Specification
Lionel Ng, ABB SACE, Specialist
January 2011 Consultant Channel
© ABB Ltd – 04-04
© ABB Group
October 7, 2013 | Slide 1
Agenda
1. Main CHARACTERISTICS
2. The RANGES
3. CONSTRUCTION characteristics
4. PROTECTION releases
1. Main CHARACTERISTICS
2. The RANGES
3. CONSTRUCTION characteristics
4. PROTECTION releases
E1 E2 E3 E4 E6
Performance levels B N B N S L N S H V L S H V H V
Rated current Iu [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 3200
[A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 4000 5000 4000
[A] 1250 1250 1600 1250 1600 1250 1600 6300 5000
[A] 1600 1600 2000 1600 2000 1600 2000 6300
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200
Breaking capacity
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 75 100 150 100 150
Icu @ 690 V AC [kA] 42 50 42 55 65 85 65 75 100 100 85 75 85 100 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 75 100 150 100 125
Ics @ 690 V AC [kA] 42 50 42 55 65 65 65 75 85 85 65 75 85 100 100 100
Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 165 220 330 220 330
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 187 143 165 187 220 187 165 186 220 220 220
Utilisation category B B B B B A B B B B A B B B B B
MORE
The ranges – Automatic circuit-breakers fully rated
E1 E2 E3 E4 E6
Standard Standard Standard
Performance levels B N B N S L N S H V L S/f H/f H/f
Rated current Iu [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 4000
[A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 5000
[A] 1250 1250 1600 1250 1600 1250 1600 6300
[A] 1600 1600 2000 1600 2000 1600 2000
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200
Breaking capacity
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 80 100 100
Icu @ 690 V AC [kA] 42 50 42 55 65 85 65 75 85 100 85 75 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 80 100 100
Ics @ 690 V AC [kA] 42 50 42 55 65 65 65 75 85 85 65 75 100 100
Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 176 220 220
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 187 143 165 187 220 187 165 220 220
Utilisation category B B B B B A B B B B A B B B
The ranges – Switch-disconnectors
E1 E2 E3 E4 E6
Version B/MS N/MS B/MS N/MS S/MS N/MS S/MS V/MS S/MS H/MS H/f MS H/MS H/f MS
Rated current Iu [A] 800 800 1600 1000 1000 2500 1000 800 4000 3200 3200 4000 4000
[A] 1000 1000 2000 1250 1250 3200 1250 1250 4000 4000 5000 5000
[A] 1250 1250 1600 1600 1600 1600 6300 6300
[A] 1600 1600 2000 2000 2000 2000
[A] 2500 2500
[A] 3200 3200
Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 143 165 286 165 220 220 220 220
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 143 165 220 165 187 220 220 220
The ranges – Automatic circuit-breakers for application
up to 1150 V AC
E2 E3 E4 E6
E2 E3 E4 E6
E1 E2 E3 E4 E6
Poles 3 4 3 4 3 4 3 4 3 4
Rated service voltage Ue [V] 750 1000 750 1000 750 1000 750 1000 750 1000
Rated insulation voltage [V] 1000 1000 1000 1000 1000
Rated impulse withstand volt. [kV] 12 12 12 12 12
Rated withstand current Icw (1s) [kA] 20 25 40 65 65
Making capacity
Icm @ 750 V DC [kA] 42 42 52,5 52,5 105 105 143 143 143 143
Icm @ 1000 V DC [kA] - 42 - 52,5 - 105 - 143 - 143
Note: the breaking capacity Icu, by means of external protection relay, with 500 ms max timing, is equal to Icw (1s)
The ranges – Derived versions
E1 E2 E3 E4 E6
Sectionalizing truck E1 CS E2 CS E3 CS E4 CS E6 CS
Iu (40°C) [A] 1250 2000 3200 4000 6300
Earthing switch with making capacity E1 MTP E2 MTP E3 MTP E4 MTP E6 MTP
Iu (40°C) [A] 1250 2000 3200 4000 6300
Earthing truck E1 MT E2 MT E3 MT E4 MT E6 MT
Iu (40°C) [A] 1250 2000 3200 4000 6300
Sezionalizing truck
Agenda
1. Main CHARACTERISTICS
2. The RANGES
3. CONSTRUCTION characteristics
4. PROTECTION releases
DOUBLE INSULATION
Construction characteristics
1. Main CHARACTERISTICS
2. The RANGES
3. CONSTRUCTION characteristics
4. PROTECTION releases
MORE
Rc D U RV
Complete set of advanced protection functions
OT UV OV RP
MORE
A V Hz
Complete set of measurements functions
W VA VAR E THD
MORE
Protection releases: general features
MORE
MORE
MORE
Protection releases: general features
MORE
Interchangeability of releases
Protection releases
Protection releases: PR121 – Basic features
Versions:
LI
LSI
LSIG
L prealarm/Alarm/Trip leds;
Fine tuning for L;
S protection up to 10In, I protection up to 15In;
time or I2t constant G protection;
Protection releases: PR121 – Additional features
Connection to SD-Pocket:
Using Test connector;
Real time current measuring;
Last 20 trips information: protection tripped, currents, time stamp;
Custom configuration of PR021/K;
Connection to DocWin for selectivity analysis.
Protection releases
Protection releases: PR122 – Basic features
Versions:
LI
LSI
LSIG
LSIRc
Evolution of PR112;
Modular architecture: configurable to fit your plant;
Last 20 Trips and 60 events information directly on display. Trips In self supply.
Up to 10 open/closed contact available;
Voltage – based features (option);
Wide quantity of thresholds;
Enhanced interface: wide graphic display; user-friendly menus;
Internal bus;
Protection releases: PR122 – Protections
Standard:
L, S, I, G;
Thermal memory for L and S;
Startup thresholds for S, I and G;
Zone selectivity interlocking for S and G;
Source Ground Return (with Homopolar toroid);
Residual current (PR122/P LSIRc only);
Phase unbalance;
Release overtemperature;
Protection releases: PR122 – Protections
Standard:
Phase, Neutral, Ground fault current;
Peak Factor;
Data logger.
MORE
Versions:
LSI
LSIG
Evolution of PR113;
Modular architecture: configurable to fit your plant;
Last 20 Trips and 60 events information directly on display. Trips In self supply.
10 open/closed contact available;
Voltage – based features;
No more need for voltage transformers;
Data logger as standard;
Protection releases: PR123 – Protections
Basic Protections;
L, S, I, G;
Thermal memory for L and S;
Startup thresholds for S, I and G;
Zone selectivity interlocking for S and G;
Source Ground Return (with Homopolar toroid);
Phase current unbalance;
Release overtemperature;
Overvoltage, undervoltage, residual voltage;
Overfrequency, underfrequency;
Reverse Power Flow;
Phase sequence (alarm);
Residual current (with Rc toroid).
Protection releases: PR123 – Protections
Advanced protections:
Double S protection;
Double G protection;
Dual setting for all protections;
Directional protection;
MORE
Zone selectivity interlocking for D.
Protection releases: PR123 – Measurements
Standard:
Phase, Neutral, Ground fault current;
Peak Factor;
Data logger;
Line voltage, phase voltage;
Frequency;
Active, reactive, apparent Power;
Historical of measurements;
Energy counters;
Waveform, RMS spectrum;
THD.
Protection releases: accessories
MORE
HMI030
Graphic display that shows all the measurements and alarm/events of the protection release. To be installed on
the front side of the switchboard
BT030
It allows Bluetooth communication between Emax protection releases and a PDA or a notebook with a Bluetooth
port. It has to be connected to Test Connector of PR121/P, PR122/P and PR123/P.
Protection releases: accessories
Discrimination table
SD-Pocket
Application design to connect the Emax releases to an hand-held or to a
personal computer, via PR120/D-BT or BT030.
It allows to:
Configure the protection threshold functions
Monitor measurement functions, including reading of data record in data logger
Verify the status of circuit-breaker
Agenda
1. Main CHARACTERISTICS
2. The RANGES
3. CONSTRUCTION characteristics
4. PROTECTION releases
Fixed version
Withdrawable version
Rear
VR
Rear
HR
Front
Accessories supplied as standard
FIXED CIRCUIT-BREAKER:
flange for switchgear compartment door (IP3X)
support for service releases
four auxiliary contacts for electrical signalling of circuit-
breaker open/closed (for automatic circuit-breakers only)
terminal box for connecting outgoing auxiliaries
mechanical signalling of trip
horizontal rear terminals
lifting plate
WITHDRAWABLE CIRCUIT-BREAKER:
flange for switchgear compartment door
support for service releases
four auxiliary contacts for electrical signalling of circuit-breaker
open/closed (for automatic circuit-breakers only)
sliding contacts for connecting outgoing auxiliaries
mechanical signalling of trip
horizontal rear terminals
anti-insertion lock for circuit-breakers with different rated
currents
racking-out crank handle
lifting plate
Electrical Accessories
Auto MS CS MTP MT
MORE
Electrical Accessories
(YC)
(UVR)
(YO)
Electrical Accessories
Auto MS CS MTP MT
MORE
Mechanical Accessories
Operation counter
Mechanical interlocks
Mechanical Accessories
Type A Type C 1 2 3
ooo
G 1 2 I oo
oo O I o
I o O O I
O I 1 2 3 O I I
1 2
I I o
I o I
Type B Type D
1 2 3 1 2 3
G ooo G ooo
I oo I oo
Oo I O I o
1 2 3 I O I 1 2 3 OO I
O I O