Data Sheet - Provolt Dual Relay Multi-Tech Occupancy Sensor (O2C05 O2C10 O2C20-MDW)
Data Sheet - Provolt Dual Relay Multi-Tech Occupancy Sensor (O2C05 O2C10 O2C20-MDW)
Data Sheet - Provolt Dual Relay Multi-Tech Occupancy Sensor (O2C05 O2C10 O2C20-MDW)
DESCRIPTION FEATURES
The Leviton Provolt™ Series Dual Relay Occupancy • Sensors combine both PIR and U/S
sensors combines line voltage occupancy sensors technology for unrivaled performance and
and photocells into a self-contained unit. The reliability
integrated design alleviates the need for separate • Sensors use PIR technology to initially turn
power pack and occupancy sensor wiring making lights ON, and use U/S technology to keep
it a low-cost, efficient energy solution for new the lights ON
construction and retrofits. For true daylight • Exclusive false-detection software assures
harvesting applications, an integrated photocell lights are ON only when needed
provides consistent daylight design levels by • Auto temperature adjusts tech sensitivity
actively switching the connected load(s) ON for optimal detection/operation
and OFF in response to available natural light • Auto-adapting: time delay and sensitivity
to maximize energy savings. Vacancy timers are continually adjusted to occupancy
continually analyze and adjust to changing pattern of use
conditions using the latest microprocessor-based • Vacancy sensing time outs
technology to optimize performance. Auto-ON/ - Delayed OFF timer
auto-OFF automatically turns lights ON and - Exclusive walk-through feature
keeps them ON when occupancy is detected and • False detection timer: (M/T) PIR scans for
automatically turns lights OFF when the space movement and shuts lights off after 31
is vacant or unoccupied. Wire terminals allow for minutes without movement, preventing false
simple connection to a line-voltage circuit and are triggers from HVAC systems
ideal for existing buildings with limited access to - Time delay and saved settings are
wiring and new construction. protected during power outages and will
return to the last known state
APPLICATIONS • Output short circuit protection
• Can be used to comply with ASHRAE 90.1 and • Industry-exclusive self-configuring local
2016 Title 24, Part 6 occupancy/vacancy sensing, manual switch input: momentary or
automatic shut-off, daylight harvesting and maintained switches are supported
stairwell control requirements • Presentation mode allows user to turn lights
• Auto-ON/auto-OFF OFF and keep them OFF while the room is
• Manual-ON/auto-OFF occupied
• Dual Relay Modes Include: • Adjustable time delay: 30s, 5min, 10min,
- Fan control 20min, 30min
- Auto-ON/manual-ON • Test mode for simplified commissioning
- Stairwell control • Manual switch and Emergency Override are
- Step dimming—alternating daylighting Class 1 and Class 2 circuits. Class 2 circuits
levels provided for flexibility
- Step dimming - load 1 primary • Industry-exclusive “fail-safe” circuitry: In the
event of product failure, return-to-closed
feature causes the relay to default ON which
eliminates life safety concerns
Leviton Manufacturing Co., Inc. Global Headquarters
201 North Service Road, Melville, NY 11747-3138 tech line 800-824-3005 fax 800-832-9538
©2017 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
PRODUCT DATA
FEATURES Photocell Features
• Industry-exclusive H.I.S. (High Inrush Stability) • Daylight harvesting applications:
technology designed to handle today’s high inrush -Auto-calibration (automatic daylight
electronic ballast loads and offer unmatched durability calibration): photocell intelligently measures
and service light levels to determine optimal daylight
• Robust and reliable mechanically held latching design levels for closed loop applications
relay provides dependability and robust performance - Closed loop: photocell detects total
for all load types and provides energy savings over photometric light from daylight or electric
electronically held relays sources in the space
• Field of view: units from 500 to 2,000 square feet - Open loop: photocell detects measurement
available of natural light only (sunlight from window or
• Lenses are easily replaceable and color-coded—red skylight)
(mid-range), black (extended range) and blue (high • Adjustable daylight design levels: Normal (OFF),
density) for contractors and end-users to easily Manual (ON/OFF) and Auto Calibration
identify lenses from the ground • Integrated photocell tested to less than 1 Fc
Provolt™ Series Dual Relay Multi-Technology (M/T) Occupancy Sensors
ballast rating 9’
4 4’ Light Fixture
3 ON trigger point
DDL Lights turn ON
2
Lights ON
1 Night time Dawn Dusk
0 Window
CLOSED LOOP
7 2.5x DDL
Zone OFF
6
5
Noon
4 Typical Dayligt Zone, about 10’
Dawn Dusk
3
2
Lights ON
1 DDL 1.25x DDL
Zone ON
0 *May require more than one occupancy sensor for total room coverage
PRODUCT DATA
FIELD OF VIEWS
TOP VIEW
TOP VIEW
TOP VIEW 15 20 TOP VIEW
20 20
16
10
11.5 11.5
11.5
8.5
5
8.5
0
0 0
0
5
8.5
11.5
8.5
10 11.5
8.5
11.5
15 20
SIDE VIEW Major Motion, IR Major Motion, IR
20
20
Major Motion, IR Minor Motion, Ultrasonic
20 Minor Motion, Ultrasonic
SIDE VIEW SIDE VIEW SIDE VIEW
8 Minor Motion, Ultrasonic Major Motion, Ultrasonic
8 Major Motion, Ultrasonic 8
Major Motion, Ultrasonic
0 0 0
20 15 11 9 5.5 3 0 3 5.5 9 11 15 20
0 3 5.6 9 11 15 20 30 25 20 15 10 5 0 5 10 15 20 25 30 23
20
17
15 11 9 5.6 3 0 3 5.6 9 11 15
17
20
23
32 22.5 22.5 32
17 23
DIMENSIONS
1.13”
(29.91mm)
Title Goes(M/T)
0.94”
(24.06mm)
Multi-Technology
2.39”
(60.71mm)
INSTALLATION
SPECIFICATIONS
ELECTRICAL
Input Voltage 120V, 50/60Hz 230V, 50Hz 277V, 50/60Hz
8A, Electronic 6A/6AX, Electronic 5A, Electronic
Ballast, 800W, Ballast, Magnetic Ballast,
Load Rating Tungsten, Ballast, Tungsten, 1200VA Ballast,
800VA Ballast, 1/3 HP Motor 1/3 HP Motor
1/4 HP Motor
Current Consumption 60-30ma
ENVIRONMENTAL
Operating Temperature 32-104° F (0-40° C)
(M/T) Occupancy Sensors
ORDERING INFORMATION
CAT. NO. DESCRIPTION
Multi-Technology