PM-DM/DMR / Pm-2Dm/2Dmr: Digital Multimeters

This document provides instructions for setting up and using a digital multimeter device to measure current, voltage, frequency, and power factor of three phases. It describes how to set the current transformer ratio, over/under voltage and current values, time delay, and password. It also explains how to view maximum/minimum demands and current/voltage/frequency readings, and indicates the device has the ability to monitor power factor as well.

Uploaded by

tonielhage
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
479 views2 pages

PM-DM/DMR / Pm-2Dm/2Dmr: Digital Multimeters

This document provides instructions for setting up and using a digital multimeter device to measure current, voltage, frequency, and power factor of three phases. It describes how to set the current transformer ratio, over/under voltage and current values, time delay, and password. It also explains how to view maximum/minimum demands and current/voltage/frequency readings, and indicates the device has the ability to monitor power factor as well.

Uploaded by

tonielhage
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PM-DM/DMR / PM-2DM/2DMR

DIGITAL MULTIMETERS

2.5. Setting Over Current Value


1. INTRODUCTION (For PM-DMR/PM-2DMR)

PM-DM/PM-DMR / PM-2DM/PM-2DMR is a microcontroller based device Press “ENTER” buton for 3 seconds. Press “UP” button until “IuL” and “SEt”
designed to measure current and voltage of three phases and frequency of the appear. Press “ENTER” button again for the lowest display to indicate existing
system. Device also stores minimum and maximum demands for both current over current limit. Enter the desired value and save via “ENTER” buton. Press
and voltage and is capable to show these values to the user when desired. PM- “UP” button until “ESC” appears on lowest display. Press “ENTER” buton to
DMR/PM-2DMR also has programmable under and over voltage limits, under start displaying of current, voltage and frequency.
and over current protection and delay time setting wih contact output. PM-
DMR/PM-2DMR has two different contact outputs for O/U Current and
2.6. Setting Under Current Value
Voltage conditions. Contact output availability is optional. PM-DMR/PM-
2DMR comes with the relay output whereas PM-DM/PM-2DM does not. (For PM-DMR/PM-2DMR)

2. USAGE OF PM-DM/DMR / PM-2DM/2DMR Press “ENTER” buton for 3 seconds. Press “UP” button until “IdL” and “SEt”
appear on display. Press “ENTER” button again for the lowest display to indicate
existing under current limit. . Enter the desired value and save via “ENTER”
All connections have to be done according to connection diagramme (Figure- button. Press “UP” button until “ESC” appears on lowest display. Press
1). When power is applied for the first time in order to see the current levels, “ENTER” to start displaying of current, voltage and frequency.
the CT Ratio should have to be set correctly. Device will start displaying
correct values. L1, L2, L3 lines refer three phases where N to neutral
2.7. Setting Time Delay
connection. Outputs of main current transformers have to be connected to I11-
I12, I21-I22, I31-I32 input terminals successively. On the other word it means (For PM-DMR/PM-2DMR)
that “IX1-IX2” pins of CTs have to be connected separately.
Press “ENTER” button for 3 seconds. Press “UP” button until “dEt” and “SEt”
appear. Press “ENTER” button again for the lowest display to indicate existing
2.1. Password Access (Optional) delay time. Enter the desired value and save via “ENTER”.

Press “ENTER” button for 3 sec. “Ctr” and “Set” texts are displayed
subsequently if password option is not selected. “Scr” is displayed for the user 2.8. Password Entry
to enter the password given by the manufacturer if provided that the password
option is already selected by the user. A wrong password access will cause to Keep pressing “UP” button until “Scr” and “Set” texts are displayed. Press
return back to main menu whereas a verified/successful access enable “Ctr” “ENTER” button to see password status option on the bottom LED. “S-A” is
and “Set” texts be displayed subsequently. Password is 015 and can not be chosen to activate the password option whereas “S-P” chosen to deactivate, by
changed. using “UP” or “DOWN” button. Press “ENTER” to accept and save. Hold
pressed “UP” button until reaching “ESC” to ENTER for displaying of Hz, U, I.
2.2. Setting Current Transformer Ratio
2.9. Monitoring Current, Voltage and Frequency
Press ENTER buton for 3 seconds. On the bottom display “Ctr” and “SEt” are
displayed alternately. Press “ENTER” button again to display the CT Ratio Current of three phases are displayed simultaneously on the first three display. If
(CTR). CTR (default is 5) value can be adjustable between 5 and 9500. When the read value of current exceeds 1000A, device will light “k” (kilos) LED and
the adjusted value exceeds 1000, “k” (kilos) LEDs will be on and the value of show the value with dot within kA.
the CTR will be shown along with “.”dot within kA. Pressing “UP” or Fourth display indicates voltage of one phase whereas the LEDs on left side refer
“DOWN” buttons enables the user adjust the desired CTR value. Pressing each subsequent line. Thus, pressing “UP” or “Down” enables the user to read L-
“ENTER” button again is needed to save it in non-volatile memory. Press “UP” L and L-N values. The frequency (Hz) is displayed on the fifth display.
button until “ESC” appears on lowest display. Press “ENTER” button again.to
enable the device display current, voltage and frequency readouts on the
display screen. 2.10.Viewing Current, Voltage, Frequency and Power Factor
(For PM-2DM/PM-2DMR)
2.3. Setting Over Voltage Level
(For PM-DMR/PM-2DMR) In normal operation device shows current of three phases at the same time on
first three displays. If read value of current exceeds 1000A, device will lights “k”
(kilos) LEDs and show the value with dot.
Press “ENTER” buton for 3 seconds. Press “UP” button until “UuL” and Fourth display shows the voltage of one phase or phase to phase voltage or
“SEt” appear on the display. By pressing “ENTER” button again, the lowest power factor (Cos ϕ) of the phase according to the user’s selection the three
display will indicate existing over voltage limit. Enter the desired value and LEDs on left side of the display lights indicates which line’s voltage or cos ϕ is
save via “ENTER” buton. Press “UP” button until “ESC” appears on lowest being displayed currently. Pressing “UP” or “DOWN” buttons will change the
display. Press “ENTER” buton to start displaying of current, voltage and current information of fourth display. User can see voltage levels of three phases
frequency.
to neutral or phase to phase voltages or power factor (Cos ϕ) of each phase by
pressing one of this buttons sequentially. Each pressing of the buttons will
2.4. Setting Under Voltage Level update the status of LEDs on left side of fourth display giving information to
(For PM-DMR/PM-2DMR) user which quantity is being displayed.
Fifth display gives information about line frequency in normal operation. When
the fourth display shows cos ϕ value of the phases, fifth display shows the
Press “ENTER” buton for 3 seconds. Press “UP” button until “UdL” and “SEt”
situation of the cos ϕ value. If the value is capacitive “Cap” text will appear on
appear on the display. By pressing “ENTER” button again, the lowest display
the fifth display. If the value is inductive “Ind” text will appear on the fifth
will indicate existing under voltage limit. Enter the desired value and save via
display. If there is no one of the current and voltage signals, “noS” text will
“ENTER” buton. Press “UP” button until “ESC” appears on lowest display.
appear on the fifth display.
Press “ENTER” buton to start displaying of current, voltage and frequency.
To measure the right power factor value, Voltage and Current signals of the
phases must match each other.
4. TECHNICAL SPECIFICATIONS
2.11. Maximum and Minimum Demands
Operating Voltage (Un) 220VAC, 120VAC ± %20 (L-N)
Press “ENTER” buton for 3 seconds when device is in normal operation mode. (Operating voltage can be changed by the
Press “UP” button until “LHı” appears on lowest display. At this time first vendor)
three displays give information about maximum read value of currents for three Operating Range (0,8-1,2)xUn
phases. The fourth display shows the maximum read value for selected line’s Operating Frequency 50/60 Hz
voltage. Line selection is done by “ENTER” button in this operation status. Power Consumption < 4VA
Each press of “ENTER” button will change information of fourth display and Input Power Consumption < 1VA
LED status, as well. If user continues pressing “UP” button until lowest display Voltage Inputs Range 0-300VAC (L-N)
shows “LLo” first three displays will give information about minimum read 0-500VAC (L-L)
values of currents of three phases and fourth display will show the minimum Current Transformer Ratio 5/5A……..9500/5A
value of voltage for the selected line. Selection can be done by “ENTER” Current Input 5A max.
button in this case. These maximum and minimum values are stored in memory Frequency Measuring Range 40-99.9 Hz
of the devices. Even if the power cut off these values will not be erased from Accuracy ±%1
the memory. So the user can see the last max. and min. values of currents and Relay Outputs 250VAC/5A (Two relays for PM-DMR/
voltages. If “UP” and “DOWN” button are pushed at the same time the devices 2DMR)
will reset the max. and min. values. When the device is reset, min. current Display Type 7 Segment, Red light, 5 lines
values will be set to 9500A and min. voltage values will be set to 500V and Mounting Type Panel Mounted
Max. current and voltage values will be set to 0 value. When the device turns Dimensions 96x96 mm
back to normal operation, these values will be updated immediately. Press“UP” Protection Class IP 20
button until lowest display shows “ESC” and press “ENTER”. K LED on the Plastic Material V0 Nonflammable
Terminal cable thickness 2
left of the “Current” LED is highlighted when the current is 1000A or above, 2.5 mm
but be retrieved as in kA value. Operating Temperature -25oC … +65oC
Weight PM-DM/PM-2DM: 470 gr.,
2.12. Contact Position According to the Failure PM-DMR/PM-2DMR: 515 gr.
(For PM-DMR/PM-2DMR)
5. SAFETY & WARNING INSTRUCTIONS
The voltage protection relay (NC2, C2, NO2) will be energized and current
protection relay (NC1, C1, NO1) will not be energized if current and voltage of • Turn off power during connection/wiring.
whole phases are measured at the adjusted current and voltage levels. When • Check correct mains voltage/wiring terminal.
one of the phase voltage goes under the adjusted Under Voltage Protection
• Installation shall only be performed by qualified personnel.
Level and/or above the adjusted Over Voltage Protection Level, the energy of
• Do not use any solvent or alike for cleaning.
the voltage protection relay (NC2, C2, NO2) will be cut and the relay will
change its contact position at the end of the adjusted delay time.
The same mentioned above is followed for the Over Current Protection. 6. MECHANICAL DIMENSIONS
Over Current and Voltage Protection Relays are activated independently as
shown on Figure-1, NC1, C1, NO1 for over current failure and NC2, C2, NO2
for over voltage failure.

3. CONNECTION DIAGRAM

Figure-1 Connection Diagram

Important Note: We highly recommend the user press “up and down
buttons” at the same time to reset the stored max. and min. demand values
when current input and voltage input are connected first time.