Electrical Layout Load Computations: Ground Floor
Electrical Layout Load Computations: Ground Floor
Electrical Layout Load Computations: Ground Floor
4
ELECTRICAL LAYOUT LOAD COMPUTATIONS
GROUND FLOOR
SECOND FLOOR
Max. Watts per load lighting outlet 100
Max. Watts per load convenience
360
outlet (2 gang) =
For Air-Condition Unit, Range Load 1119
Overcurrent Size of
No. of Conduit
CKT Description Volts Watts Amp. CKT Protective Copper
Outlet Diameter
Device Wires
1 Lighting Outlet 7 230 700 3.04 15 AT 2 - 2.0 mm2 13 mm
2 Lighting Outlet 7 230 700 3.04 15 AT 2 - 2.0 mm2 13 mm
3 Lighting Outlet 7 230 700 3.04 15 AT 2 - 2.0 mm2 13 mm
4 Convenience Outlet 5 230 1800 7.83 20 AT 2 - 3.5 mm2 13 mm
2
5 Convenience Outlet 5 230 1800 7.83 20 AT 2 - 3.5 mm 13 mm
2
6 Convenience Outlet 6 230 2160 9.39 20 AT 2 - 3.5 mm 13 mm
2
7 Air-Condition Unit (6.07A) 1 230 1119 4.87 30 AT 2 - 3.5 mm 13 mm
2
8 Air-Condition Unit (6.07A) 1 230 1119 4.87 30 AT 2 - 3.5 mm 13 mm
2
9 Air-Condition Unit (6.07A) 1 230 1119 4.87 30 AT 2 - 3.5 mm 13 mm
2
10 Water Heater (2.5kW) 1 230 2500 10.87 20 AT 2 - 3.5 mm 13 mm
TOTAL WATTAGE (except aircon) = 10360
THIIRD FLOOR