3UF70121AU000 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Data sheet 3UF7012-1AU00-0

Basic unit SIMOCODE pro V MR, MODBUS RTU interface 57.6 Kbps, RS
485, 4I/3O freely parameterizable, Us: 110...240 V AC/DC, input for
thermistor connection Monostable relay outputs, expandable by extension
modules

product brand name SIRIUS


product designation Motor management system
design of the product basic unit 2
product type designation SIMOCODE pro V MR
General technical data
product function
● bus communication Yes
● data acquisition function Yes
● diagnostics function Yes
● password protection Yes
● test function Yes
● maintenance function Yes
product component
● input for thermistor connection Yes
● digital input Yes
● input for analog temperature sensors No
● input for ground fault detection No
● relay output Yes
product extension
● temperature monitoring module Yes
● current measuring module Yes
● current/voltage measuring module Yes
● fail-safe digital I/O module Yes
● ground-fault monitoring module Yes
● control unit with display Yes
● control unit Yes
● analog I/O module Yes
apparent power consumption 8.3 V·A
consumed active power 3.6 W
insulation voltage with degree of pollution 3 at AC rated 300 V
value
surge voltage resistance rated value 4 000 V
protection class IP IP20
shock resistance
● acc. to IEC 60068-2-27 15g / 11 ms
● vibration resistance 1-6 Hz / 15 mm; 6-500 Hz / 2 g
switching capacity current of the NO contacts of the
relay outputs at AC-15

3UF70121AU000 Subject to change without notice


4.11.2021
Page 1/7 © Copyright Siemens
● at 24 V 6A
● at 120 V 6A
● at 230 V 3A
switching capacity current of the NO contacts of the
relay outputs at DC-13
● at 24 V 2A
● at 60 V 0.55 A
● at 125 V 0.25 A
mechanical service life (switching cycles) typical 10 000 000
electrical endurance (switching cycles) typical 100 000
buffering time in the event of power failure 0.2 s
reference code acc. to IEC 81346-2 F
continuous current of the NO contacts of the relay outputs
● at 50 °C 6A
● at 60 °C 5A
type of input characteristic Type 1 in accordance with EN 61131-2
Substance Prohibitance (Date) 01.05.2012 00:00:00
certificate of suitability
● according to ATEX directive 2014/34/EU BVS 06 ATEX F001
explosion device group and category according to ATEX II (2) G, II (2 ) D, I (M2)
directive 2014/34/EU
Electromagnetic compatibility
EMC emitted interference acc. to IEC 60947-1 class A
EMC immunity acc. to IEC 60947-1 corresponds to degree of severity 3
conducted interference
● due to burst acc. to IEC 61000-4-4 2 kV (power ports) / 1 kV (signal ports)
● due to conductor-earth surge acc. to IEC 61000-4-5 2 kV
● due to conductor-conductor surge acc. to IEC 1 kV
61000-4-5
● due to high-frequency radiation acc. to IEC 61000- 10 V
4-6
field-based interference acc. to IEC 61000-4-3 10 V/m
electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
conducted HF interference emissions acc. to CISPR11 corresponds to degree of severity A
field-bound HF interference emission acc. to CISPR11 corresponds to degree of severity A
Inputs/ Outputs
product function
● parameterizable inputs Yes
● parameterizable outputs Yes
number of inputs 4
● for thermistor connection 1
number of digital inputs with a common reference potential 4
digital input version type 1 acc. to IEC 61131 Yes
input voltage at digital input at DC rated value 24 V
number of outputs 3
number of semiconductor outputs 0
number of outputs as contact-affected switching 3
element
switching behavior monostable
type of relay outputs Monostable
wire length for digital signals maximum 300 m
wire length for thermistor connection
● with conductor cross-section = 0.5 mm² maximum 50 m
● with conductor cross-section = 1.5 mm² maximum 150 m
● with conductor cross-section = 2.5 mm² maximum 250 m
Protective and monitoring functions
product function
● asymmetry detection Yes
● blocking current evaluation Yes

3UF70121AU000 Subject to change without notice


4.11.2021
Page 2/7 © Copyright Siemens
● power factor monitoring Yes
● ground fault detection Yes
● phase failure detection Yes
● phase sequence recognition Yes
● voltage detection Yes
● monitoring of number of start operations Yes
● overvoltage detection Yes
● overcurrent detection 1 phase Yes
● undervoltage detection Yes
● undercurrent detection 1 phase Yes
● active power monitoring Yes
product function
● current detection Yes
● overload protection Yes
● evaluation of thermistor motor protection Yes
total cold resistance number of sensors in series 1.5 kΩ
maximum
response value of thermoresistor 3 400 ... 3 800 Ω
● of the short-circuit control 9Ω
release value of thermoresistor 1 500 ... 1 650 Ω
Motor control functions
product function
● parameterizable overload relay Yes
● circuit breaker control Yes
● direct start Yes
● reverse starting Yes
● star-delta circuit Yes
● star-delta reversing circuit Yes
● Dahlander circuit Yes
● Dahlander reversing circuit Yes
● pole-changing switch circuit Yes
● pole-changing switch reversing circuit Yes
● slide control Yes
● valve control Yes
Communication/ Protocol
● protocol is supported PROFIBUS DP protocol No
● protocol is supported PROFINET IO protocol No
● protocol is supported PROFIsafe protocol No
● protocol is supported Modbus RTU Yes
● protocol is supported EtherNet/IP No
● protocol is supported OPC UA Server No
● protocol is supported LLDP No
● protocol is supported Address Resolution Protocol No
(ARP)
● protocol is supported SNMP No
● protocol is supported HTTPS No
● protocol is supported NTP No
● protocol is supported Media Redundancy Protocol No
(MRP)
● product function is supported Device Level Ring No
(DLR)
number of interfaces
● acc. to PROFINET 0
● acc. to PROFIBUS 0
● according to Ethernet/IP 0
● according to Modbus RTU 1
product function
● web server No
● shared device No

3UF70121AU000 Subject to change without notice


4.11.2021
Page 3/7 © Copyright Siemens
● at the Ethernet interface Autocrossover No
● at the Ethernet interface Autonegotiation No
● at the Ethernet interface Autosensing No
● is supported PROFINET system redundancy No
● supports PROFIenergy measured values No
● supports PROFIenergy shutdown No
transfer rate maximum 0.057 Mbit/s
identification & maintenance function
● I&M0 - device-specific information Yes
● I&M1 – higher level designation/location designation Yes
● I&M2 - installation date Yes
● I&M3 - comment Yes
type of electrical connection of the communication 9-pin D-sub socket (57.6 Kbit) / screw terminal (57.6 Kbit)
interface
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting
height 111 mm
width 45 mm
depth 124 mm
required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
Connections/ Terminals
product function removable terminal for auxiliary and Yes
control circuit
type of connectable conductor cross-sections
● solid 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables solid 1x (20 ... 12), 2x (20 ... 14)
● at AWG cables stranded 1x (20 ... 14), 2x (20 ... 16)
tightening torque with screw-type terminals 0.8 ... 1.2 N·m
tightening torque [lbf·in] with screw-type terminals 7 ... 10.3 lbf·in
type of connectable conductor cross-sections for 2x 0.34 mm², AWG 22
PROFIBUS wire
Ambient conditions
installation altitude at height above sea level
● 1 maximum 2 000 m
● 2 maximum 3 000 m; max. +50 °C (no protective separation)
● 3 maximum 4 000 m; max. +40 °C (no protective separation)
ambient temperature
● during operation -25 ... +60 °C
● during storage -40 ... +80 °C
● during transport -40 ... +80 °C
environmental category
● during operation acc. to IEC 60721 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%),
3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
● during storage acc. to IEC 60721 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist),
1S2 (sand must not get into the devices), 1M4
● during transport acc. to IEC 60721 2K2, 2C1, 2S1, 2M2
relative humidity
● during operation 5 ... 95 %
contact rating of auxiliary contacts according to UL B300 / R300
Short-circuit protection
design of short-circuit protection per output Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature
circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A)
Safety related data

3UF70121AU000 Subject to change without notice


4.11.2021
Page 4/7 © Copyright Siemens
touch protection against electrical shock finger-safe
Galvanic isolation
(electrically) protective separation acc. to IEC 60947-1 All circuits with protective separation (double creepage paths and
clearances), the information in the "Protective Separation" test report,
No. A0258, must be observed (link see further information)
Control circuit/ Control
product function soft starter control Yes
type of voltage of the control supply voltage AC/DC
control supply voltage at AC
● at 50 Hz rated value 110 ... 240 V
● at 60 Hz rated value 110 ... 240 V
control supply voltage frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
relative symmetrical tolerance of the control supply 5%
voltage frequency
control supply voltage at DC
● rated value 110 ... 240 V
operating range factor control supply voltage rated
value at DC
● initial value 0.85
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value 0.85
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value 0.85
● full-scale value 1.1
Certificates/ approvals
For use in hazard-
General Product Approval EMC
ous locations

For use in hazardous locations Declaration of Conformity Test Certificates

Miscellaneous Special Test Certific-


ate

Test Certificates Marine / Shipping

Type Test Certific- Special Test Certific-


ates/Test Report ate

other

3UF70121AU000 Subject to change without notice


4.11.2021
Page 5/7 © Copyright Siemens
Confirmation PROFINET-Certific-
ation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3UF7012-1AU00-0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3UF7012-1AU00-0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3UF7012-1AU00-0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3UF7012-1AU00-0&lang=en
Test report No. A0258, protective separation
https://support.industry.siemens.com/cs/ww/en/view/109748152

3UF70121AU000 Subject to change without notice


4.11.2021
Page 6/7 © Copyright Siemens
last modified: 1/8/2021

3UF70121AU000 Subject to change without notice


4.11.2021
Page 7/7 © Copyright Siemens

You might also like