Cable Sizing CALCULATION
Cable Sizing CALCULATION
FOR
TABLE OF CONTENTS
ATTACHMENTS :
1.00.00 PREAMBLE
1.01.00 This document presents the calculations for sizing of 415V major incoming Power Cables being used under the scope of
Ion Exchange Infrastructure Ltd, under an EPC package for Incomers of 415V Motor Control Centre (MCC).
1.02.00 This documentscovers the cable sizing calculation for the following main power cables:
The cable sizing calculations carried out in this document are based on the following basic design data and criteria.
2.02.01 1100 V Power Cables : Stranded Aluminium Conductor, XLPE insulated, screened, PVC
Inner sheathed, Galvanised single round wire armoured and
overall FRLS PVC sheathed
2.04.00 For 1.1kV grade cables, the current ratings of the cables and applicable derating factors are taken from the technical
data's catalogues of POLYCAB.
3.00.01 Sizing Calculations of Incomer to MCC-1(Regular Power supply bus ) from PCC2
The 415V power cables referred above are required feeding power from the 415V PCC to 415V MCC.
3.01.01 The minimum cross section of the cable from short circuit considerations, is given by the formula,
A = Ish √t
k
where, A = Conductor cross section in mm2
t = Fault clearance time in secs
K = A constant depending upon
- Conductor type and its initial & final temperature
- Insulation
3.01.02 The value of K for initial conductor temperature = 90ºC and final conductor temperature = 250ºC, based on
XLPE (AL) cable and that the cable carries its rated current = 94
3.01.03 Ish = Short Circuit Current of the 415V system for a fault on the cable.
Here the maximum fault level at 415V MCC is = 50 kA
3.01.04 Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, as per requirement, the fault withstand time has been taken as 0.5 secs for all outgoing
distribution feeders to other switchboard.
Minimum selected size = 400 mm2 which corresponds to 53.2 kA for 0.5 secs
Derating Factor for Ambient [ Note : Since cables would be routed in air,
Air Temperature of 50ºC as = 0.90 derating factors for ground is not applicable.]
per Attachment II - RATING
FACTOR (Fa)
= 0.657
3.02.01 The load of MCC-1 to be carried by the circuit based on the present loading is 693 KVA ,as could be seen from
the load list
= 693 Amps
1.7321 X 0.415
= 964.08 Amps
= 1467.4 Amps
= 1.803
= 2
\ 2 nos. 1Cx 630 mm2 (AL) cables are used for interconnection between PCC-2 to MCC - 1.
\ sin f = 0.53
= 0.004215 Ohms
= 7.989 Volts
3.04.00 Conclusion
2 nos. 1CX 630 mm2 size (AL) cable for interconnection between PCC-2 & MCC-1 is adequate to satisfy
the short circuit, ampacity and voltage drop requirements.
1
3.00.01 Sizing Calculations of Incomer to MCC-1(Emergency Power Supply Bus) from DG
The 415V power cables referred above are required feeding power from the DG to 415V MCC
emergency power supply bus.
3.01.00 Based on Short Circuit
3.01.01 The minimum cross section of the cable from short circuit considerations, is given by the formula,
A = Ish √t
k
where, A = Conductor cross section in mm2
t = Fault clearance time in secs
K = A constant depending upon
- Conductor type and its initial & final temperature
- Insulation
3.01.02 The value of K for initial conductor temperature = 90ºC and final conductor temperature = 250ºC, based on
XLPE (AL) cable and that the cable carries its rated current = 94
3.01.03 Ish = Short Circuit Current of the 415V system for a fault on the cable.
Here the maximum fault level at 415V MCC is = 50 kA
3.01.04 Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, as per requirement, the fault withstand time has been taken as 0.5 secs for all outgoing
distribution feeders to other switchboard.
Minimum selected size = 400 mm2 which corresponds to 53.2 kA for 0.5 secs
Derating Factor for Ambient [ Note : Since cables would be routed in air,
Air Temperature of 50ºC as = 0.90 derating factors for ground is not applicable.]
per Attachment II - RATING
FACTOR (Fa)
= 0.657
3.02.01 The load of MCC-1 to be carried by the circuit based on the present loading is 151 KVA ,as could be seen from
the load list
= 151 Amps
1.7321 X 0.415
= 210.07 Amps
= 319.75 Amps
= 0.604
= 1
\ 1 nos. 3.5Cx 400 mm2 (AL) cables are used for interconnection between DG to MCC - 1
emergency power supply bus
\ sin f = 0.53
= 0.005901 Ohms
= 2.437 Volts
3.04.00 Conclusion
1 nos. 3.5CX 400 mm2 size (AL) cable for interconnection between DG & MCC-1 emergency power supply bus
is adequate to satisfy the short circuit, ampacity and voltage drop requirements.
3.01.01 The minimum cross section of the cable from short circuit considerations, is given by the formula,
A = Ish √t
k
where, A = Conductor cross section in mm2
t = Fault clearance time in secs
K = A constant depending upon
- Conductor type and its initial & final temperature
- Insulation
3.01.02 The value of K for initial conductor temperature = 90ºC and final conductor temperature = 250ºC, based on
XLPE (AL) cable and that the cable carries its rated current = 94
3.01.03 Ish = Short Circuit Current of the 415V system for a fault on the cable.
Here the maximum fault level at 415V PMCC/MCC is = 50 kA
3.01.04 Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, as per requirement, the fault withstand time has been taken as 0.5 secs for all outgoing
distribution feeders to other switchboard.
Minimum selected size = 400 mm2 which corresponds to 53.2 kA for 0.5 secs
Derating Factor for Ambient [ Note : Since cables would be routed in air,
Air Temperature of 50ºC as = 0.90 derating factors for ground is not applicable.]
per Attachment II - RATING
FACTOR (Fa)
= 0.657
3.02.01 The load of MCC 2 to be carried by the circuit based on the present loading is 1329 KVA, as could be seen
from the load list
= 1329 Amps
1.7321 X 0.415
= 1848.86 Amps
= 2814.1 Amps
= 3.458
= 4
\ 4 nos. 1Cx 630 mm2 (AL) cables are used for interconnection between PCC-2 to MCC - 2.
\ sin f = 0.53
= 0.00105375 Ohms
= 3.83 Volts
3.04.00 Conclusion
4 nos. 1CX 630 mm2 size (AL) cable per phase for interconnection between PCC-2 & MCC-2 is adequate
to satisfy the short circuit, ampacity and voltage drop requirements.
3.01.01 The minimum cross section of the cable from short circuit considerations, is given by the formula,
A = Ish √t
k
where, A = Conductor cross section in mm2
t = Fault clearance time in secs
K = A constant depending upon
- Conductor type and its initial & final temperature
- Insulation
3.01.02 The value of K for initial conductor temperature = 90ºC and final conductor temperature = 250ºC, based on
XLPE (AL) cable and that the cable carries its rated current = 94
3.01.03 Ish = Short Circuit Current of the 415V system for a fault on the cable.
Here the maximum fault level at 415V PMCC/MCC is = 50 kA
3.01.04 Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, as per requirement, the fault withstand time has been taken as 0.5 secs for all outgoing
distribution feeders to other switchboard.
Minimum selected size = 400 mm2 which corresponds to 53.2 kA for 0.5 secs
Derating Factor for Ambient [ Note : Since cables would be routed in air,
Air Temperature of 50ºC as = 0.90 derating factors for ground is not applicable.]
per Attachment II - RATING
FACTOR (Fa)
= 0.657
3.02.01 The load of MCC-1 to be carried by the circuit based on the present loading is 1357 KVA ,as could be seen
from the load list
= 1357 Amps
1.7321 X 0.415
= 1887.82 Amps
= 2873.4 Amps
= 3.53
= 4
\ 4 nos. 1Cx 630 mm2 (AL) cables are used for interconnection between PCC1 to MCC - 3
\ sin f = 0.53
= 0.000843 Ohms
= 3.129 Volts
3.04.00 Conclusion
4 nos. 1CX 630 mm2 size (AL) cable for interconnection between PCC 1 & MCC-3 is adequate to satisfy
the short circuit, ampacity and voltage drop requirements.
3.01.01 The minimum cross section of the cable from short circuit considerations, is given by the formula,
A = Ish √t
k
where, A = Conductor cross section in mm2
t = Fault clearance time in secs
K = A constant depending upon
- Conductor type and its initial & final temperature
- Insulation
3.01.02 The value of K for initial conductor temperature = 90ºC and final conductor temperature = 250ºC, based on
XLPE (AL) cable and that the cable carries its rated current = 94
3.01.03 Ish = Short Circuit Current of the 415V system for a fault on the cable.
Here the maximum fault level at 415V PMCC/MCC is = 50 kA
3.01.04 Value of 't' is based on the fault clearance time (Breaker tripping time + relay operation time + tolerance).
However, as per requirement, the fault withstand time has been taken as 0.5 secs for all outgoing
distribution feeders to other switchboard.
Minimum selected size = 400 mm2 which corresponds to 53.2 kA for 0.5 secs
Derating Factor for Ambient [ Note : Since cables would be routed in air,
Air Temperature of 50ºC as = 0.90 derating factors for ground is not applicable.]
per Attachment II - RATING
FACTOR (Fa)
= 0.657
3.02.01 The load of MCC-1 to be carried by the circuit based on the present loading is 1052 KVA ,as could be seen
from the load list
= 1052 Amps
1.7321 X 0.415
= 1463.51 Amps
= 2227.57 Amps
= 2.737
= 3
\ 3 nos. 1Cx 630 mm2 (AL) cables are used for interconnection between PCC1 to MCC - 4
\ sin f = 0.53
= 0.00843 Ohms
= 24.254 Volts
3.04.00 Conclusion
3 nos. 1CX 630 mm2 size (AL) cable for interconnection between PCC 1 & MCC-4 is adequate to satisfy
the short circuit, ampacity and voltage drop requirements.
4.00.00 Summary
5.00.00 REFERENCES 1
[II] DETAIL TECHNICAL SPEC FOR DATA SHEET FOR LV POWER CABLE .
CABLES DOC NO : A/IILC7-E-DSH-3_REV 0
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
FCE PUMPING & COOLING STN. MCC # 1
P14-A Horizontal Pumps Hot Well 55.00 0.930 0.87 0.49 94.57 0.6570 143.95 3.0 2XWY 70.0 AL 32.0 179 1 40 0.4430 0.5700 0.0740 0.0228 0.0030 3.49 0.84 0.30 0.95 11.40 2.75
to Cooling Tower #
3(working)
P14-B Horizontal Pumps Hot Well 55.00 0.930 0.87 0.49 94.57 0.6570 143.95 3.0 2XWY 70.0 AL 32.0 179 1 37 0.4430 0.5700 0.0740 0.0211 0.0027 3.23 0.78 0.30 0.95 10.54 2.54
to Cooling Tower #
3(working)
P14-C Horizontal Pumps Hot Well 55.00 0.930 0.87 0.49 94.57 0.6570 143.95 3.0 2XWY 70.0 AL 32.0 179 1 34 0.4430 0.5700 0.0740 0.0194 0.0025 2.96 0.71 0.30 0.95 9.69 2.33
to Cooling Tower #
3(standby)
P14-A/V Horizontal Pumps Hot Well 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 45 7.4100 9.4485 0.0985 0.4252 0.0044 1.97 0.48 0.30 0.95 5.46 1.32
to Cooling Tower #
3(working)MOV
P14-B/V Horizontal Pumps Hot Well 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 42 7.4100 9.4485 0.0985 0.3968 0.0041 1.84 0.44 0.30 0.95 5.10 1.23
to Cooling Tower #
3(working)MOV
P14-C/V Horizontal Pumps Hot Well 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 40 7.4100 9.4485 0.0985 0.3779 0.0039 1.75 0.42 0.30 0.95 4.85 1.17
to Cooling Tower #
3(standby)MOV
P15-A Emergency Pump from hot 30.00 0.914 0.84 0.54 54.36 0.6570 82.74 3.0 2XWY 25.0 AL 23.0 96 1 45 1.2000 1.5439 0.0805 0.0695 0.0036 5.68 1.37 0.30 0.95 16.47 3.97
well to CT-3(working)
P16-A Emergency Pump from 75.00 0.936 0.83 0.56 134.31 0.6570 204.43 3.0 2XWY 95.0 AL 37.5 221 1 34 0.3200 0.4117 0.0724 0.0140 0.0025 3.02 0.73 0.30 0.95 10.97 2.64
Cold Well-3 To O.H.
Tank(working)
P23-A Cold Well AVGF feed 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 48 1.9100 2.4574 0.0808 0.1180 0.0039 3.62 0.87 0.30 0.95 10.42 2.51
pumps(working)
P23-B Cold Well AVGF feed 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 50 1.9100 2.4574 0.0808 0.1229 0.0040 3.77 0.91 0.30 0.95 10.85 2.61
pumps(standby) 1
P23-A/V Cold Well AVGF feed 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 53 7.4100 9.4485 0.0985 0.5008 0.0052 2.32 0.56 0.30 0.95 6.43 1.55
pumps(working)MOV
P23-B/V Cold Well AVGF feed 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 55 7.4100 9.4485 0.0985 0.5197 0.0054 2.41 0.58 0.30 0.95 6.67 1.61
pumps(standby)MOV
FCT-A Furnace cooling tower 40.00 0.912 0.85 0.53 71.79 0.6570 109.27 3.0 2XWY 35.0 AL 25.0 117 1 65 0.8680 1.1168 0.0783 0.0726 0.0051 8.01 1.93 0.30 0.95 23.84 5.75
fan(working)
FCT-B Furnace cooling tower 40.00 0.912 0.85 0.53 71.79 0.6570 109.27 3.0 2XWY 35.0 AL 25.0 117 1 62 0.8680 1.1168 0.0783 0.0692 0.0049 7.64 1.84 0.30 0.95 22.74 5.48
fan(working)
FCT-C Furnace cooling tower 40.00 0.912 0.85 0.53 71.79 0.6570 109.27 3.0 2XWY 35.0 AL 25.0 117 1 60 0.8680 1.1168 0.0783 0.0670 0.0047 7.39 1.78 0.30 0.95 22.01 5.30
fan(standby)
1 1
FCR 3T EOT crane (furnace 7.50 0.870 0.84 0.54 14.28 0.6570 21.73 3.0 2XWY 16.0 AL 21.0 70 1 55 1.9100 2.4574 0.0808 0.1352 0.0044 2.87 0.69 0.30 0.95 7.97 1.92
cooling pump house)
(working)
FMV Makeup water line MOV 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 30 7.4100 9.4485 0.0985 0.2835 0.0030 1.32 0.32 0.30 0.95 3.64 0.88
P12-A/V Horizontal Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 45 7.4100 9.4485 0.0985 0.4252 0.0044 1.97 0.48 0.30 0.95 5.46 1.32
Well-3 To Reheating
Furnace # 2(W.R.M)
(working) MOV
P12-B/V Horizontal Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 42 7.4100 9.4485 0.0985 0.3968 0.0041 1.84 0.44 0.30 0.95 5.10 1.23
Well-3 To Reheating
Furnace # 2(W.R.M)
(standby)MOV
P13-A/V Horizontal Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 42 7.4100 9.4485 0.0985 0.3968 0.0041 1.84 0.44 0.30 0.95 5.10 1.23
Well-3 To Reheating
Furnace #1(B.M)(working)
MOV
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
P13-B/V Horizontal Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 42 7.4100 9.4485 0.0985 0.3968 0.0041 1.84 0.44 0.30 0.95 5.10 1.23
Well-3 To Reheating
Furnace #1(B.M)(standby)
MOV
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
SCALE PIT MCC # 2
BP-A Bearing cooling 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 42 1.9100 2.4574 0.0808 0.1032 0.0034 3.17 0.76 0.30 0.95 9.12 2.20
pump(working)
BP-B Bearing cooling 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 40 1.9100 2.4574 0.0808 0.0983 0.0032 3.02 0.73 0.30 0.95 8.68 2.09
pump(working)
P5-A/V Vertical Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 60 7.4100 9.4485 0.0985 0.5669 0.0059 2.63 0.63 0.30 0.95 7.28 1.75
pit to settling tankfor
BM,WRM(working) MOV
P5-B/V Vertical Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 58 7.4100 9.4485 0.0985 0.5480 0.0057 2.54 0.61 0.30 0.95 7.04 1.70
pit to settling tankfor
BM,WRM(working) MOV
P5-C/V Vertical Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 56 7.4100 9.4485 0.0985 0.5291 0.0055 2.46 0.59 0.30 0.95 6.80 1.64
pit to settling tankfor
BM,WRM(working) MOV
P5-D/V Vertical Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 54 7.4100 9.4485 0.0985 0.5102 0.0053 2.37 0.57 0.30 0.95 6.55 1.58
pit to settling tankfor
BM,WRM(working) MOV
P5-E/V Vertical Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 52 7.4100 9.4485 0.0985 0.4913 0.0051 2.28 0.55 0.30 0.95 6.31 1.52
pit to settling tankfor
BM,WRM(standby) MOV
P17-A/V Turbine Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 49 7.4100 9.4485 0.0985 0.4630 0.0048 2.15 0.52 0.30 0.95 5.95 1.43
Pit for Flume flushing
(working) MOV
P17-B/V Turbine Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 48 7.4100 9.4485 0.0985 0.4535 0.0047 2.10 0.51 0.30 0.95 5.83 1.40
Pit for Flume flushing
(working) MOV
P17-C/V Turbine Pumps from Scale 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 47 7.4100 9.4485 0.0985 0.4441 0.0046 2.06 0.50 0.30 0.95 5.70 1.37
Pit for Flume flushing
(standby) MOV
SPCR/1 5T EOT crane for scale pit 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 30 1.9100 2.4574 0.0808 0.0737 0.0024 2.26 0.55 0.30 0.95 6.51 1.57
(working)
SPCR/2 3T EOT crane for scale pit 7.50 0.870 0.84 0.54 14.28 0.6570 21.73 3.0 2XWY 16.0 AL 21.0 70 1 35 1.9100 2.4574 0.0808 0.0860 0.0028 1.82 0.44 0.30 0.95 5.07 1.22
pump house(working)
1 1
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
PUMPING & COOLING STN. ICW MCC # 3
P7-A Backwash Pumps Cold 55.00 0.930 0.87 0.49 94.57 0.6570 143.95 3.0 2XWY 70.0 AL 32.0 179 1 100 0.4430 0.5700 0.0740 0.0570 0.0074 8.72 2.10 0.30 0.95 28.49 6.87
Well-1Pressure Filters
(working)
P7-B Backwash Pumps Cold 55.00 0.930 0.87 0.49 94.57 0.6570 143.95 3.0 2XWY 70.0 AL 32.0 179 1 95 0.4430 0.5700 0.0740 0.0541 0.0070 8.28 2.00 0.30 0.95 27.07 6.52
Well-1 Pressure Filters
(standby)
P7-A/V Backwash Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 105 7.4100 9.4485 0.0985 0.9921 0.0103 4.60 1.11 0.30 0.95 12.74 3.07
Well-1Pressure Filters
(working) MOV
P7-B/V Backwash Pumps Cold 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 100 7.4100 9.4485 0.0985 0.9448 0.0099 4.38 1.06 0.30 0.95 12.14 2.92
Well-1 Pressure Filters
(standby) MOV
P21-A Cold well AVGF feed 18.50 0.900 0.81 0.59 35.31 0.6570 53.74 3.0 2XWY 16.0 AL 21.0 70 1 53 1.9100 2.4574 0.0808 0.1302 0.0043 6.60 1.59 0.30 0.95 19.00 4.58
pumps (working)
P21-B Cold well AVGF feed 18.50 0.900 0.81 0.59 35.31 0.6570 53.74 3.0 2XWY 16.0 AL 21.0 70 1 52 1.9100 2.4574 0.0808 0.1278 0.0042 6.48 1.56 0.30 0.95 18.64 4.49
pumps (standby)
P21-A/V Cold well AVGF feed 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 58 7.4100 9.4485 0.0985 0.5480 0.0057 2.54 0.61 0.30 0.95 7.04 1.70
pumps (working) MOV
P21-B/V Cold well AVGF feed 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 57 7.4100 9.4485 0.0985 0.5386 0.0056 2.50 0.60 0.30 0.95 6.92 1.67
pumps (standby) MOV
DCW-CT-A DCW cooling tower fan 60.00 0.920 0.87 0.49 104.29 0.6570 158.74 3.0 2XWY 95.0 AL 37.5 221 1 160 0.3200 0.4117 0.0724 0.0659 0.0116 11.38 2.74 0.30 0.95 40.07 9.66
(working)
DCW-CT-B DCW cooling tower fan 60.00 0.920 0.87 0.49 104.29 0.6570 158.74 3.0 2XWY 95.0 AL 37.5 221 1 155 0.3200 0.4117 0.0724 0.0638 0.0112 11.03 2.66 0.30 0.95 38.82 9.35
(working)
DCW-CT-C DCW cooling tower fan 60.00 0.920 0.87 0.49 104.29 0.6570 158.74 3.0 2XWY 95.0 AL 37.5 221 1 150 0.3200 0.4117 0.0724 0.0618 0.0109 10.67 2.57 0.30 0.95 37.57 9.05
(working)
DCW-CT-D DCW cooling tower fan 60.00 0.920 0.87 0.49 104.29 0.6570 158.74 3.0 2XWY 95.0 AL 37.5 221 1 145 0.3200 0.4117 0.0724 0.0597 0.0105 10.32 2.49 0.30 0.95 36.32 8.75
(working)
ICW-CT-A Mill ICW cooling tower fan 50.00 0.912 0.86 0.51 88.69 0.6570 134.99 3.0 2XWY 50.0 AL 27.5 142 1 100 0.6410 0.8247 0.0750 0.0825 0.0075 11.48 2.77 0.30 0.95 35.28 8.50
(FCE) (working)
ICW-CT-B Mill ICW cooling tower fan 50.00 0.912 0.86 0.51 88.69 0.6570 134.99 3.0 2XWY 50.0 AL 27.5 142 1 95 0.6410 0.8247 0.0750 0.0783 0.0071 10.91 2.63 0.30 0.95 33.51 8.08
(FCE) (working)
ICW-CT-C Mill ICW cooling tower fan 50.00 0.912 0.86 0.51 88.69 0.6570 134.99 3.0 2XWY 50.0 AL 27.5 142 1 90 0.6410 0.8247 0.0750 0.0742 0.0068 10.33 2.49 0.30 0.95 31.75 7.65
(FCE) (working)
ICW-CT-D Mill ICW cooling tower fan 50.00 0.912 0.86 0.51 88.69 0.6570 134.99 3.0 2XWY 50.0 AL 27.5 142 1 85 0.6410 0.8247 0.0750 0.0701 0.0064 9.76 2.35 0.30 0.95 29.99 7.23
(FCE) (standby)
1 1
ICW-CR 3T EOT crane (working) 7.50 0.870 0.84 0.54 14.28 0.6570 21.73 3.0 2XWY 16.0 AL 21.0 70 1 45 1.9100 2.4574 0.0808 0.1106 0.0036 2.35 0.57 0.30 0.95 6.52 1.57
DCW-CR 5T EOT crane (working) 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 50 1.9100 2.4574 0.0808 0.1229 0.0040 3.77 0.91 0.30 0.95 10.85 2.61
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
P1-A/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 80 7.4100 9.4485 0.0985 0.7559 0.0079 3.51 0.85 0.30 0.95 9.71 2.34
MOV (working)
P1-B/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 75 7.4100 9.4485 0.0985 0.7086 0.0074 3.29 0.79 0.30 0.95 9.10 2.19
MOV (working)
P1-C/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 70 7.4100 9.4485 0.0985 0.6614 0.0069 3.07 0.74 0.30 0.95 8.50 2.05
MOV (working)
P1-D/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 60 7.4100 9.4485 0.0985 0.5669 0.0059 2.63 0.63 0.30 0.95 7.28 1.75
MOV(standby)
P3-A/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 65 7.4100 9.4485 0.0985 0.6142 0.0064 2.85 0.69 0.30 0.95 7.89 1.90
MOV (working)
P3-B/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 60 7.4100 9.4485 0.0985 0.5669 0.0059 2.63 0.63 0.30 0.95 7.28 1.75
MOV(standby)
P4-A/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 85 7.4100 9.4485 0.0985 0.8031 0.0084 3.73 0.90 0.30 0.95 10.32 2.49
MOV (working)
P4-B/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 80 7.4100 9.4485 0.0985 0.7559 0.0079 3.51 0.85 0.30 0.95 9.71 2.34
MOV (working)
P4-C/V DCW BRM feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 75 7.4100 9.4485 0.0985 0.7086 0.0074 3.29 0.79 0.30 0.95 9.10 2.19
MOV(standby)
P9-A/V BRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 60 7.4100 9.4485 0.0985 0.5669 0.0059 2.63 0.63 0.30 0.95 7.28 1.75
MOV (working)
P9-B/V BRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 57 7.4100 9.4485 0.0985 0.5386 0.0056 2.50 0.60 0.30 0.95 6.92 1.67
MOV (working)
P9-C/V BRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 55 7.4100 9.4485 0.0985 0.5197 0.0054 2.41 0.58 0.30 0.95 6.67 1.61
MOV (standby)
P10-A/V WRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 60 7.4100 9.4485 0.0985 0.5669 0.0059 2.63 0.63 0.30 0.95 7.28 1.75
MOV(working)
P10-B/V WRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 57 7.4100 9.4485 0.0985 0.5386 0.0056 2.50 0.60 0.30 0.95 6.92 1.67
MOV(working)
P10-C/V WRM auxilary feed pump 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 55 7.4100 9.4485 0.0985 0.5197 0.0054 2.41 0.58 0.30 0.95 6.67 1.61
MOV(standby)
ICW MV ICW Makeup water line 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 35 7.4100 9.4485 0.0985 0.3307 0.0034 1.53 0.37 0.30 0.95 4.25 1.02
MOV(working)
DCW MV DCW Makeup water line 1.50 0.785 0.8 0.60 3.32 0.6570 5.06 3.0 2XWY 2.5 CU 16.0 29 1 70 7.4100 9.4485 0.0985 0.6614 0.0069 3.07 0.74 0.30 0.95 8.50 2.05
MOV(working)
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
SETTLING TANK MCC # 4
P11-A Transfer to Backwash 15.00 0.894 0.81 0.59 28.82 0.6570 43.86 3.0 2XWY 16.0 AL 21.0 70 1 30 1.9100 2.4574 0.0808 0.0737 0.0024 3.05 0.74 0.30 0.95 8.78 2.12
water to Thickener pump
(working)
P11-B Transfer to Backwash 15.00 0.894 0.81 0.59 28.82 0.6570 43.86 3.0 2XWY 16.0 AL 21.0 70 1 25 1.9100 2.4574 0.0808 0.0614 0.0020 2.54 0.61 0.30 0.95 7.32 1.76
water to Thickener pump
(standby) 1 1
P22-A Sludge Pumps(working) 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 2.5 CU 16.0 29 1 30 7.4100 9.4485 0.0985 0.2835 0.0030 3.03 0.73 0.30 0.95 8.29 2.00
P22-B Sludge Pumps(working) 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 2.5 CU 16.0 29 1 25 7.4100 9.4485 0.0985 0.2362 0.0025 2.53 0.61 0.30 0.95 6.91 1.66
P22-C Sludge Pumps(standby) 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 2.5 CU 16.0 29 1 20 7.4100 9.4485 0.0985 0.1890 0.0020 2.02 0.49 0.30 0.95 5.53 1.33
P22-D Sludge Pumps(standby) 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 2.5 CU 16.0 29 1 25 7.4100 9.4485 0.0985 0.2362 0.0025 2.53 0.61 0.30 0.95 6.91 1.66
P24-A Diaphragm typeThickener 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 16.0 AL 21.0 70 1 130 1.9100 2.4574 0.0808 0.3195 0.0105 3.47 0.84 0.30 0.95 9.99 2.41
underflow pumps(working)
P24-B Diaphragm typeThickener 3.70 0.840 0.81 0.59 7.57 0.6570 11.52 3.0 2XWY 16.0 AL 21.0 70 1 125 1.9100 2.4574 0.0808 0.3072 0.0101 3.34 0.80 0.30 0.95 9.60 2.31
underflow pumps(standby)
P25-A Filter press feed pumps 5.50 0.857 0.83 0.56 10.76 0.6570 16.37 3.0 2XWY 2.5 CU 16.0 29 1 25 7.4100 9.4485 0.0985 0.2362 0.0025 3.68 0.89 0.30 0.95 9.82 2.37
(Screwed Pump)(working)
P25-B Filter press feed pumps 5.50 0.857 0.83 0.56 10.76 0.6570 16.37 3.0 2XWY 2.5 CU 16.0 29 1 20 7.4100 9.4485 0.0985 0.1890 0.0020 2.94 0.71 0.30 0.95 7.86 1.89
(Screwed Pump)(standby)
DP1-A PAC Dosing pump(working) 2.20 0.810 0.8 0.60 4.72 0.6570 7.19 3.0 2XWY 2.5 CU 16.0 29 1 30 7.4100 9.4485 0.0985 0.2835 0.0030 1.87 0.45 0.30 0.95 5.18 1.25
DP1-B PAC Dosing 2.20 0.810 0.8 0.60 4.72 0.6570 7.19 3.0 2XWY 2.5 CU 16.0 29 1 30 7.4100 9.4485 0.0985 0.2835 0.0030 1.87 0.45 0.30 0.95 5.18 1.25
pump(standby)
DP2-A POLYMER Dosing 2.20 0.810 0.8 0.60 4.72 0.6570 7.19 3.0 2XWY 2.5 CU 16.0 29 1 25 7.4100 9.4485 0.0985 0.2362 0.0025 1.56 0.38 0.30 0.95 4.31 1.04
pump(working)
DP2-B POLYMER Dosing 2.20 0.810 0.8 0.60 4.72 0.6570 7.19 3.0 2XWY 2.5 CU 16.0 29 1 20 7.4100 9.4485 0.0985 0.1890 0.0020 1.25 0.30 0.30 0.95 3.45 0.83
pump(standby)
AG1-A PAC Dosing tank agitator 3.00 0.840 0.81 0.59 6.13 0.6570 9.34 3.0 2XWY 2.5 CU 16.0 29 1 35 7.4100 9.4485 0.0985 0.3307 0.0034 2.87 0.69 0.30 0.95 7.84 1.89
(working)
AG1-B PAC Dosing tank agitator 3.00 0.840 0.81 0.59 6.13 0.6570 9.34 3.0 2XWY 2.5 CU 16.0 29 1 40 7.4100 9.4485 0.0985 0.3779 0.0039 3.28 0.79 0.30 0.95 8.96 2.16
(standby)
AG2 Polymer Dosing tank 15.00 0.894 0.81 0.59 28.82 0.6570 43.86 3.0 2XWY 25.0 AL 23.0 96 1 120 1.2000 1.5439 0.0805 0.1853 0.0097 7.77 1.87 0.30 0.95 23.29 5.61
agitator (working)
AGD Holding tank agitator drive 2.20 0.810 0.8 0.60 4.72 0.6570 7.19 3.0 2XWY 2.5 CU 16.0 29 1 120 7.4100 9.4485 0.0985 1.1338 0.0118 7.48 1.80 0.30 0.95 20.70 4.99
(working)
Equip. Tag Equipment Description FDR Efficency Full Load Sin f1 Rated Full Derating Nominal No. Of Type Of Selected Type Of Overall Rated No. of Length "R" of "R" of "X" Actual Actual Voltage Voltage Motor Sin f2 Voltage Voltage
No. Rating (η) Power Load Factor of Current for Cores Cables Conduct Diameter of current Parallel of Cable Cable at Cable at Resist.of React. of Drop in Drop in Starting Drop in Drop in
Factor Current Cable selection of Cable or the Cables carrying Runs from 200C 900C of Cable Cable at Cable Cable Cable p.f. Cable Cable
(Cos f1) Cable Size capacity MCC 900C during during (Cos f2) during during
Running Running Starting Starting
(VMN) (VMN) (VMS) (VMS)
kW % Amps Amps mm² mm Amps No. Mtrs. Ohms/km Ohms/km Ohms/km Ohms Ohms Volts % Volts %
A B C D E F G H I J K L M N O P Q R S T U V W X
(1000/1.732x415
7.2xGx1.732x(Q
1.732xGx(ExQ+
MxO/ 1000xL)
MxP/1000xL)
Resistivity of
(S/415)x100
W/415x100
(C/(DxE)) x
conductor)
Nx (1+70x
Ö(1-U²)
Ö(1-E²)
xU+RxV)
FxR)
G/H
)
TA Tank agitator drive 7.50 0.870 0.84 0.54 14.28 0.6570 21.73 3.0 2XWY 16.0 AL 21.0 70 1 125 1.9100 2.4574 0.0808 0.3072 0.0101 6.52 1.57 0.30 0.95 18.12 4.37
(working)
B1-A Air Blower (working) 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 42 1.9100 2.4574 0.0808 0.1032 0.0034 3.17 0.76 0.30 0.95 9.12 2.20
B1-B Air Blower (working) 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 42 1.9100 2.4574 0.0808 0.1032 0.0034 3.17 0.76 0.30 0.95 9.12 2.20
B1-C Air Blower (standby) 11.00 0.884 0.81 0.59 21.37 0.6570 32.53 3.0 2XWY 16.0 AL 21.0 70 1 42 1.9100 2.4574 0.0808 0.1032 0.0034 3.17 0.76 0.30 0.95 9.12 2.20
ST CR 3T Crane inside room 7.50 0.870 0.84 0.54 14.28 0.6570 21.73 3.0 2XWY 16.0 AL 21.0 70 1 35 1.9100 2.4574 0.0808 0.0860 0.0028 1.82 0.44 0.30 0.95 5.07 1.22
(working)
1
Notes: 1
4 Formula used to calculate percentage voltage drop = [1.732 x Full load current x (Resistance x Cosø + Reactance x Sinø ) x Length of cable in Metre] / [Supply voltage] x 100
10 % during starting
7 Cable lengths are assumed based on layout drawing and considering the maximum length of similar type/rating feeders estimated among the no of drives for the same equipment.
8 Cable parameters and derating factors are from Manufacturer's (POLYCAB) catalogue.
10 Reference Document :Motor LoadList - Preliminary 220708 -LOAD LIST_JSPL Rev 1.xls
: Power cable specification- DATA SHEET FOR LV POWER CABLE . DOC NO : A/IILC7-E-DSH-3_REV 0
OWNER : JSPL
EPC CONTRACTOR : IIL Nominal Voltage 3 PH [V]: 415
Equip. Equipment Description Motor Efficency Full Load Sin q1 Rated Starting Running Derating Nominal No. of Type Of Selected Type Overall Rated No. of Length of "R" "R" "X" Actual Actual VD in VD in Motor Sin q2 Voltage Voltage
Tag No. FDR h Power Full Current Current Factor Current for Cores Cables Cable Of Diameter curren Parallel Cable of Cable of Cable of Cable Resist. React. Cable Cable Starti Drop in Drop in
Rating Factor Load of Cable selection of Size Condu of the t Runs fromMCC at 20 oC at 90 oC of Cable of Cable during during ng p.f. Cable Cable
ctor Cables carryi Runnin Runnin (Cos during during
(Cos q1) Current Cable ng to Motor at 90 oC g VMN g VMN q2) Starting Starting
capaci VMS VMS
ty
kW % Amps Amps Amps Amps mm² No. Mtrs. Ohms/k Ohms/k Ohms/km Ohms Ohms Volts % Volts %
m m
A B C D E F G H I J L M N O P Q R S T U V W X
Co-eff of res. Of
(1000/1.732x41
Nx (1+70xtemp
(6/(3^0.5))*G
W/415x100
(C/(DxE)) x
(ExQ+FxR)
(G/(3^0.5))
S/415x100
6xGx1.732x
(QxU+RxV)
(1000xL)
(1000xL)
1.732xGx
(Note-2)
Ö(1-U²)
Ö(1-E²)
Al/Cu)
G/H
5)
MxO/
MxP/
FCE PUMPING & COOLING STN. MCC # 1
P12-A Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 40 0.3200 0.4117 0.0724 0.0165 0.0029 3.57 0.86 0.30 0.95 10.80 2.60
To Reheating Furnace #
2(W.R.M)(working) (terminal1)
P12-A Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 40 0.3200 0.4117 0.0724 0.0165 0.0029 3.57 0.86 0.30 0.95 10.80 2.60
To Reheating Furnace #
2(W.R.M)(working)(terminal2)
P12-B Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 37 0.3200 0.4117 0.0724 0.0152 0.0027 3.30 0.80 0.30 0.95 9.99 2.41
To Reheating Furnace #
2(W.R.M)(standby) (terminal1)
P12-B Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 37 0.3200 0.4117 0.0724 0.0152 0.0027 3.30 0.80 0.30 0.95 9.99 2.41
To Reheating Furnace #
2(W.R.M)(standby)(terminal2)
P13-A Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 45 0.3200 0.4117 0.0724 0.0185 0.0033 4.02 0.97 0.30 0.95 12.15 2.93
To Reheating Furnace #1(B.M)
(working)(terminal1)
P13-A Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 45 0.3200 0.4117 0.0724 0.0185 0.0033 4.02 0.97 0.30 0.95 12.15 2.93
To Reheating Furnace #1(B.M)
(working)(terminal2)
P13-B Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 42 0.3200 0.4117 0.0724 0.0173 0.0030 3.75 0.90 0.30 0.95 11.34 2.73
To Reheating Furnace #1(B.M)
(standby)(terminal1)
P13-B Horizontal Pumps Cold Well-3 132 0.947 0.83 0.56 233.64 809.36 134.89 0.657 205.32 3.0 2XWY 95.0 AL 37.5 221 1 42 0.3200 0.4117 0.0724 0.0173 0.0030 3.75 0.90 0.30 0.95 11.34 2.73
To Reheating Furnace #1(B.M)
(standby)(terminal2)
OWNER : JSPL
EPC CONTRACTOR : IIL Nominal Voltage 3 PH [V]: 415
Equip. Equipment Description Motor Efficency Full Load Sin q1 Rated Starting Running Derating Nominal No. of Type Of Selected Type Overall Rated No. of Length of "R" "R" "X" Actual Actual VD in VD in Motor Sin q2 Voltage Voltage
Tag No. FDR h Power Full Current Current Factor Current for Cores Cables Cable Of Diameter curren Parallel Cable of Cable of Cable of Cable Resist. React. Cable Cable Starti Drop in Drop in
Rating Factor Load of Cable selection of Size Condu of the t Runs fromMCC at 20 oC at 90 oC of Cable of Cable during during ng p.f. Cable Cable
ctor Cables carryi Runnin Runnin (Cos during during
(Cos q1) Current Cable ng to Motor at 90 oC g VMN g VMN q2) Starting Starting
capaci VMS VMS
ty
kW % Amps Amps Amps Amps mm² No. Mtrs. Ohms/k Ohms/k Ohms/km Ohms Ohms Volts % Volts %
m m
A B C D E F G H I J L M N O P Q R S T U V W X
Co-eff of res. Of
(1000/1.732x41
Nx (1+70xtemp
(6/(3^0.5))*G
W/415x100
(C/(DxE)) x
(ExQ+FxR)
(G/(3^0.5))
S/415x100
6xGx1.732x
(QxU+RxV)
(1000xL)
(1000xL)
1.732xGx
(Note-2)
Ö(1-U²)
Ö(1-E²)
Al/Cu)
G/H
5)
MxO/
MxP/
P5-D Vertical Pumps from Scale pit to 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 49 0.2530 0.3048 0.0712 0.0149 0.0035 4.05 0.98 0.30 0.95 13.23 3.19
settling tankfor BM,WRM
(working) (terminal2)
P5-E Vertical Pumps from Scale pit to 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 47 0.2530 0.3048 0.0712 0.0143 0.0033 3.88 0.94 0.30 0.95 12.69 3.06
settling tankfor BM,WRM
(Sstandby) (terminal1)
P5-E Vertical Pumps from Scale pit to 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 47 0.2530 0.3048 0.0712 0.0143 0.0033 3.88 0.94 0.30 0.95 12.69 3.06
settling tankfor BM,WRM
(standby) (terminal2)
P17-A Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 44 0.4430 0.5337 0.0740 0.0235 0.0033 3.42 0.82 0.30 0.95 9.78 2.36
for Flume flushing (working)
(terminal1)
P17-A Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 44 0.4430 0.5337 0.0740 0.0235 0.0033 3.42 0.82 0.30 0.95 9.78 2.36
for Flume flushing (working)
(terminal2)
P17-B Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 43 0.4430 0.5337 0.0740 0.0229 0.0032 3.35 0.81 0.30 0.95 9.56 2.30
for Flume flushing (working)
(terminal1)
P17-B Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 43 0.4430 0.5337 0.0740 0.0229 0.0032 3.35 0.81 0.30 0.95 9.56 2.30
for Flume flushing (working)
(terminal2)
P17-C Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 42 0.4430 0.5337 0.0740 0.0224 0.0031 3.27 0.79 0.30 0.95 9.34 2.25
for Flume flushing (standby)
(terminal1)
P17-C Turbine Pumps from Scale Pit 90 0.939 0.83 0.56 160.66 556.54 92.76 0.657 141.18 3.00 2XWY 70.0 AL 32.0 179 1 42 0.4430 0.5337 0.0740 0.0224 0.0031 3.27 0.79 0.30 0.95 9.34 2.25
for Flume flushing (standby)
(terminal2)
P9-A Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.0 2XWY 70.0 AL 32.0 179 1 55 0.4430 0.5700 0.0740 0.0313 0.0041 5.53 1.33 0.30 0.95 15.57 3.75
BAR Mill for milll heat Exchange
(ICW) (working) (terminal2)
P9-B Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.0 2XWY 70.0 AL 32.0 179 1 52 0.4430 0.5700 0.0740 0.0296 0.0038 5.22 1.26 0.30 0.95 14.72 3.55
BAR Mill for milll heat Exchange
(ICW)(working) (terminal1)
P9-B Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.0 2XWY 70.0 AL 32.0 179 1 52 0.4430 0.5700 0.0740 0.0296 0.0038 5.22 1.26 0.30 0.95 14.72 3.55
BAR Mill for milll heat Exchange
(ICW) (working) (terminal2)
P9-C Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 50 0.4430 0.5337 0.0740 0.0267 0.0037 4.73 1.14 0.30 0.95 13.52 3.26
BAR Mill for milll heat Exchange
(ICW)(working) (terminal1)
P9-C Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 50 0.4430 0.5337 0.0740 0.0267 0.0037 4.73 1.14 0.30 0.95 13.52 3.26
BAR Mill for milll heat Exchange
(ICW) (working) (terminal2)
OWNER : JSPL
EPC CONTRACTOR : IIL Nominal Voltage 3 PH [V]: 415
Equip. Equipment Description Motor Efficency Full Load Sin q1 Rated Starting Running Derating Nominal No. of Type Of Selected Type Overall Rated No. of Length of "R" "R" "X" Actual Actual VD in VD in Motor Sin q2 Voltage Voltage
Tag No. FDR h Power Full Current Current Factor Current for Cores Cables Cable Of Diameter curren Parallel Cable of Cable of Cable of Cable Resist. React. Cable Cable Starti Drop in Drop in
Rating Factor Load of Cable selection of Size Condu of the t Runs fromMCC at 20 oC at 90 oC of Cable of Cable during during ng p.f. Cable Cable
ctor Cables carryi Runnin Runnin (Cos during during
(Cos q1) Current Cable ng to Motor at 90 oC g VMN g VMN q2) Starting Starting
capaci VMS VMS
ty
kW % Amps Amps Amps Amps mm² No. Mtrs. Ohms/k Ohms/k Ohms/km Ohms Ohms Volts % Volts %
m m
A B C D E F G H I J L M N O P Q R S T U V W X
Co-eff of res. Of
(1000/1.732x41
Nx (1+70xtemp
(6/(3^0.5))*G
W/415x100
(C/(DxE)) x
(ExQ+FxR)
(G/(3^0.5))
S/415x100
6xGx1.732x
(QxU+RxV)
(1000xL)
(1000xL)
1.732xGx
(Note-2)
Ö(1-U²)
Ö(1-E²)
Al/Cu)
G/H
5)
MxO/
MxP/
P10-A Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 55 0.4430 0.5337 0.0740 0.0294 0.0041 5.20 1.25 0.30 0.95 14.87 3.58
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal1)
P10-A Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 55 0.4430 0.5337 0.0740 0.0294 0.0041 5.20 1.25 0.30 0.95 14.87 3.58
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal2)
P10-B Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 52 0.4430 0.5337 0.0740 0.0278 0.0038 4.92 1.19 0.30 0.95 14.06 3.39
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal1)
P10-B Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 52 0.4430 0.5337 0.0740 0.0278 0.0038 4.92 1.19 0.30 0.95 14.06 3.39
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal2)
P10-C Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 50 0.4430 0.5337 0.0740 0.0267 0.0037 4.73 1.14 0.30 0.95 13.52 3.26
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal1)
P10-C Horizontal pumps cold well to 110 0.944 0.83 0.56 195.32 676.61 112.77 0.657 171.64 3.00 2XWY 70.0 AL 32.0 179 1 50 0.4430 0.5337 0.0740 0.0267 0.0037 4.73 1.14 0.30 0.95 13.52 3.26
W.R.Mill for milll heat Exchange
(ICW) (working)(terminal2)
OWNER : JSPL
EPC CONTRACTOR : IIL Nominal Voltage 3 PH [V]: 415
Equip. Equipment Description Motor Efficency Full Load Sin q1 Rated Starting Running Derating Nominal No. of Type Of Selected Type Overall Rated No. of Length of "R" "R" "X" Actual Actual VD in VD in Motor Sin q2 Voltage Voltage
Tag No. FDR h Power Full Current Current Factor Current for Cores Cables Cable Of Diameter curren Parallel Cable of Cable of Cable of Cable Resist. React. Cable Cable Starti Drop in Drop in
Rating Factor Load of Cable selection of Size Condu of the t Runs fromMCC at 20 oC at 90 oC of Cable of Cable during during ng p.f. Cable Cable
ctor Cables carryi Runnin Runnin (Cos during during
(Cos q1) Current Cable ng to Motor at 90 oC g VMN g VMN q2) Starting Starting
capaci VMS VMS
ty
kW % Amps Amps Amps Amps mm² No. Mtrs. Ohms/k Ohms/k Ohms/km Ohms Ohms Volts % Volts %
m m
A B C D E F G H I J L M N O P Q R S T U V W X
Co-eff of res. Of
(1000/1.732x41
Nx (1+70xtemp
(6/(3^0.5))*G
W/415x100
(C/(DxE)) x
(ExQ+FxR)
(G/(3^0.5))
S/415x100
6xGx1.732x
(QxU+RxV)
(1000xL)
(1000xL)
1.732xGx
(Note-2)
Ö(1-U²)
Ö(1-E²)
Al/Cu)
G/H
5)
MxO/
MxP/
Horizontal Pumps from Settling 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 25 0.2530 0.3048 0.0712 0.0076 0.0018 2.07 0.50 0.30 0.95 6.75 1.63
Tank to DMF(working)
(terminal1)
P6-D Horizontal Pumps from Settling 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 25 0.2530 0.3048 0.0712 0.0076 0.0018 2.07 0.50 0.30 0.95 6.75 1.63
Tank to DMF(working)
(terminal2)
P6-E Horizontal Pumps from Settling 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 30 0.2530 0.3048 0.0712 0.0091 0.0021 2.48 0.60 0.30 0.95 8.10 1.95
Tank to DMF(standby)
(terminal1)
P6-E Horizontal Pumps from Settling 160 0.95 0.83 0.56 282.31 977.94 162.99 0.657 248.08 3.00 2XWY 120.0 AL 39.5 257 1 30 0.2530 0.3048 0.0712 0.0091 0.0021 2.48 0.60 0.30 0.95 8.10 1.95
Tank to DMF(standby)
(terminal2)
Notes:
4 Formula used to calculate percentage voltage drop = [1.732 x Full load current x (Resistance x Cosø + Reactance x Sinø ) x Length of cable in Metre] / [Supply voltage x 10]
5 Motor starting curre 600 % of full load current [Reference: Design basis report ]
10 % during starting
7 Cable lengths are assumed based on layout drawing and considering the maximum length of similar type/rating feeders estimated among the no of drives for the same equipment.
8 Cable parameters and derating factors are from Manufacturer's (POLYCAB) catalogue.
: Power Cable Specific DATA SHEET FOR LV POWER CABLE . DOC NO : A/IILC7-E-DSH-3_REV 0
TYPE OF
2XWY 2XWY
CABLES
1C 2C 3C 3.5C 4C
SIZE R20 for 1.1 X at 50 Hz for Remarks Approximate Approximate Approximate Approximate Approximat
KV XLPE 1.1 KV XLPE Overall Overall Overall Overall e Overall
insulation insulation Diameter Diameter (mm) Diameter (mm) Diameter (mm) Diameter
(mm) (mm)
NOTES:
1. Cables are with XLPE insulation.
2. Cu Conductor for 1.5 mm^2 and 2.5 mm^2 sizes
3. Al Conductor for 4 mm^2 to 630 mm^2 sizes
4. All above cable data is taken from POLYCAB'S & NICC0'S catalog.
CURRENT CARRYING CAPACITIES FOR COPPER / ALUMINIUM CONDUCTOR
TYPE OF
CABLES 2XWY
4 36 43 Cu Conductor 3,3.5,4/C
6 47 54 Cu Conductor 3,3.5,4/C
10 62 72 Cu Conductor 3,3.5,4/C
16 70 73 Al Conductor 3,3.5,4/C
25 96 94 3,3.5,4/C