Theory: Ircuit Diagram Fig - No
Theory: Ircuit Diagram Fig - No
Load test (back to back or Sumpner’s test). A load test on a transformer is necessary if its maximum
temperature rise is to be determined. A small transformer can be put on full load by means of suitable
impedance. But for large transformers, full load test is difficult since it involves considerable waste of
energy and a suitable load, capable of absorbing full load power, is not easily available. However, large
transformers can be put on full load by means of Sumpner’s or back to back test. The Sumpner’s test can
also be used for calculating the efficiency of a transformer, though the latter can be determined accurately
from open-circuit and short-circuited tests.
The back-to-back test on single-phase transformers requires two identical units. Fig. (1) Illustrates the
circuit for two single-phase transformers, where two primaries connected in parallel, are energized at
rated voltage and rated frequency. With secondaries open, the wattmeter W1 records the core losses of
both the transformers. The two secondaries are connected in series with their polarities in phase
opposition, which can be checked by means of a voltmeter. The range of this voltmeter connected Should
be double the rated voltage of either transformer secondary? Zero voltmeter reading (V2 = 0) indicates
the secondaries are connected in opposition. Now if the terminals ab are short circuited, the current in the
secondary would be zero because V2 = 0 and the wattmeter reading W1 remains unaltered. In the case
of voltmeter reads the sum of the two secondary voltages; the secondaries are in the same phase. In
order to bring them in phase opposition, terminals ad should be joined together to result in zero voltage
across Transformer1 & Transformer2.
Reading may vary for different transformer’s.
It is seen from above that in Sumpner’s test, even though the transformers are not supplying any
load current, yet full iron- loss occurs in their cores and full ohmic loss occurs in their windings. Net power
input to the two transformers is (2pc+2Psc). If temperature rise of the two transformers is to be measured,
then the two transformers are kept under rated loss conditions for several hours till maximum stable
temperature is reached. If 2 I 0 is the no load current, then for the assumed directions of I 0 and I2, the
primary current of transformer 1 is less (difference of I 1 and I0) than the primary current of transformer 2
(sum of I1 and I0) Therefore the two transformers do not operate under identical conditions - one may have
PROCEDURE
PRECAUTIONS :
1. All meters should be connected in correct polarity .
2. Supply should be switched OFF while making connections.
3. Do not touch terminals on panel while supply is ON .
4. Load should be introduced in steps .
5. Do not exceed beyond rated values .
6. All connections should be tight and clean .
STANDARD ACCESSORIES
1. Thirty Two Single Point Patch Cords for Ineterconnections.
2. Instruction Manual (DOC 2410).
OPTIONAL ACCESSORIES