Notifier FMM 1 Monitor Module
Notifier FMM 1 Monitor Module
Notifier FMM 1 Monitor Module
12 Clintonville Rd
Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.1 mA (LED on)
Average Operating Current: 400µA (LED flashing)
EOL Resistance: 47K Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Noncondensing
Dimensions: 41⁄2″ H x 4″ W x 11⁄4″ D (Mounts to a 4″ square by 21⁄8″ deep box.)
Accessories: SMB500 Electrical Box
Before Installing
This information is included as a quick reference installa- 3. Secure module to electrical box (supplied by installer), as
tion guide. Refer to the control panel installation manual shown in Figure 2A.
for detailed system information. If the modules will be Figure 1. Removing
installed in an existing operational system, inform the Rotary Switch Stop:
operator and local authority that the system will be tempo-
rarily out of service. Disconnect power to the control panel
before installing the modules.
9 67 8 9
0
NOTICE: This manual should be left with the owner/user 8 4
5 10
11 1
3 12
of this equipment. 7
2
1 0 15 14
13
2
TENS
6 7 8 9
6 5
3
General Description 3
4
5 4
The FMM-1 Monitor Module is intended for use in intel- 2
ONES
10
Compatibility Requirements
To ensure proper operation, this module shall be connected
to a compatible Notifier system control panel (list available
from Notifier).
Mounting
The FMM-1 mounts directly to 4″ square electrical boxes Figure 2B:
(see Figure 2A). The box must have a minimum depth of
21⁄8″. Surface mounted electrical boxes (SMB500) are avail- 0
11
8
4 5 6 7 15 1 1 12
4 5 67
3
8 4 3
9
8 4
Wiring
0
3
9
0
2
NS 1
1 7 RE
SS
TE
2 D
6 AD
10
9
11
8
4 5 6 7 15 1 1 12
4 5 67
3
8 4 3
9
0
5 NES
2
1
4 O
8
9
0
2
NS 1
7 ES
S
TE
DR
6 AD
3
5
2
1
ES
ON
N500-48-00 1 I56-1171-05
www.PDF-Zoo.com
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
)–( )–(
TO NEXT FROM PANEL OR
)+( )+( PREVIOUS DEVICE
DEVICE
MONITOR
ANY NUMBER OF UL LISTED CONTACT CLOSURE MODULE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
SECURITY DEVICES ON THE SAME MODULE.
9 0
5
67 8 9
10 )–(
8 4
3
11
12
1
7
2 13
1 0 15 14 2
)+(
TENS
47 K EOL 6 5
6789
3
4
RESISTOR 3 COMMUNICATION LINE
5 2 4
ELR-47K ONES
10
ADDRESS 32 VDC MAX.
LOOP
TWISTED PAIR
IS RECOMMENDED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 230µA MAX @ 12 VDC MAX COMMUNICATION LOSS (OPTIONAL CONNECTION FOR
PANELS WHICH SUPPORT THIS FEATURE)
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED A78-2280-13
Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D:
)–( )-(
TO NEXT FROM PANEL OR
DEVICE )+( )+(
PREVIOUS DEVICE
IS INTERNAL AT
LOOP ADDRESS 32 VDC MAX
TERMINALS 8 & 9. SHIELDED-TWISTED PAIR
IS RECOMMENDED
Figure 5. Typical 2-wire initiating circuit configuration for security systems (with alarm versus short capability):
Note: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
)–( )–(
TO NEXT FROM PANEL OR
)+( )+( PREVIOUS DEVICE
DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE MONITOR
DEVICES MAY BE USED. DO NOT MIX FIRE
MODULE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE. CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
14K SERIES RESISTOR
9 0
5
67 8 9
10 )–(
8 4
3
11
12
1
7
2 13
1 0 15 14 2
)+(
TENS
47 K EOL 6 5
6789
3
4
RESISTOR 3 COMMUNICATION LINE
5 2 4
ELR-47K ONES
10
32 VDC MAX.
LOOP ADDRESS
SHIELDED-TWISTED PAIR
IS RECOMMENDED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 230µA MAX @ 12 VDC MAX COMMUNICATION LOSS (OPTIONAL CONNECTION FOR
PANELS WHICH SUPPORT THIS FEATURE)
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED A78-2281-59
N500-48-00 2 I56-1171-05