0% found this document useful (0 votes)
122 views60 pages

Abb Acb

The document discusses the ranges of circuit breakers and switch-disconnectors offered by ABB, including their rated currents and breaking/making capacities at various voltages. It provides detailed specifications in tables for the different product levels from E1 to E6.

Uploaded by

ilen elaine
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
122 views60 pages

Abb Acb

The document discusses the ranges of circuit breakers and switch-disconnectors offered by ABB, including their rated currents and breaking/making capacities at various voltages. It provides detailed specifications in tables for the different product levels from E1 to E6.

Uploaded by

ilen elaine
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

Regional

Specification
Lionel Ng, ABB SACE, Specialist
January 2011 Consultant Channel
© ABB Ltd – 04-04

© ABB Group
October 7, 2013 | Slide 1
Agenda

1. Main CHARACTERISTICS

2. The RANGES

3. CONSTRUCTION characteristics

4. PROTECTION releases

5. Terminals and ACCESSORIES


New Emax: The evolution continues.
New Emax: Lively performances.

800A to 6300A 42 to 150 kA @ Wireless communication Extremely simple installation


440 V AC
New Emax: Brilliant intelligence

Completely new Rating plug Modularity Fault recording


protection releases
Agenda

1. Main CHARACTERISTICS

2. The RANGES

3. CONSTRUCTION characteristics

4. PROTECTION releases

5. Terminals and ACCESSORIES


The ranges – Automatic circuit-breakers

E1 E2 E3 E4 E6

Performance levels B N B N S L N S H V L S H V H V

Rated current Iu [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 3200
[A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 4000 5000 4000
[A] 1250 1250 1600 1250 1600 1250 1600 6300 5000
[A] 1600 1600 2000 1600 2000 1600 2000 6300
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200

Breaking capacity
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 75 100 150 100 150
Icu @ 690 V AC [kA] 42 50 42 55 65 85 65 75 100 100 85 75 85 100 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 75 100 150 100 125
Ics @ 690 V AC [kA] 42 50 42 55 65 65 65 75 85 85 65 75 85 100 100 100

Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 165 220 330 220 330
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 187 143 165 187 220 187 165 186 220 220 220

Rated withstand current


Icw @ 1 s [kA] 42 50 42 55 65 10 65 75 75 85 15 75 100 100 100 100
Icw @ 3 s [kA] 36 36 42 42 42 - 65 65 65 65 - 75 75 75 85 85

Utilisation category B B B B B A B B B B A B B B B B

MORE
The ranges – Automatic circuit-breakers fully rated

E1 E2 E3 E4 E6
Standard Standard Standard
Performance levels B N B N S L N S H V L S/f H/f H/f

Rated current Iu [A] 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 4000
[A] 1000 1000 2000 1250 1000 1600 3200 1250 1000 1250 2500 4000 5000
[A] 1250 1250 1600 1250 1600 1250 1600 6300
[A] 1600 1600 2000 1600 2000 1600 2000
[A] 2000 2500 2000 2500
[A] 3200 2500 3200
[A] 3200

Breaking capacity
Icu @ 415 V AC [kA] 42 50 42 65 85 130 65 75 100 130 130 80 100 100
Icu @ 690 V AC [kA] 42 50 42 55 65 85 65 75 85 100 85 75 100 100
Ics @ 415 V AC [kA] 42 50 42 65 85 130 65 75 85 100 130 80 100 100
Ics @ 690 V AC [kA] 42 50 42 55 65 65 65 75 85 85 65 75 100 100

Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 286 143 165 220 286 286 176 220 220
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 187 143 165 187 220 187 165 220 220

Rated withstand current


Icw @ 1 s [kA] 42 50 42 55 65 10 65 75 75 85 15 80 85 100
Icw @ 3 s [kA] 36 36 42 42 42 - 65 65 65 65 - 75 75 85

Utilisation category B B B B B A B B B B A B B B
The ranges – Switch-disconnectors

E1 E2 E3 E4 E6

Version B/MS N/MS B/MS N/MS S/MS N/MS S/MS V/MS S/MS H/MS H/f MS H/MS H/f MS

Rated current Iu [A] 800 800 1600 1000 1000 2500 1000 800 4000 3200 3200 4000 4000
[A] 1000 1000 2000 1250 1250 3200 1250 1250 4000 4000 5000 5000
[A] 1250 1250 1600 1600 1600 1600 6300 6300
[A] 1600 1600 2000 2000 2000 2000
[A] 2500 2500
[A] 3200 3200

Rated service voltage Ue


AC [V] 690 690 690 690 690
DC [V] 250 250 250 250 250

Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000

Rated impulse withstand volt. [kV] 12 12 12 12 12

Rated withstand current


Icw @ 1 s [kA] 42 50 42 55 65 65 75 85 75 100 85 100 100
Icw @ 3 s [kA] 36 36 42 42 42 65 65 65 75 75 75 85 85

Making capacity
Icm @ 415 V AC [kA] 88,2 105 88,2 143 187 143 165 286 165 220 220 220 220
Icm @ 690 V AC [kA] 88,2 75,6 88,2 121 143 143 165 220 165 187 220 220 220
The ranges – Automatic circuit-breakers for application
up to 1150 V AC

E2 E3 E4 E6

Version B/E N/E H/E H/E H/E

Rated current Iu [A] 1600 1250 1250 3200 5000


[A] 2000 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200
Rated service voltage Ue AC [V] 1150 1150 1150 1150
Rated insulation voltage [V] 1250 1250 1250 1250
Breaking capacity
Icu @ 1000 V AC [kA] 20 30 50 65 65
Icu @ 1150 V AC [kA] 20 30 30 65 65
Ics @ 1000 V AC [kA] 20 30 50 65 65
Ics @ 1150 V AC [kA] 20 30 30 65 65
Making capacity
Icm @ 1000 V AC [kA] 40 63 105 143 143
Icm @ 1150 V AC [kA] 40 63 63 143 143
Rated withstand current Icw (1s) [kA] 20 30 50 65 65
The ranges – Switch-disconnectors for applications
up to 1150 V AC

E2 E3 E4 E6

Version B/E MS N/E MS H/E MS H/E MS H/E MS

Rated current Iu [A] 1600 1250 1250 3200 5000


[A] 2000 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200

Poles 3/4 3/4 3/4 3/4


Rated service voltage Ue AC [V] 1150 1150 1150 1150
Rated insulation voltage [V] 1250 1250 1250 1250
Rated impulse withstand volt. [kV] 12 12 12 12
(1)
Rated withstand current Icw (1s) [kA] 20 30 30 65 65
Making capacity Icm @ 1000 V AC [kA] 40 63 105 143 143

(1) The performance at 1000 V is 50 kA


Note: the breaking capacity Icu, by means of external protection relay, with 500 ms max timing, is equal to Icw (1s)
The ranges – Switch-disconnectors for applications
up to 1000 V DC

E1 E2 E3 E4 E6

Version B/E MS N/E MS H/E MS H/E MS H/E MS

Rated current Iu [A] 800 1250 1250 3200 5000


[A] 1250 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200

Poles 3 4 3 4 3 4 3 4 3 4
Rated service voltage Ue [V] 750 1000 750 1000 750 1000 750 1000 750 1000
Rated insulation voltage [V] 1000 1000 1000 1000 1000
Rated impulse withstand volt. [kV] 12 12 12 12 12
Rated withstand current Icw (1s) [kA] 20 25 40 65 65
Making capacity
Icm @ 750 V DC [kA] 42 42 52,5 52,5 105 105 143 143 143 143
Icm @ 1000 V DC [kA] - 42 - 52,5 - 105 - 143 - 143

Note: the breaking capacity Icu, by means of external protection relay, with 500 ms max timing, is equal to Icw (1s)
The ranges – Derived versions

E1 E2 E3 E4 E6

Sectionalizing truck E1 CS E2 CS E3 CS E4 CS E6 CS
Iu (40°C) [A] 1250 2000 3200 4000 6300

Earthing switch with making capacity E1 MTP E2 MTP E3 MTP E4 MTP E6 MTP
Iu (40°C) [A] 1250 2000 3200 4000 6300

Earthing truck E1 MT E2 MT E3 MT E4 MT E6 MT
Iu (40°C) [A] 1250 2000 3200 4000 6300

Earthing truck with making capacity Earthing truck

Sezionalizing truck
Agenda

1. Main CHARACTERISTICS

2. The RANGES

3. CONSTRUCTION characteristics

4. PROTECTION releases

5. Terminals and ACCESSORIES


Construction characteristics

SHEET STEEL STRUCTURE

SINGLE POLE CONSTRUCTION CONCEPT

DOUBLE INSULATION
Construction characteristics

ONLY 4 (E1, E2, E3) OR 6 (E4, E6) FIXING POINT

SAME HEIGHT AND DEPTH FOR THE WHOLE RANGE

PRE-WIRED ELECTRICAL ACCESSORIES


Construction characteristics
Agenda

1. Main CHARACTERISTICS

2. The RANGES

3. CONSTRUCTION characteristics

4. PROTECTION releases

5. Terminals and ACCESSORIES


Protection releases
Protection releases: general features

Complete set of standard protection functions

MORE

Rc D U RV
Complete set of advanced protection functions
OT UV OV RP

MORE

A V Hz
Complete set of measurements functions
W VA VAR E THD

MORE
Protection releases: general features

New generation current sensor

MORE

A new concept for setting the current ratings: Rating Plug

MORE

Optional modules to upgrade the protection releases

MORE
Protection releases: general features

Check of main connection integrity


(opening solenoid & current sensors)

Complete information about last trips in self-supply

Neutral protection from OFF to 200%


Protection releases: general features

Test connector for PR010/T and BT030

Internal Bus to connect accessory devices HMI030, PR021/K...

MORE

Interchangeability of releases
Protection releases
Protection releases: PR121 – Basic features

Versions:
LI
LSI
LSIG

L prealarm/Alarm/Trip leds;
Fine tuning for L;
S protection up to 10In, I protection up to 15In;
time or I2t constant G protection;
Protection releases: PR121 – Additional features

Connection to SD-Pocket:
Using Test connector;
Real time current measuring;
Last 20 trips information: protection tripped, currents, time stamp;
Custom configuration of PR021/K;
Connection to DocWin for selectivity analysis.
Protection releases
Protection releases: PR122 – Basic features

Versions:
LI
LSI
LSIG
LSIRc

Evolution of PR112;
Modular architecture: configurable to fit your plant;
Last 20 Trips and 60 events information directly on display. Trips In self supply.
Up to 10 open/closed contact available;
Voltage – based features (option);
Wide quantity of thresholds;
Enhanced interface: wide graphic display; user-friendly menus;
Internal bus;
Protection releases: PR122 – Protections

Standard:
L, S, I, G;
Thermal memory for L and S;
Startup thresholds for S, I and G;
Zone selectivity interlocking for S and G;
Source Ground Return (with Homopolar toroid);
Residual current (PR122/P LSIRc only);
Phase unbalance;
Release overtemperature;
Protection releases: PR122 – Protections

With PR120/V (except PR122/P LSIRc):


Overvoltage, undervoltage, residual voltage;
Overfrequency, underfrequency;
Reverse Power Flow;
Phase sequence (alarm);
Residual current (with Rc toroid).
Protection releases: PR122 – Measurements

Standard:
Phase, Neutral, Ground fault current;
Peak Factor;
Data logger.
MORE

With PR120/V (except PR122/P LSIRc):


Line voltage, phase voltage;
Frequency;
Active, reactive, apparent Power;
Energy counters;
Protection releases: PR123 – Basic features

Versions:
LSI
LSIG

Evolution of PR113;
Modular architecture: configurable to fit your plant;
Last 20 Trips and 60 events information directly on display. Trips In self supply.
10 open/closed contact available;
Voltage – based features;
No more need for voltage transformers;
Data logger as standard;
Protection releases: PR123 – Protections

Basic Protections;
L, S, I, G;
Thermal memory for L and S;
Startup thresholds for S, I and G;
Zone selectivity interlocking for S and G;
Source Ground Return (with Homopolar toroid);
Phase current unbalance;
Release overtemperature;
Overvoltage, undervoltage, residual voltage;
Overfrequency, underfrequency;
Reverse Power Flow;
Phase sequence (alarm);
Residual current (with Rc toroid).
Protection releases: PR123 – Protections

Advanced protections:
Double S protection;
Double G protection;
Dual setting for all protections;
Directional protection;
MORE
Zone selectivity interlocking for D.
Protection releases: PR123 – Measurements

Standard:
Phase, Neutral, Ground fault current;
Peak Factor;
Data logger;
Line voltage, phase voltage;
Frequency;
Active, reactive, apparent Power;
Historical of measurements;
Energy counters;
Waveform, RMS spectrum;
THD.
Protection releases: accessories

Optional modules (Measurements, signalling,


communication, wireless com)

MORE

Test unit and PR010/T configuration


Test, programming and readout of parameters for PR121/P, PR122/P
and PR123/P

PR021/K Signalling Unit


It converts digital signals supplied by PR121/P, PR122/P and PR123/P
into electrical signals
Protection releases: accessories

PR030/B Power Supply Unit


It makes possible to read and configure the parameters of the unit whatever the status of the circuit-breaker
(always supplied with PR122/P and PR123/P)

HMI030
Graphic display that shows all the measurements and alarm/events of the protection release. To be installed on
the front side of the switchboard

BT030
It allows Bluetooth communication between Emax protection releases and a PDA or a notebook with a Bluetooth
port. It has to be connected to Test Connector of PR121/P, PR122/P and PR123/P.
Protection releases: accessories

EP010-FBP E-plug Interface


Adapter for field bus plug systems

Discrimination table

SD-Pocket
Application design to connect the Emax releases to an hand-held or to a
personal computer, via PR120/D-BT or BT030.

It allows to:
Configure the protection threshold functions
Monitor measurement functions, including reading of data record in data logger
Verify the status of circuit-breaker
Agenda

1. Main CHARACTERISTICS

2. The RANGES

3. CONSTRUCTION characteristics

4. PROTECTION releases

5. Terminals and ACCESSORIES


Accessories
Available terminals

Fixed version

Rear HR Rear VR Front

Withdrawable version

Rear HR Rear VR Front Flat

NB: Mixed combiantion of upper and lower termianals are available


Terminals conversion kits

For Fixed version:


Rear
VR
Rear
HR
Front

For Withdrawable version

Rear
VR

Rear
HR
Front
Accessories supplied as standard

FIXED CIRCUIT-BREAKER:
flange for switchgear compartment door (IP3X)
support for service releases
four auxiliary contacts for electrical signalling of circuit-
breaker open/closed (for automatic circuit-breakers only)
terminal box for connecting outgoing auxiliaries
mechanical signalling of trip
horizontal rear terminals
lifting plate

WITHDRAWABLE CIRCUIT-BREAKER:
flange for switchgear compartment door
support for service releases
four auxiliary contacts for electrical signalling of circuit-breaker
open/closed (for automatic circuit-breakers only)
sliding contacts for connecting outgoing auxiliaries
mechanical signalling of trip
horizontal rear terminals
anti-insertion lock for circuit-breakers with different rated
currents
racking-out crank handle
lifting plate
Electrical Accessories

Auto MS CS MTP MT

1a) Shunt opening/closing release (YO/YC)


1a) Second opening release (YO2)
1b) SOR test unit
2a) Undervoltage release (YU)
2b) Time-delay device for undervoltage release (D)
3) Geared motor for charging of the closing springs (M)
4a) Signalling of overcurrent releases tripped NEW
4b) Signalling tripped remote reset command NEW
5a) Signalling of circuit-breaker open/closed (1)
5b) Signalling of circuit-breaker open/closed suppl.tary
5c) Signalling of circuit-breaker racked-in/test/racked-out
5d) Contact signalling closing springs charged
5e) Contact signalling UVR de-energized (C. Aux YU)
6a) Ext.Current transformer for neutral conductor
6b) Homopolar toroid
6c) Homopolar toroid for residual current NEW

MORE
Electrical Accessories

Opening/Closing release unified (YO/YC) and second


opening release (YO2)

Undervoltage release (YU)

(YC)
(UVR)
(YO)
Electrical Accessories

Time-delay device for undervoltage release

SACE SOR Test Unit


Electrical Accessories

Motor operator for automatic loading of closing springs

Electrical indication of Overcurrent release


tripped with or without remote reset command
Electrical Accessories

4 or 10 Electrical signaling of circuit-breaker


open/closed (all contacts are available, also with
PR122 and PR123 *)

15 External supplementary electrical signaling of


circuit-breaker open/closed
Electrical Accessories

Electrical signaling of circuit-breaker


connected/test/disconnected position

Contact for signaling closing springs loaded


Electrical Accessories

Current transformer for external neutral

External toroid for transformer star-enter (Source


Ground Return)
Homopolar toroid for residual current protection
Mechanical Accessories

Auto MS CS MTP MT

7) Mechanical operation counter


8a) Lock in open position: key NEW NEW NEW
8b) Lock in open position: padlocks
8c) Circuit-breaker lock in racked-in/racked-out/test NEW NEW NEW
8d) Accessories for lock in racked-out/test
8e) Accessory for shutter padlock device
8f) Mechanical lock for compartment door
9a) Protection for opening and closing pushbuttons
9b) IP54 door protection
10) Interlock between circuit-breakers
11) Automatic transfer switch - ATS010

MORE
Mechanical Accessories

Operation counter

Lock in open position (padlock or key lock devices -


Ronis / Kirk)
Mechanical Accessories

Lock in connected / test / disconnected position


(padlock and key lock devices - Ronis / Kirk)

Accessory for lock in disconnected / test position


Mechanical Accessories

Padlock device for safety shutters

Mechanical lock for compartment door


Mechanical Accessories

Protection for opening and closing push-buttons

IP54 protective cover for door


Mechanical Accessories

Mechanical interlocks
Mechanical Accessories

Type A Type C 1 2 3
ooo
G 1 2 I oo
oo O I o
I o O O I
O I 1 2 3 O I I
1 2
I I o
I o I
Type B Type D
1 2 3 1 2 3
G ooo G ooo
I oo I oo
Oo I O I o
1 2 3 I O I 1 2 3 OO I
O I O

O =Open Circuit-Breaker - I = Closed Circuit-Breaker


ATS010: Automatic Transfer Switches

One standardized version for all CB


6 Operating modes
Microprocessor technology
Direct connection to CBs
Wide range for settings
Signaling contacts for alarms and status
Accessories