Control Transformers: Technical Data
Control Transformers: Technical Data
Technical data_________________________________________________
Control Transformer Class 1 Isolation Transformer with Earth Screen between Primary
and Secondary
Standard IEC / BS-EN 61558
Primary Voltages 220-230-240-380-400-415V
Secondary Voltages One of the following. 12V, 24V (12-0-12V), 48V,
110V(55-0-55V), 230V
Frequency 50/60Hz
Insulation Class B
Insulation Resistance ˃ 5 Meg Ω
Dielectric Strength Primary to Secondary. ˃ 2.5kV
Primary to Earth ˃ 2.5kV
Secondary to Earth ˃ 2.5kV
Ambient Temperature 40° C
Primary circuit. The primary side of the Transformer should be protected against short circuit
thereby cutting the supply voltage in the event of a short circuit fault.
The rating of the primary protection device has to take into account the high inrush current during
energizing of the Transformer.
The table below gives suggested protection values to avoid nuisance tripping on inrush
Rating Primary Amps Fuse Type C Type D Primary Amps Fuse Type C Type D
VA Volts MCB MCB Volts MCB MCB
50 230 0.21 1 1 1 415 0.12 500mA 1 1
75 230 0.27 1 1 1 415 0.15 500mA 1 1
100 230 0.43 1 2 1 415 0.24 1 1 1
150 230 0.65 2 2 1 415 0.36 1 1 1
200 230 0.86 2 6 2 415 0.48 1 2 1
250 230 1.09 3.15 6 2 415 0.60 2 2 1
300 230 1.2 3.15 6 3 415 0.72 2 2 2
500 230 2.17 4 10 6 415 1.20 3.15 6 4
750 230 3.26 6 10 6 415 1.80 3.15 6 4
1000 230 4.34 8 10 6 415 2.40 5 6 4
1500 230 6.52 10 16 10 415 3.61 6 10 6
2000 230 8.69 12 16 10 415 4.82 10 10 6
2500 230 10.86 16 25 16 415 6.02 10 16 10
Secondary circuit. The secondary circuit should be protected against short circuit and overload.
The value of the protection should be the same or less than the rated output current.
Part No. A B C D E Weight % Reg. Watts Inrush VA Inrush VA
VA Kg Loss For 10% For 5%
Volt drop Volt drop
SCL25 66 68 77 50 44 0.7 11 6 48 36
SCL50 76 70 86 56 47 1.1 9.8 9 105 77
SCL75 76 76 86 56 53 1.4 8.9 11 135 102
SCL100 84 78 95 64 63 2.2 8.4 14 250 175
SCL150 96 76 102 84 65 3.1 6.7 18 375 260
SCL200 96 86 102 84 72 4 5.8 21 550 375
SCL250 96 101 102 84 90 5 5.6 27 720 470
SCL300 120 88 122 90 73 6 5.3 31 870 585
SCL400 120 100 122 90 85 6.75 5.0 30 1200 790
SCL500 120 120 122 90 106 7.5 4.1 31 1700 1100
SCL750 150 110 140 122 90 10 5.2 60 2200 1475
SCL1000 150 161 140 122 106 13 3.3 67 4000 2500
SCL1500 150 188 140 122 134 16 3.2 88 6200 3850
SCL2000 192 172 180 160 125 18 3.3 100 8060 5030
SCL2500 192 192 180 160 153 24 2.6 120 12100 7300
Winding Voltage
Primary 220-230-240-380-400-415V
Primary A-D = 240V, B-D = 230V, C-D = 220V
Connections A-E = 415V, B-E = 400V, C-E = 380V
Secondary 0-12V
24V Centre tapped (12-0-12V)
0-48V
110V Centre tapped (55-0-55V)
0-230V
For a 100VA Transformer with an output of 110V the Part Number would be SCL100110