CENTRAL ELECTRICITY AUTHORITY
A. INTRODUCTION
1. The phenomenal growth of Indian Power System includes a vast
power transmission system of both HVAC and HVDC with
highest transmission system voltage of 765 kV AC and ± 800 kV
DC. This transmission network is spread over different
geographical areas, difficult terrains, coastal areas which are
prone to frequent cyclonic storms/ high speed winds, etc. The
transmission system assets include transmission lines & sub
stations/switchyards (both AIS & GIS) and damage to these
assets due to natural calamities or unprecedented events such
as sabotage or outage during system operation cannot be
completely avoided. Outage free transmission system is
practically impossible. However, steps can be taken to maintain
highest availability of transmission system and down time can
be reduced by adopting suitable mechanism of fast restoration.
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 1
CENTRAL ELECTRICITY AUTHORITY
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 2
CENTRAL ELECTRICITY AUTHORITY
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 3
CENTRAL ELECTRICITY AUTHORITY
B. GUIDELINES
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 4
CENTRAL ELECTRICITY AUTHORITY
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 5
CENTRAL ELECTRICITY AUTHORITY
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 6
CENTRAL ELECTRICITY AUTHORITY
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 7
CENTRAL ELECTRICITY AUTHORITY
**************************************
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 8
CENTRAL ELECTRICITY AUTHORITY
ANNEXURE- A
1.0 Mandatory spare towers for 66 kV upto 400 kV voltage level transmission
lines
The following quantity of normal towers of same/ standard design along with
their extensions shall be maintained as spare by the utility for each voltage
class and wind zone separately, provided such towers/ extensions are in use
in the transmission lines, which are in operation/under construction:
Table 1
Type of Quantity of Extensions for towers
Normal
Quantity Special type
tower
of (negative,
(same/ +3 M +6 M +9 M +18 M +25 M +30 M
Tower unequal
standard
etc.)
design)
5 Nos/
A/DA 1 No. 1 No. 1 No. 1 No. 1 No. - 1 No.
8 Nos.**
2.0 Mandatory spare towers for lines of 765 kV, 500 kV HVDC, 800 kV HVDC,
400 kV Quad bundle line, Multi Circuit Towers (towers with more than
two circuits) and towers of special design having ice loading etc.:
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 9
CENTRAL ELECTRICITY AUTHORITY
ANNEXURE- A
Table 2
Type of Quantity Quantity of Extensions for towers
Normal of Tower +3 M +6 M +9 M +18 +25 Special
tower M M type
(same/ (negati
standard ve,
design)
unequa
l etc.)
Suspension 5 Nos./ 1 No. 1 No. 1 No. 1No. 1 No. 1 No.
towers with 8 Nos.**
stub and
cleats
Tension 1No. 1No. 1No. 1No. 1No. 1No. 1 No.
towers with
stub and
cleats
Stub setting Template for each type suspension towers- 2 sets#
Stub setting Template for each type tension towers- 1 set each#
Table 3
Name of Material Unit Quantity
Stubs & cleats for 66 kV upto 400 kV Set
voltage level same / standard design
5/8** for each type
suspension towers for each wind zones (A
& DA)
Stubs & cleats for 66 kV upto 400 kV Set
voltage level same /standard design
1 for each type
tension towers for each wind zones (B &
DB, C & DC, D & DD)
Stubs setting templates for 66 kV upto Set
400 kV voltage level same / standard
2 for each type
design towers for each wind zones (A &
DA)#
Stubs setting templates for 66 kV upto Set
400 kV voltage level same / standard
1 for each type
design towers for each wind zones (B &
DB, C & DC, D & DD)#
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 10
CENTRAL ELECTRICITY AUTHORITY
ANNEXURE- A
Note (1): The accessories for conductor & earthwire / OPGW and the number
of insulators (discs / long rod insulators) & associated hardware fittings shall
be maintained by the utility for one kilometer (1km) of line for various sizes.
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 11
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 12
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 13
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 17
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 18
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 19
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 20
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 21
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 22
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 24
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 25
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 26
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 27
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 28
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 32
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 33
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 35
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 37
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 38
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 40
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 43
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 44
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 46
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 50
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 51
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 52
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 53
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
7.7 Set of relays, power contactors & switch fuses for Complete
electrical Control ckt. replacement for one
isolator (3 ph)
7.8 Rotary bearing for isolator Complete
replacement for one
isolator (3 ph)
8 Cooling Water System :
8.1 Fine Water Pump complete with Motor 1 set
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 54
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
11 220V Batteries
11.2 Terminal connectors with Bolts & Nuts 10 Nos. (each type)
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 55
CENTRAL ELECTRICITY AUTHORITY
Annexure-B
13 DG SETS :
14 LT Switchgear
GUIDELINES FOR AVAILABILITY OF SPARES AND INVENTORIES FOR POWER TRANSMISSION SYSTEM
TRANSMISSION LINES & SUBSTATION/SWITCHYARD) ASSETS 56
Annexure-E
S. No. Type of tower Wind zone Voltage level Available Quantity of Extensions for towers
Available
(A/B/C/D or Quantity of Special
DA/DB/DC/DD same / type
or multi-circuit) Standard +3 M +6 M +9 M +18 M +25 M +30 M (negative,
Design unequal
Tower etc.)
II. Mandatory spare towers for lines of 765 kV, 500 kV HVDC, 800 kV HVDC, 400 kV Quad bundle
line, Multi Circuit Towers (towers with more than two circuits) and towers of special design
having ice loading etc.:
S. No. Type of tower Wind zone Voltage level Available Quantity of Extensions for towers
with stub and Available
cleats Quantity of Special
(A/B/C/D or same / type
DA/DB/DC/DD Standard +3 M +6 M +9 M +18 M +25 M +30 M (negative,
or multi-circuit) Design unequal
Tower etc.)
Annexure-E
to 400 kV twin
bundle
6. ERS suitable for 765 Set
kV/ 500 kV HVDC/
800 kV HVDC/ 400
kV Quad Bundle (in
States having such
system)
7. Galvanized steel
sections for
Nos.
replacement of
missing members
8. Anti-theft Galvanized
nut bolts & washers Nos.
of various length
Conductor/Earthwire/OPGW:
S. Material Unit Available Shortfall w.r.t.
No. Quantity quantity specified
in the guidelines
1. ACSR Moose conductor Km
2. ACSR Zebra conductor (for 220 kV lines) Km
3. ACSR Zebra conductor (for 765 kV D/C lines) Km
4. ACSR Panther conductor Km
5. ACSR Dog conductor Km
6. ACSR Bersimis conductor Km
7. ACSR Snowbird conductor Km
8. ACSR lapwing Conductor Km
9. Other special type of conductor like AAAC Km
INVAR, HTLS etc.
10. 7 X 3.66 mm GS Earth wire Km
Annexure-E
13. OPGW Km
14. Any other size/type of conductor/earthwire Km
(please specify)