EP..F+MP Datasheet en-AP
EP..F+MP Datasheet en-AP
EP..F+MP Datasheet en-AP
F+MP
Characterised control valve with
sensor-operated flow control, 2-way,
Flange, PN 16 (EPIV)
• Nominal voltage AC/DC 24 V
• Control modulating, communicative
• For closed cold and warm water
systems
• For modulating control of air-
handling and heating systems on the
water side
• Communication via Belimo MP-Bus
or conventional control
• Conversion of active sensor signals
and switching contacts
Type overview
Type DN DN V’nom V’nom kvs theor. PN n(gl)
[ ] [“] [ l/s] [ l/min] [ m³/h] [ ] [ ]
EP065F+MP 65 2 1/2 8 480 50 16 3.2
EP080F+MP 80 3 11 660 74 16 3.2
EP100F+MP 100 4 20 1200 126 16 3.2
EP125F+MP 125 5 31 1860 195 16 3.2
EP150F+MP 150 6 45 2700 254 16 3.2
kvs theor.: Theoretical kvs value for pressure drop calculation
Technical data
Electrical data Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 9.5 W
Power consumption in rest position 6.5 W
Power consumption for wire sizing 13 VA
Connection supply / control Cable 1 m, 4 x 0.75 mm²
Parallel operation Yes (note the performance data)
Functional data Torque Motor 20 Nm (DN 65...80)
40 Nm (DN 100...150)
Operating range Y DC 2...10 V
Input Impedance 100 kΩ
Operating range Y variable Start point DC 0.5...24 V
End point DC 8.5...32 V
Options positioning signal Modulating (DC 0...32 V)
Position feedback U DC 2...10 V
Position feedback U note Max. 1 mA
Position feedback U variable Start point DC 0.5...8 V
End point DC 2...10 V
Sound power level Motor 45 dB(A)
Adjustable flow rate V’max 30...100% of Vnom
Control accuracy ±5% (of 25...100% Vnom) @ 20°C / Glycol 0%
vol.
Media Cold and warm water, water with glycol up to
max. 60% vol.
Medium temperature -10...120°C
Close-off pressure ∆ps 690 kPa
Differential pressure ∆pmax 340 kPa
Flow characteristic equal percentage (VDI/VDE 2178), optimised in
the opening range (switchable to linear)
Leakage rate air-bubble tight, leakage rate A (EN 12266-1)
Pipe connectors Flange PN 16 according to EN 1092-2
Installation position upright to horizontal (in relation to the stem)
Servicing maintenance-free
Manual override with push-button, can be locked
Technical data
Flow measurement Measuring principle Ultrasonic volumetric flow measurement
Measuring accuracy flow ±2% (of 25...100% Vnom) @ 20°C / Glycol 0%
vol.
Min. flow measurement 1% of V’nom
Safety Protection class IEC/EN III Safety Extra-Low Voltage (SELV)
Degree of protection IEC/EN IP54
EMC CE according to 2014/30/EU
Mode of operation Type 1
Rated impulse voltage supply / control 0.8 kV
Control pollution degree 3
Ambient temperature -30...50°C
Storage temperature -20...80°C
Ambient humidity Max. 95% r.H., non-condensing
Materials Flow measuring pipe EN-GJL-250 (GG 25), with protective paint
Closing element stainless steel AISI 316
Stem seal EPDM
Ball seat PTFE, O-ring Viton
Safety notes
• This device has been designed for use in stationary heating, ventilation and air
! conditioning systems and must not be used outside the specified field of application,
especially in aircraft or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation
or aggressive gases interfere directly with the actuator and that is ensured that the
ambient conditions remain at any time within the thresholds according to the data
sheet.
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The connection between the control valve and the measuring tube should not be
separated.
• The device contains electrical and electronic components and must not be disposed
of as household refuse. All locally valid regulations and requirements must be
observed.
Product features
Mode of operation The final controlling device is comprised of three components: characterised control
valve (CCV), measuring pipe with volumetric flow sensor and the actuator itself.
The adjusted maximum flow (max) is assigned to the maximum positioning signal
(typically 10 V / 100%). The final controlling device can be controlled communicative
or analogue. The medium is detected by the sensor in the measuring pipe and is
applied as the flow value. The measured value is balanced with the setpoint. The
actuator corrects the deviation by changing the valve position. The angle of rotation α
varies according to the differential pressure through the final controlling element (see
volumetric flow curves).
Flow characteristic
Flow rate curves
∆p3
∆p1 < ∆p2 < ∆p3
∆p2
∆p1
Product features
Transmission behaviour HE Heat exchanger transmission behaviour
Depending on the construction, temperature spread, medium and hydraulic circuit,
the power Q is not proportional to the water volumetric flow (Curve 1). With the
classical type of temperature control, an attempt is made to maintain the control signal
Y proportional to the power Q (Curve 2). This is achieved by means of an equal-
percentage valve characteristic curve (Curve 3).
Y
Product features
Control characteristics The velocity of the medium is measured in the measuring component (sensor
electronics) and converted to a flow rate signal.
The positioning signal Y corresponds to the power Q via the exchanger, the
volumetric flow is regulated in the EPIV. The control signal Y is converted into an
equal-percentage characteristic curve and provided with the V̇max value as the new
reference variable w. The momentary control deviation forms the positioning signal Y1
for the actuator.
The specially configured control parameters in connection with the precise flow rate
sensor ensure a stable quality of control. They are however not suitable for rapid
control processes, i.e. for domestic water control.
U5 displays the measured volumetric flow as voltage (factory setting). As an
alternative, U5 can be used for displaying the valve opening angle. It is always in
reference to the respective V̇nom, i.e. if V̇max is e.g. 50% of V̇nom, then Y = 10 V,
U5 = 5 V.
1. Standard equal percentage Vmax = Vnom / 2. effect Vmax < Vnom
U5 [V] U5 [V]
1 2
nom nom
100% 100%
25%
0 Y [V] 0 Y [V]
80%100% 80%100%
D U5
1)
A
Y
A
1)
D w
PP/MP
D
Y1
k
A
max
DN
Product features
Definition Flow control
V̇nom is the maximum possible flow.
V̇max is the maximum flow rate which has been set with the greatest positioning
signal. V̇max can be set between 30% and 100% of V̇nom.
V̇min 0% (non-variable).
100% nom
30% max
0 Y
100%
Creep flow suppression Given the very low flow speed in the opening point, this can no longer be measured by
the sensor within the required tolerance. This range is overridden electronically.
Opening valve
The valve remains closed until the volumetric flow required by the positioning signal Y
corresponds to 1% of V̇nom. The control along the valve characteristic curve is active
after this value has been exceeded.
Closing valve
The control along the valve characteristic curve is active up to the required flow rate of
1% of V̇nom. Once the level falls below this value, the flow rate is maintained at 1% of
V̇nom. If the level falls below the flow rate of 0.5% of V̇nom required by the reference
variable Y, then the valve will close.
1%
0 Y
0.5% 1% 100%
Converter for sensors Connection option for a sensor (active sensor or switching contact). The MP actuator
serves as an analogue/digital converter for the transmission of the sensor signal via
MP-Bus to the higher level system.
Configurable actuators The factory settings cover the most common applications. Single parameters can be
modified with the Belimo Service Tools MFT-P or ZTH AP.
Positioning signal inversion This can be inverted in cases of control with an analogue positioning signal. The
inversion causes the reversal of the standard behaviour, i.e. at a positioning signal of
0%, regulation is to max, and the valve is closed at a positioning signal of 100%.
Hydraulic balancing With the Belimo tools, the maximum flow rate (equivalent to 100% requirement) can
be adjusted on-site, simply and reliably, in a few steps. If the device is integrated in the
management system, then the balancing can be handled directly by the management
system.
Manual override Manual override with push-button possible (the gear is disengaged for as long as the
button is pressed or remains locked).
High functional reliability The actuator is overload protected, requires no limit switches and automatically stops
when the end stop is reached.
Accessories
Description Type
Gateways Gateway MP zu BACnet MS/TP UK24BAC
Gateway MP to Modbus RTU UK24MOD
Gateway MP to LonWorks UK24LON
Gateway MP to KNX UK24EIB
Description Type
Electrical accessories Stem heating flange ISO 5211, F05 (30 W) ZR24-F05
Connection cable 5 m, A: RJ11 6/4, B: 6-pin New Generation for ZTH ZK1-GEN
AP
Connection cable 5 m, A: RJ11 6/4, B: free wire end for ZTH AP ZK2-GEN
Connecting board MP-Bus for wiring boxes EXT-WR-FP20-MP (IP20) ZFP2-MP
and EXT-WR-FP65-MP (IP65)
MP-Bus power supply for MP actuators ZN230-24MP
Description Type
Service Tools Service tool for configurable and communicative Belimo actuators / ZTH AP
VAV controller and HVAC performance devices
Belimo PC-Tool, Software for adjustments and diagnostics, for MF/MP/ MFT-P
MOD/LON/KNX actuators incl. fire protection, CD with Software and
instructions (de/en), for Windows operating systems
Adapter for Service-Tool ZTH MFT-C
Level converter USB/MP ZIP-USB-MP
Electrical installation
Wiring diagrams
Y DC (0)2…10 V Y Sensor
U DC 2…10 V U MP
Functions
Functions
Functions when operated on MP-Bus
A)
A) A)
Override control and limiting with AC 24 V with relay contacts Override control and limiting with DC 24 V with relay contacts
T ~ + -
Y (DC 0 ... 10 V) Y (DC 0 ... 10 V)
e e
a b d a b
e.g. 1N 4007
a b d e
Close a b d e
1 2 3 5 1 2 3 5
max Close
~ Open ~ max
Y U Y U
T T
Y Y
Control 3-point
T ~
U
a b
e.g. 1N 4007
1 2 3 5
Installation notes
Recommended installation positions The ball valve can be installed upright to horizontal. The ball valve may not be installed
in a hanging position, i.e. with the stem pointing downwards.
90° 90°
Before any service work on the final controlling device is carried out, it is essential to
isolate the rotary actuator from the power supply (by unplugging the electrical cable
if necessary). Any pumps in the part of the piping system concerned must also be
switched off and the appropriate slide valves closed (allow all components to cool
down first if necessary and allways reduce the system pressure to ambient pressure
level).
The system must not be returned to service until the ball valve and the rotary actuator
have been correctly reassembled in accordance with the instructions and the pipeline
has been refilled by professionally trained personnel.
Installation notes
Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with,
since otherwise the flow rate will be measured incorrectly.
Inlet section In order to achieve the specified measuring accuracy, a flow-calming section or inflow
section in the direction of the flow is to be provided upstream from the flow sensor. Its
dimensions should be at least 5x DN.
DN L min.
65 5 x 65 mm = 325 mm
80 5 x 80 mm = 400 mm
100 5 x 100 mm = 500 mm
125 5 x 125 mm = 625 mm
150 5 x 150 mm = 750 mm
L ≥ 5 x DN
General notes
Valve selection The valve is determined using the maximum required flow rate V̇max.
A calculation of the kvs value is not required.
V̇max = 30…100% of V̇nom
If no hydraulic data are available, then the same valve DN can be selected as the heat
exchanger nominal diameter.
Minimum differential pressure The minimum required differential pressure (pressure drop through the valve) for
(pressure drop) achieving the desired volumetric flow max can be calculated with the aid of the
theoretical kvs value (see type overview) and the below-mentioned formula. The
calculated value is dependent on the required maximum volumetric flow max. Higher
differential pressures are compensated for automatically by the valve.
Formula
2 ∆pmin: kPa
max
∆pmin = 100 x max: m3/h
kvs theor. kvs theor.: m3/h
Example (DN100 with the desired maximum flow rate = 50% nom)
EP100F+MP
kvs theor. = 115 m 3/h
nom = 1200 l/min
50% * 1200 l/min = 600 l/min = 36 m3/h
2 2
max 36 m3/h
∆pmin = 100 x = 100 x = 10 kPa
kvs theor. 115 m3/h
Behaviour of sensor failure In case of a flow sensor error, the EPIV will switch from flow control to position
control. Once the error disappears, the EPIV will switch back to the normal
control setting.
Service
Service Tools connection The actuator can be parameterised by ZTH AP via the service socket.
For an extended parameterisation the PC tool can be connected.
Connection ZTH AP / PC-Tool
AC 24 V
T ~
– + DC 24 V
Y
U
MP
ZTH AP
USB
i esc OK
BELIMO
PC-Tool
1 2 3 5
USB
Y U
Dimensions / Weight
Dimensional drawings
min. Y min. X
H
D
d
K
L
If Y <180 mm, the extension of the hand crank must be demounted as necessary.
Type DN L H D d K X Y Weight
[ ] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm] [ mm]
EP065F+MP 65 379 205 185 4 x 19 145 220 150 26 kg
EP080F+MP 80 430 205 200 8 x 19 160 220 160 35 kg
EP100F+MP 100 474 221 229 8 x 19 180 240 175 52 kg
EP125F+MP 125 579 249 252 8 x 19 210 260 190 70 kg
EP150F+MP 150 651 249 282 8 x 23 240 260 200 90 kg
Further documentation
• Overview MP Cooperation Partners
• Tool connections
• Introduction to MP-Bus Technology
• General notes for project planning