MIC-5010 / MIC-5005: Insulation Resistance Meter
MIC-5010 / MIC-5005: Insulation Resistance Meter
WMGBMIC5005
· Digital filters function for measurements in high noise enviroment (10 s, 30 s, 60 s).
· MIC-5010: Continuity measurement of protective connections and equipotential bonding in accordance with
Sonel S.A. EN 61557-4 with current > 200 mA.
ul. Wokulskiego 11 · MIC-5010: Adjustable limits for measured resistance RISO and RCONT.
58-100 Świdnica, PL · Measurement of leakage current during insulation resistance testing.
· Measurement of capacitance during the measurement of RISO.
tel. +48 74 85 83 860
· DC and AC voltage measurement in the range of 0…600 V.
fax +48 74 85 83 809 · 990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR
adapter) or through a USB cable.
· Power supply from main power line or battery packs, low battery warning indicator, built-in fast charger.
[email protected] · Keyboard and display backlit (MIC-5005 - only display).
The instruments meet the requirements of the EN 61557 standard.
www.sonel.pl
MIC-5010/MIC-5005
Insulation resistance measurement
Measurement range acc. to IEC 61557-2: 50 kΩ...15,0 TΩ (IISOnom = 1,2 mA or 3 mA) Measurement of capacitance
1...999 nF 1 nF
0...999 kΩ 1 kΩ ±(5% m.v. + 5digits)
1.00...49.99 µF 0.01 µF
1.00..9.99 MΩ 0.01 MΩ
10.0...99.9 MΩ 0.1 MΩ · Capacity measurement result is displayed after the RISO measurement
±(3% m.v. + 10 digits)
100..999 MΩ 1 MΩ
1.00...9.99 GΩ 0.01 GΩ DC and AC voltage measurement
10.0...99.9 GΩ 0.1 GΩ
Range Resolution Accuracy
100...999 GΩ 1 GΩ ±(3.5% m.v. + 10 digits)
1.00...9.99 TΩ 0.01 TΩ ±(7.5% m.v. + 10 digits) 0.0...29.9 V 0.1 V ±(2% m.v. + 20 digits)
10.0...15.0 TΩ 0.1 TΩ ±(10% m.v. + 10 digits) 30.0...299.9 V 0.1 V ±(2% m.v. + 6 digits)
300...600 V 1V ±(2% m.v. + 2 digits)
Values of measured resistance depending on measurement voltage · Frequency range: 45...65Hz
v.2