DNV Considerations For ESS Fire Safety 2017
DNV Considerations For ESS Fire Safety 2017
DNV Considerations For ESS Fire Safety 2017
Project Name: Considerations for ESS Fire Safety DET NORSKE VERITAS (U.S.A.), INC.
(DNV GL)
Customer: Consolidated Edison
Materials & Corrosion Technology Center
Contact Person: Britt Reichborn-Kjennerud O&G Materials Compatibility / Energy
5777 Frantz Road
Date of Issue: January 18th, 2017 Dublin, OH 43017-1886
Project No.: PP151894 United States
Tel: (614) 761-1214
Organization Unit: O&G Corrosion Control/Energy Fax: (614) 761-1633
Report No.: OAPUS301WIKO(PP151894), Rev. 3 www.dnvgl.com
Davion Hill, Ph.D. Nick Warner, M.S. William Kovacs III, P.E.
Energy Storage Leader, Americas Engineer, EAA Laboratories Senior Engineer
Reference to part of this report, which may lead to misinterpretation, is not permissible.
Rev. No. Date Reason for Issue: Prepared by: Verified by: Approved by:
0 2016-11-01 First Issue Davion Hill
1 2016-11-14 Second Issue Davion Hill
2 2016-11-29 Third Issue Davion Hill
3 2017-1-18 Final Issue Davion Hill Nick Warner William Kovacs
Executive Summary
This report summarizes the main findings and recommendations from extensive fire and
extinguisher testing program that evaluated a broad range of battery chemistries1. The
testing was conducted through much of 2016 on behalf of the New York State Energy
Research & Development Authority (NYSERDA) and Consolidated Edison, as they engaged
the New York City Fire Department (FDNY) and the New York City Department of Buildings
(NY DOB) to address code and training updates required to accommodate deployment of
energy storage in New York City. This executive summary can be read as a standalone
summary of the main project findings and recommendations.
The main conclusion from the program is that installation of battery systems into buildings
introduces risks, though these are manageable within existing building codes and fire
fighting methods when appropriate conditions are met. This statement comes with caveats.
There is a need to clarify a universal finding in this program: in the case of heating by fire
or thermal abuse all batteries tested emitted toxic gases. It should also be noted that the
average emissions rates of equivalent masses of plastics exceed those of batteries. Every
battery tested emitted toxic gases (Table 3 on page 29); however, this can be expected
from most fires.
The toxicity of the battery fires was found to be mitigated with ventilation rates common to
many occupied spaces. While it was found that all batteries tested emitted toxic fumes, the
toxicity is similar to a plastics fire and therefore a precedent exists. The batteries exhibited
complex fire behaviors that led to abundant water use; however, it was found that the
extinguishing requirements for batteries need not be excessive if an intelligent, system-level
approach is taken that includes external fire ratings, permits direct water contact, and
implements internal cascading protections. The general outcome of the work is that fire
safety considerations are applicable to all the batteries tested in this program, even though
vanadium redox and lead acid electrolytes were not observed to be flammable. The data
presented in this report supports these findings.
All energy systems carry with them a risk in their deployment; however, the risks identified
in this study are manageable within the limits of today’s engineering controls for safety
when appropriate conditions are met. The resulting requirements in codes, if implemented,
are within the boundaries of the typical built environment.
1
Chemistries are listed in the Appendix on page 107
In addition, at the request of FDNY the following extinguishing agents were tested:
1. Water
2. Pyrocool
3. F-500
4. FireIce
5. An aerosol agent
Greater detail is found within the report. It is suggested the reader use cross references
provided in the report to see where technical information can be found that supports these
findings. This report extensively uses cross references so that the reader can begin reading
at any point in the document and quickly find relevant supporting information in other
sections of the document, similar to a handbook.
Table of Contents
1.0 ACKNOWLEDGEMENTS ............................................................................... 1
2.0 ACRONYMS............................................................................................... 2
List of Tables
Table 1 Statistics on cell failure rates for the entire test program including all Li-
ion variants. ........................................................................................... 21
Table 2 Average release rate for battery materials over a 30 minute time period. ............ 23
Table 3 Inventory of Toxic and Flammable Hazards found in this Study ........................... 29
Table 5 Battery specific codes for battery systems in buildings, existing and
proposed. ............................................................................................... 44
Table 6 Immediately Dangerous to Life and Health (IDLH) for the emphasized
toxic gases identified in the testing work. ................................................... 49
Table 8 Benchmarks for airflow and water flow for typical structures. ............................. 51
Table 9 Values derived from probabilistic analysis of water flow rates (GPM) and
air flow rates (CFM) per system energy (kWh) or mass (kg). ........................ 52
Table 11 Air change rates based on HCl emissions as a function of room size and
quantity of failing cells. ............................................................................ 65
Table 12 Air change rates based on HCN emissions as a function of room size
and quantity of failing cells. ...................................................................... 65
Table 13 Air change rates based on CO emissions as a function of room size and
quantity of failing cells. ............................................................................ 66
Table 14 Air change rates based on HF emissions as a function of room size and
quantity of failing cells. ............................................................................ 66
Table 15 Conversions from ACH to CFM based on the example room volumes for
energy storage systems. .......................................................................... 66
Table 18 Battery burn tests without extinguishing, combustible batteries only ................. 82
List of Figures
Figure 1 Diagram of the abuse chamber used for fire testing of batteries
in the BESS program. ............................................................................. 4
Figure 4 Peak ppm per kg (in a 0.44 m3 volume) for all batteries tested
as compared to plastics. ....................................................................... 10
Figure 5 Average emissions per kg per minute of test mass for plastics
vs. batteries. ........................................................................................ 11
Figure 6 Emission of HCl was observed from the vanadium redox flow
electrolyte. ........................................................................................... 12
Figure 11 Some battery modules still had residual voltage after fire
testing. ................................................................................................. 16
Figure 15 Relationship of heat release rate (kW) per gram of mass lost. ............... 22
Figure 18 Estimated air change over rate (air changes per hour) as a
function of room volume and battery mass undergoing failure
for CO. Because the IDLH of CO is much higher, there is little
dependency on battery masses at these scales. ................................... 24
Figure 22 For Li-ion batteries, the mass loss is directly proportional to the
state of charge prior to failure. ............................................................ 27
Figure 24 Smoke plume rising through door gaps and out of top vents in
the burn container. .............................................................................. 31
Figure 32 Example of the air flow requirement for a 1 MWh Li-ion system,
demonstrating that the distribution of values is strongly
skewed leftward. .................................................................................. 54
Figure 38 Battery weight and the peak room temperature are positively
correlated............................................................................................. 76
Figure 39 Large abuse test chamber design for battery fire and
extinguishing testing. .......................................................................... 78
1.0 ACKNOWLEDGEMENTS
The battery and extinguishing companies identified below all donated their products for testing in this
project. The Con Edison - NYSERDA team and DNV-GL are extremely grateful for the generosity and
engagement with this project by these companies. We also thank the key stakeholders for their
significant contributions to this effort.
NCM 1: LG Chem
NCM 2HE and NCM 2HP: Samsung SDI
NCM 3: Kokam (donated by Sunverge)
NCM 4: Electrovaya
LFP 1: BYD
LFP 2: XO Genesis
T 1: Toshiba
BM-LMP: C4V
VR 1: UET
PBA 1: EnerSys
Aerosol agent: Fireaway Inc. (product Stat-X)
2.0 ACRONYMS
ACH – Air Changes per Hour
AHJ – Authority Having Jurisdiction
BESS – Battery Energy Storage Safety
BIC – Building Information Card
BMS – battery management system
BM-LMP – Bio-mineralized Lithium Mix-Metal Phosphate
BSCAT – Barrier-Based Systematic Cause Analysis Technique
BTM – Behind the Meter
CFM – Cubic Feet per Minute
CFR – Code of Federal Regulations
CHP – Combined Heat and Power
CID – Current Interrupt Device
CO – Carbon Monoxide
COF – Certificate of Fitness
C-rate – charge rate
DCE – Duty Cycle Eccentricity
DMC – Dimethyl Carbonate
DOB – New York City Department of Buildings
DOD – depth of discharge
EC – Ethylene Carbonate
EDS – energy dispersive spectroscopy
ERPG – Emergency Response Planning Guidelines
ESS – Energy Storage System
FAQ – Frequently Asked Questions
FID – Flame Ionization Detector
FDNY – New York City Fire Department
FEA – Finite Element Analysis
FMEA – Failure Mode Effects Analysis (sometimes FMECA to include “Criticality”)
FTA – Fault Tree Analysis
FTIR – Fourier Transform Infrared Spectroscopy
GPM – Gallons Per Minute
HAZID – Hazard Identification
HCl – Hydrochloric Acid
HRR – Heat Release Rate
HCN – Hydrogen Cyanide
HF – Hydrofluoric Acid
HVAC – Heating, Ventilation, and Air Conditioning
IDLH – Immediately Dangerous to Life and Health
IE – Independent Engineer(ing)
IEC – International Electrotechnical Commission
IFC – International Fire Code
IPP – Independent Power Producer
LEL – Lower Explosion Limit
LMO – Lithium Manganese Oxide
LTO – Lithium Titanium Oxide
NYSERDA – New York State Energy Research and Devlopment Authority
NAVSEA – Naval Sea Systems Command
NCA – Nickel Cobalt Aluminum
NCM – Nickel Cobalt Manganese
Air Inlets
Figure 1 Diagram of the abuse chamber used for fire testing of batteries in the
BESS program.
Finally, gas sampling was performed by a Gasmet DX4000 Fourier transform infrared
spectroscopy (FTIR) gas analyzer. This analyzer monitored HCl, HF, HCN, CO, CO 2, O2, SO2,
NO, NO2, and a range of hydrocarbons including methane, ethane, ethylene, benzene,
toluene, and others. In line with the FTIR analyzer were MSA Ultima sensors for O 2
(redundant measurement), H2, and F2/Cl2. A final MSA sensor was placed directly off the
chamber for flammability measurements. The sensor was of the catalytic bead type and was
factory calibrated to non-specific gas for total LEL measurement. This was deemed suitable
as a range of flammable gases were expected and calibration to one may show improper
bias. In addition to the gas sensors, gas capture bags were set up off of the exhaust stacks.
Select gas bag samples were taken periodically and were used to verify the FTIR
measurement.
For extinguishing, the abuse chamber was fitted with a 2.5-gallon water can with an
extinguishing trigger. The can was pressurized and engaged by a temperature trigger, with
an in-line electronic solenoid valve for actuation. Once a single temperature exceeded
350°C, the solenoid was opened and the extinguisher released. The can was typically filled
with 1 gallon of liquid and the entirety of the can was emptied. In one test, an 8-second
pulse of water was used and the solenoid reclosed. The extinguisher nozzle was fixed
approximately 10 inches from the battery, to the side and about 3 inches above. The nozzle
was a fogging mist nozzle, and because of proximity, tank pressure was reduced to 75 psi
to allow better saturation. All cells for extinguisher testing were tested at 90% SOC.
For large scale testing, a purpose built propane torch was constructed by Fire Force Inc, a
builder of aircraft fire simulators. This torch was used to apply a direct propane flame to
battery modules which were placed in a walled off shipping container shown in Figure 2 and
Figure 24. The “room” was approximately 10 feet into the trailer, with one end being the
trailer door and having a man door installed into a double sheeted drywall wall on the
interior wall. A series of ventilation ports were cut into the room to allow for ventilation
testing (two high, two low, one roof) and positive and negative ventilation were tested. In
addition, two sprinklers were piped into the room for suppression testing. Most tests were
conducted with doors open; however, two tests were conducted with the container closed to
test ventilation. In addition to the sprinklers, hose suppression was used at times as well to
assess effectiveness.
Venting ports were constructed above and below the burn platform to control ventilation
and also provide sampling locations. The doors to the burn chamber could be opened or
closed to test the effect on oxygen, toxicity, and heat release of the fire (Figure 2).
density will continue to evolve, these metrics will capture that evolution as codes
follow the market.
- Many small systems are dependent on the ventilation and fire suppression in the
space, and there should be a means to check if the host-infrastructure is adequate.
- Large systems may have standalone ventilation and fire suppression equipment.
- One of the main stakeholders of this report is the New York Fire Department (FDNY)
and consequently most United States (US) fire departments, and they are familiar
with GPM and CFM units of measure for firefighting and codes.
The water flow calculations presented in this document are addressing a key issue in battery
safety. Over-reaction to the threat of thermal runaway has led to recommendations for
“copious amounts of water” [12] for the extinguishing of Li-ion battery systems. Such
recommendations inflate the perceived water requirement. The reasoning for this is logical;
it is better to err on the side of caution and advise first responders to use as much water as
possible to indirectly cool the battery system.
This work has demonstrated that excessive water need not be the design criteria but should
instead be considered part of an intelligent set of safety systems including external fire
ratings, internal cascading protections, and fixed suppression systems to slow the
propagation of heat in a combined manner such as in Figure 3. If a systems approach to
safety is taken, the water requirements may be far less severe. If and when first responders
need to react to a system fire, it may be the case that these systems be overridden or
overcome, and a “copious amounts of water” approach may be desired. Therefore water
requirements for the codes and water requirements for first responders are
separate issues.
Question: Are the commonly cited battery fires in the media due to spontaneous
ignition events?
Finding: No. The Literature Review (an addendum to this report) covers several incidents in
detail. In the context of fire risk and firefighting for batteries, it is helpful to summarize the
abuse tests that are performed in United Nations (UN) 38.3, the required testing scope in
order to ship and transport Li-ion batteries. The eight separate tests in UN 38.3 are a
checklist of nearly all physically conceivable abuses that could cause a Li-ion battery to
catch fire. These abuse events are:
1. Low ambient pressure
2. Overheating
3. Vibration
4. Shock
5. External short circuit
6. Impact
7. Overcharge
8. Forced discharge
All of the safety incidents commonly reported in the general media can be traced to one of
these abuse mechanisms. In some cases, contaminants in the battery (as a result of
manufacturing defects) weaken the ability of the battery to withstand instances of these
eight abuse factors. In general it is good practice to avoid any scenario that may introduce
the threat of any action on the above list. Three items in particular (overheating, external
short circuit, and impact) are the abuse mechanisms that have increased probability of
occurring to a battery during and after a fire. The fire is the most obvious heat source, but
subsequent heating may occur internally once batteries reach critical temperatures
(typically > 120oC). Short circuiting may occur by contact with tools or equipment or by
water. Items #7 and #8 are electrical stimuli that are typically monitored and controlled by
active safety barriers in the battery management system (BMS).
battery, for example) is higher per kilogram of material than a plastics fire, as shown in
Figure 4. This illustrates that a smoldering Li-ion battery on a per kilogram basis can be
treated with the same precautions as something like a sofa, mattress, or office fire in terms
of toxicity, but during the most intense moments of the fire (during the 2-3 minutes that
cells are igniting exothermically) precautions for toxicity and ventilation should be taken. It
should be noted that if Li-ion battery modules are equipped with cascading protections, the
cell failure rate may be randomized and staggered. The randomized failure rate limits the
toxicity and heat release rate of the fire.
Figure 4 Peak ppm per kg (in a 0.44 m3 volume) for all batteries tested as
compared to plastics.
Figure 5 Average emissions per kg per minute of test mass for plastics vs.
batteries.
Figure 6 Emission of HCl was observed from the vanadium redox flow electrolyte.
Question: What kind of testing is required to certify the safety of battery systems?
Finding: The most commonly referenced system level safety testing the US is Underwriters’
Laboratories (UL) 1973. For marine and automotive applications, International
Electrotechnical Commission (IEC) 62619 covers many of the same requirements and has a
more stringent pass/fail criteria to demonstrate limited cascading between cells. The US
market appears to be moving toward UL 9540 which includes aspects of UL 1973 and UL
1642 (for cell safety) in addition to an up-front failure mode effects analysis (FMEA) on the
system. As mentioned, such a risk analysis should also include the site under unique
circumstances. It is also conventional to have a third party inspect the field installation and
provide a sign-off for the local authority having jurisdiction (AHJ). Globally, UN 38.3 is the
most widely recognized safety testing for Li-ion battery cells and is a requirement for
transport. The results of accredited safety testing are an indicator of the strength of the
barriers in a risk model.
poses a hazard for continuing (not reigniting) the fire. Therefore, it is technically inaccurate
to classify this as re-ignition if the primary cause of the hazard is never removed. After a
fire, a battery module or system may contain intact cells that still have DC voltage, meaning
there is a persisting electrical hazard (Figure 11). Water shorting out cells, for example, is a
genuine risk (such as was witnessed in the Chevrolet Volt crash test or the flooded Fisker
cars [15,17 ]). In addition, if the heat deep within the module has not been removed, that
heat poses a continued thermal hazard. DNV GL and Rescue Methods witnessed this effect
during testing as shown in Figure 9, the cause of which was lack of thermal barriers
between cells. DNV GL replicated this effect in more controlled laboratory tests in Figure 10
and observed that temperatures between battery cells can be 300 oC higher than the
exterior during extinguishing unless there is a means to remove internal heat or prevent its
transfer between cells. First responders should be cognizant that all electrical, thermal, and
mechanical hazards have been mitigated before deeming a battery fire fully extinguished.
Question: How long does it take for a Li-ion battery to go into thermal runaway if
it is being heated?
Finding: This is entirely dependent on the rate of heat absorption into the cell. DNV GL
observed in this work and other projects that a Li-ion cell can smolder for more than an
hour if the heat transfer rate is slow. By the time temperatures near 120oC (248oF) were
reached, all Li-ion batteries tested (including LiFePO4 and LTO chemistries) offgassed and/or
ruptured. If the threshold near 120oC is never crossed, the battery may smolder and gas
but never ignite unless an external spark ignites the flammable gases emitted from it. It
was common for LiFePO4, LTO, and the BM-LMP cells to offgas without flame, but their
offgas composition contains the same flammable and toxic constituents as batteries with
higher temperature failures.
Figure 11 Some battery modules still had residual voltage after fire testing.
to lack of thermal mass, poorer thermal conductivity, and restricted access to the deep
seated heat source—were not observed to cool as quickly as water can. Water has been
historically recommended because of its ability to cool. It was found in this program that
water cools best, with the potential unwanted side effect of shorting other cells.
Question: Is a 2 ½” hose line with 250 GPM sufficient to put out a battery fire?
Finding: This is dependent on the battery size. DNV GL translated the findings to both
GPM/kg and GPM/kWh of battery mass (Table 9). In general, however, if the water can be
targeted at the deep seated, highest temperature areas of the fire, it will be most effective
and the water requirement will be reduced. It is demonstrated as an example in Table 7
that 250 GPM is more than sufficient for typical battery systems on the market, provided
that cascading protections and external fire rating requirements are also met.
Question: What are the differences in safety considerations for outdoor vs. indoor
systems?
Finding: Please cross reference to “considerations for System Types and Locations”.
Outdoor systems may have standalone safety equipment such as fixed suppression systems
and self-contained heating, ventilation, and air conditioning (HVAC). The risk to the site
should be considered in all cases, which is intended to be addressed in the FMEA required
by UL 9540. A risk analysis should guide stakeholders toward a probable risk consideration
during project commissioning. This probability-driven analysis helps avoid over- or under-
prescribing safety systems. Outdoor systems may have different or lower ventilation
requirements, but their size and proximity to inhabited structures may dictate heat or plume
considerations in the event of fire (see Figure 25 and considerations in” Present Day
Industry-Accepted Safety Practices for Energy Storage Project” on page 31). Indoor systems
may be dependent on the building infrastructure for ventilation and fire suppression. If that
is the case, the risk analysis should identify if these systems are adequately sized, using the
guidance identified in Table 9.
Figure 13 Residue analysis from a coupon hung in the headspace of the vanadium
redox boiling test.
Table 1 Statistics on cell failure rates for the entire test program including all Li-ion
variants.
Figure 15 Relationship of heat release rate (kW) per gram of mass lost.
Table 2 Average release rate for battery materials over a 30 minute time period.
Figure 16 Estimated ventilation rates (air changes per hour) as a function of room
volume and mass of battery undergoing failure for HCl.
Figure 17 Estimated air changeover rate (air changes per hour) as a function of
room volume and battery mas undergoing failure for HCN.
Figure 18 Estimated air change over rate (air changes per hour) as a function of
room volume and battery mass undergoing failure for CO. Because the IDLH of CO
is much higher, there is little dependency on battery masses at these scales.
Figure 19 Estimated air change rate (ACH) as a function of room volume and
battery mass during failure for HF.
anything less than 15 simultaneously burning battery cells are the same for HCl and HF (see
Figure 16 and related figures starting on page 23).
Question: Is the combined LEL of the flammable gases lower than any of the gases
alone?
Finding: Yes. This phenomenon is described by Le Chatelier's Mixing Rule which states that
the combined LEL of a mixture of gases is the sum of the weighted ratios of volume to LEL
for each individual gas species. Because the emissions rates are constantly varying and
therefore never in a prolonged chemical equilibrium such that this simplified textbook
solution may apply, DNV GL was able to observe that ignitions occurred as low as 400oC at
CO concentrations as low as 3,000 ppm. (Figure 21) Frequently observed gases of C2H4, CO,
and CH4, if coexisting in a mixture, have the lowest autoignition temperature of 490oC and
100,000 ppm, respectively (see below):
As expected the combined LEL is indeed lower than the individual components but as
mentioned above, the ventilation requirements should be set by the IDLH, which
should exceed and override LEL considerations. Therefore LEL is less of an
immediate concern than IDLH.
Figure 21 The combined LEL and autoignition temperature of mixed gases emitted
from Li-ion batteries may be as low as 3,000 ppm and less than 400oC, as
flammable gases were ignited and burned off above this temperature.
Question: Are Li-ion batteries more volatile with higher states of charge?
Finding: Yes. There is a very direct increasing relationship between mass lost and the SOC
before failure as shown in Figure 22. However, the BMS limits the SOC of the battery
intentionally for both longevity and safety reasons. As shown in the figure, the decline in
mass loss is significant as the SOC of the battery is decreased from 100% to 90% or 80%.
As many battery systems limit the upper electrochemical SOC range to 80-90%, a
significant safety precaution has already been made. It should be noted that the GPM/kg
and CFM/kg metrics found in this program are inherently conservative because they include
the peak emission rates observed at 100 % SOC and they also capture the short lived peak
emission events. In reality, a system fire spends most of its time smoldering, and if the BMS
is properly functioning, no cells should be at 100% SOC.
Figure 22 For Li-ion batteries, the mass loss is directly proportional to the state of
charge prior to failure.
Figure 23 It is generally true that LiFePO4, LTO, and BM-LMP batteries demonstrate
lower than average temperatures during failure. The temperatures indicated for
Pb acid and vanadium redox batteries is the peak heating temperature, as these
electrolytes did not demonstrate flammable or exothermic properties as they were
tested.
Question: What is the solubility of liberated gases, and are some of them
consumed by fire?
Finding: The solubility of the gases observed is shown in Table 3. Those consumed by fire
have an indicated flammability limit and autoignition temperature.
- For most tests the water runoff was slightly acidic measuring pH 6-7. In one
case, however, the water became alkaline climbing to pH 10-11 after a few
hours of submersion. This case was observed for a battery that was highly
consumed in the fire.
- Batteries did not climb in temperature after submersion, indicating that even
if cells short circuited, their temperature was never permitted to climb to
thermal runaway conditions.
- Some battery cells still had voltage on them after 24 hours of submersion.
While some cells may have shorted, not all shorted. The water did not have
any additives such as salt to make it more conductive.
- CO: 28.01
- HF: 20.01
- HCl: 36.4
- HCN: 27.02
Figure 24 Smoke plume rising through door gaps and out of top vents in the burn
container.
The types of battery energy storage systems being deployed are both utility solutions at the
multi-MW scale in consolidated sites, typically with energy storage batteries housed in
shipping-container like systems with integrated BMS, ventilation and cooling, and fixed fire
suppression. Smaller, behind the meter energy storage systems are designed to be
deployed near the customer and controlled as an aggregate fleet. These smaller systems
have a BMS and may have active cooling, but rarely have integrated fire suppression.
Shipping container systems are typically located outdoors and are MW scale, whereas
behind the meter systems are typically sited at a commercial site (or potentially residential)
and may be indoors, and will have ratings in 10’s of kW.
Energy storage can be utility owned or it can be owned by an independent power producer
(IPP). Much of the US energy storage market is presently being driven by IPPs. The IPP may
monetize the energy storage asset through utility contracts or a commercial power purchase
agreement. Some IPPs have the balance sheet to pay for energy storage projects
themselves, but many seek financing. With financing comes insurance to underwrite risk in
both the finance and safety of the project. Because of these additional parties that are
exposed to financial risk, a performance and safety review are a critical piece for
financing an energy storage project, which is performed by an independent
engineer (IE).
In the context of safety the IE is tasked with independently evaluating the adequacy of
safety systems appropriate to the project. With the business case and project site(s)
identified, the AHJ is likely to become aware of the project when the project developer is
seeking permit(s). The AHJ will typically respond with requirements, which may be few or
many, at which point the project developer takes actions to fulfill them in order to secure
the sites as quickly as possible. Project finance may be secured or will be sought in parallel
to this process. Because the project developer is encouraged to obtain the IE report by the
financial stakeholders, it is most cost effective for the project developer to use the IE report
to simultaneously satisfy requirements for the AHJ and the financial parties. The objectivity
of the report should increase comfort in the transaction(s) between parties. Therefore at the
request of the project developer, the IE report is written in the context of generalized
project specifications so that it may enable as many transactions as possible. Therefore it is
never the case that more than one IE report is generated for identical projects because it is
a cost that can be practically avoided. It is also common practice for large aggregated
projects of similar system types to have inspections performed on a subset of sites.
For an outdoor container system, the IE may provide the following services related to
safety:
Assessment of the adequacy of the safety systems
Assessment of the safe perimeter around the site
Emergency response plans
Review or recommendations of materials to be provided to the local AHJ
for permitting or code review
Adequacy of firefighting equipment
Impact of a fire scenario on the site or surrounding area, which may
include a plume study if residential or populated areas are nearby
Risk model for the site
For an indoor system, the following IE services related to safety may be requested:
Review of safety testing
Assessment of the adequacy of safety systems
Recommendations on the requirements for indoor room locations
Adequacy of cooling and venting
Review of fire ratings
Inspection of installation
Risk analysis related to the system and its site(s)
In the case of behind the meter systems, this review is usually done at the project
portfolio level unless specific site considerations require local review.
The first and foremost finding from this report is that the equipment available to present
day first responders can be considered adequate for battery fire fighting with
additional considerations.
system with an unknown internal hazard may pose risks to the surrounding
environment or to fire fighters and may be better handled via a defensive
posture than entry and attack.
Answers to the above questions will indicate whether the system fire has already peaked or
if it is expanding. Support from an SME, an information display panel, or other form of
emergency contact will greatly aid in assessing the risk.
If the system is gassing but onboard suppression (if any) has already triggered, and
temperatures are remaining stable, it is likely that a single cell or module fire has occurred
and been isolated, and may have been managed by the onboard system. Additional
suppression may not be required in this case. Eventually, the system will need to be
ventilated to remove the internal atmosphere, but only if temperatures have remained
stable for approximately 60 minutes.
The list below summarizes key points from this study that are directly relevant to
firefighters and other first responders. This section may stand on its own as an independent
part of this report and may be distributed to fire departments and first responders
nationwide independent of this document. It is not intended to serve as an SOP on its own,
but should inform the response and development of SOPs for situations involving ESS.
There has been much said about ESS fires in the past which has led to several myths about
these fires. DNV GL wishes to dispel the falsehoods while promoting real world, data driven
facts when dealing with these systems. Ultimately, findings suggest that while these
systems are unique in the combination of threats posed, none of the threats on their own
are unfamiliar to firefighters, and they remain manageable so long as certain points are
known and followed.
Toxicity: In general, battery fires resemble plastic fires in terms of emission of toxic
gases including CO, HCl, HF, HCN, Benzene, and Toluene
o The average toxicity of the fire is equivalent to many plastics on a per mass
basis. Li-ion fires will have short peaks of toxicity as individual cells randomly
fail.
o However, battery fires, even once extinguished, continue to emit CO as long
as the batteries remain hot.
o DNV GL and Rescue Methods (RM) recommend continued monitoring of CO
from ESS fires, especially in enclosed spaces, and the continued use of
personal protective equipment (PPE), including self-contained breathing
apparatus (SCBA), until CO levels are shown to be at normal levels. These
practices may include monitoring for HCl, if applicable or possible.
found that even in systems that appeared thoroughly damaged, live cells and
stranded energy can remain. These cells may pose a shock/arcing risk and
can reignite if physically damaged, reheated, or allowed to short.
Extinguishing: DNV GL tested several water based extinguishing agents and found
none to be as effective for cooling as water. These included PyroCool, F500, and
FireIce.
o The most challenging aspect of the battery fire is its deep-seated nature.
Access to the heat source is necessary to provide adequate cooling.
o Cooling the battery once flames are knocked down is the most important
aspect of containing battery fires. The tested agents proved slightly less
effective than water at cooling the cells. On a module level, there was no
evidence to suggest these agents perform better than water.
o Because many encapsulating agents, including foam (AFFF) are intended to
blanket the fire, and a battery fire needs to have heat removed as quickly as
possible, DNV GL generally recommends against using foam for ESS fires.
Foam has been tested in other projects and used in real world ESS fires. In
testing in other projects, it failed to perform better than other agents.
o The aerosol may prove effective at knocking down flames from ESS. Gas
based agents may suppress the flammability of contained atmospheres with
high explosive gas content; however, in the case of severe ESS fires where
these agents would be tasked to suppress flammability, cells may be
producing heat above the autoignition temperature of their flammable gases.
This may result in fire if oxygen were reintroduced to the system. DNV GL
recommends gas-based systems be backed up by water-based suppression
when cooling becomes a necessity, in combination with cascading protections
in the modules and systems.
o Though water proved most effective for cooling, water and any water-based
agent introduces shorting risks when applied on a full system. This may
exacerbate the situation in addition to presenting a collateral damage risk.
o Several entities, including DNV GL, have advised that class D fire
extinguishers and agents be investigated for use during the incipient stage of
the fire. Based on the findings from this program, DNV GL views the
deployment of classical class D agents as impractical due to the short lived
peak of a cell fire and its deep seated nature, which prevents direct access.
o RM’s experience during suppression testing suggests forced access to the
interior of battery systems may be difficult or inadvisable for first responders.
In this case, water should be used to provide indirect cooling on the outside
of the system to prevent spreading.
o Water use inside the system, if applicable, should be done with care to avoid
shorting neighboring and surviving cells, i.e., the failing module should be
isolated and targeted. Fully involved systems may be compromised enough to
allow better water penetration. Fully involved systems posing a risk to
surrounding life and property, or neighboring systems, should be suppressed
immediately and heavily to avoid spreading.
o If the fire appears to be stable and not expanding, periodically stop water
flow and monitor temperatures. Note that the temperature may “spring back”
after water extinguishing stops, but it should plateau and stabilize if the fire
fuel has been consumed.
o Observe for water shorting other cells. They may begin to heat, meaning the
deep seated heat remains.
o Repeat extinguishing process as needed, while ventilating the area as much
as possible.
o If the battery system has closed doors, do not open them unless absolutely
necessary or it has been determined that opening the doors will not introduce
new hazards. Forced entry is discouraged unless a prior access plan has been
described.
o Suppression of large, fully involved systems may take more time than fires of
similar size with different fuels. It is recommend fire service personnel
continue to suppress with water for as long as required and then ensure the
system is fully cooled throughout once suppression appears complete.
As shown in Figure 26, submerging battery modules in water provided adequate cooling to
slow and prevent delayed cascading thermal runaway in the remaining battery cells;
however, the batteries persistently off-gassed even under water. The primary gases
detected in the bubbles generated were CO and possibly hydrogen. The figure demonstrates
the bubbles observed even after submersion for over 30 minutes.
Even after submerging, some batteries generated a severely alkaline solution climbing to pH
10-11. Other solutions gradually became slightly acidic (pH 6). There was not a clear
explanation for the pH behavior of the solutions, other than one of the most severely burned
batteries created the most basic solution. Therefore, if water submersion is used by
first responders for isolating spent modules, preparation to deal with alkaline or
basic water for disposal should be a consideration.
Lastly, it was found that after extinguishing the persistent emission of CO was sometimes in
quantities large enough to trigger threshold alarms on the gear worn by fire fighters. The
persistent emission is perhaps a more insidious risk than the emissions during the fire, as
the apparent climax of the fire has passed, and first responders may be inclined to remove
their masks. After extinguishing, continued ventilation and monitoring of the area
with gas monitors is highly recommended.
As the climax of the fire has concluded, but continued ventilation and monitoring is
underway, first responders are left with the final challenge of determining when they can
relinquish control of the area. There are several risks that first responders wish to avoid and
they are prioritized by the list demonstrated on page 57. It is highly recommended that
battery systems installed within buildings have an established emergency contact
list and a SME who can arrive on the scene to take over containment, cleanup, and
eventual disposal of damaged battery equipment. This recommendation requires
involvement from the project development and systems integration community.
This is a necessary risk transfer procedure to mitigate the first responder concern that they
are responsible for damaged battery systems for hours or days after they have been
involved in a fire or catastrophic safety event.
against shocks in this testing; however, high voltage DC may penetrate PPE in
cases where it is damaged or otherwise compromised, such as a torn glove or
a exposure to sharp metals. These kinds of hazards were not studied in this
testing program.
o DNV GL and RM recommend fire fighters continue to wear PPE and SCBA even
during overhaul as CO levels may remain elevated even after flames are
extinguished as batteries remain hot and continue to offgas. DNV GL
recommends CO levels, especially in enclosed or unventilated spaces be
monitored and SCBA worn until levels are shown to be safe.
o Complete submersion of damaged batteries in water provides cooling for
damaged batteries; however, batteries continued to offgas CO. Because
handheld sensors are cross sensitive to CO, H2 may have also been emitted
while submerged. In addition, this did not always entirely neutralize the
voltage on surviving cells. However, cells seem to remain stable once pulled
from water and dried. Caution should be exercised when removing damaged
batteries from enclosure/containment per the risks discussed above.
Whenever possible, a relevant subject matter expert from the site, project
owner, or manufacturer should provide guidance or control of removal.
3
Cells not integrated into modules or systems
The boundary conditions are a fixed wall temperature of 811K (537oC or 1000oF). Model
components are a steel wall with temperature-dependent conductivity, an air gap (1 in) with
temperature-dependent conductivity, and a composite battery case made of aluminium with
fixed conductivity and polypropylene with fixed conductivity. The heat transfer modes are
natural convection and conduction.
4
This may seem counterintuitive; the aluminum conducts heat away faster and therefore maintains a lower
temperature than polypropylene.
Figure 28 Direct fire exposure model to a steel wall with a 1/16” thickness and 1”
air gap between the wall and battery modules.
Accountable parties
FMEA/HMA
Inspections
Signage Flammable, keep away
from open flames
Table 5 Battery specific codes for battery systems in buildings, existing and
proposed.
Battery Related Codes
Code Item IBC IFC 608 NFPA 1 Chapter 52 FDNY Certificate of Fitness (COF) B-29
(Uninterruptible Power Supply)
Ventilation 307.1.1 Rooms shall None for Li-ion Required for Valve Regulated Lead Acid
have ventilation, (VRLA) only, designed to limit H2
batteries shall have buildup to 1% of the entire room
venting caps volume; Continuous ventilation = 1
CFM per ft^2 of room
Fire suppression 403.3 and 903.2 Proposed Chapter 5 Sprinklers not required but
Not required in of NFPA 13. recommended. Portable Class ABC on
external structures hand.
with fire detection
Monitoring: Detection, 907.2.23 Smoke Hydrogen monitoring or handheld
alarm, display detection system detector for COF holder, system health
status
Capacity limitation > 50 gallons 100 gallons of 50 gallons of electrolyte for Pb acid,
dependent on space electrolyte or 1000 electrolyte VRLA, NiCd, or 1000 lbs. for Li-ion
lbs. Li-ion. Proposed (sprinklered) or
20 kWh limit for 50 gal electrolyte
single units, 600 (unsprinklered) or
kWh limit for total 1000 lb. Li-ion
in a room.
Clearance Proposed 3 ft
between arrays no
larger than 50 kWh.
5 ft from lot lines
for outdoor.
Thermal runaway Required Required for both VRLA and Li-ion
protection
Fire rating Table 509 1 and 2
hour ratings
Location Proposed no more
than 75 ft above or
30 ft below fire
access, exceptions
on non-combustible
rooftops
Seismic rating Appropriate for Required for zone Appropriate for Appropriate for zone
zone zone
Accountable parties Equipment shall be under "general
supervision" of certificate holder, in
case of emergency there shall be a
hazardous materials liaison, contact
info available to fire command center
FMEA/HMA HMA required
Inspections Performed by COF holder. Record
keeping on site.
Signage Warning against electrolyte or voltage.
Battery information on Building
Information Card.
9.2 Extinguishing
DNV GL tested a number of extinguishers during cell and module testing. During testing,
DNV GL found that all extinguishers tested5 could put out the fire if applied immediately
upon detection of a thermal spike (indicating the immediate onset of thermal runaway).
While extinguishing was accomplished with all extinguishers, water demonstrated the best
ability to cool and maintain cool temperatures on the battery.
Because the consumption of a single cell is rapid, the metal fire fuels (Class D) are rapidly
consumed and the fire evolves to Class A, B, or C quickly. Because of the rapid evolution
of a cell fire, DNV GL does not see an advantage to using a Class D extinguisher on
a single cell or system fire. This has direct implications for first responders who are
accustomed to using water as their primary extinguishing agent. In the event of a single cell
fire, cascading protections should limit propagation to other cells. First responders may still
respond to a call reporting smoke, but in the best case scenario the fire has consumed itself
and burned out. If a fixed suppression agent is installed within an enclosed environment
containing the single failed battery cell, it may suppress flammability in the enclosed space.
The use of water may be unnecessary at this point unless the fire has progressed. A key
issue to be addressed in later sections is how the first responder is able to determine if this
single cell fire has been mitigated or if further action (and water extinguishing) is needed,
and hence some system health information, an emergency response phone line, or some
other means to gain information on system health is a need that requires industry
engagement to overcome. The first responder is not comfortable deeming the site
extinguished and is technically responsible for the scene until this information allows them
to make the decision to leave the control of the scene with a responsible party.
DNV GL found that water extinguishes, cools, and maintains lower temperatures on a
battery fire than other tested agents. As shown in Figure 29, water consistently maintained
a 50-100oC sustained cooling advantage over equivalent volumes of other water borne
5
For the complete list of extinguishers tested, see the Appendix, page 82.
agents in the seconds and minutes following extinguishing. The behavior demonstrated in
the figure is consistent for all battery types, with the heat decay duration, “reheat” period,
and peak temperatures varying as a function of cell mass.
The initial cooling rate is nearly equivalent for all extinguisher types, but the thermal mass
of the battery causes the extinguishing agent to evaporate as temperatures climb back to
250-275oC. Extinguishers were triggered the moment the battery fire climbed above 350 oC.
In each case 1 gallon of water was applied. In all instances the total extinguishing time
spanned less than 60 seconds, or about 1 GPM.
The duration of this “reheating” is approximately 200s for non-water agents, whereas water
is shown to reheat for about 100 seconds. Therefore, DNV GL saw no particular cooling
advantage of water borne agents such as F-500, FireIce, or Pyrocool over water alone.
(Figure 29) Some of these agents are encapsulators, which are designed to blanket a fire
and insulate surrounding areas from heat; in an exothermic battery fire, trapping heat is
undesirable. The figure demonstrates that cooling with water persistently achieves lower
sustained temperatures after extinguishing, with as much as a 50-100oC advantage within
1-2 minutes of extinguishing (See appendix on page 76). This data demonstrates that water
and all water borne agents reduce cell temperatures from > 400 oC to near 50oC within 10-
30 seconds. Water can maintain cell temperatures after extinguishing below 100oC even as
the initial mass of water evaporates.
An additional vendor provided an aerosol agent to be tested. The aerosol was observed to
extinguish the cell fire. The aerosol provides some initial cooling but does not reduce cell
temperature until the exothermic reactions of the battery begin to decay. It was shown that
the cooling ability of the aerosol was significantly less than water.
Because cooling is an inevitable need, a fixed suppression gas agent may reduce
or mitigate flammability in an environment until ventilation and/or cooling
strategies are implemented.
While the use of water demonstrates excellent cooling capability, it also potentially shorts
out undamaged cells or neighboring modules. The use of water is a fully committed
extinguishing tactic that is highly likely to result in a total loss of the asset.
Because it was noted that the aerosol test demonstrated extinguishment of the fire upon
execution, aerosols can potentially serve as an initial attack for the fire followed by water as
a backstop.
Stage 1 provides an opportunity for avoiding collateral damage and total asset loss. Stage 2
provides a backstop for a situation when more than one battery cell is on fire. Both stages
may also include some form of alarm or notification external to the battery system that
notifies first responders of elevated risk.
Similarly, it was found that vanadium oxide electrolytes emit HCl and HF, with HCl occurring
in greatest quantities (see Figure 6 on page 12). Lead acid battery electrolytes emit SO2 and
HCl when heated (see page 12, Figure 7, and Figure 8). The mass and volume equivalent
concentrations of emissions from all battery types are included in Figure 4 (peaks) and
Figure 5 (average ppm per kg per minute).
A common toxic emission from all battery types was HCl. This is also common with plastics
fires. Because the IDLH rating for HCl is low and the quantity of HCl emission is typically
largest among the four toxic constituents monitored, the ACH rating is therefore governed
by HCl. As shown in Figure 5 all battery types average lower than 2 ppm per kilogram per
minute in the categories of CO, HF, HCN, and HCl emissions.
IDLH and Emergency Response Planning Guidelines (ERPG) values for HCl, HF, HCN, and CO
are shown in Table 6. The term immediately dangerous to life or health (IDLH) is defined by
the US National Institute for Occupational Safety and Health (NIOSH) as exposure to
airborne contaminants that is "likely to cause death or immediate or delayed permanent
adverse health effects or prevent escape from such an environment."
ERPG-1 is the maximum airborne concentration below which nearly all individuals
could be exposed for up to 1 hour without experiencing more than mild, transient
adverse health effects or without perceiving a clearly defined objectionable odor.
ERPG-2 is the maximum airborne concentration below which nearly all individuals
could be exposed for up to 1 hour without experiencing or developing irreversible or
other serious health effects or symptoms which could impair an individual's ability to
take protective action.
ERPG-3 is the maximum airborne concentration below which nearly all individuals
could be exposed for up to 1 hour without experiencing or developing life-threatening
health effects.
Table 6 Immediately Dangerous to Life and Health (IDLH) for the emphasized toxic
gases identified in the testing work.
This dynamic and varying emissions rate was time-averaged and then charted as a function
of air change over rate (air changes per hour, or ACH), of the battery mass undergoing
failure, and the room volume. Because this time averaged calculation includes the nonlinear
effect of higher emissions during the peak, this ACH calculation is overly conservative for
40-90% of the duration of the battery failure event. As mentioned previously and as shown
below, HCl (Figure 16) governs the dominating air change over requirement because of the
low IDLH value. The chart in Table 15 on page 66 converts ACH to CFM based on room size
and approximate room footprint. In all cases the ACH rate is calculated to maintain gas
concentrations below IDLH.
An air change rate of 0.25 ACH is sufficient for limited cell failure scenarios to mitigate HCl
in the room sizes considered (see Figure 16). The peak emissions rate for up to 1.5 Li-ion
modules (typical masses assumed) would require up to 11.5 ACH. This is within normal
laboratory building ACH requirements, by comparison (Table 8 on page 51), and ASHRAE
notes that 1 – 4.4 ACH is common in residential and commercial environments. [26] This
clarifies DNV GL’s recommendation that ventilation requirements are within
established limits of the built environment as long as the system demonstrates it
can limit propagation of cell failures with cascading protections
CO (Figure 18 and Table 13 on page 66) can be mitigated in all scenarios with only
0.25 ACH.
HF (Figure 19 and Table 14 on page 66) can be mitigated with 0.25 ACH in the most
probable failure scenarios and may require up to 14.5 ACH in the smallest room
considered.
HCN emissions rates can be mitigated for the most probable failure scenarios (a
single or multiple cells) with only a 0.25 ACH. In the worst case scenario of 1.5
failing modules, the ACH is 7.5.
Note that HCl and HF govern the ventilation requirements, which implies that the
ventilation requirement is determined by toxicity, not flammability. This is because
toxic gas IDLH limits are between 30-50 ppm, while flammability limits for many gases are
in the 1,000-10,000+ ppm range. The assumptions used in this calculation are shown
below. The emissions rates assumed for the ACH calculations are the average of the
emissions measured during cell testing. A 30-minute release rate is conservative, and
accounts for an average of emissions rate that is higher than the low level emissions leading
up to peak failure, and lower than the peak emissions.
The theoretical minimum water requirement for the battery mass (not the system mass) is
calculated in Table 7. It should be noted that the water calculation is determined in units of
GPM/kg; dividing this number by the energy density (commonly given in Wh/kg) will
convert the result to GPM/Wh, and multiplying by 1000 Wh/kWh will convert the result to
GPM/kWh. A cross check for these conversions will be needed as energy density of batteries
will inevitably increase over time.
For context and benchmarking, typical ventilation and water sprinkler requirements are
shown in Table 8 on page 51. The range of possible values for the GPM/kg of battery are
shown in Figure 31 on page 54. Table 15 on page 66 shows conversion factors between
ACH, CFM, and CFM/ft2.
The aggregate of such data is shown on page 67, which demonstrates the means to
estimate water flow and ventilation flow requirements based on system size. In some cases
it can be seen that the ventilation rates and GPM requirements are within the norm of
building codes. This is translated in Table 10 on page 53. However, the factors that affect
this most are the mass of batteries, their energy density, and the volume of the room where
they are installed. The air volume in larger rooms will dilute emissions, resulting in lower
requirements for air change.
DNV GL and Rescue Methods found that the water requirement per kg of battery material
decreased as the quantity of modules became larger (Figure 31). It is acknowledged that
initial testing began with an arbitrary water volume at the cell level, and it was found that
this quantity was more than sufficient—and is therefore excessive—for a practical
application. DNV GL recommends that further study be considered to find the
minimum water requirement for extinguishing and measure the physical
parameters impacting water contact efficiency
Because outdoor systems are likely containerized they are also likely to include on-board
gas-based fixed suppression systems. As recommended by DNV GL in the extinguishing
section (see page 45), a gas based suppression system may serve as a first line of
extinguishing. Adequate sizing of nearby fire hydrants should be considered in the context
of the maximum possible heat load during a system fire.
Table 8 Benchmarks for airflow and water flow for typical structures.
Based on the known test data, DNV GL is able to recommend the following across the
aggregate of battery chemistries. The values in Table 9 are derived from Table 16. These
are converted to example CFM/ft2 and GPM/ft2 values in Table 10 on page 53.
6
Estimated by phenolic, given that the battery is a composite of multiple polymers, liquids, and some metals.
Table 9 Values derived from probabilistic analysis of water flow rates (GPM) and air
flow rates (CFM) per system energy (kWh) or mass (kg).
Scalable Metrics for Systems based on Electrochemical Battery Mass and Energy
Content
25th Percentile Mean 75th Percentile
The energy density, cell mass, and emissions rate from the cell are the greatest influencing
factors in 90% of the calculated outcomes. DNV GL recommends that when calculating
the air flow and water extinguishing rate, one must account for battery energy
density (only the battery cells, not the entire system) as well as the duration of
the event. The sensitivity of the calculation of the water flow rate is shown in Figure 36.
The two main factors influencing the calculation are the range of flow rates found during
testing and the range of possible energy densities of the battery system.
These uncertainties demonstrate the following:
Energy density and the emissions duration should dictate the ventilation requirement
Energy density and the duration of the event affect the extinguishing requirement
In Table 10 some example ventilation and water extinguisher ratings are calculated based
on hypothetical systems. The values in Table 10 are calculated from Table 7 and
demonstrate the mean of probability distributions generated from Table 16. The
distributions of the water requirement is skewed to the left, as shown in Figure 31. The
table demonstrates how these findings translate to codes development via examples. The
table demonstrates that the ventilation and water requirements are within the scope of
present requirements for the built environment when the system is placed within adequate
room volumes (compare with Table 8). Considerations of whether the spaces are occupied
or whether they are outdoors apply.
In practice, these results will depend on the actual system weight and room size on a per
project basis. When considering a containerized system, the following additional
considerations may occur:
A containerized system may not be considered a livable or occupied space and
therefore may have different code considerations.
The water requirement in Table 10 is equivalent to about 4-5 garden hoses and is
less than half the GPM rating of a typical 2.5” line (250 GPM). If the system is
already equipped with a gas-based fixed suppression system, a parallel water
connection on the exterior would accomplish the goal for first responders to create a
cost effective internal sprinkler system as a backup to the fixed suppression system.
The calculated airflow requirement can be oversized with a variable speed fan that meets
the minimum air change requirement and may peak upon detection of smoke or
particulates.
The leftward skewness of the distributions for both the GPM requirement and the ACH
requirement is demonstrated in Figure 31 and Figure 32.
System System Estimated Estimated Ventilation Theoretical Median GPM GPM CFM/ft2 Min Median
Size Chemistry Mass (kg) Room Size Requirement Minimum Requirement Requirement GPM/ft2 GPM/ft2
(kWh) (ft2) (CFM) GPM at 0.1
Requirement GPM/kg
20 Li-ion 133.3 100 2.3 2.0 2.2 13.3 0.02 0.02 0.02
100 Li-ion 666.7 146 11.7 9.8 11.2 66.7 0.08 0.07 0.08
100 Pb Acid 3,333.3 200 58.4 UPS 0.29
Requirement
1000 Li-ion 6,666.7 300 116.8 98.1 111.8 666.7 0.39 0.33 0.37
1000 Vanadium 20,000.0 1500 350.4 Standard 0.23
Redox Commercial
Note: Fire flows in excess of 3,000 GPM per buildings are considered impractical for many state fire codes. Consideration of battery
flammability, cascading protections, and building water supply should be considered. For containerized systems, a parallel system may be
fed externally by fire hose.
Figure 31 Distribution of gallons per minute for a 1 MWh battery, calculated from
cell testing and extrapolating with the latent heat value, which demonstrates that
the 0.1 GPM/kg estimation is highly conservative.
Figure 32 Example of the air flow requirement for a 1 MWh Li-ion system,
demonstrating that the distribution of values is strongly skewed leftward.
Similar to the code for uninterruptible power supplies, which recommends hydrogen
monitoring and a system health status display (see Table 5), DNV GL recommends at a
minimum that an error status panel, emergency response contact, or other form of
error notification be available to first responders, and that the energy storage
supply chain engage with first responders to propose a viable solution. Current
codes for UPSs include a display panel for inspection and error notification purposes.
If a system has been in a fire which has been contained by internal fire suppression, such a
display panel is enough to alert first responders that the system has sustained damage.
They may be able to call in a specialist to handle the hazard and relieve FDNY of their
responsibility for the site.
There are technical parameters that have direct impact on the volatility of the system,
though it is debatable whether they should be the responsibility of the first responder.
Recall that the ultimate objective of the first responder is to protect life, preserve property,
and ultimately secure the scene. The intent of system health notifications or an emergency
response network is to alleviate the concern of the first responder that he/she will somehow
be obligated to own an unknown hazard. The project development community would serve
its own interest to support first responders in creating a means to facilitate a hand-off from
the first responder to a project owner with good certainty that the hazard is under control.
9.5 Clearances
As referenced in Table 4 and Table 5, the majority of codes identify a 3-5ft clearance on
energy devices within enclosed spaces. [4]
The current rule structures (NFPA 855, IBC, and IFC updates may allow for local AHJ
exceptions for the spacing and quantity of energy storage systems provided they pass a risk
analysis).
This recommendation is consistent with the IEEE 1547 and ANSI recognition of UL 9540
because of its FMEA process. Because cascading protections have been overlooked in safety
incidents (see Literature Review) it is highly important that this consideration be
emphasized in the up-front risk analysis. Clearances to nearby structures are presently
being recommended on a kWh basis, which may inadvertently limit the effectiveness of
energy storage by artificially increasing its footprint and therefore its effective functional
power and energy density. The risk analysis should provide a foundation for stakeholder
agreement on when the risks are deemed acceptable to exceed these requirements.
Similarly, the fire rating of the enclosure, if exceeding specification, may create
opportunities to reduce spacing or clearances. And the most probable failure mode is the
most important part of the risk analysis; it helps differentiate risks that seem significant but
are actually low probability, versus risks that are probable and measurable, and then design
with cost effectiveness and practicality.
Does the protective casing provide adequate insulation and fire blocking?
(Example, Figure 28)
The output of this analysis should determine if the rules are too prescriptive for the case
being considered, or alternatively, if the rules have not adequately captured a safety risk.
While not tested explicitly in this study, it is also worth mentioning that under rare
circumstances lead acid batteries are also capable of so-called thermal runaway, i.e., an
exothermic failure. Because the members of the battery industry have taken great care to
differentiate themselves in the area of safety, with nearly all chemistries that are not Li-ion
using marketing language such as “safe”, “nonflammable”, “thermally stable”,
“environmentally benign” or “incapable of thermal runaway”, there is a need to clarify a
universal finding in this program: in the case of external fire, all batteries emit toxic gases.
It should also be noted that the average emissions rates of equivalent masses of plastics
exceed those of batteries. Every battery tested either emitted a gas or left a residue that
has a varying degree of hazard (Table 3 on page 29); however, this can be expected from
most fires. The general findings of this work conclude that water and ventilation
requirements are within the technical limitations of legacy building codes, i.e., there are
precedents for managing these hazards.
All of the batteries tested carry with them a risk in their deployment; however, all of the
risks identified are manageable within the realm of today’s engineering controls for safety.
In addition, the toxicity and flammability risks identified are not insurmountable or highly
unique when compared to the challenges of burning hydrocarbons or plastics, and the
resulting requirements in codes, if implemented, are within the boundaries of the typical
built environment.
Lastly, the emissions rates of equivalent amounts of plastics during a fire, including
common every day materials that are found in office environments, commercial and
industrial settings, and even residential homes, can exceed the quantity of emissions from a
battery fire and will emit HCl as well.
The gases emitted are also found in plastics fires in greater time-averaged
quantities. This should be considered in the context of prescriptive codes because
these hazards are likely to already exist in the built environment.
DNV GL recommends that the lowest level ventilation rate - if prescribed - be
continuous under normal systems operation. The study concludes this may be as low
as 0.25 ACH, which is lower than what is required for most occupied spaces.
Regardless of chemistry, DNV GL recommends sizing for ventilation and extinguisher
systems as the following (these may be translated to GPM/ft 2 and CFM/ft2 or ACH
starting on page 50).
DNV GL recommends that minimizing the water requirement be an area of further
study as it has likely been overstated in these recommendations for
conservativeness.
DNV GL recommends at a minimum that an error status from an operating energy
storage system be readily apparent to first responders for the following parameters,
and recommends that a dialog be opened with system integrators to
determine the most effective and economic way to address this need:
o Internal atmosphere (normal or gas detected)
o Temperature (above normal or normal)
o Current (normal or threshold exceeded)
o Voltage (normal or threshold exceeded)
During and after fire extinguishing, it is recommended that if first responders choose
to use water submersion to cool and isolate battery modules, that preparation to
deal with alkaline or acidic water be considered.
After extinguishing, continued ventilation and monitoring of the area is highly
recommended to protect first responders from continued toxic and flammable gas
emissions. The first responder team can monitor the area with handheld sensors to
determine the appropriate time to stop ventilation.
It is highly recommended that an emergency contact list and/or subject matter
expert be available for all battery systems installed in buildings in order to introduce
the opportunity for first responders to relinquish control of the scene to the system
developer or a designate after the site has been secured and extinguishing has been
completed. This is likely to require involvement from the project development and
systems integration community.
If a battery is demonstrated to have a non-flammable electrolyte, there may be
considerations for a reduced water extinguisher requirement, or at a minimum, a
water requirement equivalent to that required for the space without battery systems
installed.
The ventilation requirements—if prescribed—should be the same for all battery
chemistries tested in this program because they all emit similar HCl levels.
In order to meet or exceed UL 9540 requirements, DNV GL recommends that a risk
analysis be performed on any basis where a battery system or portfolio of systems
shall be installed in an enclosed space near occupants. The analysis should look at
the general safety picture of the project(s) —in aggregate if possible—with a focus
on these risks:
o Does the system have design features that prevent cascading failure between
cells and modules? (See fire test, UL 1973 test, or IEC 62619 test data.)
o Are ventilation systems at the intended site(s) adequately rated to handle the
most probable failure mode? (Example: Table 7)
o Are sprinkler systems at the intended site(s) adequately designed for the
potential heat load and battery chemistry? (Example: Figure 29 and Table 7)
o Does the protective casing provide adequate insulation and fire blocking?
(Example: Figure 28)
10.1 Conclusions
Many historic battery incidents are due to external damage factors which have
created confusion and overreaction to the topic of battery safety.
Existing building codes and engineering controls can be adequate in many cases to
handle battery safety issues.
The toxic emissions from fires in this study can be managed by today’s engineering
controls and are not anomalous or excessive when compared to a plastics fire.
Plastics fires can generate similar gases in larger quantities over the average
emissions duration on an equivalent mass basis.
The water requirements from this study can be lessened for building fire extinguisher
systems when combined system-level safety approaches are implemented.
Legacy codes could provide insightful interim requirements for battery systems used
in energy management, provided that technical and practical engineering
considerations are made.
Gas-based agents that can reduce flammability in an enclosed environment can put
out single battery fires, but should not be considered an adequate cooling measure.
Water demonstrated the highest cooling efficacy of all extinguishing agents tested.
The use of water should only be considered if there is an acceptable risk of shorting
additional cells or collateral damage to the remainder of the system.
Water volumes for cooling can be minimized based on the expected duration of a
failure event. Systems with adequate internal cascading protections will minimize the
water volumes required for extinguishing.
Staged extinguishing with fixed aerosol or gas suppression agents first, followed by
water in the event of a cooling need, is recommended. It may be possible to use
parallel water inputs on fixed suppression systems for containerized battery systems.
Forced ventilation is recommended for first responders, even after the fire has been
extinguished.
The historical legacy of safety concerns has validity, though understanding of the
root causes and failure modes is necessary in order to understand the true threats
and failure modes.
Appropriate mitigation of risk shall include a pre-commissioning design review per accepted
industry practices that are presently being used in California and other states. Overall
DNV GL’s findings are that these hazards are manageable for building code officials and first
responders. No significant technology barrier exists that prevents code officials or first
responders from doing their duty when encountering battery energy storage systems.
11.0 REFERENCES
1. US Department of Labor, “Confined Spaces”. Occupational Safety and Health Administration
(OSHA) https://www.osha.gov/SLTC/confinedspaces/
2. 1 RCNY §50-01 Chapter 50 Distributed Energy Resource Standards.
3. “Home Fires”, Federal Emergency Management Agency (FEMA). http://www.ready.gov/home-
fires. Accessed May 10, 2015.
4. Hopper, Howard. “Energy Storage Systems Fire Safety Considerations”. UL Codes and
Advisory Services.
5. United States Department of Energy , DOE Global Energy Storage Database,
www.energystorageexchange.org. Accessed 11/11/16
6. Milke, Kodur, Marrion. “Overview of Fire Protection in Buildings”. Federal Emergency
Management Agency (FEMA). Appendix section from “World Trade Center Building
Performance Study: Data Collection, Preliminary Observations, and Recommendations”. 2002
7. Tyler, David. “Battery Related Fire Damages Famed Hybrid Tug, Puts it Out of Service.”
Professional Mariner, Nov 8, 2012.
8. Hayman, Susan. “Final Report on Battery Re-Installation; Campbell Foss and Carolyn
Dorothy”. Foss, 2015.14
9. Junod, Thomas. “Gaseous Emissions and Toxic Hazards Associated with Plastics in Fire
Situations – A Literature Review.” NASA Technical Note, NASA TN D-8338. Lewis Research
Center, Cleveland, OH. Oct 1976.
10. Hoff, Steeves. “New Insights into Thermal Runaway of Valve Regulated Lead-Acid Batteries”.
Battcon 2005.
11. Hill, et al. “Sensor Enhanced and Model Validated Life Extension of Li-Ion Batteries for Energy
Storage” APRA-E Advanced Management & Protection of Energy Storage Devices (AMPED)
Annual Program Review. January 8-10, 2014. Denver, CO
12. Tran, Lyda. “Statement of National Highway Traffic Safety Administration On Possible Fires in
Lithium-Ion Vehicles Involved in a Crash.” November 11, 2011.
13. Andersson, et al. “Investigation of Fire Emissions from Li-ion Batteries” Fire Technology, SP
Report 2013: 15.
14. NTSB Case Number: DCA13IA037, Interim Factual Report. Boeing 787-8, JA829J, Japan
Airlines. National Transportation Safety Board, Office of Aviation Safety. March 7, 2013
15. “Chevrolet Volt Battery Incident Overview Report” DOT HS 811 573. US Department of
Transportation, National Highway Traffic Safety Administration (NHTSA). January, 2012.
16. Shepardson, David. “Tesla Recalls 29k Vehicle Chargers That Could Spark Fire” The Detroit
News, January 14, 2014.
17. Chernova, Yulia. “Electric Car Maker Fisker Lost More Than 300 Cars in Hurricane Sandy
Flooding” The Wall Street Journal, Nov 6 2012.
18. Blanco, Sebastian. “GM Battery Lab Explosion Cost could Reach $5M” April 18th, 2012.
Autoblog.
19. Webster, Harry. “Lithium Battery Fire Tests” FAA William J Hughes Technical Center
20. Webster, Harry. “Flammability Assessment of Bulk-Packed, Nonrechargeable Lithium Primary
Batteries in Transport Category Aircraft. June 2004
21. DOT/FAA/AR-04/26
22. Lithium-Ion Batteries Hazard and Use Assessment. Fire Protection Research Foundation
Exponent. July 2011
23. Recommendations on the Transport of Dangerous Goods. Manual of Tests and Criteria, 5 th Ed.
Amendment 1, United Nations, Section 38. 38.3: “Lithium metal and Lithium Ion Batteries.”
24. Navy Sea Systems Command Advanced Change Notice for Lithium Battery Firefighting
Procedures.
25. Florence, Laurie. “Establishing Safety of Energy Storage – An Overview of UL Safety
Standards.” CPUC Energy Storage Workshop, August 19, 2015.
26. Fennel, Haehnel. “Setting Airtightedness Standards” American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE), 2005.
27. "ANSI/ASHRAE Standard 62.2-2013: Ventilation and Acceptable Indoor Air Quality in Low-Rise
Residential Buildings". Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning
Engineers. 2013
28. Stout, Roger. Beyond the Data Sheet: Demystifying Thermal Runaway. ON Semiconductor,
Nov 1 2007. Power Electronics.
29. Stout, Roger. Power Electronics System Thermal Design: Thermal Runaway. IEEE Power
Energy and Industry Application Courses, Feb 2007.
30. Ultracapcitor Safety Data Sheet, Maxwell Technologies.
31. Allcell Technologies, LLC. 2014 “Prevent Thermal Runaway Propagation”.
32. Winsun Energy Solutions, LiFePO4 specifications
33. “PBES announces world’s first commercialized thermal runaway suppression system”. Plan B
Energy Solutions (PBES).
34. SurePower, ”What is Thermal Runaway?” 2015 http://www.sure-power.com/2013/07/what-is-
thermal-runaway/
35. CD Technologies Technical Bulletin 41-7944: “Thermal Runaway in VRLA Batteries – Its Cause
and Prevention.” 2012
36. Rydh, Car Johan. “Environmental Assessment of Vanadium Redox and Lead Acid Batteries for
Stationary Energy Storage.” Journal of Power Sources 80 (1999) 21-29
37. Redox “Safety Data Sheet for Vanadium Pentoxide” Rev. 2 Jan 15 2014.
38. (cited with permission) DNV GL report, on behalf of ICL Industrial Products. “Safety Review of
Bromine-Based Electrolytes for Energy Storage Applications”, ICL Industrial Products, Report
No 1 Rev 1 Feb 26, 2016
39. “Guidelines and Considerations for Safer Deployment of ZnBr Based Battery Systems”. DNV GL
Feb 2016
40. Roman, Jesse. “The Li-ion Conundrum: Ignition and Reignition Issues with Batteries in Electric
Vehicles are Also Concerns for Energy Storage Systems.” Accessed March 4, 2016
41. DNV GL Guideline: Cell Level, Risk Based Testing and Modeling of Li-Ion Batteries for
Maritime, Energy Storage, and Other Applications Rev. 5.1, JANUARY 2016
42. Neubauer, et al. “The Effect of Variable End of Charge Battery Management on Small-Cell
Batteries.” NASA/TM-2007-215044, AIAA-2007-4789. December 2007
43. Dynamic Stress Test Power Profile. USABC Electric Vehicle Battery Test Manual Rev. 2 1996
44. Pinson, Bazant. “Theory of SEI Formation in Rechargeable Batteries: Capacity Fade,
Accelerated Aging, and Lifetime Prediction.” MIT, Department of Physics. 2012
45. Kuami, et al. “Gas Generation Mechanism due to Electrolyte Decomposition in Commercial Li-
Ion Cell.” Journal of Power Sources 81-82 (1999) 715-719
46. Hill, et all. “Sensor Enhanced and Model Validated Life Extension of Li-Ion Batteries for Energy
Storage”. Advanced Research Projects Agency – Energy (ARPA-e). DNV GL Final Report. July
1, 2015.
47. DNV GL Recommended Practice (GRIDSTOR). DNV GL RP 0043. “Safety, Operation, and
Performance of Grid Connected Energy Storage Systems.”
48. “Qualification of New Technologies” DNV Recommended Practice. DNV RP A203.
49. International Standard IEC 60812, “Analysis Techniques for System Reliability – Procedure for
Failure Mode and Effects Analysis.” 2nd Edition 2006, International Electrotechnical Commission
50. Huggett, Levin. “Toxicity of the Pyrolysis and Combustion Products of Poly(Vinyl Chlorides): A
Literature Assessment. Fire and Materials, Vol 11 131-142 (1987).
51. Ames, et al. Chapter 15: “Upholstered Furniture Predictions by Correlations”. Excerpt accessed
at the National Institute of Standards and Technology (NIST),
http://fire.nist.gov/bfrlpubs/fire92/PDF/f92017.pdf
52. Carbon-Monoxide – Hydrogen Combustion Characteristics in Severe Accident Containment
Conditions. NEA/CSNI/R(2000)10. Nuclear Energy Agency, Committee on the Safety of
Nuclear Installations. March, 2000.
53. Canadian Center for Occupational Health and Safety (CCOHS). Cheminfo, MSDS, Hydrogen
Chloride. Accessed 7-12-16.
http://www.chem.utoronto.ca/~pmeindl/labs/msds%20files/hydrogen%20chloride.htm
54. Dupont Teflon AF. Amorphous Fluoroplastics, Safety in Handling and Use. 2016.
55. Liyu Li, et al. “Vanadium Redox Flow Battery Using Mixed Acid Electrolytes”. US DOE Energy
Storage Systems (ESS) Program Review, Washington DC Nov 2 2010
56. Vanadium Redox Flow Batteries (VRB). Electricity Storage Association (ESA). Accessed 3-9-16.
57. Wang, Wei. Vanadium Redox Flow Batteries. US Department of Energy, Electricity Delivery
and Energy Reliability, Energy Storage Program. Pacific Northwest National Laboratory (PNNL).
58. Witlox, et al. “Validation of PHAST Dispersion Model as Required for USA LNG Siting
Applications.” Chemical Engineering Transactions, Vol 31, 2013. ISBN 978-88-95608-22-8
59. Dupont, Gauthier. “NGK’s NAS Batteries Long Recovery” August 23, 2012.
60. Fayet, et al. “Safety Issues Related to Stationary Electrochemical Energy Storage on Industrial
Sites.” CEt Chemical Engineering Transactions, Vol 48, 2016.
61. NAATBatt International, UET. March, 2015. NAATBatt Annual Meeting, Litchfield Park, AZ.
62. Trickett, David. NREL/TP-460-25553. “Current Status of Health and Safety Issues of
Sodium/Metal Chloride (ZEBRA) Batteries.” 1998
63. Willet, Ken. “Safety Validation in Grid Energy Storage.” Energy Storage Association, May 2014.
Washington DC.
that the mass loss ranges from 0-57%, the duration of the event lasts from 13-83 minutes,
and the emissions rate (in ppm per kg per min) in the 0.44 m3 chamber ranges from zero to
0.719 for HCl, 0.032 for HF, 0.027 for HCN, and 2.341 for CO. This data demonstrates that
CO is emitted in greatest quantity and HCl is emitted in the second greatest quantity, but
because HCl has a lower IDLH this threshold is met first in most scenarios.
The following tables demonstrate the calculated ACH as a function of burning battery mass
and room size. The tables below are the same data that is visually presented in Figure 16
and related figures. It is clear from the visual representation of the data that these
relationships are nonlinear. The estimations limit the failure to 1.5 modules, with the
presumption that the system should demonstrate adequate separations, cascading
protections, and suppression systems to limit failure to a single cell or at least a single
module. The probability of failure for multiple modules should be very low for systems with
these active and passive barriers to catastrophic failure. Catastrophic failure scenarios can
be examined by risk analysis to determine which barriers are in place to prevent it and the
relative strength of those barriers. The risk analysis places practical boundaries on the
probability of high consequence events, and should either 1) tame the deployment of
extreme safety measures with a low probability of utilization or 2) identify likely failure
scenarios that have been overlooked in the context of the site and system.
Table 11 Air change rates based on HCl emissions as a function of room size and
quantity of failing cells.
80 ft X
20 ft 40 ft 80 ft
container container room
HCl 33.1 67.6 3624
1 cell 1.54 0.25 0.25 0.25
5 cells 7.70 0.25 0.25 0.25
10 cells 15.40 0.25 0.25 0.25
15 cells 23.10 1.25 0.25 0.25
20 cells 30.80 3.25 0.25 0.25
24 cells 36.96 4.75 0.25 0.25
1 module 44 6.5 0.6 0.25
30 cells 46.20 7 1 0.25
35 cells 53.90 8.5 2 0.25
1.5 modules 66 11.5 3.5 0.25
Table 12 Air change rates based on HCN emissions as a function of room size and
quantity of failing cells.
80 ft X
20 ft 40 ft 80 ft
container container room
HCN 33.1 67.6 3624
1 cell 1.54 0.25 0.25 0.25
Table 13 Air change rates based on CO emissions as a function of room size and
quantity of failing cells.
80 ft X
20 ft 40 ft 80 ft
container container room
CO 33.1 67.6 3624
1 cell 1.54 0.25 0.25 0.25
5 cells 7.70 0.25 0.25 0.25
10 cells 15.40 0.25 0.25 0.25
15 cells 23.10 0.25 0.25 0.25
20 cells 30.80 0.25 0.25 0.25
24 cells 36.96 0.25 0.25 0.25
1 module 46.20 0.25 0.25 0.25
30 cells 53.90 0.25 0.25 0.25
35 cells 44 0.25 0.25 0.25
1.5 modules 66 0.25 0.25 0.25
Table 14 Air change rates based on HF emissions as a function of room size and
quantity of failing cells.
80 ft X
20 ft 40 ft 80 ft
container container room
HF 33.1 67.6 3624
1 cell 1.54 0.25 0.25 0.25
5 cells 7.70 0.25 0.25 0.25
10 cells 15.40 0.25 0.25 0.25
15 cells 23.10 2.5 0.25 0.25
20 cells 30.80 5 0.25 0.25
24 cells 36.96 7 1 0.25
1 module 44 9 2 0.25
30 cells 46.20 9.5 2.5 0.25
35 cells 53.90 11.5 4 0.25
1.5 modules 66 14.5 5.5 0.25
Table 15 shows conversion factors from air changes per hour to CFM and CFM/ft 2 for the
modeled energy storage rooms and enclosures.
Table 15 Conversions from ACH to CFM based on the example room volumes for
energy storage systems.
Shipping Container, 40 ft 68 2,407 301 195 781 3,906 7,811 23,434 0.65 2.60 12.98 25.96 77.88
Room, 80x80 ft 3,624 128,290 16,036 417,549 1,670,195 8,350,973 16,701,946 50,105,838 26.04 104.15 520.76 1041.52 3124.55
Notes: Occupied laboratories = 4-12 ACH, emergency ventilation ~ 30 ACH.
In Table 16, useful metrics derived directly from testing are provided. As mentioned
previously these values are input into a probabilistic model 7 to generate the sensitivity
analysis demonstrated in Figure 35 and related figures. The min, average, and max values
are used to generate triangular probability distributions. The GPM/kg measurement is a
direct measure of the water used to extinguish fires across the entire spectrum of cell to
module testing. The cell masses, mass loss, emissions range, HRR, and duration are the
ranges of values observed from cell testing. The energy density is calculated directly from
the cells. The estimated peak cell temperature is directly sourced from the cell data. The
fraction of cells simultaneously burning is a factor used to estimate the impact of total
emissions rate and account for the observed fact during module testing that cell failures
were rarely simultaneous and occurred as discrete events. It should be noted in the table
that the water contact efficiency averages 1-2%. This highly conservative number greatly
drives the water requirement estimation. Any method by which a battery manufacturer or
system integrator can demonstrate that the water contact efficiency is higher will reduce the
water requirement overall.
7
Palisade @Risk
Probabilistic Inputs
Parameter min avg max Dist Notes
Cell Mass kg 0.5 1.6 6.5 2.867 From cell test data
Peak Cell Temperature (°C) 350 525 700 525 From cell test data
Probabilistic Outputs
Delta T to Cool Battery to 25 C 325 500 675 500 Calculated from Above
Required Water Mass including 0.09 0.44 2.39 0.78 Q battery = Q water, m_water = Q
battery / (energy to heat water to
heat of vaporization (kg) 100 C + dHv)
Required Water Volume (gal) 0.02 0.12 0.65 0.21 divide by 3.7 kg/gal
GPM/kg with water contact 23.916 0.158 0.030 0.099 Divide by water contact efficiency
efficiency
Fraction of cells simultaneously 0.12 0.16 0.2 0.16 From module testing, 1-3 out of 8-
15
burning
The latter method was observed to be effective during testing as the water use in DNV GL
and Rescue Methods’ testing became progressively smaller (on a GPM/kg basis) as the
timing of the extinguishing event became decoupled with the peak HRR. In other words,
extinguishing the module or large pack was an exercise of removing distributed heat and
preventing perpetuating failure modes.
Therefore the extinguishing strategy should be arrest the climbing temperatures before they
reach the transition temperature at 120oC. This more practical approach takes into account
that automatic fixed suppression systems typically lack the intelligence to sense and trigger
according to specific gas species or gas emission rates; i.e., they are discharged upon
detection of smoke via a sensor that is generally sensitive to multiple particulate and
hydrocarbon species. As a result, fixed suppression will trigger very early in the cell failure
process. This would be the case for all battery types tested, as smoldering and gaseous
emissions from the plastics used for containment began as early as 60 oC. Just the fumes
from the plastics may be enough to trigger a smoke alarm.
If the module has adequate cascading protections and a 1-hour fire rating, there is
an opportunity to contain the cell failure and avoid the issue of oversizing the
water requirement to the peak and instead size the water requirement to the
battery mass.
As a result the water calculation is simplified by sizing the water flow to the battery mass
rather than the HRR at thermal runaway. This strategy is only valid if the cascading
protections are demonstrated to contain single cell failures and prevent cascading from cell
to cell and module to module, and the fire rating of the system provides adequate time to
address an external fire.
Following this method, the energy to be removed from the system is:
Q = mcΔT
8
Simulated as phenolic due to its specific heat which is near the average of the battery composition by material
For a 1 kg battery cell with an estimated composite specific heat similar to phenolic
(1.4 kJ/kg°C), and a temperature change of 525oC – 25oC = 500oC, the energy of heat
transferred is 700 kJ. This calculation neglects the additional removal of heat by water from
the heat of vaporization, which is addressed below.
The specific heat of water is 4.1 kJ/kg°C. The objective is to use the minimum amount of
water before water flashes into steam. If we target a volume of room temperature water
necessary to prevent the water from flashing off into steam, we assume ΔT = 70 oC (70+25
= 95oC, or just under the boiling point). This translates to
This states that 2.43 kg of water is required to cool a 1 kg battery from 500 oC to 25oC, and
the water will have risen in temperature to 95oC. This calculation should be very
conservative, as it neglects the vaporization of water into steam and assumes the entire
mass of the battery is contributing to the heat.
The density of water is 3.7 kg/gal, and therefore the theoretical conservative minimum
volume of water required is 0.65 gal. However recall that this reaction occurs over 1-3
minutes during the peak, and up to 40 minutes over a slow duration, and therefore the
gallons per minute required is 0.02-0.6 GPM/kg with the latter being
conservatively sized to still address the peak. The major factors driving the GPM/kg
requirement are the battery mass and the duration of the event.
The water requirements need not be excessive if the battery system employs
simple, industry proven safety measures such as an external fire rating and
cascading protections between cells and modules. Most of the batteries tested had
masses from 0.5-1.5 kg, with one battery being particularly large at 6 kg, which skews the
average to 2.8 kg and therefore makes this calculation more conservative. The values in the
table are probabilistic and the resulting distribution of water flows is shown in Figure 31.
The skewness of the distribution demonstrates that the theoretical minimum water
requirement mean is actually 0.019 GPM/kg, or very near the minimum.
The required energy to heat water from 25o C and then vaporize to steam at 100oC is:
� = ��∆� + �∆��
The specific heat of water C is 4.187 kJ/kgC and the latent heat of vaporization ΔHv is
2257kJ/kg. Using these numbers, the energy required to heat and boil one kilogram of
water from 25o C is:
� = �� ∗ . ∗ − + ∗
�� + , �� = , ��
It can be seen from the calculation that the latent heat of vaporization is 7x greater than
the energy required to heat from 25-100o C. This is important for cooling considerations
because the heat energy of the fire is transferred from the fire to the heating and boiling of
water; water withdraws energy from the fire, reducing its destructive power and energy.
Every kilogram of room temperature water that that is heated and flashed into steam draws
2,571 kJ from the fire.
Energy is most efficiently drawn from the fire when water contact is as complete as
possible. The method of delivery for the water will affect this contact efficiency such as mist,
spray, and jet. Access to the deepest seated batteries will govern the water contact
efficiency as well. When more water is in contact with the hot surfaces of the battery, the
rate of the water-to-steam conversion process increases, which saps energy from the fire
and reduces overall temperature as a result.
Expanding on the prior section, if the following assumptions are reconsidered with the
inclusion of latent heat of vaporization, the calculation follows:
Using the conversion factor 3.7 kg/gal, the resulting water volume is 0.07 gal. Again
assuming 1-3 minutes of battery burn duration, and up to 40 minutes for a slow duration
failure, the water requirement is 0.07 gal over 1-40 minutes or 0.001-0.07 GPM per
kilogram of battery. Note that this requirement is nearly 10x less than the thermal
mass balance calculation in the previous section. The latent heat of vaporization is
therefore a significant contributor to the cooling of the battery fire.
Figure 36 Regression coefficients for the water flow rate in GPM/kg demonstrate
that the duration of the event and the water contact efficiency are the strongest
drivers in reducing the water requirement.
The water contact efficiency of the extinguishing method is highly relevant to the overall
cooling effectiveness. The calculations demonstrate physically possible water flow rates,
however the testing is the most telling. As testing progressed, DNV GL was able to reduce
the water requirement from 1.7 GPM/kg at the module level to 0.1 GPM/kg. Conservative
factors accounting for water contact efficiency have resulted in DNV GL’s recommendations
in Table 9.
Based on the testing results and the calculations, 0.07 GPM/kg (including latent heat of
vaporization) and 0.1 GPM/kg (observed in testing a multi-module configuration) brackets a
significant range in heating and cell failure rate scenarios. A value of 0.1 GPM/kg appears to
be a highly conservative extinguishing rate as it does not account for the added benefit of
latent heat of vaporization and it provides a substantial compensation for water contact
efficiency.
An example shown is mechanical damage by the red arrows progressing from the left of the
diagram to the right. In this example, there may be monitoring methods in place that did
not react quickly enough to identify and prevent consequences of mechanical damage, and
other barriers (such as physical barriers) may have failed. If these barriers are breached
and the top event occurs, then a possible consequence is thermal runaway. There may also
be reactive controls such as fire alarms, automatic module disconnects, or emergency
cooling systems to draw heat from the battery before the thermal runaway threshold is
reached. Either side of the Bowtie model may be expanded into multiple threat or
consequence layers, depending on the detail of the model.
The Bowtie model is the highest level analysis that can be done and may be performed in
tandem with or in lieu of a failure mode effects and criticality analysis (FMECA). The FMECA
process involves a listing of all possible failure modes and a relative ranking of the
probability of their occurrence. The Bowtie model adds a visual representation of the
incident paths, the consequence of their occurrence, the barriers that are in place to prevent
the occurrence, and the escalation factors that can either defeat barriers or increase the
probability of the event occurring. Escalation factors are typically included on the left hand
side of a Bowtie model and demonstrate how outside factors increase the likelihood of a
barrier failure. Barrier defeating mechanisms can occur on either side of the top event in the
figure, but are more commonly included in the right hand side. The list of possible failure
modes in the FMECA analysis is a rank order list of all possible incident pathways diagramed
in the Bowtie model. Thus the Bowtie model is descriptive and qualitative in nature, while
the FMECA analysis is more quantitative. The Bowtie output can easily be converted to a
FMEA output and vice versa. Together, the Bowtie and the FMECA listing can be used to
address risks and outline recommendations for improvement in safety systems.
Figure 37 BowTie analysis permits the visualization of threats to a top event, such
as loss of battery control, and ties these threats to consequences.
Figure 38 Battery weight and the peak room temperature are positively correlated.
Computer Modeling
Computer modeling was used to extrapolate small scale burn test results to larger scale fire
scenarios involving battery racks. A model at the system scale (rack level) was constructed
for each of the chemistries tested. Model predictions were validated through comparison
with burn testing of small units.
Final Report
The final report (this document) includes the following for each family of chemistries:
findings from the literature review, results from the small scale cell level tests, results of the
system size modeling, an assessment of risk at the system scale, effectiveness of
extinguishers and techniques, and any other code relevant findings that emerge. First
responder training materials and guidelines are also a deliverable from this report.
The testing program is designed to address two hazards: 1) toxic or flammable off gases as
well as solids and liquids released during the burn and during fire suppression, and 2) heat
load and release rate. The testing program is designed to determine what toxic and
flammable gases are present as a function of chemistry and when they are released during
the fire. The heat release data provides scalable data as a function of chemistry to
determine passive fire protection requirements (as part of container or room design), as
well as the quantity and duration of release for fire extinguishers.
13.4 Procedure
The setup for all tests is depicted in the figure below. Additionally, all batteries underwent
multiple tests and state of charge (SOC) was varied to account for differences in energy
levels10. Battery voltages were measured during and after each test to determine their
potential for re-ignition, if any.
To filtration, metering and exhaust pump
Destructive Testing
Containment Chamber
(30”x30”x30”)
Flue Gas Direction
Air Inlets
Figure 39 Large abuse test chamber design for battery fire and extinguishing
testing.
9 ASTM 906: Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using a
Thermopile Method, ASTM 1354: Standard Test Method for Heat and Visible Smoke Release Rates for Materials
and Products Using an Oxygen Consumption Calorimeter, and ASTM E1623: Standard Test Method for
Determination of Fire and Thermal Parameters of Materials, Products, and Systems Using an Intermediate Scale
Calorimeter (ICAL)
10
Current plan is for testing at 50% and 100% SOC
11
Items in bold are actions to be determined as a function of testing progress – requires attentive monitoring by
technician.
12
No such events were observed.
13
Items in bold are actions to be determined as a function of testing progress – requires attentive monitoring by
technician.
Step 6: Execute extinguisher based on recommended extinguisher use 14. Monitor and
record temperature and gas sensors. Gas bag sample immediately after.
Step 7: Monitor decaying heat. Gas bag sample as appropriate. Monitor and record
gas sensor and thermocouple data.
Step 8: Monitor decaying heat until temperatures reach safe levels. May take hours
or overnight.
Step 9: Once battery remains are deemed safe, collect surface swabs, coupons, PPE
swabs, and secure battery in flame proof enclosure.
Step 10: Battery remains will be secured and monitored (video and temperature) for
24 hours. If re-ignition does not occur, batteries will be observed and intentionally
re-ignited the following day to observe remaining fire load. Battery will be allowed to
burn out on its own to ensure complete destruction and remove change of re-
ignition.
13.4.3 Testing Procedure: Flow and Lead Acid Battery Electrolyte (liquid)
A sealed autoclave with heater was used to contain the test. A sample of either liquid
(vanadium redox) or acid soaked glass mat (Pb AGM) was placed in a smaller container
within the autoclave. The autoclave was heated and off gases measured.
Step 1: Put electrolyte (liquid or wet glass mat) in autoclave, verify function of all
sensors. Electrolyte for each test will be taken from batteries charged to different
SOCs to maintain SOC variance in testing.
Step 2: Compile gas sensor baselines, capture ambient gas bag for baseline before
heating
Step 3: Initiate radiative heating element. Monitor liquid and ambient temperature.
Step 4: Collect gas bag sample. Monitor temperature and gas sensors. If
electrolyte is not expected to heat exothermically, monitor that heat rise is
consistent with controller setting. Monitor for flammables such as hydrogen, VOCs,
and sulfuric gases (SO2 and H2S).
Step 5: Record increasing heat with thermocouple measurements. Gas bag sample
as appropriate
Step 6: Continue heating to predetermined temperature 15. Collect gas bag sample
as appropriate. Monitor gas sensor and thermocouples. This may occur in durations
< 5 minutes.
Option Step 7A: Attempt spark ignition. If fluid vapor is known to be inert, this step
shall be skipped.
Option Step 7B: Execute extinguisher. Monitor and record temperature and gas
sensors. Gas bag sample immediately after.
Step 8: Monitor decaying heat. Gas bag sample as appropriate. Monitor and record
gas sensor and thermocouple data.
14
Different extinguishers, including automated extinguishers, have different guidelines for use and deployment.
Execution of extinguisher will be based on FDNY recommendations and use cases.
15
Peak temperature for flow batteries may vary. Temperature may be based on common class A/B/C/D fire
temperatures to determine fluid behavior during boiling or combustion. Max testing temperature may specified
by NYSERDA or Con Ed.
Step 9: Monitor decaying heat until temperatures reach safe levels. May take hours
or overnight.
16
No HRR will be performed on the lead acid or flow components as the energy storage portions of these
technologies are non flammable, only the balance of system will add to the fire load.
17
Likely PTFE or PET plastic or basic construction materials (wood).
Incipien Sensors: CO, CO2, Toxic or flammable Early stage heat release Modified ASTM 906
t/ O2, H2S, HF, F2, gases during fire rate, potential (thermopile); modified
Ignition SO2, VOCs, H2, LEL incipient stage. combustibility of ASTM 1354 (O2
radiantly heated batteries consumption
calorimetry) ; modified
ASTM 1623 (intermediate
Gas scale calorimetry)
Chromatography
Bags, post test
analysis: VOCs,
fluoride
compounds, CO,
CO2, heavy
metals19
18
See below test procedures for flow battery electrolytes
19
If contained within battery, based on MSDS
20
Compliments gas analysis
Incipient Sensors: CO, Toxic or flammable gases Early stage heat Modified ASTM
CO2, O2, H2S, during fire incipient stage. release rate, 906
HF, F2, SO2, potential (thermopile);
VOCs, H2, LEL combustibility of modified ASTM
radiantly heated 1354 (O2
batteries consumption
calorimetry) ;
Gas modified ASTM
Chromatography 1623
Bags, post test (intermediate
analysis: VOCs, scale
fluoride calorimetry)
compounds, CO,
CO2
Heat Climax Same Gas composition during Peak heat loads, Same
fire climax O2 consumption
Decaying fire Same Gas composition as fire Heat decay rate, Same
evolves and decays. ability to
Changes in gas sustain cooling
composition as a result with
of extinguishing extinguisher
Debris (Background) Residual fumes. Changes Residues and HAZMAT Turnout gear
in gas composition as a considerations. after exposure.
result of extinguishing. Changes in residues Coupons for
as a result of SEM/EDAX/XRD.
21
Flow battery electrolytes may be heated to achieve the simulation of external heating due to a fire. Some flow
battery electrolytes are not expected to be exothermic.
22
Complements gas analysis
23
To be compared against benchmark “without extinguishing”
24
Evaluation of heat management as a result of extinguishing will inform firefighter extinguisher guidelines
extinguishing, Ion
HAZMAT impact, chromatography
degradation to PPE may be
performed with
swabs from
turnout gear.
Change in
residues as a
result of
extinguishing.
Liquid samples
for IC will
determine if
extinguisher
liquid residues
are toxic.