Important User Information: 2.2. Physical Installation
Important User Information: 2.2. Physical Installation
It is the installer's responsibility to follow all instructions in this manual and to follow correct
electrical practice.
2. Installation
CAUTION
Remove mains and control voltage from the soft starter before attaching or removing
accessories. Failure to do so may damage the equipment.
1. Remove control power and mains supply from the soft starter.
2. Attach the module to the soft starter as illustrated.
3. Set the module address to match the address set in the Master configuration tool.
4. Apply control power to the soft starter.
5. Insert the network connector and power up the module.
3. Configuration
Import the latest .gsd file into your Master configuration tool. This file is available from
www.danfoss.com/drives.
If your Master uses on-screen icons, two graphic bitmap files are available from the website.
SSPM_N.bmp indicates normal mode. SSPM_D.bmp indicates diagnostic mode.
N.B.!:
The Profibus Module has a slave address range of 0 to 99.
If the Profibus network fails, the module will leave data exchange mode after the network
watchdog timeout period has expired. This timeout period is set at the Master configuration tool.
A Communication Timeout parameter in the GSD file sets how soon after this event the soft
starter will be forced into a trip state.
The user can adjust the Communication Timeout parameter in the GSD file to any setting
between 0 and 100 seconds. The default setting is 10 seconds.
N.B.!:
If the Communication Timeout parameter is set to 0, the current state of the soft
starter will remain unchanged on a network failure. This gives the user the option of
operating the soft starter via local control, but is NOT failsafe.
4. Adjustment
Before powering up the Profibus Module, set the two rotary switches so that the module address
matches the address set in your Master configuration tool (the diagram shows the factory default
setting for the rotary switches).
5. Connection
The module connects to the Profibus network via a standard 9-pin Sub-D connector.
The Profibus Module can be powered either through the network cable or externally (24 VDC).
MCD 200: For the Profibus Module to accept serial commands, a link must be fitted across
terminals A1-N2 on the soft starter.
In order for the MCD 500 to accept commands from the serial network, the soft starter must be in
Auto On mode and links must be fitted to terminals 17, 18 and 25, 18.
In Hand On mode, the starter will not accept commands from the serial network but the starter's
status can still be monitored.
N.B.!:
If MCD 500 parameter 3-2 Comms in Remote is set to Disable Comms in Remote, the
starter will not accept start or stop commands from the serial network (the starter will
still accept reset commands and allow status monitoring).
N.B.!:
If communication fails between the module and the network, the Bus Status LED will go
off. When communication is restored, the Bus Status LED will come back on.
N.B.!:
When a communications failure occurs, the soft starter may trip if the Communication
Timeout parameter for the network is set greater than zero. When communication is
restored, the soft starter must be reset.
7. Data Structures
The GSD file contains three operating modules, supporting data I/O structures as follows:
Parameter Upload/
Data Structure Basic Module Extended Module
Download Module
Soft Starter Control I/O
on page 5
Soft Starter Monitoring
I/O on page 6
Soft Starter Programming
I/O on page 9
The Basic Module allows the user to start and stop the soft starter and read limited information on
operating status.
The Extended Module defines additional bytes allowing the user to read soft starter operating
data such as actual motor current and motor temperature.
The Parameter Upload/Download Module allows the user to read and write soft starter parameter
values (only applicable to MCD 500 soft starters).
Byte 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Reserved Quick stop Motor set Reserved Reserved
Byte 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Reserved Reserved Reset Reserved Reserved Fwd run
N.B.!:
The Quick stop bit must be set to 0 before the soft starter can perform a start.
Byte 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1
Ramping Hand On Motor current (% FLC)
Byte 1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Reserved Reserved Warning Fault On Ready
1
Motor current (% FLC) represents current as a percentage of the set motor full load current. A
maximum value of 63 represents 200% full load current. To convert this value to a readable
percentage, divide by 0.315.
Ready is set when the soft starter is ready to start the motor.
On is set when the soft starter is starting, running or soft stopping the motor.
Warning is set when the soft starter detects a warning condition.
Fault is set when the soft starter has tripped.
Ramping is set when the soft starter is starting or soft stopping the motor.
Hand On is set when the soft starter is set to Hand On mode.
Byte 2
Operating data request (Data request numbers 1 to 14)
Slave > Master input bytes, in response to an operating data request, are structured as follows:
Byte 2
Echo data request number
Byte 3
Bits 7 to 1 Reserved Bit 0 = 1: Invalid data request number
Byte 4
Data value - high byte
Byte 5
Data value - low byte
N.B.!:
An invalid data request number will result in the invalid data request number bit being
set = 1.
Data values are defined as follows:
4 = MCD 200
7 = MCD 500
2
For models MCD5-0428C and smaller this value will be 10 times greater than the value displayed
on the LCP.
3
Motor temperature is calculated using the soft starter thermal modelling.
N.B.!:
Data request numbers 5 to 11 are only valid for MCD 500 starters. MCD 200 starters
will return zero values.
MG17GA02 - VLT® is a registered Danfoss trademark 6
MCD Profibus Module Instructions Soft Starter Monitoring I/O Data Structure
9.2. Power
Input bytes for data request numbers 6 and 7 are defined as follows:
Trip Code Trip Type MCD 201 MCD 202 MCD 500
1 Excess start time
2 Motor overload (thermal model)
3 Motor thermistor
4 Current imbalance
5 Frequency (Mains supply)
6 Phase sequence
7 Instantaneous overcurrent
8 Power loss/Power circuit
9 Undercurrent
10 Heatsink overtemperature
11 Motor connection
12 Input A trip
13 FLC too high (FLC out of range)
14 Unsupported option (function not available in
inside delta)
15 Starter communication (between module and
soft starter)
16 Network communication (between module and
network)
17 Internal fault x (where x is the fault code
detailed in the table below).
23 Parameter out of Range
25 Bypass fail (bypass contactor)
26 L1 phase loss
27 L2 phase loss
28 L3 phase loss
29 L1-T1 shorted
30 L2-T2 shorted
31 L3-T3 shorted
33 Time-overcurrent (Bypass overload)
35 Battery/clock
36 Thermistor circuit
255 No trip
For MCD 500, time-overcurrent protection is only available on internally bypassed models.
0 = Read only
1 = Operator (MCD 500 parameter groups 1 to 8)
2 = Supervisor (MCD 500 parameter groups 15 and 16)
3 = Commissioning (MCD 500 parameter group 20)
N.B.!:
This operating module only functions with MCD 500 soft starters.
In Freeze Mode, inputs are only updated with new data from the soft starter when another Freeze
action is carried out. An Un-Freeze action returns the Profibus Module to normal operation.
In Sync Mode, commands to the soft starter are not processed until another Sync action is carried
out. An Un-Sync action returns the Profibus Module to normal operation.
15. Specifications
Enclosure
Dimensions ........................................................... 40 mm (W) x 166 mm (H) x 90 mm (D)
Weight .................................................................................................................. 250 g
Protection ............................................................................................................... IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter ....................................................................................... 6-way pin assembly
Contacts .................................................................................................. Gold flash
Network ....................................................................................................... DB9 female
External power supply .......................................................... 2-way removable screw type
Maximum cable size .................................................................................... 2.5 mm2
Settings
Network address
Setting ......................................................................... MSD and LSD rotary switches
Range .......................................................................................................... 0 to 99
Data rate
Setting ................................................................................................... Auto-detect
Range ...................................................................................... 9.6 kb/s ~ 12.0 Mb/s
Power
Consumption (steady state, maximum) ................................................... 35 mA at 24 VDC
Reverse polarity protected
Galvanically isolated
Certification
C ...................................................................................................... IEC 60947-4-2
CE ....................................................................................................... IEC 60947-4-2
Profibus International ........................................................................................................
È710-02936-00J\ËÍ