CEP Plate and Frame HX
CEP Plate and Frame HX
CEP Plate and Frame HX
Designing
Plate-and-Frame
Heat Exchangers
Christopher Haslego,
Alfa Laval Use these design charts for preliminary sizing.
Graham Polley,
www.pinchtechnology.com
W/m2-K
2,000 2.5 cP changer at 60°F and leaves at 168°F.
9,000 The average viscosity of the water
1,500
5 cP passing through the unit is 0.33 cP
1,000 6,000
10 cP
and the average viscosity of the oil in
3,000 the unit is 215 cP. The maximum-
500 100 cP allowable pressure drop through the
0 plate heat exchanger is 15 psi on the
5 10 15 20 25 30
hot and cold sides.
Pressure Drop, psi Step 1: Calculate the LMTD.
From Eq. 1, LMTD = [(200 – 168)
■ Figure 2. Heat-transfer correlations for water-based fluids, 0.25 < NTU < 2.0. – (175 – 60)]/ln[(200 – 168)/(175 –
60)] = 64.9°F.
Pressure Drop, kPa
Step 2: Calculate NTUhot and
NTUcold. From Eqs. 2 and 3, NTUhot =
50 100 150 200 (200 – 175)/64.9 = 0.38 and NTUcold
h = Local Heat-Transfer Coefficient,
12,000
W/m2-K
2,000 2.5 cP < 2.0. Although there is not a vis-
9,000
cosity line for 215 cP, the line repre-
1,500 senting 100 cP can be used for vis-
5 cP
1,000 6,000 cosities up to about 400–500 cP. The
10 cP
heat exchanger will be pressure-
500 3,000 drop-limited and the heat-transfer
100 cP
coefficient will not change apprecia-
0
5 10 15 20 25 30 bly over this viscosity range for
plate-and-frame exchangers. Read-
Pressure Drop, psi
ing from the chart, a pressure drop
of 15 psi corresponds to hhot ≈ 50
■ Figure 3. Heat-transfer correlations for water-based fluids, 2.0 < NTU < 4.0. Btu/h-ft2-°F.
Step 4: Read hcold from the chart.
Pressure Drop, kPa Use Figure 2, which applies to water-
based liquids when 0.25 < NTU < 2.0.
50 100 150 200
Again, the exact viscosity line needed
h = Local Heat-Transfer Coefficient,
3,500
18,000 for pure water (0.33 cP) in this case is
3,000 Water-Based Fluids not available. However, the 1.0 cP
15,000 line provides a very good estimate of
2,500 1 cP the heat-transfer coefficient for pure
Btu/h-ft2-˚F
12,000
W/m2-K
Btu/h-ft2-˚F
brine enters the exchanger at 50°F 600
W/m2-K
and leaves at 171°F. The average 3,000
2.5 cP
viscosity of the water passing 400 2,400
through the unit is 0.46 cP and the 5 cP
average viscosity of the brine in the 1,600
200 10 cP
unit is 1.10 cP. The maximum-allow- 800
able pressure drop through the plate 100 cP
heat exchanger is 10 psi on the hot 0
5 10 15 20 25 30
(water) side and 20 psi on the cold
(brine) side. Pressure Drop, psi
The LMTD is calculated to be
38.5°F. NTUhot and NTUcold are 2.59 ■ Figure 5. Heat-transfer correlations for hydrocarbons, 0.25 < NTU < 2.0.
and 3.14, respectively. From the
charts for 2.0 < NTU < 4.0 (water
based), hhot ≈ 2,000 Btu/h-ft2-°F Pressure Drop, kPa
and hcold ≈ 2,500 Btu/h-ft2-°F. Al- 50 100 150 200
h = Local Heat-Transfer Coefficient,
1,000
1 cP
sizing. U is calculated to be 918 600
W/m2-K
2 3,000
Btu/h-ft -°F.
2.5 cP 2,400
400
Implications of size reduction
5 cP 1,600
Alternative technologies offer 10 cP
200
significant size advantages over 800
shell-and-tube heat exchangers. 100 cP
1,000
structural steel used to support the 5,400
plant can be reduced, and because 800 4,600
of the weight saving, the load on Hydrocarbon-Based Fluids
1 cP
600
W/m2-K