Process and Control System (General)
Process and Control System (General)
Sponsored Links
A Process Flow Diagram - PFD - (or System Flow Diagram - SFD) shows the relationships between the
major components in the system. PFD also tabulate process design values for the components in
different operating modes, typical minimum, normal and maximum. A PFD does not show minor
components, piping systems, piping ratings and designations.
Process Piping
Major equipment symbols, names and identification numbers
Control, valves and valves that affect operation of the system
Interconnection with other systems
Major bypass and recirculation lines
System ratings and operational values as minimum, normal and
maximum flow, temperature and pressure
Composition of fluids
pipe class
pipe line numbers
minor bypass lines
isolation and shutoff valves
maintenance vents and drains
relief and safety valve
code class information
seismic class information
P&ID shows all of piping including the physical sequence of branches, reducers, valves,
equipment, instrumentation and control interlocks.
The block or rectangles used represent a unit operation. The blocks are connected by straight
lines which represent the process flow streams which flow between the units. These process flow
In order to prepare clear, easy to understand and unambiguous block flow diagrams a number of
rules should be followed:
unit operations such as mixers, separators, reactors, distillation columns and heat
exchangers are usually denoted by a simple block or rectangle.
groups of unit operations may be noted by a single block or rectangle.
process flow streams flowing into and out of the blocks are represented by neatly
drawn straight lines. These lines should either be horizontal or vertical.
the direction of flow of each of the process flow streams must be clearly indicated
by arrows.
flow streams should be numbered sequentially in a logical order.
unit operations (i.e., blocks) should be labeled.
where possible the diagram should be arranged so that the process material flows
from left to right, with upstream units on the left and downstream units on the
right.
Analog Signal
Analog signals are like voltage or electric current signal, representing temperature, pressure, level
etc. Usually the electrical current signal is of magnitude 4-20 mA where 4 mA is the minimum
point of span and 20 mA is the maximum point of span.
Auto Mode
In auto mode the output is calculated by the controller using the error signal - the difference
between set point and the process variable.
Closed Loop
Controller in automatic mode.
Cascade
Two or more controllers working together. The output of the master controller is the set point for
the "slave" controller.
Controller Output - CO
Output signal from the controller.
Dead Band
The range through witch an input can be varied without initiating a response.
Dead Time
Dead time is the amount of time it takes for the process variable to start changing after changing
output as a control valve, variable frequency drive etc.
Derivative - D
The derivative - D - part of a PID controller. With derivative action the controller output is
proportional to the rate of change of the process variable or process error.
Delay
A term commonly used in stead of dead time.
Digital Signal
A discrete value at which an action is performed. A digital signal is a binary signal with two
distinct states - 1 or 0, often used as an on - off indication.
Discrete Logic
Refers to digital "on - off" logic.
Discrete I/O
On or off signals sent or received to the field.
Error
In the control loop the error = set point - process value.
Gain
Gain = 100 / Proportional Band. More gain in the controller gives a faster loop response and a
more oscillatory (unstable) process.
Gain in the process is defined as the change in input divided by the change in output. A process
with high gain will react more to the controller output changing.
Gain Margin
The difference in the logarithms of the amplitude ratios at the frequency where the combined
phase angle is 180 degrees lag is the gain margin.
Hysteresis
The signal change before the output unit (valve or similar) moves.
Input/Output - I/O
Electronic hardware where the field devices are wired.
Integral Action - I
The integral part of the PID controller. With integral action, the controller output is proportional to
the amount and duration of the error signal. If there is more integral action, the controller output
will change more when error is present.
Load Upset
An upset to the process not from changing the set-point.
Measurement
Measurement is the same as the process value.
Manual Mode
In manual mode the output is set manual.
Mode
The controller can be set in auto, manual, or remote mode.
Output
Output of the controller.
Overshoot
The amount a process exceed the set point during a change in the system load or change in the
set point.
PID Controller
Controller including Proportional, Integrating and Derivative controller functions. Cfr. ANSI/IEE
Standard 100-1977.
Process Value - PV
The actual value in the control loop, temperature, pressure, flow, composition, pH, etc
Process Variable - PV
The actual value in the control loop, temperature, pressure, flow, composition, pH, etc. See
Process Value.
Proportional Band - P
With proportional band the controller output is proportional to the error or a change in process
variable. Proportional Band = 100/Gain
Rate
Same as the derivative or "D" part of PID controllers.
Register
A data storage location in a PLC.
Regulator
A controller changing the a output variable to move the process variable back to the set point
Reset
Same as the integral or "I" part of PID controllers.
Reset Windup
Integral action continuing to change the controller output value after the actual output reaches a
physical limit.
Response Time
The rate of interrogating a transmitter.
Sample Interval
The rate at which a controller samples the process variable and calculates a new output.
Set Point
The set point is the desired value of the process variable.
Time Constant
Same as lag time.
Transmitter
A transmitter sense the actual value of a system and transforms the value to a standardized signal
- 4-20 mA is common for analog signals - as input for the control system.
5. Process Controllers
Basic process controllers with proportional, integrating and derivative
functions
Sponsored Links
Basic Controller
The Basic Controller for an application can be visualized as
Controller Principles
The Control Units are in general build on the control principles
proportional controller
integral controller
derivative controller
where
Er = error or deviation between the set point value and the measured value
where
P = proportional band
The proportional band P, express the value necessary for 100% controller output. If P = 0, the gain
or action factor kP would be infinity - the control action would be ON/OFF.
Note! A proportional controller will have the effect of reducing the rise time and will reduce, but
never eliminate, the steady-state error.
where
dt = time sample
The integral controller produce an output proportional with the summarized deviation between the
set point and measured value and integrating gain or action factor.
Integral controllers tend to respond slowly at first, but over a long period of time they tend to
eliminate errors.
The integral controller eliminates the steady-state error, but may make the transient response
worse. The controller may be unstable.
The integral regulator may also cause problems during shutdowns and start up as a result of the
integral saturation or wind up effect. An integrating regulator with over time deviation (typical
during plant shut downs) will summarize the output to +/- 100%. During start up the output is set
to 100%m which may be catastrophic.
where
dt = time sample
The derivative or differential controller is never used alone. With sudden changes in the system
the derivative controller will compensate the output fast. The long term effects the controller allow
huge steady state errors.
A derivative controller will in general have the effect of increasing the stability of the system,
reducing the overshoot, and improving the transient response.
Note that these correlations may not be exactly accurate, because P, I and D are dependent of
each other. Changing one of these variables can change the effect of the other two.
Small
P Decrease Increase Decrease
Change
Small Small
D Decrease Decrease
Change Change
Sponsored Links
Related Topics
Sponsored Links
Related Documents
6. ISA Instrumentation Codes in Process Control Systems
The ISA standards and symbols are important for the P&IDs and documents
describing the process control system
Sponsored Links
Analyses A Alarm A
Combustion B Controller C
Power J Indicator I
LI
For unique identification it is common to add a number to the ISA code, by example the code for
level indicator no. eight may be:
LI 08
First Letter
First letter indicates a measured or initiating variable, or a modifier, such as Current (I), Speed (S)
or Flow (F).
A - Analysis
B - Burner, combustion
C - User's choice
D - User's choice
E - Voltage
F - Flow rate
G- User's choice
H - Hand
I - Current (electrical)
J - Power
K - Time, time schedule
L - Level
M- User's choice
N- User's choice
O- User's choice
P - Pressure, vacuum
Q - Quantity
R - Radiation
S - Speed, frequency
T - Temperature
U - Multivariable
V - Vibration, mechanical analyses
W - Weight, force
X - Unclassified
Y - Event, state or presence
Z - Position, dimension
Modifier
D - Differential
F - Ration (fraction)
J - Scan
K - Time rate of change
M - Momentary
Q - Integrate, totalizer
S - Safety
X - X-axis
Y - Y-axis
Z - Z-axis
A - Alarm
B - User's choice
E - Sensor (primary element)
G- Glass, viewing device
I - Indication
L - Light
N- User's choice
O- Orifice, restriction
P - Point (test connection)
R - Record
U - Multifunction
W - Well
X - Unclassified
Output Function
B - User's choice
C - Control
K - Control Station
N- User's choice
S - Switch
T - Transmit
U - Multifunction
V - Valve, damper, louver
X - Unclassified
Y - Relay, compute, convert
Z - Driver, actuator
Modifier Function
B - User's choice
H - High
L - Low
M - Middle, intermediate
N- User's choice
U - Multifunction
X - Unclassified
Flowmeter - Indicating
FI 001
TT 001
Control Valve
FV 001
ZSH 001