenance space
35 Conductor overlap max.
15
82

Panel cutout

52
25
165

2-ø11
Terminal size
Type t1 t2 t3 W N
85 85 85
AR208S 10 10 15 17.5
AR212S 10 10 15 17.5

t1
AR216S 20 15 25 22.5 165 165(3P) 4-ø14
250(4P) Horizontal terminals
AR220S 20 15 25 ——

174
Mounting holes
¶1: UVT controller is required when fixed type undervoltage
trip is fitted with AGR-11 OCR or Without OCR.
Note 1: The top 2 mounting holes should be only used for horizontal or
UVT controller can be mounted externally if required.
vertical type connections.
If externally mounted controller is required please specify

138
on order.
¶2: Panel cut should be 339 mm not 335 mm when the door
flange is used. Refer to page 43.
• N represents the neutral pole of 4-pole ACBs.
82 165 118
• Reverse power trip function is not available for Fixed type. M8 screw
365 earth terminal

48 49
5 Outline Dimensions
P
¡Type AR325S, AR332S,

conductor overlap. max


C
5
3-ø11 N 130 130 130
AR316H, AR320H, AR325H, AR332H Draw-out type

15
35
P
C : Front panel centre line
• With reverse power trip function, the length of the line side
main terminals become 55 mm longer, and the applicable ACBs
35
depend on the connection method of main terminals. Front connection

515

35 conductor overlap. max


Type Front connection Vertical terminal Horizontal terminal
AR325S — õ —
AR332S — õ — 83 88
AR316H õ — 11.5 25 25 21.5 28 25 25 10
AR320H õ —
AR325H õ —
AR332H õ —

65
õ : Available

15
25 10 28 21.5 11.5
— : Not available
318 25 25 25 25
88 83
380
CP CONNECTED position
TEST position P
C
Control circuit terminal cover
Maintenance ISOLATED position (optional)
2-ø20 N 5
rear panel cut 211.5 81 space 14 21
Lifting hole
130 130 130
front panel cut 17 194 35 conductor overlap. max
CP

18
15

12.5
78
ON-OFF button cover 30

25 25 25
N

100
12
Vertical terminal 65

232

12.5 12.5
9

120
4-ø11 54.5
335 ¶3
400

329

460

490

500
M8 screw

25 25 25
R earth terminal

100
11 140
6

32
165
12.5
50

40
33

60 7
25

30

27
250 94 141 110 21
With UVT Controller ¶1 9 345 40 29 20
216 216(3P) 238
draw-out handle 265 385 192.5(3P) ¶2
336(4P)
230 230(3P) 35 conductor overlap. max 312.5(4P) P
C
350(4P) 15
257 257(3P)
For fitted with breaker fixing bolts N 5

15
panel cut-out 377(4P)
130 130 130

25 25
293 293(3P)

80
413(4P)
Maintenance Maintenance
space space

15
94

3-ø11

30
¶1: UVT controller is required when fixed type undervoltage
141

trip is fitted with AGR-11 OCR or Without OCR.


UVT controller can be mounted externally if required.

154
If externally mounted controller is required please specify Horizontal terminal
on order.
¶2: Conductors including connecting bolts should be
separated min-7mm from Draw-out arm.

30
4-ø14

148
¶3: Panel cut should be 339 mm not 335 mm when the door
flange is used. Refer to page 43.
• N represents the neutral pole of 4-pole ACBs. 172.5 172.5(3P)
292.5(4P) Draw-out arm
• For High fault series vertical terminal is standard and
horizontal terminal is optional, and front connection is not 385 (comes out when breaker is drawn out)
available. Mounting holes

50 51
5 Outline Dimensions
¡Types: AR325S, AR332S Fixed type P
C

Conductor overlap max.


5
P N 130 130 130 3-ø11
P C

15
C : Front panel centre line

35
Mounting
hole
(Note 1)

N Front connections

515

220
220

85

Conductor overlap max.


85

35
65
185

35
10 28 21.5 11.5

15
217.5 217.5(3P) 25 M8 screw
337.5(4P) earth terminal 25 25 11.5 21.5 25 25 28 10
41
233 233(3P) 88 83
82 250 25 25 25 25
P 353(4P) 83 88
C P 332
C 228(3P)
293 293(3P) 228 222.5(3P) 212.5
348(4P) 102 165
413(4P) 342.5(4P)
17 194 Control circuit terminal cover (optional)
Lifting P

18
Conductor overlap max. C 5
hole 35 N
130 130 130
Front panel cut ON-OFF 15

12.5 25 25 25 12.5 12.5 25 25 25 12.5


81 button cover

140

100
N 12

550 (Arc space)


Vertical terminals
550

460

490

120
335 ¶2

232
329

100
165
76
6 20
33

20(max)
30

238
100

250 With UVT 4-ø11


Controller ¶1 82 165 118
233 233(3P) M8 screw
9 365 earth terminal
353(4P) Mounting holes
Maintenance space
(Note 1)
35 Conductor overlap max.
15
82

15
Panel cutout

25 25

80
165

15
3-ø11 P
C

N 5
130 130 130

30
217.5 217.5(3P) 4-ø14
337.5(4P) Horizontal terminals

154
Mounting holes
¶1: UVT controller is required when fixed type undervoltage
trip is fitted with AGR-11 OCR or Without OCR. Note 1: The top 2 mounting holes should be only used for horizontal or
UVT controller can be mounted externally if required. vertical type connections.

30
If externally mounted controller is required please specify

148
on order.
¶2: Panel cut should be 339 mm not 335 mm when the door
flange is used. Refer to page 43.
• N represents the neutral pole of 4-pole ACBs. 82 165 118
• Reverse power trip function is not available for Fixed type. M8 screw
365 earth terminal

52 53
5 Outline Dimensions
¡Types: AR440S Draw-out type
P
C : Front panel centre line

42.5(3P)
48(4P)
P
C

181
181

15
50
Control circuit terminal cover

181
CONNECTED position

15
TEST position
ISOLATED position

Lifting holes
rear panel cut ON-OFF 14 21
P button cover 2-ø20
front panel cut C 435.5(3P) 81 Maintenance 40(conductor overlap max.) P
194 C
P 605.5(4P) space
C 20 417(3P)

18
587(4P)
4-ø11

12.5
78
N 42.5

25
25

100
N 12

25
232

12.5 12.5
500
490
460

120
335 ¶3

400

329
17

25 25 25
100
16

140 30

40
165
50
R1

32
12.5
25

27
30

33

42.5 With UVT Controller ¶1


draw-out handle Front panel M8 screw
7
250 earth terminal
238
9 375 29
164 441(3P) ¶2
611(4P) 177 454(3P) 295 428 35 Rear panel Drow out arm
624(4P) (comes out when breaker
For fitted with breaker fixing bolts is drawn out)
94 141 193
Maintenance space 204 481(3P)
651(4P)
240 517(3P)
Panel cutout 687(4P)
4-ø14

397(3P)
567(4P)
P
¶1: UVT controller is required when fixed type undervoltage C

120
trip is fitted with AGR-11 OCR or Without OCR.
UVT controller can be mounted externally if required.
If externally mounted controller is required please specify
on order.
¶2: Conductors including connecting bolts should be
separated min-7mm from Draw-out arm.
¶3: Panel cut should be 339 mm not 335 mm when the door
flange is used. Refer to page 43.
• N represents the neutral pole of 4-pole ACBs.

54 55
6 Circuit Diagram (with AGR-11 OCR or without OCR)
¶4
CT for Control Motor charging/ Continuously-rated
Main circuit neutral line power Operation Operation circuit shunt trip Fixed type UVT Position switches Auxiliary switches
i{j
i{j i{j ¶1 i{j
` ` ` ON switch ` Common
PB

PB
¶3 Standard equipment Optional Optional
AUX.
SW
4c 3c 3c
01 11 05 02 12 03 10 09 08 18 28 24 30 151 141 131 121 111 211 311 411 511 611 711 811 911 011

S1 S3
UVT control circuit
CT1 CT3
Over-current release
(type AGR-11 OCR)
Ry LRC SHT ¶2

S2 M

CT2
MHT UVT

19 29 21 15 25 06 16 26 17 27 22 20 154 152 144 142 134 132 124 122 114 112 214 212 314 312 414 412 514 512 614 612 714 712 814 812 914 912 014 012

K k X X X X X X X
CT for
neutral line ` ` `
L R i|j i|j i|j

i
05 and 15
For single-contact indication only 05
Terminal description Position switches Operation/control circuits Auxiliary switches
Check OCR voltage before connecting. Top 151 141 131 121 01 02 03 04 05 06 07 08 09 10 111 211 311 411 511 611 711 811 911 011
Middle 154 144 134 124 11 12 13 14 15 16 17 18 19 20 114 214 314 414 514 614 714 814 914 014
‚1¤1Control power supply AC200 - 240V, DC200 - 250V, DC48V ‚1⁄1Control power supply AC100 - 120V ⁄1¤1Control power supply DC100 - 125V, DC24V Bottom 152 142 132 122 21 22 23 24 25 26 27 28 29 30 112 212 312 412 512 612 712 812 912 012
‚2¤2Operation power supply AC100 - 240V, DC100 - 220V, DC24V, DC48V ⁄2Operation switch, common ‚3ON switch (Standard 4c + optional 6c arrangement)
‚5Operation indication terminal, common ⁄5LT trip indication or single-contact indication ¤5ST/INST trip indication ‚6PTA indication Top 131 121 111 211 311 411
⁄6GF trip indication ¤6System alarm indication ⁄7Trip indication ¤7Spring charge indicator ⁄0¤0Continuously-rated shunt trip Middle 134 124 114 214 314 414
Bottom 132 122 112 212 312 412
⁄9Separate CT for neutral line (k) ¤9Separate CT for neutral line (R) ‚8,⁄8,¤8UVT power supply ‚9UVT power supply common (Standard 4c arrangement)
UVT power supply
Term. AC 100V AC 200V AC 400V
No. coil coil coil
‚8-‚9 100V 200V 380V
Designation of terminals for auxiliary and position switches
Symbols for accessories ⁄8-‚9 110V 220V 415V CONNECTED position : 121–124 ON
¤8-‚9 120V 240V 440V * * * 121–122 OFF
1: Common, 2: b-contact, 4: a-contact
CT1 - CT3 : Power CTs TEST position : 131–134 ON
S1 - S3 : Current sensors 1: Auxiliary switch 131–132 OFF
M : Charging motor ¶1: Do not connect “b”contact of auxiliary switch to ON switch 2: Position switch (for CONNECTED) ISOLATED position : 141–144 ON
LRC : Latch release coil in series, otherwise, pumping may occur. 3: Position switch (for TEST) 141–142 OFF
MHT : Magnetic Hold Trigger ¶2: See P. 21 for the circuit diagram of the continuously-rated 4: Position switch (for ISOLATED) INSERT position : 151–154 ON
Isolating terminal connector 5: Position switch (for INSERT) 151–152 OFF
(for draw-out type) shunt trip device with capacitor trip device.
Manual connector
User wiring
¶3: Use “a” contact of auxiliary switch of ACB. ( 1A,–B,0:C:Switch numbers
Auxiliary switches for microload
For operation sequence of
position switches, see page 17.
X Relay or indicator lamp ¶4: For motor split circuit, terminals ‚2 , ¤2 and ‚3 , ‚4 are
used for charging and closing operation respectively.

56 57
6 Circuit Diagram (with AGR-21, 22 OCR)
Main circuit Operation circuit CT for Control
Operation UVT/RPT/APR-1P/ Continuously-rated Position switches Auxiliary switches
neutral line power APR-1CMM/AGR-22 shunt trip
i{j OCR i{j
i{j ¶4 i{j
` ON OFF reset ` ` R-phase S-phase T-phase `
switch switch switch

Standard equipment Optional Optional

4c 3c 3c
02 12 03 13 23 04 14 01 11 05 08 18 28 10 151 141 131 121 111 211 311 411 511 611 711 811 911 011

S1 S3

CT1 CT3 Over-current release (type AGR-21, 22 OCR)

SHT ¶5

S2

CT2
M LRC TC

22 19 29 21 15 25 06 16 26 07 17 27 09 20 154 152 144 142 134 132 124 122 114 112 214 212 314 312 414 412 514 512 614 612 714 712 814 812 914 912 014 012

` ` `
K
i|j i|j
X X X X X X X X Detection of i|j
k N-phase voltage
CT for
neutral line
L R

i
05 and 15
For single-contact indication only 05
Terminal description Position switches Operation/control circuits Auxiliary switches
Check OCR voltage before connecting. Top 151 141 131 121 01 02 03 04 05 06 07 08 09 10 111 211 311 411 511 611 711 811 911 011
Middle 154 144 134 124 11 12 13 14 15 16 17 18 19 20 114 214 314 414 514 614 714 814 914 014
‚1¤1Control power supply AC200 - 240V, DC200 - 250V, DC48V ‚1⁄1Control power supply AC100 - 120V ⁄1¤1Control power supply DC100 - 125V, DC24V Bottom 152 142 132 122 21 22 23 24 25 26 27 28 29 30 112 212 312 412 512 612 712 812 912 012
‚2¤2Operation power supply AC100 - 240V, DC100 - 250V, DC24V, DC48V ⁄2Operation switch, common ‚3ON switch ¶1 ⁄3OFF switch ¶1 ¤3OCR reset switch ¶1 (Standard 4c + optional 6c arrangement)
‚4Operation switch for signal separation ¶2 ⁄4Operation switch for signal separation ¶2 ¤4 —— ‚5Operation indication terminal, common Top 131 121 111 211 311 411
⁄5LT trip indication or single-contact indication ¤5ST/INST trip indication ‚6PTA indication ⁄6GF, RPT or ELT trip indication ¤6System alarm indication ‚7HEAT indication Middle 134 124 114 214 314 414
Bottom 132 122 112 212 312 412
⁄7UVT indication ¶3 ¤7Spring charge indicator or PTA2 ‚8⁄8¤8UVT/RPT power supply R.S.T. (Max. AC460V) (Standard 4c arrangement)
‚9N-phase voltage detection ⁄9Separate CT for neutral line (k) ¤9Separate CT for neutral line (R) ⁄0¤0Continuously-rated shunt trip ‹0 ——

¶1: Operation input signal is rated at DC40V 5mA.


Symbols for accessories ¶2: Used for separation of operation input signals. Designation of terminals for auxiliary and position switches
CONNECTED position : 121–124 ON
¶3: Can be used for trip indicator in place of UVT indication.
* * * 121–122 OFF
¶4: For AGR-22 OCR connect the measured power source 1: Common, 2: b-contact, 4: a-contact
CT1 - CT3 : Power CTs TEST position : 131–134 ON
S1 - S3 : Current sensors to the terminals, ‚8, ⁄8, ¤8, ‚9. 1: Auxiliary switch 131–132 OFF
M : Charging motor In case of no reverse 2: Position switch (for CONNECTED)
R-phase S-phase ISOLATED position : 141–144 ON
LRC : Latch release coil power trip function with 3: Position switch (for TEST) 141–142 OFF
TC : Tripping coil AGR-21 OCR, UVT can 4: Position switch (for ISOLATED) INSERT position : 151–154 ON
be used with single 5: Position switch (for INSERT)
Isolating terminal connector 151–152 OFF
(for draw-out type) phase power supply as 08 18 28
Manual connector
User wiring
right.
¶5: See P. 21 for the circuit diagram of the continuously-rated ( 1A,–B,0:C:Switch numbers
Auxiliary switches for microload
For operation sequence of
position switches, see page 17.
X Relay or indicator lamp shunt trip device with capacitor trip device.

58 59
7 Technical Data
Dielectric strength

Rated Impulse withstand


Circuit Withstand voltage (at 50/60 Hz) voltage Uimp
Main circuit Between terminals, AC3500V for 1 minute 12kV
terminal group to earth
Auxiliary switches For general service Terminal group to earth AC2500V for 1 minute 6kV
Control circuits

For microload Terminal group to earth AC2000V for 1 minute 4kV


Position switches Terminal group to earth AC2000V for 1 minute 4kV
Over-current release (OCR) Terminal group to earth AC2000V for 1 minute 4kV
Power supply for undervoltage/ Terminal group to earth AC2500V for 1 minute 6kV
reverse power trip function
Other accessories Terminal group to earth AC2000V for 1 minute 4kV
Note: The values shown above are those measured on phase connections and cannot be applied to control terminals on the ACB.

Internal resistance and power consumption


• Standard Series
Type AR208S AR212S AR216S AR220S AR325S AR332S AR440S
Rated current (A) 800 1250 1600 2000 2500 3200 4000
DC internal resistance per pole (mΩ) 0.030 0.030 0.028 0.024 0.014 0.014 0.014
AC power consumption for 3 poles (W) 170 310 350 490 600 780 1060

• High fault Series


Type AR212H AR216H AR220H AR316H AR320H AR325H AR332H
Rated current (A) 1250 1600 2000 1600 2000 2500 3200
DC internal resistance per pole (mΩ) 0.024 0.024 0.024 0.014 0.014 0.014 0.014
AC power consumption for 3 poles (W) 260 350 490 310 430 600 780

60
8 Order Form (With AGR-11 OCR or Without OCR)
For general feeder circuits (L/R-characteristic)
Please check boxes and fill in underlined spaces as appropriate.
Your company name: Order Number:
________________________________________________________________ __________________________________
Quantity Delivery time required
_________ _________ _________
Your specifications
z Type † AR208S † AR212S † AR216S † AR220S † AR325S † AR332S † AR440S
† AR212H † AR216H † AR220H † AR316H † AR320H † AR325H † AR332H
x Number of poles † 3-pole † 4-pole
For the requirement of 2-pole type, specify 3-pole type and use 2 poles on both sides.
c Circuit voltage and frequency AC______V. ______Hz. DC______V. † 3ø3W † 3ø4W
v Applicable standard and Applicable standard
ambient temperature
† 40°C † 45°C
b Type of mounting † Fixed type
† Draw-out type † Draw-out handle _______ pcs. † Mal-insertion prevention device
† Draw-out storage handle _______ pcs. ¶1 Code _ _ __ pcs, Code _ _ __ pcs, Code _ _ __ pcs
† Main circuit safety shutter † Position switches type ALR–________P
† Padlocking unit † Door interlock
† Control circuit safety shutter † Lifting plates
† Test jumper (lead wire 5m) ______ sets † Earthing device
† Breaker fixing bolts † Inter-pole barrier
Line side: †Horizontal terminals †Vertical terminals †Front connections
Load side: †Horizontal terminals †Vertical terminals †Front connections
Control circuit terminals: †Tab terminals †Screw terminals
n Type of spring charged operation † Manual charging
† Motor charging Supply voltage AC_____V, DC_____V
† Step-down transformer _____sets
† Automatic closing spring release
† Spring charge indicator

m Over-current release (OCR) a OCR type AGR–11†–†††


N: N-phase protection
s Control power
AC100–120V DC100–125V DC24V

AC200–240V )Common †
DC200–250V )
Common †
DC48V
Common)
d Rated primary current [ICT] ______A
f Rated current [In] ______A
at 600% [IR] for L-char.
g LT [IR] _____A ([In] ~ _____%) [tR] ______s
at 300% [IR] for R-char.
h ST [Isd] _____A ([In] ~ _____%) [tsd] ______ms
j † INST † MCR [I i] _____A ([In] ~ _____%) ¶2
k PTA [IP1] _____A ([In] ~ _____%) [tP1] ______s at [IP1] or more
l GF [Ig] _____A ([ICT] ~ _____%) [tg]______ms
† CT for neutral line
¡0 NP [IN] _____A ([ICT] ~ _____%) (Factory set to a fixed value)
, Electrical tripping devices † Continuously-rated shunt trip device AC_____V, DC_____V † Capacitor trip device
† Fixed type Undervoltage Trip AC_____V, DC_____V ¶3, † AUR-1BS † AUR-1BD
. Other accessories † ON-OFF cycle counter † Control circuit terminal cover
† Auxiliary switches type AXR–_____ † IP55 cover
† Key lock († Lock-in OFF † Lock-in ON) † OFF padlock
† Key interlock († Cylinder lock † Castell lock) (Castell lock not supplied) † Door flange († IP20 † IP31)
† Mechanical interlock † Trip indicator
P1: mm P2: mm
ACB A: Type poles
ACB B: Type poles
ACB C: Type poles
⁄0 Special environment specification † Not required
† Tropicalization (fungus and moisture treatment) † Cold climate treatment † Anti-corrosion treatment
⁄1 Spare parts † Not required † Required (Contact Terasaki for recommended spare parts)
⁄2 Test report † English ____ copies
⁄3 Other † Lifter
† OCR checker with AC100–110V power supply † OCR checker with AC100–240V power supply + Type C plug
¶1: When you require the Draw-out storage handle, please specify with ACBs on order.
¶2: When the AR-H High fault series ACBs are used without Instantaneous trip function MCR should be set to work.
The rated breaking capacity will reduce to the level of the latching current without MCR function.
¶3: Fixed type Undervoltage Trip can not be fitted with shunt trip device. However, Instantaneously rated shunt trip can be used together with fixed type undervoltage trip
with special specification. Contact terasaki for details.

62
8 Order Form (With AGR-21,22 OCR)
For general feeder circuits (L/R-characteristic)
Please check boxes and fill in underlined spaces as appropriate.
Your company name: Order Number:
________________________________________________________________ __________________________________
Quantity Delivery time required
_________ _________ _________
Your specifications
z Type † AR208S † AR212S † AR216S † AR220S † AR325S † AR332S † AR440S
† AR212H † AR216H † AR220H † AR316H † AR320H † AR325H † AR332H
x Number of poles † 3-pole † 4-pole
For the requirement of 2-pole type, specify 3-pole type and use 2 poles on both sides.
c Circuit voltage and frequency AC______V. ______Hz. DC______V. † 3ø3W † 3ø4W
v Applicable standard and Applicable standard
ambient temperature
† 40°C † 45°C
b Type of mounting † Fixed type
† Draw-out type † Draw-out handle _______ pcs. † Mal-insertion prevention device
† Draw-out storage handle _______ pcs. ¶1 Code _ _ __ pcs, Code _ _ __ pcs, Code _ _ __ pcs
† Main circuit safety shutter † Position switches type ALR–________P
† Padlocking unit † Door interlock
† Control circuit safety shutter † Lifting plates
† Test jumper (lead wire 5m) ______ sets † Earthing device
† Breaker fixing bolts † Inter-pole barrier
Line side: †Horizontal terminals †Vertical terminals †Front connections
Load side: †Horizontal terminals †Vertical terminals †Front connections
Control circuit terminals: †Tab terminals †Screw terminals
n Type of spring charged operation † Manual charging † Motor charging Supply voltage AC_____V, DC_____V
† Step-down transformer _____sets
† Automatic closing spring release

m Over-current release (OCR) a OCR type AGR–2††–††††††††


C : Communication function (MODBUS)
P : Operation panel ¶3
AGR–22 O : Contact temperature monitoring 155°C ¶3
(Contact TERASAKI for details) N : N-phase protection
s Control power
AC100–120V DC100–125V DC24V

AC200–240V )Common †
DC200–250V )
Common †
DC48V )
Common

d Rated primary current [ICT] ______A


f Rated current [In] ______A
g UVT rated supply voltage [Uc] ______V
at 600% [IR] for L-char.
h LT [IR] _____A ([In] ~ _____%) [tR] ______s
at 300% [IR] for R-char. ¡4 Power supply unit for
j ST [Isd] _____A ([In] ~ _____%) [tsd] ______ms communication
k † INST † MCR [I i] _____A ([In] ~ _____%) ¶4 AC100–120V, 200–240V

l PTA [IP1] _____A ([In] ~ _____%) [tP1] ______s at [IP1] or more DC100–125V, 200–250V
¡0 GF [Ig] _____A ([ICT] ~ _____%) [tg]______ms † DC24V
† CT for neutral line † DC48V
¡1 NP [IN] _____A ([ICT] ~ _____%) (Factory set to a fixed value)
¡2 ELT [I∆R] _____A [t∆R] ______ms
¡3 UVT Pick-up voltage setting _____V ([Uc] ~ _____%) Time setting ____s
, Electrical tripping devices † Tripping coil TC ¶2 † Continuously-rated shunt trip device AC_____V, DC_____V
† Capacitor trip device
. Other accessories † Operation panel † Mechanical interlock
† ON-OFF cycle counter P1: mm P2: mm
† Auxiliary switches type AXR–_____ ACB A: Type poles
† Manual reset device (Contact TERASAKI for details) ACB B: Type poles
† Key lock († Lock-in OFF † Lock-in ON) ACB C: Type poles
† Key interlock († Cylinder lock † Castell lock) (Castell lock not supplied) † Control circuit terminal cover
† IP55 cover
† OFF padlock
† Door flange († IP20 † IP31)

⁄0 Special environment specification † Not required


† Tropicalization (fungus and moisture treatment) † Cold climate treatment † Anti-corrosion treatment
⁄1 Spare parts † Not required † Required (Contact Terasaki for recommended spare parts)
⁄2 Test report † English ____ copies
⁄3 Other † Lifter
† OCR checker with AC100–110V power supply † OCR checker with AC100–240V power supply + Type C plug
¶1: When you require the Draw-out storage handle, please specify with ACBs on order. ¶2: The tripping coil comes standard with ACBs equipped with OCR.
¶3: Available for AGR-21 only ¶4: When the AR-H High fault series ACBs are used without Instantaneous trip function MCR should be set to work. The rated breaking
capacity will reduce to the level of the latching current without MCR function.

63
8 Order Form (With AGR-11 OCR or Without OCR)
For generator protection (S-characteristic)
Please check boxes and fill in underlined spaces as appropriate.
Your company name: Order Number:
________________________________________________________________ __________________________________
Quantity Delivery time required
_________ _________ _________
Your specifications
z Type † AR208S † AR212S † AR216S † AR220S † AR325S † AR332S † AR440S
† AR212H † AR216H † AR220H † AR316H † AR320H † AR325H † AR332H
x Number of poles † 3-pole † 4-pole
For the requirement of 2-pole type, specify 3-pole type and use 2 poles on both sides.
c Circuit voltage and frequency AC______V. ______Hz. DC______V. † 3ø3W † 3ø4W
v Applicable standard and Applicable standard
ambient temperature
† 40°C † 45°C
b Type of mounting † Fixed type
† Draw-out type † Draw-out handle _______ pcs. † Mal-insertion prevention device
† Draw-out storage handle _______ pcs. ¶1 Code _ _ __ pcs, Code _ _ __ pcs, Code _ _ __ pcs
† Main circuit safety shutter † Position switches type ALR–________P
† Padlocking unit † Door interlock
† Control circuit safety shutter † Lifting plates
† Test jumper (lead wire 5m) ______ sets † Earthing device
† Breaker fixing bolts † Inter-pole barrier
Line side: †Horizontal terminals †Vertical terminals †Front connections
Load side: †Horizontal terminals †Vertical terminals †Front connections
Control circuit terminals: †Tab terminals †Screw terminals
n Type of spring charged operation † Manual charging
† Motor charging Supply voltage AC_____V, DC_____V
† Step-down transformer _____sets
† Automatic closing spring release
† Spring charge indicator

m Over-current release (OCR) a OCR type AGR–11S–††


s Control power
AC100–120V DC100–125V DC24V

AC200–240V )
Common †
DC200–250V )
Common †
DC48V
Common )
d Rated primary current [ICT] ______A
f Generator rated current [In] ______A
g LT [IR] _____A ([In] ~ _____%) [tR] ______s at 120% [IR]
h ST [Isd] _____A ([In] ~ _____%) [tsd] ______ms
j † INST † MCR [I i] _____A ([In] ~ _____%) ¶3
k PTA [IP1] _____A ([In] ~ _____%) [tP1] ______s at [IP1] or more
, Electrical tripping devices † Continuously-rated shunt trip device AC_____V, DC_____V † Capacitor trip device
† Fixed type Undervoltage Trip AC_____V, DC_____V ¶2, † AUR-1BS † AUR-1BD
. Other accessories † ON-OFF cycle counter † Control circuit terminal cover
† Auxiliary switches type AXR–_____ † IP55 cover
† Key lock († Lock-in OFF † Lock-in ON) † OFF padlock
† Key interlock († Cylinder lock † Castell lock) (Castell lock not supplied) † Door flange († IP20 † IP31)
† Mechanical interlock † Trip indicator
P1: mm P2: mm
ACB A: Type poles
ACB B: Type poles
ACB C: Type poles
⁄0 Special environment specification † Not required
† Tropicalization (fungus and moisture treatment) † Cold climate treatment † Anti-corrosion treatment
⁄1 Spare parts † Not required † Required (Contact Terasaki for recommended spare parts)
⁄2 Test report † English ____ copies
⁄3 Other † Lifter
† OCR checker with AC100–110V power supply † OCR checker with AC100–240V power supply + Type C plug
¶1: When you require the Draw-out storage handle, please specify with ACBs on order.
¶2: Fixed type Undervoltage Trip can not be fitted with shunt trip device. However, Instantaneously rated shunt trip can be used together with fixed type undervoltage trip
with special specification. Contact terasaki for details.
¶3: When the AR-H High fault series ACBs are used without Instantaneous trip function MCR should be set to work.
The rated breaking capacity will reduce to the level of the latching current without MCR function.

64
Derating
• Standard Series
Based Ambient Type AR208S AR212S AR216S AR220S AR325S AR332S AR440S
Standards temperature Connecting 2~50~5t 2~80~5t 2~100~5t 3~100~5t 2~100~10t 3~100~10t 4~150~6t
(°C) bar sizes
IEC60947-2 40 (Standard ambient 800 1250 1600 2000 2500 3200 4000
EN 60947-2 temperature)
AS3947.2 45 800 1250 1600 2000 2500 3200 4000
JIS C8201-2
50 800 1250 1600 2000 2500 3200 4000
55 800 1250 1600 1820 2500 2990 4000
60 800 1250 1460 1740 2400 2850 3760
NEMA, SG-3 40 (Standard ambient 800 1250 1540 2000 2500 3200 3700
ANSI C37.13 temperature)
45 800 1240 1470 1960 2500 3010 3580
50 800 1180 1390 1860 2440 2860 3470
55 800 1110 1310 1750 2300 2690 3350
60 800 1040 1230 1640 2150 2520 3150
JIS C8372 40 (Standard ambient 800 1250 1600 2000 2500 3200 3700
temperature)
45 800 1250 1600 1900 2470 2900 3580
50 800 1250 1540 1820 2400 2800 3470
55 800 1250 1460 1740 2310 2710 3350
60 800 1230 1390 1650 2230 2610 3230

Note: The values are applicable for both Draw-out type and Fixed type.
The values of AR208S, AR212S and AR216S are for horizontal terminals on both line and load side.
The values of AR220S, AR325S, AR332S and AR440S are for vertical terminals on both line and load side.
Above figures are subject to the design of the enclosure and rating of busbar.

• High fault Series


Based Ambient Type AR212H AR216H AR220H AR316H AR320H AR325H AR332H
Standards temperature Connecting 2~80~5t 2~100~5t 3~100~5t 2~100~5t 3~100~5t 2~100~10t 3~100~10t
(°C) bar sizes
IEC60947-2 40 (Standard ambient 1250 1600 2000 1600 2000 2500 3200
EN 60947-2 temperature)
AS3947.2 45 1250 1600 2000 1600 2000 2500 3200
JIS C8201-2
50 1250 1600 2000 1600 2000 2500 3200
55 1250 1600 1820 1600 2000 2500 2990
60 1250 1550 1740 1600 2000 2400 2850
NEMA, SG-3 40 (Standard ambient ¶ 1600 2000 ¶ ¶ 2500 3200
ANSI C37.13 temperature)
45 ¶ 1560 1960 ¶ ¶ 2500 3010
50 ¶ 1480 1860 ¶ ¶ 2440 2860
55 ¶ 1390 1750 ¶ ¶ 2300 2690
60 ¶ 1300 1640 ¶ ¶ 2150 2520
JIS C8372 40 (Standard ambient 1250 1600 2000 1600 2000 2500 3200
temperature)
45 1250 1600 1900 1600 2000 2500 2900
50 1250 1600 1820 1600 2000 2500 2800
55 1250 1550 1740 1600 2000 2400 2710
60 1250 1480 1650 1600 1900 2280 2610

Note: The values are for vertical terminals on both line and load side.
Above figures are subject to the design of the enclosure and rating of busbar.
¶: Contact Terasaki for details.

61
8 Order Form (With AGR-21,22 OCR)
For generator protection (S-characteristic)
Please check boxes and fill in underlined spaces as appropriate.
Your company name: Order Number:
________________________________________________________________ __________________________________
Quantity Delivery time required
_________ _________ _________
Your specifications
z Type † AR208S † AR212S † AR216S † AR220S † AR325S † AR332S † AR440S
† AR212H † AR216H † AR220H † AR316H † AR320H † AR325H † AR332H
x Number of poles † 3-pole † 4-pole
For the requirement of 2-pole type, specify 3-pole type and use 2 poles on both sides.
c Circuit voltage and frequency AC______V. ______Hz. DC______V. † 3ø3W † 3ø4W
v Applicable standard and Applicable standard
ambient temperature
† 40°C † 45°C
b Type of mounting † Fixed type
† Draw-out type † Draw-out handle _______ pcs. † Mal-insertion prevention device
† Draw-out storage handle _______ pcs. ¶1 Code _ _ __ pcs, Code _ _ __ pcs, Code _ _ __ pcs
† Main circuit safety shutter † Position switches type ALR–________P
† Padlocking unit † Door interlock
† Control circuit safety shutter † Lifting plates
† Test jumper (lead wire 5m) ______ sets † Earthing device
† Breaker fixing bolts † Inter-pole barrier
Line side: †Horizontal terminals †Vertical terminals †Front connections
Load side: †Horizontal terminals †Vertical terminals †Front connections
Control circuit terminals: †Tab terminals †Screw terminals
n Type of spring charged operation † Manual charging
† Motor charging Supply voltage AC_____V, DC_____V
† Step-down transformer _____sets
† Automatic closing spring release

m Over-current release (OCR) a OCR type AGR–2†S–†††††††


AGR–22 C : Communication function (MODBUS)
(Contact TERASAKI for details) P : Operation panel ¶2
O : Contact temperature monitoring 155°C ¶2
s Control power
AC100–120V DC100–125V DC24V

AC200–240V )
Common †
DC200–250V )
Common †
DC48V
Common )
d Rated primary current [ICT] ______A
f Generator rated current [In] ______A
g RPT/UVT rated supply voltage [Uc] ______V ¡3 Power supply unit for
h LT [IR] _____A ([In] ~ _____%) [tR] ______s at 120% [IR] communication
j ST [Isd] _____A ([In] ~ _____%) [tsd] ______ms AC100–120V, 200–240V

k † INST † MCR [I i] _____A ([In] ~ _____%) ¶3 DC100–125V, 200–250V
l PTA [IP1] _____A ([In] ~ _____%) [tP1] ______s at [IP1] or more † DC24V
¡0 PTA2 [IP2] _____A ([In] ~ _____%) † DC48V
¡1 RPT [PR] _____kW ([Pn] ~ _____%) Time setting ______s at [PR] ¶4
¡2 UVT Pick-up voltage setting _____V ([Uc] ~ _____%) Time setting ____s
, Electrical tripping devices † Tripping coil TC ¶5 † Continuously-rated shunt trip device AC_____V, DC_____V
† Capacitor trip device
. Other accessories † Operation panel † Mechanical interlock
† ON-OFF cycle counter P1: mm P2: mm
† Auxiliary switches type AXR–_____ ACB A: Type poles
† Manual reset device (Contact TERASAKI for details) ACB B: Type poles
† Key lock († Lock-in OFF † Lock-in ON) ACB C: Type poles
† Key interlock († Cylinder lock † Castell lock) (Castell lock not supplied) † Control circuit terminal cover
† IP55 cover
† OFF padlock
† Door flange († IP20 † IP31)

⁄0 Special environment specification † Not required


† Tropicalization (fungus and moisture treatment) † Cold climate treatment † Anti-corrosion treatment
⁄1 Spare parts † Not required † Required (Contact Terasaki for recommended spare parts)
⁄2 Test report † English ____ copies
⁄3 Other † Lifter
† OCR checker with AC100–110V power supply † OCR checker with AC100–240V power supply + Type C plug
¶1: When you require the Draw-out storage handle, please specify with ACBs on order.
¶2: Available for AGR-21 only
¶3: When the AR-H High fault series ACBs are used without Instantaneous trip function MCR should be set to work.
The rated breaking capacity will reduce to the level of the latching current without MCR function.
¶4: CT for RPT is not provided in the case of AR440S.
¶5: The tripping coil comes standard with ACBs equipped with OCR..

65