0% found this document useful (0 votes)
475 views132 pages

Multi Type Room Air Conditioner: Service Manual

This document provides product specifications and operating instructions for multiple models of multi-type room air conditioners. It includes specifications for several indoor units ranging from 7,000 to 18,000 BTU/H cooling capacity, and their paired outdoor units ranging from 23,400 to 25,200 BTU/H maximum cooling capacity. It also details dimensions, wiring diagrams, functions, installation, troubleshooting guides, and exploded views of parts.

Uploaded by

oribata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
475 views132 pages

Multi Type Room Air Conditioner: Service Manual

This document provides product specifications and operating instructions for multiple models of multi-type room air conditioners. It includes specifications for several indoor units ranging from 7,000 to 18,000 BTU/H cooling capacity, and their paired outdoor units ranging from 23,400 to 25,200 BTU/H maximum cooling capacity. It also details dimensions, wiring diagrams, functions, installation, troubleshooting guides, and exploded views of parts.

Uploaded by

oribata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 132

Multi Type Room

Air Conditioner
SERVICE MANUAL
INDOOR UNIT: AMNN076L/M/NQA0
AMNN096L/M/NQA0
AMNN126L/M/NRA0
AMNN186L/M/NTA0
AMNN246L/M/NTA0
AMNN096APA0
AMNN126APA0
AMNN126TEA0
AMNN186TEA0
AMNN186VBA0

OUTDOOR UNIT: A2UN186FA0


A3UN216FA0
A4UN306FA0
Contents

Functions...................................................................................................................................... 3

Product Specifications .................................................................................................................6

Dimensions..................................................................................................................................10

Wiring Diagram ...........................................................................................................................15

Refrigeration Cycle Diagram......................................................................................................17

Operation Details ........................................................................................................................18

Display Function .........................................................................................................................34

Self-diagnosis Function .............................................................................................................34

Installation ...................................................................................................................................35

Operation .....................................................................................................................................73

Disassembly of the parts (Indoor Unit) .....................................................................................77

Valve service(3-way) ...................................................................................................................86

Cycle Troubleshooting Guide ....................................................................................................90

Electronic Parts Troubleshooting Guide...................................................................................91

Electronic Control Device ........................................................................................................104

Schematic Diagram...................................................................................................................111

Exploded View and Replacement Parts List...........................................................................116

-2-
Functions

Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature

• Room temperature sensor. (THERMISTOR)


Room temperature control

• Maintains the room temperature in accordance with the Setting Temp.


Starting Current Control

• Indoor fan is delayed for 5 seconds at the starting.

Time Delay Safety Control

• Restarting is inhibited for approx. 3 minutes.

Indoor Fan Speed Control

• Room/Art Cool/Convertible Type Indoor Unit: High, Med, Low, Chaos


• Cassette Type Indoor Unit: High, Mde, Low, Auto
Operation indication Lamps (LED) Natural Air Control by CHAOS Logic
• The fan is switched to intermittent or irreg-
• Room/Art Cool/Convertible type Indoor Unit
ular operation
-- Lights up in operation • The fan speed is automatically switched
-- Lights up in Sleep Mode from high to low speed.
-- Lights up in Timer Mode Airflow Direction Control
-- Lights up in Deice Mode • The louver can be set at the desired posi-
tion or swing up and down automatically.
• Cassette type Indoor Unit
-- Lights up in Operation PLASMA
-- Lights up in Filter replacement • The function will be operated while in any
-- Lights up in Timer Mode operation mode with selecting the function.
• The function is to be stopped while it is
-- Lights up in Defrost Mode or Hot Start Operation.
operating with selecting the function.
-- Operation procedures when the remote control
can't be used. Deice (defrost) control (Heating)
Soft Dry Operation Mode • Both the indoor and outdoor fan
stops during deicing.
• Intermittent operation of fan at low speed. • Hot start after deice ends.
Sleep Mode Auto Control Hot-start Control (Heating)
• The fan is switched to low(Cooling), med(Heating) speed. • The indoor fan stops until the
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. evaporator piping temperature will be
reached at 28°C.

-3-
Outdoor Unit

Power relay control

• If power is on, it will operate to chage capacitor on controller and power relay will operate after about
10sec.

Comp. Freq. control

• The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp.,
target freq., owing to CT.

Overheatng. Protection(Power module)

Freq. speed control(up/down speed)

V/F control

• It will be changed the drive voltage of comp. according to operating frequency.

Total current control (over current protection)

DC peak current control

4 way valve control


• It is only operated in the heating operation mode except defrosting operation.

Outdoor fan motor control


• High speed/Low speed

Discharge pipe temp. control

Overpressure protection

-4-
Remote Controller

Operation ON/OFF

Operation Mode Selection


Cooling Operation Mode.( ) Auto Operation Mode.( )
(Cooling (Heating
model only) model only) Healthy Dehumidification Operation Mode.( ) Heating Operation Mode.( )

Fan Speed Selection

(Low) (Med) (High) (CHAOS)

Room, Temperature Display


: (High: 39°C LOW : 11°C)

Temperature Setting
TEMPERATURE HIGH LOW Down to 18°C Down to 16°C
Cooling Heating
Up to 30°C Up to 30°C

JET COOL

Setting the Time or Timer

Timer Selection
ON OFF
: OFF, ON, OFF ON

Timer Setting
SET

Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer

Airflow Direction Control

Fan Operation Mode

: Fan Operates without cooling or heating.

Reset

-5-
Product Specifications
Model Indoor AMNN076L/M/NQA0 AMNN096L/M/NQA0 AMNN126L/M/NRA0 AMNN186L/M/NTA0
Item Outdoor A3-N216FA0/A2-N186FA0
Btu/h 7,000 9,000 12,000 18,000
Cooling Capacitor (Indoor)
W 2,051 2,637 3,517 5,274
Btu/h 23,400
Max. Cooling Capacitor (Outdoor)
W 6,856
Btu/h 8,000 10,000 13,000 19,000
Heating Capacitor (Indoor)
W 2,344 2,930 3,809 5,567
Btu/h 25,200
Max. Heating Capacitor (Outdoor)
W 7,384
Moisture Removal l/h 1.0 1.2 1.7 2.0
Power Supply Ø, V, Hz 1, 220-240, 50
Indoor, Max 6.5 7.0 9.5 13
Air Circulation CMM
Outdoor, Max 56
Indoor, High 35 37 40 43
Indoor, Med 33 34 36 40
Noise Level (1m) dB(A)±1
Indoor, Low 30 31 32 37
Outdoor, Max 54
Cooling 880~2,660
Input W
Heating 1,210~2,360
Cooling 4.6~12.1
Running Current A
Heating 6.1~11.1
Indoor 5.3 8.4 14.4 22
Motor Output W
Outdoor 68
Indoor mm 824 x155 x 260 824 x155 x 260 900 x 156 x 285 1090 x 172 x 314
Dimensions
Outdoor (W*D*H) 870 x 320 x 655
Indoor 7 7 8 12
Net Weight Kg
Outdoor 64
Refrigerant R-410A g 1600(at 7.5m)
Airflow Direction Control(Up & Down) O O O O
Remocon Type L.C.D Wireless
Luquid 1/4"(6.35)
Service Valve inch(mm)
Gas 3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 1/2"(12.7)
Sleeping Operation O
Connection Cable O

-6-
Model Indoor AMNN076L/M/NQA0 AMNN096L/M/NQA0 AMNN126L/M/NRA0 AMNN186L/M/NTA0 AMNN246L/M/NTA0
Item Outdoor A4-N306FA0
Btu/h 7,000 9,000 12,000 18,000 23,000
Cooling Capacitor (Indoor)
W 2,051 2,637 3,517 5,274 6,739
Btu/h 31,000
Max. Cooling Capacitor (Outdoor)
W 9,083
Btu/h 8,000 10,000 13,800 19,000 26,000
Heating Capacitor (Indoor)
W 2,344 2,930 4,044 5,567 7,618
Btu/h 34,000
Max. Heating Capacitor (Outdoor)
W 9,962
Moisture Removal l/h 1.0 1.2 1.7 2.0 2.5
Power Supply Ø, V, Hz 1, 220-240, 50
Indoor, Max 6.5 7.0 9.5 13 14
Air Circulation CMM
Outdoor, Max 60
Indoor, High 35 37 40 43 47
Indoor, Med 33 34 36 40 44
Noise Level (1m) dB(A)±1
Indoor, Low 30 31 32 37 40
Outdoor, Max 58
Cooling 1,430~3,800
Input W
Heating 1,950~3,910
Cooling 7.0~19.5
Running Current A
Heating 9.3~20.0
Indoor 5.3 8.4 14.4 22 29
Motor Output W
Outdoor 68
Indoor mm 824 x 155 x 260 824 x 155 x 260 900 x 156 x 285 1090 x 172 x 314 1090 x 172 x 314
Dimensions
Outdoor (W*D*H) 870 x 320 x 800
Indoor 7 7 8 12 12
Net Weight Kg
Outdoor 75
Refrigerant R-410A g 2,000(at 7.5m)
Airflow Direction Control(Up & Down) O O O O O
Remocon Type L.C.D Wireless
Luquid 1/4"(6.35)
Service Valve inch(mm)
Gas 3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 1/2"(12.7)
Sleeping Operation O
Connection Cable O

-7-
Model Indoor AMNN096APA0 AMNN126APA0 AMNN126TEA0 AMNN186TEA0 AMNN186VBA0
Item Outdoor A3-N216FA0/A2-N186FA0
Btu/h 9,000 12,000 12,000 18,000 18,000
Cooling Capacitor (Indoor)
W 2,638 3,517 3,517 5,275 5,275
Btu/h 23,400
Max. Cooling Capacitor (Outdoor)
W 6,856
Btu/h 10,000 13,800 13,800 19,000 19,000
Heating Capacitor (Indoor)
W 2,931 4,044 4,044 5,567 5,567
Btu/h 25,200
Max. Heating Capacitor (Outdoor)
W 7,384
Moisture Removal l/h 1.0 1.2 1.5 3.3 2.5
Power Supply Ø, V, Hz 1, 220-240, 50
Indoor, Max 7.0 8.3 9.25 13.5 14
Air Circulation CMM
Outdoor, Max 56
Indoor, High 39 41 41 47 49
Indoor, Med 35 38 39 45 47
Noise Level (1m) dB(A)±1
Indoor, Low 33 36 37 43 45
Outdoor, Max 54
Cooling 880~2,660
Input W
Heating 1,210~2,360
Cooling 4.6~12.1
Running Current A
Heating 6.1~11.1
Indoor 24 24 18.3 25 -
Motor Output W
Outdoor 64
Indoor mm 570 x 137 x 568 570 x 137 x 568 570 x 570 x 269 570 x 570 x 269 1,200 x 205 x 615
Dimensions
Outdoor (W*D*H) 870 x 320 x 655
Indoor 9 9 19 19 30
Net Weight Kg
Outdoor 64
Refrigerant R-410A g 1,600
Airflow Direction Control(Up & Down) O O O O O
Remocon Type L.C.D Wireless
Luquid 1/4"(6.35)
Service Valve inch(mm)
Gas 3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 1/2"(12.7) 1/2"(12.7)
Sleeping Operation O
Connection Cable O

-8-
Model Indoor AMNN096APA0 AMNN126APA0 AMNN126TEA0 AMNN186TEA0 AMNN186VBA0
Item Outdoor A4-N306FA0
Btu/h 9,000 12,000 12,000 18,000 18,000
Cooling Capacitor (Indoor)
W 2,638 3,517 3,517 5,275 5,275
Btu/h 23,400
Max. Cooling Capacitor (Outdoor)
W 6,856
Btu/h 10,000 13,800 13,800 19,000 19,000
Heating Capacitor (Indoor)
W 2,931 4,044 4,044 5,567 5,567
Btu/h 25,200
Max. Heating Capacitor (Outdoor)
W 7,384
Moisture Removal l/h 1.0 1.2 1.5 3.3 2.5
Power Supply Ø, V, Hz 1, 220-240, 50
Indoor, Max 7.0 8.3 9.25 13.5 14
Air Circulation CMM
Outdoor, Max 60
Indoor, High 39 41 41 47 49
Indoor, Med 35 38 39 45 47
Noise Level (1m) dB(A)±1
Indoor, Low 33 36 37 43 45
Outdoor, Max 58
Cooling 1,430~3,800
Input W
Heating 1,950~3,910
Cooling 7.0~19.5
Running Current A
Heating 9.3~20.0
Indoor 24 24 18.3 25 -
Motor Output W
Outdoor 64
Indoor mm 570 x 137 x 568 570 x 137 x 568 570 x 570 x 269 570 x 570 x 269 1,200 x 205 x 615
Dimensions
Outdoor (W*D*H) 870 x 320 x 655
Indoor 9 9 19 19 30
Net Weight Kg
Outdoor 64
Refrigerant R-410A g 2,000(at 7.5m)
Airflow Direction Control(Up & Down) O O O O O
Remocon Type L.C.D Wireless
Luquid 1/4"(6.35)
Service Valve inch(mm)
Gas 3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 1/2"(12.7) 1/2"(12.7)
Sleeping Operation O
Connection Cable O

-9-
Dimensions
1. Indoor Unit
• Room Type Indoor Unit

D
W

Installation plate

MODEL
7K, 9K Btu Series 12K Btu Series 18K, 24K Btu Series
DIM

W mm 824 900 1,090

H mm 260 285 314

D mm 155 156 172

- 10 -
• Art Cool Type Indoor Unit

Hanger Hole
W D

Pipe Hole Fix Hole

MODEL
INDOOR UNIT
DIM Unit

W mm 570

H mm 568

D mm 137

- 11 -
• Convertible Type Indoor Unit

1200mm 61
5m
m

205mm

63mm
38mm

39
26 2m
5m m
m

46
8m
m 175mm

(Installation Plate)
250mm

mm
36

6 mm
107

(Rear Side)
mm
36

- 12 -
• Cassette Type Indoor Unit

670

269

670
670
670

CLOSE OPEN OPEN CLOSE

55

570
450
570

521

40
30

110 110
269

90

90

190.5
160
120.4

52

- 13 -
2. Outdoor Unit

L1
D
L2
L3
H

L10

L10

L9

L9

L6 L5 L7 L8
L4

MODEL
A2UN186FA0/A3UN216FA0 A4UN306FA0
DIM
W mm 870 870

H mm 655 800

D mm 320 320

L1 mm 370 370

L2 mm 25 25

L3 mm 630 775

L4 mm 25 25

L5 mm 546 546

L6 mm 160 160

L7 mm 160 160

L8 mm 53 53

L9 mm 50 50

L10 mm 40 40

- 14 -
Wiring Diagram
1. Room Type Indoor Unit 2. Art Cool Type Indoor Unit

CN-GND
MAIN PCB ASSY

CN-MOTOR2
WH
BK
FAN
MOTOR YL

CN-TH1
RD

CN-UD
STEP
MOTOR

CN-POWER

CN-LR1
FUSE
250V 3.15A STEP
MOTOR

GN/YL
BR
BL

RD

CN-LR2
1(L) 2(N) 3 4
STEP
MOTOR
3854A20135F CN-D1 CN-D2

TO OUTDOOR UNIT

STEP CONNECT DISPLAY


MOTOR PCB ASSY PCB
ASSY

STEP
MOTOR INDOOR WIRING DIAGRAM
3854A20219A

3. Cassette Type Indoor Unit 4. Convertible Type Indoor Unit

THERMISTOR
TRANS-
FORMER
SENSOR

BR CAPACITOR
ROOM

INDOOR DRAIN STEP


MOTOR PUMP MOTOR CN-TRANS CN-TH
GN/YL YL BR YL
CN-FAN
OR
BK

BL
BL

OR

CN-UP/DOWN 1,2
FUSE RD RY-L STEP
250V 5A
3(L) 4(N)

BR FUSE T3.15A GN/YL MOTOR BL RY-M MOTOR


BK RY-H
BL PIPE
DOOR S/W 1,2 MAIN PCB
SENSOR ASSY STEP
TO OUTDOOR UNIT

MOTOR

GN/YL
RD
5
6

FUSE T3.15A
FLOAT S/W
CN-POWER CN-DISP
CN - DISP
7

BR BL RD
1(L) 2(N) 4 5 6 TERMINAL
BLOCK
TERMINAL
BLOCK DISPLAY PCB DISPLAY PCB
ASSY
TO OUTDOOR UNIT
INDOOR WIRING DIAGRAM
3854A20221A INDOOR WIRING DIAGRAM 3854A20220A

- 15 -
4. Outdoor Unit
Comp.
RD WH WH
U U N 400V,2500µF(DC LINK)
WH BK CAPACITOR
V IPM P
V BL
W W BK
CN- CN- CN-
GATE1 GATE2 IPM
BK WH

BK BK
MOTOR BRIDGE
DIODE

4WAY
YL BR BL BK OR RD

CAPACITOR
BK

REACTOR
BR YL

RD
BR

OR
BK
BL
WH BK
CAPACITOR
(8PIN) (7PIN) (9PIN) RD (400V,165µF)

CN- CN- CN- CN-FAN CN-DC RD WH


BL
GATE1 GATE2

CN-4WAY
IPM

RY-HIGH
BRIDGE

RY-LOW
OPTION
DIODE

BL
CN-LEV3 CN-LEV2 CN-LEV1 CN-LEV4

CN-SV CN-SV(H)
D-LEV RD WH
MAIN S.V

A-LEV
PCB BL
S.V BR

WH
B-LEV BR
BR

CN-AC
PWR
(RD)

CT
RY-
RY-START
POWER 4 2
C-LEV RELAY 0 1

CN-PWR
WH
COND BK BK

CN-TH6
SENSOR YL
AIR YL
SENSOR L/P SWITCH BR
YL
A-PIPE RD

CN-TH5
SENSOR H/P SWITCH

250V, 3.15A
B-PIPE BL

FUSE
SENSOR

CN-TH4
WH BL
C-PIPE
SENSOR

POWER-OUT
GN/YL

CN-POWER

GND
CN-TH3
D-PIPE NL
SENSOR BL
(WH) (WH)

CN-TH2
SUCTION BK
SENSOR BR

250V,25A
FUSE
CN-DATA
(RD) NOISE

CN-TH1
DISCHARGE WH
SENSOR POWER-IN FILTER

RD WH YL
BK BR BL
GN/YL GN/YL GN/YL
BL BL BL
BR BR BR

3 1(L) 2(N) 3 3 1(L) 2(N) 3 1(L) 2(N)

OPTION

D C B A MAIN POWER
1Ø, 220~240V, 50Hz

TO INDOOR UNIT 3854AP7050Z

- 16 -
Refrigeration Cycle Diagram
1. A2-N186FA0
Refrigerant flow

Indoor Unit Outdoor Unit


B-gas pipe sensor

A-gas pipe sensor

Gas side
Service Valve 4-WAY VALVE
UNIT-B UNIT-A Heating
sensor

Discharge
pipe
sensor
Indoor

A-liquid pipe
temperature

B-liquid pipe
sensor

sensor
sensor
Comp
Heat
Exchanger
A-LEV
B-LEV

Strainer

Liquid side
Service Valve

2. A3-N216FA0 Refrigerant flow

Indoor Unit Outdoor Unit

C-gas pipe sensor


B-gas pipe sensor

A-gas pipe sensor

Gas side
Service Valve 4-WAY VALVE
UNIT-C UNIT-B UNIT-A Heating
sensor

Discharge
pipe
sensor
Indoor
A-liquid pipe

temperature
C-liquid pipe

B-liquid pipe

sensor
sensor
sensor

sensor

Comp
Heat
Exchanger
A-LEV
B-LEV
C-LEV Strainer

Liquid side
Service Valve

3. A4-N306FA0 Indoor Unit Outdoor Unit


D-gas pipe sensor
C-gas pipe sensor
B-gas pipe sensor
A-gas pipe sensor

Solenoid
Gas side Valve
Service Valve
UNIT-D UNIT-C UNIT-B UNIT-A
Heating
sensor

Discharge
Indoor pipe
sensor
A-liquid pipe

temperature
D-liquid pipe

C-liquid pipe

B-liquid pipe

sensor
sensor
sensor

sensor

sensor

Section pipe
sensor
Comp
A-LEV Heat
Exchanger
B-LEV
C-LEV Strainer
D-LEV

Liquid side
Service Valve

ex) Solenoid valve Cooling & Deice


LEV Heating
Capillary tube

- 17 -
Operation Details
1. Room/Art Cool Type Indoor Unit
(1) The Function of main control
• DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)

Sleep Timer Indicator


• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause

Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled

Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control

■ Cooling Mode Operation


• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp ➲ Setting Temp+0.5°C
Compressor OFF Temp ➲ Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.

■ Soft Dry Operation Mode


• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Intake Air Temp<26°C ➲ Intake Air Temp-1°C
18°C ≤ Intake Intake Air Temp<24°C ➲ Intake Air Temp-0.5°C
Intake Air Temp<18°C ➲ 18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp. ➲ Setting Temp+0.5°C
Compressor OFF Temp. ➲ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

■ Heating Mode Operation


• When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp. ➲ Setting Temp.
Compressor OFF Temp. ➲ Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 26°C, when above 28°C , it
operates with the low or setting airflow speed.

-18-
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.

■ Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -5°C after 40 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation or after the outdoor fan operates with-
in max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -5°C after 40 minutes passed
from ending of the first defrost and more than 10 minutes operation of compressor.

■ Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp ➲ Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C ➲ Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C ➲ Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1) Fuzzy Operation for Cooling


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C
Compressor OFF Temp ➲ Setting Temp – 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C≤ Intake Air Temp ➲ 25°C
24°C≤ Intake Air Temp<26°C ➲ Intake Air Temp – 1°C
22°C≤ Intake Air Temp<24°C ➲ Intake Air Temp – 0.5°C
18°C≤ Intake Air Temp<22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem-
perature.

-19-
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C
Compressor OFF Temp ➲ Setting Temp – 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp ➲ 25°C
24°C ≤ Intake Air Temp<26°C ➲ Intake Air Temp – 1°C
22°C ≤ Intake Air Temp<24°C ➲ Intake Air Temp – 0.5°C
18°C ≤ Intake Air Temp<22°C ➲ Intake Air Temp
Intake Air Temp<18°C ➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.

3) Fuzzy Operation for Heating


• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp
Compressor OFF Temp ➲ Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C≤Intake Air Temp ➲ Intake Air Temp + 0.5°C
Intake Air Temp<20°C ➲ 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.

■ Airflow Speed Selection


• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow
speed selection key on the remote control.

■ On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

■ Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.

-20-
■ Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.

■ Sleep Timer Operation


• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-
ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.

■ Chaos Swing Mode


• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.

■ Chaos Natural Wind Mode


• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.

■ Jet Cool Mode Operation


• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.

■ Auto Restarting Operation


• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• The slide switch on the main unit of the appliance should be on the Auto Restarting position in order that the
Auto Restarting operation is available.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected Airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour)
• Incase the power comes on again after a power failure,
Auto Restarting operation is the function to operate procedures
automatically to the previous operating conditions. (Art Cool Type)

-21-
■ Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched to the Auto Restarting (or test operation) position or switched from the remote control
position to the forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera-
tion condition is set according to the intake air temperature as follows.
24°C≤Intake Air Temp ➲ Cooling Mode Operation, 22°C, High Speed
21°C≤Intake Air Temp<24°C ➲ Dehumidification Operation, 23°C, High Speed
Intake Air Temp<21°C ➲ Heating Mode Operation, 24°C, High Speed

■ Remote Control Operation Mode


• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.

■ Protection of the evaporator pipe from frosting


• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C and higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.

■ Buzzer Sounding Operation


• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.

-22-
2. Cassette Type Indoor Unit
(1) The function of main control
■ Time Delay Safety Control
• 3 min... The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 5 sec... Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
• 5 sec... The 4-way valve is ceased for 5 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode when compress is off.
While compressor is running, it takes 3~5 seconds to switch.

■ Auto Swing Control


• This function is to swing the louver up and down automatically.

■ Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by Micom Control.

■ Cooling Mode Operation


• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote
controller and the operation diagram is as following

Intake Air temp.

COMP. ON
(SET TEMP.+0.5°C)

COMP. OFF
(SET TEMP. -0.5°C) More than More than
3 minutes 3 minutes

INDOOR FAN Selecting Low Selecting Low Selecting


fan speed fan speed fan speed

- 23 -
■ Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

Intake Air temp. minimum 3min


Setting temp.+3°C
(Compressor OFF)

A B A

Setting temp.
(Compressor ON)
1min minimum minimum minimum
10sec. 1min. 10sec.

INDOOR FAN Hot Start Low Selecting


Low OFF Low Selecting fan Low OFF
Fan Speed speed

• A point; While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when
it becomes lower than 40˚C fan stops.

• B point; When the indoor Heat-Exchanger temperature is higher than 31°C, fan operates at selected fan
speed, when it becomes lower than 31°C, the fan operates at low speed for 10sec, after 10sec, it
operates at selected fan speed.

■ Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 25°C.
The operation diagram is as following.

PIPING 1min
TEMPERATURE
25°C

22°C

INDOOR FAN OFF LOW Selected Fan

COMPRESSOR ON

- 24 -
■ Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to
cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrost control is available 45 min. later since heating mode operation started, and it will not prolong over 10 min.
• Defrost control is carried out according to the following priority order while in heating mode operation.
1st priority : Defrost control is carried out according to the indoor pipe temp 60 min. later since heating mode opera-
tion started.
2nd priority : The temp differences between the indoor pipe temp and the intake air temp 25 min. later(∆T1) and 45
min. later (∆T2) since heating mode operation started are measured, then defrost control is carried out
according to the dirrerence (∆T=∆T1-∆T2)
3rd priority : Defrost control is carried out according to the temp difference (E=TE1-TE2) between the indoor pipe
temperatures of 25 min later(TE1) and 45 min later (TE2) after heating mode operation started.
• When the indoor pipe temp is 41°C or above, defrost control is not carried out even if the condition is one of the
defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.

The outdoor More than 45 minutes Within More than 45 minutes


of heating operation 9min. 45sec. of heating operation
piping Temp.
More than 10 min.
running of compressor
12°C OFF

-6°C ON

HOT-
START

INDOOR FAN ON OFF ON

COMPRESSOR ON

4-WAY VALVE ON OFF ON

- 25 -
3. Convertible Type Indoor Unit
(1) The function of main control
■ Time Delay Safety Control
• 3min… The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 5sec… Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
• 30sec… The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.

■ Airflow Direction Control


• This function is to swing the louver up and down automatically and to set it at the desired position.
• The procedure is as the following.

1st ; Press the ON/OFF Button to operate the product.


2nd ; Press the Airflow Direction Control Button to swing the louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the louver as the desired position.

MODE 0
MODE1
135°
MODE 2
MODE 3 Cooling
MODE 4
MODE 5 MODE 9
MODE 6 (CLOSE)

MODE 7

For Heating Model


• Airflow direction control figure when installed on • Airflow direction control figure when installed
the floor. under the ceiling.
OPEN OPEN
MODE 1 MODE 1
MODE 2 12° 12°
MODE 2
Cooling Cooling
MODE 3 MODE 3
MODE 4 MODE 4 Heating
Heating
Heating
MODE 5 MODE 5
135° 135°
MODE 6 MODE 6
MODE 7 MODE 7
MODE 8 MODE 8
MODE 9 MODE 9
CLOSE CLOSE

OPEN
MODE 1
MODE 2 12°
Cooling
MODE 3
MODE 4
Heating
Heating
MODE 5
135°
MODE 6
MODE 7
MODE 8
MODE 9

CLOSE

- 26 -
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following

Intake Air temp.

COMP. ON
(SET TEMP.+0.5°C)

COMP. OFF
(SET TEMP. -0.5°C) More than More than
3 minutes 3 minutes
Selecting Selecting Selecting
INDOOR FAN Low Low
fan speed fan speed fan speed

COMPRESSOR ON OFF ON OFF ON

4. Cooling or Heating Mode with Sleep Mode Auto Operation


• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the
operation diagram is as following.
Cooling Mode with the Sleep Mode
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp. 30 minutes 30 minutes
1°C
COMP. ON
1°C
(SET TEMP.+0.5°C)

COMP. OFF
(SET TEMP. -0.5°C) More than More than
3 minutes 3 minutes

INDOOR FAN Low Low Low Low Low


COMPRESSOR ON OFF ON OFF ON

Heating Mode with the Sleep Mode.


• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

Setting Temp. +3°C


(Compressor OFF)

Setting Temp.
(Compressor ON)

Indoor Fan Low. Low. Low. Low. Low. Low.


Compressor ON OFF ON OFF ON OFF

- 27 -
5. Auto Operation
• The operation procedure is as following. (Cooling & Heating Model)

Press Start/Stop Button

Select Auto Operation Mode

Check the Room temperature

Operation mode
Indoor fan speed are automatically decided by Fuzzy rule.
Setting temperature

Intake-air Over below


below 21°C ~ Over 24°C
temperature 21°C 24°C

Operation Mode Heating Soft Dry Cooling

If initial mode is decided, that mode is continued without the room temperature changing.
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.

• Auto Operation for Cooling. (Cooling only Model)

Operation Condition Intake-air Temperature Setting temperature Fan speed Air Direction Control
Over 26°C 25°C
Over 24°C~below 26°C Intake air -1°C In this mode, when
When Auto Operation pressing the verti-
Over 22°C~below 24°C Intake air -0.5°C
initial start cal air diretion con-
Over 20°C~below 22°C intake air temperture Controlled trol.
below 20°C 20°C by Fuzzy logic Button, louvers
moves to 1/f
When pressing room temp- Over 20°C~below 30°C Fuzzy control rhythm (refer to
erature setting button below 20°C 20°C page 17)
during Auto Operation over 30°C 30°C

Intake-Air temp

Setting Temp. +0.5°C


(Compressor OFF)

Setting Temp.-0.5°C
(Compressor ON)

Indoor Fan Fuzzy Speed


Compressor ON OFF ON OFF

- 28 -
• Auto Operation for Soft Dry

The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C

• Auto Operation for Heating.

Intake Air temp. below 20°C over 20 ~below 21°C

Setting temp. 20°C Intake air temp. +0.5°C

- Compressor ON temperature; Setting temperature


- Compressor OFF temperature; Setting temperature +3°C

Setting temp.

21.5°C

20.5°C

20°C

20°C 21°C Intake-Air temp.

• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, lou-
ver moves as following cycle.

MODE0
Start
MODE1

MODE2

MODE3

MODE4

MODE5 End

MODE6 MODE9
(CLOSED)

- 29 -
6. Natural wind by CHAOS logic

For more fresh feeling than other fan speed mode, press
the indoor fan Speed Selector and set to CHAOS mode.
In this mode, the wind blows like natural breeze by auto-
matically changing fan speed according to the CHAOS
logic.

Intake Air temp. Setting CHAOS Natural wind

Cooling on temp.
(Setting temp.+0.5)
Setting temp.

Cooling off temp.


(Setting temp.-0.5)

INDOOR FAN

OUTDOOR FAN/COMP.

: Setting fan speed : CHAOS Natural wind : LOW : COMP ON : COMP OFF

GRAPH of Natural wind by the CHAOS logis (During Cooling operation)

Intake Air temp. Setting CHAOS Natural wind

Heating off temp.


(Setting temp.+3.0)

Heating on temp.
(Setting temp.) 30sec

INDOOR FAN LOW OR STOP

OUTDOOR FAN/COMP.

: Setting fan speed : CHAOS Natural wind : LOW : COMP ON : COMP OFF

GRAPH of Natural wind by the CHAOS logis (During Heating operation)

- 30 -
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.

• For Heating Model

Indoor piping temp.

28°C

26°C

Intake Air temp.

Setting temp. +3.0˚C


(Compressor OFF)

Setting temp.
(Compressor ON) minimum
30sec.
minimum minimum minimum minimum
1min. 3min. 3min. 1min.
COMPRESSOR ON OFF ON OFF ON

OUTDOOR FAN ON OFF ON OFF ON


Fan Low Selected Low Fan Selected Fan Low Fan Fan Stop Low Selected
INDOOR FAN Stops Fan Fan Fan Fan
4-WAY VALVE ON

8. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28 .
• During heating operation, if piping temperatures falls below 26°C fan stops.
• The operation diagram is as following.

PIPING 1min
TEMPERATURE
28°C
(22˚C)
26°C
(20˚C)

INDOOR FAN

COMPRESSOR ON

: Selected Fan : Low Fan : Fan Stop

- 31 -
9. Deice Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature.
• The first deicing starts only when the outdoor pipe temperature falls below -6°C after 45(30) minutes passed
from starting of heating operation.
• Deicing ends after 10(6) minutes passed from starting of deice operation or when the outdoor pipe temperature
rises over 12°C even if before 10(6) minutes.
• The second deicing starts only when the outdoor pipe temperture falls below -6°C after 45(30) minutes passed
from ending of the first deicing.

The outdoor More than 45(30) minutes Within More than 45(30) minutes
of heating operation 10(6) minutes of heating operation
piping Temp.
Deicing Deicing
12°C
DEICE OFF

-6°C
DEICE ON

HOT-
START

INDOOR FAN ON OFF ON OFF

COMPRESSOR ON ON ON ON

4-WAY VALVE ON OFF ON OFF

10. Soft Dry Operation


• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In micom dehumidify mode, control of fan speed is as following.

Intake Air temp.

Setting temp. +1.0˚C


(Compressor ON)

Setting temp.

Setting temp. -0.5˚C


(Compressor OFF)
Cooling 2min.58sec. 10min. 7min. 10min. Within 7min. Cooling 2min.58sec.

COMPRESSOR ON OFF ON OFF ON OFF ON OFF ON OFF


OUTDOOR FAN ON OFF ON OFF ON OFF ON OFF ON OFF
Selected Selected
INDOOR FAN Fan Low Fan Fan Low Fan

- 32 -
11. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
Heat pump Model
Cooling Model
Room Temp 24°C 21°C Room Temp 24°C Room Temp 21°C
Operation Mode Cooling Cooling Soft Dry Heating
FAN Speed High High Soft Dry Rule High
Setting Temp. 24°C 22°C Air Intake Temperature 24°C

• Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to
intake Air temperature.
Forced
Operation Button Press the Forced Operation Button.

•Press the Forced Operation Button once


again to stop operation.

12. Protection of the evaporator pipe from frosting


If the temperature of the indoor coil is below 0°C after 7 minutes from starting the compressor, the
compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor and
the temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoperated.
Indoor fan operates at low speed (comp. OFF) or at selected speed (comp. ON)
13. Inlet grille open
Once the inlet grille is opened during operation of the unit, the unit automatically stops operation and the
lamps will be turned-off. But memorized functions are still available.
When the inlet grille is closed again, the unit become waiting state for operation. From then, the unit can be
operated by forced operation button or Start/Stop button of remote controller.
14. Test Operation
• When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan
regardless of room temperature and resets in 18 min.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
15. Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance should be on the automatically operates in the mode
on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)

- 33 -
Display Function
Operation Indicator
• Cooling, Soft Dry, Fan, Heating
Sleep Timer Indicator
• Sleep Mode
Timer Indicator
• Timer Mode
Defrot Indicator
• Hot-start, Defrost

Self-diagnosis Function
■ Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.

Error Error LED


Code Error contents SVC check point
(Indoor body operation LED)
(once) • Indoor temperature thermistor open/short.
1 • Indoor pipe temperature thermistor • Indoor TH ass'y check
3sec 3sec 3sec open/short.
(twice) • Outdoor temperature thermistor
2 open/short. • Outdoor TH ass'y check
3sec 3sec
• Outdoor pipe temperature thermistor open/short.
(5times)
• Poor communication • Communication line/circuit
5
3sec

(8times)
• Main PCB CT check
8 3sec
• CT / Current error • Wiring and PWM cable check

(9times)
• Excessive amount of refrigerant
9 • DC Peak • Blocking condenser
3sec
(10times)
10 • DC low voltage • Outdoor wiring check
3sec
(11times)
• High pressure/Instantaneous power • Pressure check
11 failure • Main power check
3sec
(1times) (3times)
13 • Overload combination • Indoor unit combination check
3sec 3sec 3sec
(1times) (4times)
• Discharge pipe temperature • Refrigerant leakage
14 overheating • Check refrigeration cycle
3sec 3sec 3sec

-34-
Installation of Indoor, Outdoor Unit
1. Selection of the best location
(1) Indoor unit
1. Room Type Indoor Unit Front
• There should not be any heat source or steam near the
unit. Left
• There should not be any obstacles to prevent the air cir-
culation. Rear left

• A place where air circulation in the room will be good.


Down right
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into considera- Right Rear right
tion.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence, or other obstacles. More than 5 cm
More than
5 cm

More than
5 cm
More than eye-level

2. Cassette Type Indoor Unit


• There should not be any heat source or steam near the
unit.
• There should not be any obstacles to the air circulation.

30 or more
Ceiling
• A place where air circulation in the room will be good. Ceiling Board
Ceiling Board

• A place where drainage can be easily obtained.

30 or less
• A place where noise prevention is taken into consideration.
or more

50 or 50 or
• Do not install the unit near the door way. more more
330 or less
Above 250
100

• Ensure the spaces indicated by arrows from the wall, ceil-


ing, or other obstacles. Unit:cm
• The indoor unit must have the maintenance space around
Floor

3. Art Cool Type Indoor Unit


• Do not have any heat or steam near the unit.
More than 10cm
• Select a place where there are no obstacles in front of
the unit.
• Make sure that condensation drainage can be conve- More than 50cm
niently routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the
unit is more than 50cm. The unit should be installed as
high on the wall as possible, allowing a minimum of More than 50cm
10cm from ceiling.
• Use a stud finder to locate studs to prevent unneces- More than 2m
sary damage to the wall.

- 35 -
4. Convertible Type Indoor Unit
More than
• There should not be any heat source or steam near the 20cm
unit.
• There should not be any obstacles to prevent the air cir- More than
R

culation. 20cm
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into considera- More than eye-level
tion. (Ceiling installation)
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, More than
ceiling, or other obstacles. 20cm

R
More than
20cm

(Floor/Wall installation)

(2) Outdoor unit


• If an awning is built over the unit to prevent more than
direct sunlight or rain exposure, be careful that more than
10cm
heat radiation from the condenser is not restrict- 20cm
ed.
• There should not be any animals or plants which
could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence, or other obstacles. more than
70cm

(3) Piping length and the elevation


Pipe Size Max. piping Max. Indoor unit
length Elevation
GAS LIQUID A (m) B (m)
A

1/2"(3/8") 1/4" 15 5~7


B

Outdoor unit

- 36 -
2. Piping and Drainage of Indoor Unit
(1) Preparation of pipings
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes pur-
chased locally.
• Measure the distance between the indoor and Copper
tube 90° Slanted Uneven Rough
the outdoor unit.
• Cut the pipes a little longer than the measured
distance.
• Cut the cable 1.5m longer than the length of the
pipe.

2. Remove burrs.
• Remove burrs from cut edges of pipes.
Pipe
• Turn the pipe end toward down to avoid the
metal powder entering the pipe. Reamer

CAUTION
Point down

• If burrs are not removed, they may cause a gas leak-


age.

3. Flaring the pipes.


• Insert the flare nuts, mounted on the connection Handle
ports of both indoor and outdoor unit, onto the Bar Bar
copper pipes. Some refrigerant gas may leak, "A" Yoke
when the flare nuts are removed from the indoor
Cone
unit, as some gas is charged to prevent the
inside of the pipe from rusting.
Copper pipe
• Fit the copper pipe end into the Bar of flare tool
about 0.5~1.0mm higher. (See illustration) Clamp handle
Red arrow mark
• Flare the pipe ends.

Outside diameter A
mm inch mm
Smooth all round
ø6.35 1/4 0.5~0.8
Inside is shining without scratches
ø9.52 3/8 0.5~0.8
ø12.7 1/2 0.5~0.8
= Improper flaring =
ø15.88 5/8 0.8~1.0

4. Tape the flaring portion to protect it from the


dust or damages. Inclined Surface Cracked Uneven
damaged thickness
Even length
all round

- 37 -
Piping Connection

1. Form the piping according to its routing. Avoid


bending and bending back the same piping point
more than three times. (This will result in hard-
Liquid side
ening the pipe.)
2. After deforming the piping, align centers of the
Indoor
union fitting of the indoor unit and the piping, and
unit
tighten them firmly with wrenches.
Outdoor
3. Connect pipe to the service valve or ball valve unit Flare connection
which is located below the outdoor unit.
4. After completing the piping connection, be sure Gas side
to check if there is gas leakage in indoor and Flare connection

outdoor connection.

Vacuum drying

After completing the piping connection, execute


vacuum drying for the connecting piping and the
indoor unit.
The vacuum drying must be carried out using the
service ports of both the liquid and gas side valves.

CAUTION

Use two wrenches and tighten with regular torque.

Flare nut fastening torque


Ø6.35mm(1/4") 1.8kg.mm
Ø9.52mm(3/8") 4.0kg.mm Union
Ø12.7mm(1/2") 5.5kg.mm
Ø15.88mm(5/8") 6.6kg.mm

- 38 -
3. The Indoor Unit Installation
(1) Room Type Indoor Unit Installation Plate
The mounting wall should be strong and solid enough
to protect it from the vibration.

1. Mount the installation plate on the wall with four


Type "A" screws. marking-off line
Type "A" screw
(If mounting the unit on the concrete wall, consider Thread
using anchor bolts.)
• Always mount the Installation plate horizontally by Weight
aligning the marking-off line by means of the
thread and a level.
The lower left and the right side of
Installation Plate
2. Drill the piping hole with 70mm dia. holecore
drill.
• Line according to the arrows marked on lower the
left and the rght side of the Installation Plate. C
The meeting point of the extended line is the cen- Installation plate

B
ter of the hole.
• Drill the piping hole at either the right or the left and Ø70mm
A
Ø70mm

the hole should be slightly slant to the outdoor Left rear piping Right rear piping

side.

CHASSIS Distance (mm)


(Grade) A B C D Wall
SQ 75 12 80 12 Indoor Outdoor
SR 0 40 20 40
ST 105 0 210 0

5~7mm

- 39 -
1) Connection of Pipings
Installation plate
1. Remove the installation plate
• Pull the two '∆' marked portion of bottom of the
chassis and pull the installation plate out of chas-
sis. Pull

2. Route the drain hose and the indoor tubing. Pull

For left rear piping

3. Route the tubing and the drain hose straight


backwards(see figure).

4. Insert the connecting cable into the indoor


unit through the piping hole. Tubing holder
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy con- • To remove the holder, press
the bottom of the chassis near
nection later. the holder upwards and the
tab is clear of its hole.
• Trit clockwise approx. 90° and
remove it. • ➀ Press

5. Tape the tubing, drain hose and the connecting


cable. Be sure that drain hose locates at the
lowest side of the bundle.
Locating at the upper side can be a reason that
drain water overflows drain pan inside the unit.

Gas side piping


Connecting
cable Liquid side piping
Drain hose

- 40 -
6. Indoor unit installation.
• Hook the indoor unit onto the upper position of
the installation plate. (Engage the two hooks of
the rear top of the indoor unit with the upper
edge of the installation plate.) Connecting
Ensure the hooks are properly seated on the cable
installation plate by moving it in left and right.

Drain hose

Press the lower left and right side of the unit


against the Installation Plate until the hooks
engage with their slots (sound click).

7. Connecting the pipings to the indoor unit.


• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench
until the wrench clicks.
Wrench tightening the flare nut with forque
wrench, ensure the direction for tightening fol-
lows the arrows on the wrench. Indoor unit tubing Flare nut Pipings

Outside diameter A
mm inch mm
ø6.35 1/4 0.5~0.8
ø9.52 3/8 0.5~0.8 Spanner
Torque wrench
ø12.7 1/2 0.5~0.8
ø15.88 5/8 0.8~1.0

8. Wrap the insulation material around the con-


necting portion.

CAUTION Plastic bands


Insulation material
• Take care to arrange the pipings, drain hose and
cables as the right upper picture for inserting it into
the indoor unit and refixing the tubing holder easily.

Wrap the insulation material around the connecting


portion.

- 41 -
9. Set the pipings and the connecting cable to
the back of the chassis with the tubing
holder.
• Hook the edge of tubing holder to tap on chas-
sis and push the bottom of tubing holder to be
engaged in the bottom of chassis.

Drain hose
Taping
Piping
Tubing holder

1 Hook

2 Push

10. Indoor unit installation.


• Hook the indoor unit onto the upper portion of
installation plate. (Engage the two hooks of the
rear top of the indoor unit with the upper edge Connecting
of the installation plate.) cable
Ensure the hooks are properly seated on the
installation plate by moving it in left and right.

Drain hose

Press the lower left and right side of the unit


against the Installation Plate until the hooks
engages with their slots (sound click).

- 42 -
(2) Cassette Type Indoor Unit
1) Ceiling opening dimensions and hanging bolt location
• The dimensions of cardboard for installing are the
same as those of the ceiling opening dimensions. 600 (Ceiling opening)

39.5 521(Hanging bolt) 39.5

Ceiling

75
600 (Ceiling opening)
450 (Hanging bolt)
Level gauge
570 Unit size

570 Unit size


CAUTION

75
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, be careful not to damage Unit:mm
electric wires.

• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain
direction after considering the direction of drain hose. Ceiling board
• Drill the hole for anchor bolt on the wall.

NOTE:
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.

Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

- 43 -
Ceiling

Hanging bolt Keep the length of the bolt

150mm
(W3/8 or M10) from the bracket to 40mm
Nut
Flat washer for M10 Air Conditioner body
(W3/8 or M10)
(accessory) Ceiling board Ceiling board
Spring washer
(M10)

Flat washer for M10


(accessory) Cardboard Set screw of
Nut for installation cardboard (4 pieces)
(W3/8 or M10)

Adjust the same height Open the ceiling board


along the outer edge of the
paper model

• The following parts are local purchasing. • Drill the piping hole on the wall slightly tilted to the
Hanging Bolt - W 3/8 or M10 outdoor side using a Ø 70 hole-core drill.
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10 Wall
Indoor Outdoor
CAUTION
• Tighten the nut and bolt to prevent the unit from
falling off.

CAUTION 5~7mm
• Install certainly the cassette trim.
• Cool air leakage causes sweating. Water drops fall.

Good example Bad example


Air conditioner unit

Air conditioner Air Cool air leakage


unit
(no good)

Ceiling Ceiling
board board
Cassette trim Cassette trim
Fit the insulator (this part) and
be careful for cool air leakage

- 44 -
2) Installation of Decorative Panel

The decorative panel has its installation Before installing the decorative panel,
direction. always remove the paper template.

1. Temporarily fix two decorative panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount
10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decorative panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decorative panel key hole ( ) on the screws fixed in step above, and slide the panel so that
the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).

Air conditioner unit Piping side

Decorative panel fixing screws Control box cover


(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Inlet Grille
Louver motor

Decorative panel
Display
Key holes

Lead wire for


louver motor and
display

Decorative panel fixing screws


(Hexagon M5 screw)

Inlet Grille

- 45 -
(3) Art Cool Type Indoor Unit 2. Cover pipe and cover side remove
• Remove two screws(for fixing cover pipe)
1) Preparing work for Installation
• Pull up the cover side of desired connecting direc-
The wall you select should be strong and solid enough tion, then cover side is separated.
to prevent vibration • In case connecting direction is left or right, path
through the hole of cover side.
1. Open panel front
CAUTION
• First,Pull the grille bottom, then remove screws
(2 pieces), and close grille bottom again. After removing the pipe hole, cut the burr for safety.
• The moment of lifting the both lower parts of panel
front, you can hear sound this panel came out, In
this time panel front is separated
• After pull down this panel a bit, and separate con-
necting wire with product.

Pipe hole

NOTE: When connecting pipe path through rear


wall, don’t remove the hole.

3. Drain hose junction


• Remove the rubber stopple of desired drain direction.
• As the following picture, Insert drain hose in the han-
dle of drain pan, and join drain hose and connecting
hose.

Panel Front
Connector

Only one
Adhesive
desiring direction

Connecting
part
Drain
rubber cap
hose

-46-
2) Sticking the installation guide map and
fixing Indoor unit
1. Put an Installation Guide Map on the desired 7. Drill the piercing part for connecting pipe as
surface. diameter 50mm. (In case of piercing rear surface)
INSTALLATION GUIDE MAP

Refer to No. 5 on this page when making a hole in the wall.

2. Make a hole with diameter of 6mm and depth of 8. First, Drive the two points of the upper parts by
30-35mm when piercing a screw point. screws. (Leave 10mm for hanging product)
IN
ST
AII
AT
IO
N
GU
ID
EM
IN
AP

10
mm ST
AL
LA
TIO
N
3. Drive the fore plastic anchors into drilled points.
GU
IN
ST
AL
LA
TIO
N
9. Drive the lower parts after facing the hole of
GU
ID
EM product with plastic anchors, and fix completely
AP
the upper screws.

Plastic anchors
Plastic anchors

4. Hang the hole of product at the upper screws.


(In this time, Remove the map) In case of nothing wrong in the matter,
INS
(Falling attention) TAL
LAT
ION
GUID connect the pipe and the wire.
EM
AP (Installation manual reference)

Hanger hole
(Rear side of
product)

5. Check the fixed product with light power.


3) Preparing work for installation
1. Drill a hole in the wall
• Drill the piping hole with a ø50mm hole core drill.
Drill the piping hole at either the right or the left with
the hole slightly slanted to the outdoor side.

WALL
Indoor Outdoor
6. Look at suited horizon by horizontal meter on
the horizontal setting line, and Fix lightly the
map by adhesive tape. IN
ST
AL
LA
(0.2~0.3")

Horizontality TIO
N
5-7mm

GU
ID
EM
AP

-47-
4) Connection of piping Indoor • Tighten the flare nut with a wrench.
• Preparing the indoor unit's piping and drain hose for
installation through the wall. Open-end wrench (fixed)
1. Route the indoor tubing and the drain hose in the
direction of rear left or right.
Flare nut
Connection pipe
Wrench
2. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the Indoor unit tubing
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
• When extending the drain hose at the indoor unit,
install the drain pipe.

Drain pipe

Loop Indoor unit drain hose

Vinyl tape(narrow)
Adhesive
Gas side piping
Connecting
cable
4. Wrap the insulation material around the connecting
Liquid side piping portion.
Drain hose
• Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
NOTE: If the drain hose is routed inside the room,
together with vinyl tape so that there is no gap.
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
Plastic bands Insulation material
furniture or floors.
*Foamed polyethylene or equivalent is recommended.

3. Connecting the pipings to the indoor unit and drain


hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.

Indoor unit tubing Flare nut Pipes

-48-
• Wrap the area which accommodates the rear piping
housing section with vinyl tape.

Connection Indoor
pipe unit pipe

Vinyl tape Wrap with vinyl tape


(wide)

Connecting cable

Pipe

Vinyl tape(narrow)

• Bundle the piping and drain hose together by wrap-


ping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.

Wrap with vinyl tape

Pipe

Vinyl tape(wide)
Drain hose

-49-
5) Panel Front Assembly
1. First, Check the side cover assembly exactly, Fix
power cord in the bottom groove of cover side
left.

2. Assemble connecting lead wire with controller


and first fix the upper part of panel front, then
match the lower part of panel front

Panel Front
Connector

3. Drive two screws.

-50-
(4) Convertible Type Indoor Unit
■ Before Installing, prepare Installation Plates
• 'Installation Plates' are attached at the bottom of
indoor unit. Side Plate
Detach them by removing each 3 screws at both
R

sides.
• Detach 'Side Plate (R,L)' by removing each 2 screws
on both sides. Install Plate
• Pull the upper right and left side of 'Inlet Grille' to the
front, and it will stop at slightly tilted position.
• Unhook the 'Inlet hanger' from the 'Hanger screw' on
the both left and right side.
• Detach the 'Inlet Grille' from the Indoor Unit.

Inlet hanger
1) Installation on the ceiling
• Measure and mark the position for the R

Suspension bolts and the piping hole.


• Drill the hole for anchor nut on the ceiling.
Hanger
Inlet Grille screw

1) 1076 265

Before secure the Installation Plates, select the bent


Suspension
direction of the Installion Plate to the inside or the bolt
outside according to the installation circumstances. Center-line for the
piping hole

2) 1236 265

• Drill the piping hole on the wall slightly tilted to the


outdoor side using a ø70 hole-core drill.

Indoor WALL Outdoor

5~7mm

–51–
• Insert the nuts and washer onto the suspension bolts 1)
Anchor nut

for locking the suspension bolts on the ceiling. Ceiling


• Mount the suspension bolts to the anchor-nuts firmly.
• Secure the Installation plates onto the Suspension Nut Washer

bolts (adjust level roughly.) using nuts, washers and Suspension


bolts
spring washers.

Suspension
bolts

Spring
washer Nut

max.
12mm Washer

2)

• Engage 2 hooks on the both left and right side


of the unit to the lower slot of Installation Plates.
• Adjust a level with a level gauge on the direction Lower slot
of left-right, back-forth by adjusting suspension Level gauge
bolts.
• Move the hooks on the unit to the upper slot of R

Installation Plates. Then the unit will be declined


to the bottomside so as to drain well.

Suspension Adjust a level


bolt

Installation plate

Upper slot

–52–
CAUTION

1. Install declination of the indoor unit is very important for the drain of the convertible type air
conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 7mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined
to the bottomside.

Front of view

• The unit must be horizontal or declined to the drain hose connected when finished installation.
Ceiling

Drain hose

Ceiling

Side of view

• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling

–53–
• Secure the unit to the Installation Plates with four M8
bolts and washers.

• Before working, refer to "Connecting pipe


and cable to Indoor Unit" on page 59.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw. Inlet hanger

Hook
Cabinet Bottom

• Fit the projection hooks of the side plates to the 'Side


Panel' and the 'Front Panel' by lifting it.
• Fasten the screws.

R
2

–54–
2) Installation on the Wall
• Select and mark the position for fixing bolts and piping
hole. 1076
Decide the position for fixing bolts slightly tilted to the mor
drain direction after considering the direction of drain e th
260 an
hose.
• Drill the hole for anchor nut on the wall.

265

• Drill the piping hole on the wall slightly tilted to the out-
door side using a ø70 hole-core drill.
Wall
Indoor Outdoor

5~7mm
• Secure the 'Install Plate' onto the wall with four anchor
bolts, washers and spring washers.
Spring
washer Wall

Nut

Washer
Anchor nut

Less than
12mm

Before secure the Install Plates, select the bent direc-


tion of the 'Install Plate' to the inside or outside accord-
ing to the installation circumstances. 123
6

–55–
Install the Indoor unit onto Installation Plate.
• Insert 2 hooks on the both left and right side of the unit
to the inner slot (wall side) of the Installation Plate. Inner slot

• Secure the unit to the Installation Plate with four M8


bolts and washers. R

• Before working, refer to "Connecting pipe


and cable to Indoor Unit" on page 55.
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.

• Fit the projection hooks of the side plates to the 'Side


Panel' and the 'Front Panel' by lifting it.
• Fasten the screws.

–56–
3) Installation on the floor
Installation of Mount Bracket. From the left wall
• Select and mark the position for Mount Brackets and more than 760mm
the piping hole.
• Drill the hole for the anchor nut on the wall.
• Drill the piping hole using a ø70 hole-core drill. From the
right wall
• Secure the Mount Brackets on the wall with four M4 more than 840mm
screws.

Install the indoor unit onto the Mount Brackets.


• Engage the slot at the back of the unit with Mount
Bracket.
Slot

448mm
Floor mount
bracket

• Drill the piping hole with 70mm dia, hole core drill.
• Piping hole should be slightly slant to the outdoor side.
Wall
Indoor Outdoor

5~7mm
After Installing, reassemble detached parts.
• Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the
Hanger Screw.
• Assemble the 'Side Plates(R,L)' with 2 screws on both Slot
left and right side. Wall

Floor mount
bracket
Install plate

Piping hole

–57–
4) Connecting the pipes to the indoor unit
(Installation on the ceiling)
The pipe can be connected to right side, bottom
R

or back of the unit. 2


1
1. For the Right Side Piping
• After bending an end of the connecting tube, align the
center of the pipings and sufficiently tighten the flare
nut with fingers. Hose
• Finally, tighten the flare nut with torque wrench until Bracket
the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet. 3
Drain hose should be go through under the Hose
Bracket as shown in figure .
• Hang the drain hose on the hose hanger and fix it to R

the hole of the hose bracket with a screw.


4

Piping
5

Drain Hose
2. For the Bottom Side Piping Hose Hanger
• Remove the knock-out on the bottomside of Inlet Grille
• Align the center of the pipings and sufficiently tighten
the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until
the wrench clicks. R

• Connect the Drain Hose insulated to the drain outlet.


• Hang the drain hose on the hose hanger and fix it to
the hole of cabinet bottom with a screw. Hose
Hanger

5) Connecting the Drain Hose


• The drain hose can be connected to not only the
right side but also left side of the unit.
• If the drain hose is connected to the left side, it
should go through the cabinet bottom.
• Hang the drain hose on the hose hanger and fix it to
the hole of cabinet bottom with a screw.

BOTTOM
Hose Hanger
Drain Hose

–58–
6) Connecting the pipes to the indoor unit
(Installation on the wall or floor)
1. For the Right Rear Piping
• Remove the knock-out at the back side of the cabinet.
• After bending an end of the connecting tube, align the Piping
center of the pipings and sufficiently tighten the flare
nut with fingers.
Taping
• Finally, tighten the flare nut with torque wrench until
the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet. Drain Hose
• Tape the Drain Hose to the pipings to avoid coming
off the drain-outlet.

2. For the Right Side Piping


• After bending an end of the connecting tube, align the
center of the pipings and sufficiently tighten the flare
nut with fingers. Piping
• Finally, tighten the flare nut with torque wrench until
the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
• Tape the Drain Hose to the pipings to avoid coming Taping
off the drain-outlet.
Drain Hose

3. For the Right Bottom Piping


• Align the center of the pipings and sufficiently tighten
the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until
Piping
the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
Taping

Drain Hose
Connecting
Cable

7) Connecting the Drain Hose


• The drain hose can be connected to not only right
side but also left side of the unit.

REAR

Drain Hose
BOTTOM

–59–
(5) Connecting Pipings and the cable to Outdoor unit
1) Connecting the pipings to the Outdoor unit
1. When piping installation work you must be used the 2. Align the center of the pipings and sufficiently tight-
connector. en the flare nut by hand
Indoor Units Gas Liquid
A B A B
12K
18K Ø9.52→Ø12.7 Not necessary
24K

Connector

3. Finally, tighten the flare nut with torque wrench until


A B the wrench clicks.
■ When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
*Connecting pipe size Outdoor unit Liquid side piping
Connector C-UNIT
Indoor Units Gas side Liquid side
7K Ø9.52(3/8) Ø6.35(1/4) B-UNIT
9K Ø9.52(3/8) Ø6.35(1/4)
12K Ø12.7(1/2) Ø6.35(1/4) A-UNIT
18K Ø12.7(1/2) Ø6.35(1/4)
24K Ø12.7(1/2) Ø6.35(1/4)
Torque
wrench Gas side piping

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be
guided by the circuit diagram pasted on the inside of control box cover.
2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have
an air gap contact separation of at least 3mm in each active(phase) conductors.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal
function of a overload protection device.
• Proper starting power is not given to the compressor.

- 60 -
2) Connection of the cable
1. Room Type Indoor Unit 3. Cassette Type Indoor Unit
• Remove the cover control from the unit by loos- • Open the control box cover and connect the Indoor
ening the screw. power wires.
Connect the wires to the terminals on the control
board individually.
• Secure the cable onto the control board with the
holder (clamper).
• Refix the cover control to the original position with
the screw.
• Use a recongnized circuit breaker between the
power source and the unit. A disconnection
device to adequately disconnect all supply lines
must be fitted. Indoor
power cord
Control
box cover

Control box cover


fitting screw(2 units)

[Air inlet side view]

2. Art Cool Type Indoor Unit


• Connect the cable to the indoor unit by connect-
ing the wires to the terminals on the control
board in dividually according to the outdoor unit
connection.
The earth wire should be longer than the common
wires.

• When installing, refer to the circuit diagram on the


Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.

- 61 -
4) Convertible Type Indoor Unit
R

1) Remove the Air guide - L by loosening 2


screws after removing the Inlet grille from the
Indoor unit.
2) Connect the wires to the terminals on the con-
trol board individually according to the outdoor AIR GUIDE-L
unit connection.
• Ensure that the color of the wires of outdoor
unit and the terminal No. are the same as
those of indoor unit respectively INDOOR UNIT

Clamp 1

Control
Panel

CAUTION
The power cord connected to the outdoor unit should be complied The connecting cable connected to the indoor and outdoor unit should
with the following specifications (Rubber insulation, type H05RN-F be complied with the following specifications (Rubber insulation,
approved by HAR or SAA). type H05RN-F approved by HAR or SAA).

NORMAL NORMAL
CROSS-SECTIONAL CROSS-SECTIONAL
GN GN
/YL AREA 3.5mm2 /YL AREA 0.75mm2
8.5mm

7.5mm

20 20
mm mm

If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its
service agent.

WARNING
Make sure that the screws of the terminal are free from looseness.

- 62 -
3) Electrical Wiring
1. Remove the cover control from the unit by loosen- Outdoor unit
ing the screw. Terminal block
Connect the wires to the terminals on the control
board individually as the following. Over 5mm
Holder for
Terminal on the OUTDOOR UNIT OUTDOOR UNIT power supply
3 1(L) 2(N) 3 3 1(L) 2(N) 3 1(L) 2(N) cord
Power cord
Cover control

Connecting
cable
1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3
Power cord
Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT
D-UNIT C-UNIT B-UNIT A-UNIT

Terminal on the OUTDOOR UNIT OUTDOOR UNIT


3 1(L) 2(N) 3 3 1(L) 2(N) 3 1(L) 2(N)
2. Secure the cable onto the control board with the
Power cord holder (clamper).
3. Refix the cover control to the original position with
the screw.
1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3 4. Use a recongnized circuit breaker between the
Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT power source and the unit. A disconnection device
C-UNIT B-UNIT A-UNIT
to adequately disconnect all supply lines must be
Terminal on the OUTDOOR UNIT OUTDOOR UNIT fitted.
3 1(L) 2(N) 3 3 1(L) 2(N) 3 1(L) 2(N)

Power cord

1(L) 2(N) 3 1(L) 2(N) 3

Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT


B-UNIT A-UNIT

CAUTION
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Main power source Main power source

Air Air
Conditioner Circuit Breaker Conditioner Circuit Breaker
Use a 20A circuit Use a 25A circuit
breaker or time breaker or time
delay fuse. delay fuse.
(21K) (30K)

CAUTION
The power cord connected to the outdoor unit The connecting cable connected to the indoor
should be complied with the following specifica- and outdoor unit should be complied with the
tions (Rubber insulation, type H05RN-F following specifications (Rubber insulation, type
approved by HAR or SAA). H07RN-F approved by HAR or SAA).
ø8.5mm

ø7.5mm

NORMAL CROSS- NORMAL CROSS-


SECTIONAL AREA SECTIONAL AREA
GN
/YL 3.5mm2 GN
/YL 0.75mm2

20 20
mm mm

- 63 -
4. Remote Controller Installationa

HOW TO MOUNT ONTO A WALL

HOW TO INSERT BATTERIES

Remove the battery cover from the remote controller.


• Slide the cover according to the arrow direction.
• Do not use rechargeable batteries, such batter-
ies differ from standard dry cells in shape,
dimensions, and performance.
Insert the two batteries.
• Be sure that the (+) and (-) directions are correct. • Romove the batteries from the remote con-
• Be sure that both batteries are new. troller if the air conditioner is not going to be
used for some long time.

Re-attach the cover.


• Slide it back into position.

- 64 -
5. Checking the Drainage and Pipe forming
(1) Checking the Drainage
1) Room Type Indoor Unit
1. Remove the Grille from the cabinet
• Set the up-and-down air direction louver to
open position(horizontally) by finger pressure.
• Remove the securing screws. Screw
• To remove the Grille, pull lower the left and
Pull the right and
right side of the grille toward you (slightly tilted)
the left side.
and lift it straight upward.

2. Check the drainage


• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor unit
without any leakage.

2) Cassette Type Indoor Unit


• Drain piping must have down-slope (1/50 to 1/100):
be sure not to provide up-and-down slope to prevent
Upward
reversal flow. Pipe clamp
routing
• During drain piping connection, be careful not to exert not allowed
extra force on the drain port on the indoor unit. Indoor unit
• The outside diameter of the drain connection on the
indoor unit is 32mm.
Piping material: Polyvinyl chloride pipe VP-25 Maintenance
and pipe fittings drain port

• Be sure to execute heat insulation on the drain piping.


Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Drain Test Feed water Flexible drain hose
The air conditioner uses a drain pump to drain water. (accessory)
Use the following procedure to test the drain pump Main
operation: drain pipe
• Connect the main drain pipe to the exterior and leave
it provisionally until the test comes to an end. Drain
Drain Pump port Glue the joint
• Feed water to the flexible drain hose and check the
piping for leakage. Drain hose connection
Use the clip (accessory)
• Be sure to check the drain pump for normal operating
and noise when electrical wiring is complete.
• When the test is complete, connect the flexible drain
hose to the drain port on the indoor unit. Drain pan

- 65 -
3) Art Cool Type Indoor Unit
• Pour a glass of water on the evaporator.
• Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out
the drain exit.

4) Convertible Type Indoor Unit


1. Remove the Air Filter.
• To remove air filter, take hold of tab and pull
slightly upwards.

2. Check the drainage.


• Spray one or two glasses of water upon the
evaporator.
• Ensure that water flows drain hose of indoor
unit without any leakage.

- 66 -
(2) Form the pipings
1. Wrap the connecting portion of indoor unit
with the Insulation material and secure it with
two Plastic Bands(for the left pipings).
• If you want to connect an additional drain hose, Taping
the end of the drain-outlet should keep distance
from the ground.(Do not dip it into water, and fix Drain hose
it on the wall to avoid swinging in the wind.)

In case of the Outdoor unit is installed bellow


position of the Indoor unit. Plastic Pipings
band Connecting
cable
2. Tape the Pipings, drain hose and Connecting
Cable from down to up.

Power supply
3. Form the pipings gathered by taping along the cord
exterior wall and fix it onto the wall by saddle
or equivalent.

• Trap is required to prevent water from entering


into electrical parts.

In case of the Outdoor unit is installed upper


position of the Indoor unit.
Seal a small opening
around the pipings
1. Tape the Pipings and Connectiong cable from with gum type sealer.
down to up. Trap

2. Form the pipings gathered by taping along the


exterior wall and the Trap to be required to
prevent the room from entering the water.

3. Fix the pipings onto the wall by saddle or


equivalent.

- 67 -
(3) Heat Insulation
1. Use the heat insulation material for the refriger-
ant piping which has an excellent heat-resis- Fastening band
tance (over 120°C). (accessory)

2. Precautions in high humidity circumstance:


This air conditioner has been tested according
to the "KS Standard Conditions with Mist" and
Refrigerant piping
confirmed that there is not any default.
However, if it is operated for a long time in high Indoor unit
humid atmosphere (dew point temperature:
Thermal insulator
more than 23°C), water drops are liable to fall. (accessory)
In this case, add heat insulation material
according to the following procedure:
• Heat insulation material to be prepared...
Adiabatic glass wool with thickness 10 to
20mm.
• Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
• In addition to the normal heat insulation
(thickness: more than 8mm) for refrigerant
piping (gas piping: thick piping) and drain pip-
ing, add further 10mm to 30mm thickness
material.

- 68 -
(4) Air Purging of the Pipings and indoor unit

The air which contains moisture remaining in the is refrigeration cycle may cause a malfunction on the
compressor.

1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port
by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below-76cmHg.
5. Disconnect the charge hose and fit the nut to the service port.
(Tightening torque: 1.8kg.m)
6. Remove the valve stem nuts, and fully open the stems of the Liquid and Gas side service valves with a
hexagon wrench.
7. Tighten the valve stem nuts of the Liquid and Gas side service valve.

Indoor unit Liquid side

Outdoor unit

3-way
valve

Gas side
Closed

3-way
valve

Vacuum pump
Closed
OPEN OPEN

- 69 -
(5) Maximum Length of Pipe and Freon Extra Charge

Charge amount per 1m

Capacity STANDARD CONNECTION TYPE Charge am't(g)


(Btu/h) LENGTH(m) A B C D per 1m

~7000 7.5 7 15 7 15 20
~9000 7.5 7 15 7 15 20
~12000 7.5 7 15 7 15 20
~24000 7.5 7 15 7 15 30

B(Length)
INDOOR UNIT
A(Height)
OUTDOOR UNIT
C(Height)
INDOOR UNIT
D(Length)

** A, B mean indoor unit higher located than outdoor unit.


C, D mean outdoor unit higher located than indoor unit.

- 70 -
6. Test Running
1. Check that all tubing and wiring have been properly
connected. Bolt
2. Check that the gas and liquid side service valves are
fully open.
(1) Prepare remote controller
Remove the battery cover by pulling it according to
the arrow direction.
Insert new batteries making sure that the (+) and Tubing connection
(–) of battery are installed correctly.
Reattach the cover by pushing it back into position. (4) Evaluation of the performance
1. Measure the temperature of the intake and discharge
air.
2. Ensure the difference between the intake temperature
and the discharge one is more than 8°C.
3. For reference; the gas side pressure of optimum condi-
tion is as below.(Cooling)

Intake temperature
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable Discharge air
batteries.
• Remove the batteries from the remote controller if the
system is not going to be used for a long time.
(2) Precautions in test run Discharge
■ The initial power supply must provide at least 90% temperature
of the rated voltage.
Otherwise, the air conditioner should not be operat-
ed.
■ For test run, carry out the cooling operation firstly
even during heating season. If heating operation is
carried out firstly, it leads to the trouble of compres-
sor. Then attention must be paid.
■ Carry out the test run more than 5 minutes without Thermometer
fail. (Test run will be cancelled 18 minutes later
Intake temperature
automatically)
Discharge air
■ The forced operation is started by pressing button
for 2 seconds. (Cassette Type)
The test run is started by pressing button for 5 sec-
onds. (Cassette Type)
The test run is started by pressing timer cancel but-
ton five times continuously. (Room type)
■ To cancel the test run, press any button.
Discharge
(3) Settlement of outdoor unit temperature

■ Anchor the outdoor unit with a bolt and nut(ø10mm)


tightly and horizontally on a concrete or rigid mount.
■ When installing on the wall, roof or rooftop, anchor the
R
mounting base securely with a nail or wire assuming
the influence of wind and earthquake.
■ In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber. Thermometer

- 71 -
CAUTION

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out
of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to
the normal function of a overload protection device.
• Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning,
temperature control, etc.).

- 72 -
Operation
■ Room type Indoor Unit
1. Name and Function-Remote Controller(Door Closed)
The remote control transmits the signals to the system.

Remote Control 1 START/STOP BUTTON


Operation starts when this button is pressed and stops
when the button is pressed again.
Signal transmitter
2 OPERATION MODE SELECTION BUTTON
Used to select the operation mode.

3 ROOM TEMPERATURE SETTING BUTTONS


Used to select the room temperature.

4 INDOOR FAN SPEED SELECTOR


Used to select fan speed in four steps low, medium, high
and CHAOS.

5 JET COOL
5 1 Used to start or stop the speed cooling. (Speed cooling
6 operates super high fan speed in cooling mode.)
CHAOS SWING BUTTON
3 6
Used to stop or start louver movement and set the desired
4 up/down airflow direction.
2 10 ON/OFF TIMER BUTTONS
CANCEL 7 Used to set the time of starting and stopping operation.
7 9
ON OFF SET

11 TIME SETTING BUTTONS


12 8
8 Used to adjust the time.
13 14 TIMER SET/CANCEL BUTTON
9
15 16 Used to set the timer when the desired time is obtained
and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
10
Used to set Sleep Mode Auto operation.

Flip-up door 11 AIR CIRCULATION BUTTON


(opened) Used to circulate the room air without cooling or heating.
ROOM TEMPERATURE CHECKING BUTTON
Operation Mode 12
Used to check the room temperature.

Cooling Operation 13 PLASMA(OPTIONAL)


Used to start or stop the plasma-purification function.
Auto Operation 14 HORIZONTAL AIRFLOW DIRECTION CONTROL
BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction.
Healthy Dehumidification Operation
15 RESET BUTTON
Used prior to resetting time or after replacing batteries.
Heating Operation
16 2nd F Button
Used prior to using modes printed in blue at the bottom of
buttons.

-73-
■ Cassette/Art Cool Type Indoor Unit
1. Name and funcition-Remote Controller (Door Closed)

Room type
(Chaos)
1. START/STOP BUTTON
Operation starts when this button is pressed and
stops when the button is pressed again.
Cassette type
(Auto)
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.

3. ROOM TEMPERATURE SETTING BUTTONS


5 6 Used to select the room temperature.

4 1 4. INDOOR FAN SPEED SETTING


BUTTONS
3 Used to select fan speed in four steps
low, medium, high, or chaos/auto.

Flip-up door 5. JET COOL


(closed) Used to start or stop the speed cooling. (Speed
2 cooling operates super high fan speed in cooling
mode.)

6. CHAOS/AUTO SWING BUTTON


Used to stop or start louver movement and
set the desired up/down airflow direction.

- 74 -
2. Name and Function-Remote Control (Door Opened)

Signal transmitter 1. ON/OFF TIMER BUTTONS


Used to set the time of starting and stopping opera-
tion.

2. TIME SETTING BUTTONS


Used to adjust the time.

3. TIMER SET/CANCEL BUTTONS


Used to set the timer when the desired time is
obtained and to cancel the Timer operation.

4. SLEEP MODE AUTO BUTTON


Used to set Sleep Mode Auto operation.

ON OFF
4 5. AIR CIRCULATION BUTTON
1
Used to circulate the room air without cooling or
2 5 heating (turns indoor fan on/off).
SET CANCEL
3 6
7 6. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.

7. RESET BUTTON
Used prior to resetting time or after replacing
batteries.

- 75 -
■ Convertible Type Indoor Unit
1. Name and funcition-Remote Controller (Door Opened)

OPERATION DISPLAY
1 Displays the operation conditions.

START/STOP BUTTON
2 Operation starts when this button is pressed and stops
when the button is pressed again.

OPERATION MODE SELECTION BUTTON


1 3 Used to select the operation mode.

ON/OFF TIMER BUTTONS


4 Used to set the time of starting and stopping operation.

5 TIME SETTING BUTTONS


Used to adjust the time.
3 7
TIMER SET/CANCEL BUTTONS
2 6 Used to set the timer when the desired time is obtained
and to cancel the Timer operation.

ON OFF AIR FLOW DIRECTION START/STOP BUTTON


4 8 7 Used to stop or start louver movement and set the
desired up/down airflow direction.
5 9
SET CANCEL
SLEEP MODE AUTO BUTTON
6 10 8 Used to set Sleep Mode Auto operation.
11
AIR CIRCULATION BUTTON
9 Used to circulate the room air without cooling or heat-
ing (turns indoor fan on/off).

ROOM TEMPERATURE CHECKING BUTTON


10 Used to check the room temperature.

RESET BUTTON
11 Used prior to resetting time or after replacing batteries.

- 76 -
Disassembly of the parts (Indoor unit)
(1) Room Type Indoor Unit
Warning :
Disconnect the unit from power supply before mak-
ing any checks.
Be sure the power switch is set to “OFF”.

To remove the Grille from the Chassis.


• Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift
it straight upward.

1. Before removing the control box, be sure to


take out the wire screwed at the other end. Display
P.C.B
Conductor

Sensor
Conductor

Motor
Conductor

Step Motor
Conductor
Earth
Conductor

- 77 -
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis care-
fully.

3. To remove the Discharge Grille.


• Unhook the discharge grille and pull the dis-
charge grille out from the chassis carefully.

4. To remove the Evaporator.


• Remove 3 screws securing the evaporator(at
the left 2EA in the Eva Holder, at the right
1EA).

- 78 -
• Unhook the tab on the right inside of the chas-
sis at the same time, slightly pull the evapora-
tor toward you until the tab is clear of the slot.

5. To remove the Motor Cover


• Remove 2 securing screw.
• Pull the motor cover out from the chassis
carefully.

Motor cover

6. To remove the Cross-Flow Fan


• Loosen the screw securing the cross-flow fan
to the fan motor (do not remove).
• Lift up the right side of the cross-flow fan and
the fan motor, separate the fan motor from the
cross-flow fan.

• Remove the left end of the cross-flow fan from


the self-aligning bearing.

- 79 -
(2) Art Cool Type Indoor Unit
Warning :
Disconnect the unit from power supply before making
any checks.
Be sure the power switch is set to “OFF”.

1. To remove the Grille from the Chassis.


- Pull the grille bottom, the remove 2 securing
screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting
wire with product.

Panel Front
Connector

2. To remove the Control Box.


- Before removing the control box, be sure to
disconnect the wires from PWB.
Step Motor Connectors
- Pull the cover control out from the control box Sensor Connector
and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.

- 80 -
3. To remove the Evaporator.
- Remove 4 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.

4. Before removing the Turbo Fan.


- Remove the securing screws from the chassis. Top Cover Air Guide
- Pull the pipe cover, top cover and the air guide.

Pipe Cover

5. To remove the Motor.


- Remove the securing bolt from the motor shaft. Bracket
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the Turbo Fan
chassis and lift up the motor mount and the brack-
et.

Bolt Motor Mount

- 81 -
(3) Convertible Type Indoor Unit
Warning :
Disconnect the unit from power supply before mak-
ing any checks.
Be sure the power switch is set to “OFF”.

1. Remove the air filter.


• Pull the inlet grille slightly toward you.
R

• Pull out the air filter. (2 pieces)

Inlet Grille

2. Remove the girlle from chassis


• Remove the screws securing the side plate and
push to the bottom-side.
• Unhook the hanger from the hanger screw at
the left and the right side.
• Pick out the inlet grille.
R

4 3

Hanger

Hanger
Screw 2

3. Remove the lower air guide


• Remove a screw of both side fixing "barrier air-
guide".
• Remove the screws of both sides of the lower
air-guide.
• Remove the lower air-guide toward “arrow
mark” by turning upwards as shown in figure. R

Barrier Air guide

Lower Air guide

- 82 -
4. Remove air guide upper, crossflow fan and
motor.
• Remove the screws of both sides and center
securing the upper air-guide.
• Remove 2 screws fastening the bracket of door
switch. Door
Switch
R

• Remove a bearing assembly by removing a


screw and the bearing cover.
• Remove 4 screws securing the motor cover.
• Loosen the screw securing the crossflow fan to
the fan motor shaft. (do not remove)
• Remove the crossflow fan by sliding it out from Bearing Bearing
Cover
the shaft of fan motor.
Motor R

Cover

5. Remove the control box Assembly.


• Disconnect the step motor connector, fan motor
connector, display PCB connector, thermistor
connector and door switch connector from the
main PCB.
• If necessary, disconnect power supply cord and
connecting cable from the terminal block and R

remove the cord clamp screw.


• Remove 2 screws securing the control box and
pick out the control box carefully.

- 83 -
6. Remove the front panel.
• Remove the screws of both sides fixing the Diffuser frame
front panel. Diffuser
frame
• Push the upper side of front panel strongly to
pull out the front panel from the inner hook of Hook
diffuser frame. Front
• Pull down the front panel carefully not so as to Panel
Front
harm the display PCB wires and thermistor Panel
wires. R

7. Remove the diffuser assembly.


• Remove the screws of both side of diffuser
assembly. (4 pieces) Diffuser
• Push the upper side of cabinet strongly to pull frame
out the inner hook of diffuser frame from the Hook
cabinet hole. Cabinet
• Take up the diffuser frame carefully not so as to
harm the display PCB wires and the step motor
wires.

8. Remove display PCB assembly.


• Remove the screws at the both side of display
cover.
• If necessary, disconnect the display PCB con-
nector from PCB assembly.
• Remove 2 screws of PCB assembly.
Display Cover

- 84 -
9. Remove the vane-upper, vane-lower and step
motor.
Step Motor
• Remove 2 screws securing the step motor
assembly and pull it out from the vanes careful- Vane Supporter
ly.
• Unhook the vanes from the vane supporter and
remove the upper vane and lower vane by
pulling the center of vanes with care.

Lower Vane Upper Vane

10. Remove the drain pan assembly.


• Remove the both side of screws. (4 pieces)
• Pull out the drain pan assembly.
• Be careful not to harm to the EPS packing of
drain pan and the tubings of evaporator.

EVA. Barrier-L
11. Remove the evaporator.
• Remove the screws of both sides securing the
EVA barrier-R/L on the side cabinet.
• Remove the screws which fasten the barrier on
the evaporator and take out the barrier assem-
bly.
• Remove the evaporator assembly by sliding
toward arrow mark. (As shown in figure) Side Cabinet

EVA. Barrier-R

- 85 -
Valve Service (3-way)

3-way Valve (Liguid Side) 3-way Valve (Gas Side)

Valve cap Valve cap

Open position Open position


Closed position Closed position

Pin Pin

To piping To piping
Service Service connection Service Service
connection port cap port
port cap port
To outdoor unit To outdoor unit

Works Shaft position Service port Shaft position Service port

Shipping Closed Closed Closed Closed


(with valve cap) (with cap) (with valve cap) (with cap)

Air purging Open Open Closed Open


1. (Installation) (counter-clockwise) (push-pin or with (clockwise) (push-pin or with
vacuum pump) vacuum pump)

Operation Open Closed Open Closed


(with valve cap) (with cap) (with valve cap) (with cap)

Pumping down Closed Closed Open Open


2.
(Transfering) (clockwise) (with cap) (counter-clockwise) (connected
manifold gauge)

Evacuation Open Open Open Open


3. (Servicing) (connected (connected
manifold gauge) manifold gauge)

Gas charging Open Closed Open Open


4. (Servicing) (with cap) (with charging
cylinder)

Pressure check Open Open Open Open


5. (Servicing) (connected (connected
manifold gauge) manifold gauge)

Gas releasing Open Open Open Open


6. (Servicing) (connected (connected
manifold gauge) manifold gauge)

- 86 -
(1) Pumping down

Indoor unit Liquid side

Outdoor unit

3-way
valve

Gas side
Closed

3-way
manifold gauge valve

Open
Low-handle Hi- handle
(CLOSE) (CLOSE)

• Procedure
1. Confirm that both the gas side and liquid side 6. Operate the air conditioner at the cooling cycle
valves are set to the open position. and stop it when the gauge indicates 1kg/cm g.
2

- Remove the valve stem caps and confirm that 7. Immediately set the gas side valve to the closed
the valve stems are in the raised position. position.
- Be sure to use a hexagonal wrench to operate - Do this quickly so that the gauge ends up indi-
the valve stems. cating 1kg/ g.
2. Operate the unit for 10 to 15 minutes. 8. Disconnect the charge set, and mount the liquid
side and gas side valve caps and the service
3. Stop operation and wait for 3 minutes, then con-
port nut.
nect the manifold gauge to the service port of
- Use torque wrench to tighten the service port
the gas side valve.
nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Connect the hose of the gauge with the push
pin to the service port. - Be sure to check for gas leakage.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge
slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.

- 87 -
(2) Evacuation
(All amount of refrigerant leaked)

Indoor unit Liquid side

Outdoor unit

3-way
valve

Gas side Open

3-way
manifold gauge valve

Vacuum pump
Low- Open
handle Hi- handle
(OPEN) (OPEN)

• Procedure
1. Confirm that both the liguid side valve and gas 6. Disconnect the charge hose from the vacuum
side valve are set to the opened position. pump.
2. Connect the vaccum pump to the center hose of - Vacuum pump oil.
the manifold gauge. If the vacuum pump oil becomes dirty or deplet-
3. Connect the service port of the gas side valve to ed,replenish as needed.
the low side of the gauge. 7. Mount the valve caps and the service port caps.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge nee-
dle does not move(approximately 5 minutes
after turning off the vacuum pump).

- 88 -
(3) Gas Charging
(After Evacuation)

Indoor unit Liquid side

Outdoor unit

3-way
valve

Gas side
Closed

3-way
Charging manifold gauge valve
cylinder

Low- Open
handle Hi- handle
(CLOSE)
Check valve (OPEN)

• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect- This is different from previous procedures.
ed from the vacuum pump to the valve at the Because you are charging with liquid refrigerant
bottom of the cylinder. from the gas side, absolutely do not attempt to
- If you are using a gas cylinder, also use a scale charge with larger amounts of liquid refrigerant
and reverse the cylinder so that the system can while operating the air conditioner.
be charged with liquid.
2. Purge the air from the charge hose. - Stopping partway will allow the gas to be dis-
- Open the valve at the bottom of the cylinder and charged.
press the check valve on the charge set to - If the system has been charged with liquid
purge the air. (Be careful of the liquid refriger- refrigerant while operating the air conditioner
ant). The procedure is the same if using a gas turn off the air conditioner before disconnecting
cylinder. the hose.
3. Open the low handle on the gauge and charge 5. Mount the valve stem nuts and the service port
the system with liquid refrigerant. nut.
- If the system can not be charged with the speci- - Use torque wrench to tighten the service port
fied amount of refrigerant, it can be charged nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
with a little at a time (approximately 150g each - Be sure to check for gas leakage.
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from
the gas side valve's service port.

- 89 -
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.

Temp. difference : approx. 0°C All amount of refrigerant leaked out.


Current : less than 80% of Check refrigeration cycle.
rated current

Temp. Difference
Temp. difference : approx. 8°C Refrigerant leakage
Current : less than 80% of Clog of refrigeration cycle
rated current Defective compressor

Operating Current
Temp. difference : less than 8°C
Excessive amount of refrigerant
Current : near the rated
current

Temp. difference : over 8°C Normal

Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.

2. Check temperature and pressure of refrigeration cycle.

Suction pressure Temperature


(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)

High Defective compressor Current is low.

Higher
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation.

Insufficient amount of Current is low.


Lower Higher refrigerant(Leakage)
Clogging

Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition.
2

2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.

- 90 -
Electronic Parts Troubleshooting Guide
❇ Refer to electronic contorol device drawing & schematic diagram.

Trouble 1 The Product doesn’t operate at all.

Turn off the main power and wait to 5 seconds

Turn on the main power again.

Does "Beeping" sound is made from the indoor unit?

NO YES

Check the voltage of power(AC220V/AC240V, 50Hz). • Primarily, the operating condi-


tion of Micom is O.K.
• The voltage of main power.
• The voltage applied to the unit.
• The connecting method of Indoor/Outdoor connecting cable (each color)
• The P.W.B. Ass'y
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.) • Check CN-DISP1

The operation check of the P.C.B. Ass'y

Procedure Specification Remedy


1) The input voltage of power trans- 1) AC230V ± 30V 1) Replace
former. : Check the rated voltage power transfomer.
2) The output voltage of power 2) 14V ± 3V 2) Replace
transformer. power transfomer.
3) IC01D(7812) 3) DC12V 3) Replace IC01D.
4) IC02D(7805) 4) DC5V 4) Replace IC02D.
5) IC01A(KIA7036) 5) The voltage of micom pin 29 5) Replace IC01A.
: DC4.5V↑

-91-
Trouble 2 Product doesn't operate with the remote controller.

Turn on main power.

While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed.


At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)

Caused by the remote controller. Caused by other parts except


the remote controller

When the mark ( ) is displayed in LCD Check the contact of CN-DISP 1 connector
screen, replace battery.

When the detect switch (double key) inside the Check DISP PWB Ass'y
remote controller door is fault, it is impossible to -Voltage between CN1 ➀ - ➆ : DC +5V
operate temperature regulating(▲ / ▼) and wind
speed selecting.

Check the Display PWB Ass'y • Check receiver ass'y

-92-
Trouble 3 The Compressor/Outdoor Fan are unable to drive.

Turn on the main power.

Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1°C at least.

When in air circulation mode, compressor/outdoor fan is stopped.

Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)

When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.
• Check the related circuit of R02H(12.1K), R01H(1K), R04H(6.2K), R03H(1K), C01H(102),
C02H(102), Micom(pin No. , ).
• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).

Check the Relay(RY-PWR, RY-START) for driving Compressor.


• Check the voltage between brown and blue cable of terminal to connect the Outdoor
(About AC220V / 240V).
• Check the related circuit of relay in Outdoor PCB Ass'y.

Check Point Comp. ON Comp. OFF

Between Micom(No. 19) and DC 5V DC 0V


GND
Between IC01M(No. 10) and DC 1V↓ DC 12V
GND

Turn off main power.

Check the electrical wiring diagram of Outdoor side.


Check the open or short of connecting wires between Indoor and Outdoor.

-93-
Trouble 4 When indoor Fan does not operate.

Turn off main power.

Check the connection of CN-FAN.

Check the Fan Motor.

Check the Fuse(AC250V, T2A).

Check the related circuit of indoor Fan Motor.

• The pin No. 38 of micom and the part for driving SSR.(Q01M)
• Check the related pattern.
• Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.

Turn on the main power

Check the SSR high speed operation by remote control.


(the Indoor Fan Motor is connected)

The voltage of Pin No 1(orange) and 3(black) of CN-FAN.

About AC 160V over About AC 50V over

SSR is not damaged Check SSR

-94-
Trouble 5 When the vertical louver does not operate.

• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal

• Check the connecting condition of CN-U/D Connector


• Check the soldering condition(on PCB) of CN-U/D Connector

Check the operating circuit of the vertical louver

• Confirm that there is DC +12V between pin ➀ of CN-U/D and GND.


• Confirm that there is a soldering short at following terminals.
- Between 1 , 2 , 3 and 4 of MICOM - Between 17 , 18 , 19 and 20 of MICOM
- Between 4 , 5 , 6 and 7 of IC01M - Between 5 , 6 , 7 and 8 of IC01M

If there are no problems after above checks.

• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver

-95-
Trouble 6 The Outdoor Unit does not operate at all.

YES
Does the Operating LED of indoor unit blink
Refer to the self-diagnosis function.
when Operation's ON?

NO
NO

Is the Connection between CN-Power of Check the connecting state of connector


indoor unit and terminal block?

YES
NO
Indoor Outdoor
Is the connection of cable between indoor
and outdoor unit right? 1(Brown) 1(Brown)
2(Blue) 2(Blue)
3(Green/YL) 3(Green/YL)
YES 4(Red) 4(Red)

NO

Is the voltage of CN-POWER , in out- Check the Fuse of Outdoor PCB Ass'y.
door PCB Ass'y about AC220V / 240V ? Check the connecting state of wires.

YES

NO

Is the operation of outdoor Ass'y right?


Replace the parts.
(IC04D, IC01A)

NO

Replace the PCB Ass'y.

-96-
Trouble 7-1 When compressor does not operate normally.

■ Communication error between Indoor and Outdoor (Error Code )


NO
Does the operating LED in display PCB • Check the state of connecting cable
Ass'y blink 5 times? (4 line) bewteen indoor and outdoor unit .

YES
NO
Is the connecting state of connector out- • Electrical wiring diagram(Colors)
door PCB Ass'y right. • Check the connecting state
of connectors in outdoor PCB Ass'y
(CN_Data - Terminal Block.)
YES

NO
Is the connection of CN-DATA between • Reconnect the cable to terminal block.
indoor and outdoor unit right? • Check the PCB pattern(Resoldering).

YES

Replace the PCB Ass'y.

• Main PCB Ass'y (Indoor/Outdoor)

-97-
Trouble 7-2 When compressor does not operate normally.

■ CT Error (Error Code )


NO
• Check the state of connecting cable
Does the operating LED in Display PCB
(3 line) bewteen Indoor and Outdoor Unit .
Ass'y blink 8 times?
• Check fuse, Noise Filter, PTC, etc.

YES

NO
Is the current transformer(CT) in Main PCB
Ass'y right? Check the PCB pattern(resoldering)

YES
NO

Is the connecting state of connectors right?


(CN-IPM, U.V.W and Compressor wires) Check the state of connecting wires.

YES

NO

Is the indoor/outdoor fan locked? Check the indoor/outdoor fan motor.

YES
NO

Is the discharge temperature of Indoor unit Check the compressor.


right(11°C~17°C) in the cooling mode?

YES
NO

Is the refrigerant pressure right? Supply the refrigerant

YES

Replace the PCB Ass'y.

• Main PCB Ass'y(Outdoor)


• Control Box Ass'y(Outdoor)

-98-
Trouble 7-3 When compressor does not operate normally.

■ DC Peak Error(Error Code )

Does the operating LED in display PCB


Ass'y blink 9 times?

YES

NO
Is the connecting state of connectors in out- • Electrical wiring diagram (Colors)
door Sub. PCB Ass'y right? • Check the connecting state of connectors
(CN-UVW, CN-IPM, CN-Gate 1, CN-Gate 2) in PCB Ass'y(Main/Sub)
• If CN-UWV is connected, the comprressor
YES can be operated a opposite direction.

NO
• Check the short P-N P-U, V, W, and N-U,
Is the power module in Sub PCB Ass'y
V, W of IPM and then collector, emiter of
right?
IGBT
• Replace the Sub PCB Ass'y.
YES

NO
Is the voltage of CN-AC over than
AC170V? Check the supplied voltage.

YES

NO
Is the voltage of CN-DC over than about • Check CN-IPM connector(Pin No. 12)
DC260V? • Replace the Sub PCB Ass'y.

YES

Replace the PCB Ass'y.

• Main PCB Ass'y


• Sub PCB Ass'y
• Control Box Ass'y

-99-
Trouble 7-4 When compressor does not operate normally.

■ DC Low Voltage Error (Error Code )

Does the operating LED in display PCB


Ass'y blinks 10 times?

YES

NO
Is the connecting state of connectors in out-
door PCB Ass'y right? Reconnect the connector.
(CN-DC, CN-AC)

YES

NO

Is the voltage of capacitor over 187Vdc? Check the wiring state.

YES

NO
Is the connecting state of wires in outdoor
Check the electrical wiring diagram (Colors)
unit?

YES

Replace the PCB Ass'y.

• Main PCB Ass'y (Outdoor)

-100-
Trouble 7-5 When compressor does not operate normally.

■ High press Error (Error Code )

Does the operating LED in display PCB


Ass'y blink 11 times?

YES

NO
Is the installation condition of outdoor unit
right. Check the installation condition.

YES

NO

Is the indoor/outdoor fan locked? Check the indoor/outdoor fan motor.

YES

NO

Is the refrigerant pressure right? Remove or supply the refrigerant.

YES

Replace the PCB Ass'y.

• Main PCB Ass'y (Outdoor)

-101-
■ The problem of missing the connector (INDOOR MAIN PCB ASSY)

Connectors Condition Problem (error mode)

CN-POWER (1,2) • Malfunctions all indoor & outdoor unit.


OPEN
• Malfunctions remocon, force, test operation mode.

• Malfunctions outdoor unit.


CN-POWER (3) OPEN • Stop compressor and outdoor fan motor.
• The operation LED blinks 5 times.
• Communicaion error.

CN-FAN OPEN • Malfunctions indoor fan motor.

CN-DISP1 OPEN • Malfunctions remote controller.


• Don't operate the power display module.

CN-TH OPEN/SHORT • The operation LED blinks once.


• Enable to receive remote singnal.

• Malfunctions UP/DOWN step motor.


CN-U/D OPEN • Don't operate louver.

- 102 -
■ The problem of missing the connector (OUTDOOR MAIN PCB ASSY)
Connectors Condition Problem (error mode)

• Malfunctions outdoor unit.


CN-POWER OPEN • Stop compressor and outdoor fan.

• Malfunctions outdoor unit.


CN-AC OPEN • Stop compressor and outdoor fan.
• The operation LED blinks 10 times.

• Malfunctions outdoor unit.


CN-DC OPEN • Stop compressor and outdoor fan.
• The operation LED blinks 10 times.

• Malfunctions inverter circuit.


CN-IPM OPEN • Stop compressor and outdoor fan.
• The operation LED blinks 8 times.

• Malfunctions inverter circuit


CN-Gate 1, 2 OPEN
• The operation LED blinks 9 times.

CN-GND OPEN • Malfunctions EMI /EMS

CN-FAN OPEN • Malfunctions fan.

CN-TH OPEN/SHORT • The operation LED blinks twice.

• The LED01K blinks 10 times.


• Continue Comp. operation.
CN-COMP OPEN/SHORT (when the discharge pipe TH opens)
• Stop Comp. operation
(when the discharge pipe TH shorts)

■ The problem of missing the connector (SUB PCB ASSY)


Connectors Condition Problem (error mode)

CN-UVW OPEN • Stop compressor.

• Malfunctions inverter circuit.


CN-IPM OPEN • Stop compressor and outdoor fan.
• The operation LED blinks 8 times.

• Malfunctions inverter circuit


CN-Gate 1, 2 OPEN
• The operation LED blink 9 times.

- 103 -
Electronic Control Device
1. Room Type Indoor Unit
• MAIN P.C.B DC ASM

• MAIN P.C.B AC ASM

- 104 -
2. Cassette Type Indoor Unit
• MAIN P.C.B DC ASM

- 105 -
3. Art Cool Type Indoor Unit
TOP VIEW BOTTOM VIEW

- 106 -
4. Convertible Type Indoor Unit

- 107 -
5. Display ASSY
• Room Type Indoor Unit

• Convertible Type Indoor Unit

• Art Cool Type Indoor Unit


TOP VIEW

BOTTOM VIEW

- 108 -
6. SUB P.W.B ASSEMBLY
• Art Cool Type Indoor Unit

TOP VIEW BOTTOM VIEW

- 109 -
7. Outdoor Unit
• MAIN P.C.B ASM

P N U V W

-110-
Schematic Diagram
1. Room Type Indoor Unit

- 111 -
C05D
DC310V 681 12V R11K C11K
NF01J R01J D01D IC03D C09D IC11K(TLP621)
CN-POWER 250V/ ZNR01J 22mH/3A 10K 102
RX
1M,1/2W 1N4007 S/Trans L01D KID78L05BP 220uF/50V M_RTX Multi_RX
LIVE T3.15A,3A INR14D561K 1 2 3
1 2 6,7 I O R12K,1K
2 2 7805 5V R13K
D03D 3.3uH 1.5K 1 4
NTC01D G DC 5V
ZD01D UF5402 DC 5V
NF 10D-9 R04D C10D M_RTX
P6KE200A C06D C08D
NEUTRAL 3 4 3 470uF/35V
39
104 103 D11K
1SR139-400
R16K
1 1 AC_N 4,5 D12K 10K
C03J
C01J C02J 1SR139-400 3 2 TX Multi_TX
10nF D02D C07D C11D
100nF 100nF C01D D IC02D(TLP521) 223/1KV
275V UF4005 330uF/35V 4 1 Q11K
SIGNAL 275V 275V 10uF/ 5 EN DC 5V
400V 4 C12D R14K
3 3 M_RTX
IC01D
TNY R15K IC12K(TLP627) KRC104M
R03D 103/1KV 1K
RY-COMP 255P 82K/3W
TNY255P BP
2 1 150
AC_L S
C03D
3,7,8 ZD02D
103
11V
D01K L01K
CN-OUT C04D
RY-OUTFAN IC02M DAN212K 100nH
RY-OUTFAN 103/250VA
DC 12V KID65004AF IC02M 12V
1 1 5V
DC 12V KID65004AF DC 12V CN-REMO
RY-4WAY Q03K
RY-4WAY DC12V
3 3 STEP M STEP M5 HEATER KRC104M 3 3
P75 R02K L03K Signal
RY-HEATER RY-HEATER 1 P76 64 유선_TX 2 2
4.7K GND
5 5 MED P74 4WAY 1 1
2 P77 63 Q01K L02K
CN-D/PUMP D/PUMP OUTFAN KRA104M C05K
1 1
3 P00 P73 62 C04K C06K
Drain
Motor
STEP M STEP M2 A/C 104 103
3 3 4 P01 P72 61 R07H R05H R03H 12V
COMP 12.1K 12.1K 12.1K 5V
CN-LOUVER
RY-D/PUMP STEP M STEP M3 C03K
1% 1% 1%
5 P02 P71 60 5V
R01K
102
1 1 LOUVER STEP M4 STEP M R08H R06H R04H R02H 1K
Louver
Motor 6 P03 P70 59 12.1K 12.1K 12.1K 6.2K R01H
유선_RX
3 3
HIGH 1% 1% 1% 1% 12.1K
1% D02K
RY-LOUV 7 P04 VDD 58 5V
DAN212K
CN-MOTOR1 LOW OPTION6 C01K C02K Q04K
1 1 8 P05 (AIN7)/P67 57 102 102 KRA104M
Q02K
壤 IC01M OPTION5
2 2 KID65004AF 9 P06 (AIN6)/P66 56 CN-PIPE KRC104M
FAN RY-L DC 12V OPTION4

3
MOTOR 3 3 10 P07 (AIN5)/P65 55

- 112 -
RY-M OPTION3
FREQ 5V 5V
11 P10(INT0) (AIN4)/P64 54

1
4 4 50/60Hz
RY-H REMO OPTION2 R03C R06C

3
CN-MOTOR2
NF01M
SSR
NF01M
REMO
C02L
12 P11(INT1) (AIN3)/P63 53 10K 10K
PIPE TH IC01C
1 1 681 R04C
BZ01E
13 P12(INT2/TC1) (AIN2)/P62 52 AC_L 4.7K 50/60Hz

1
FAN 2 2 ROOM TH Q01C
MOTOR
3 3
ZNR01M
R02E 14 P13(DVO) (AIN1)/P61 51 CN-ROOM
R02C
1K R05C C01C
20 PHASE OPTION 1
15 P14(PPG) (AIN0)/P60 50 AC_N
1K 103
R01E EERROM
R02A 10K Q CN_M C R01C
1K 8 1
P15(TC2) VARF
16 49 5V
S
5V VCC 200K/2W
5V
D
12V 1 1 12V
R01A 1K 7 2 VASS C01U
1 3 DU C
17 P16 48 GND
103
KIA7036P
SB3 OR6 OR5 OR4 OR3 OR2 OR1 C02H C01H 5V 2 2 5V
+ 3 C
IC01A 2 C02A 6 ORG D
18 P17 P54 47 S_B3 103 103
C01A
3.6V 3.3uF 102 SB2 R01U GND 3 3 GND
5 VSS Q 4
S C02U
/50V 19 P20(INT5/STOP) P53 46 S_B2 10K
103
5V
SB1
5V 4 4 PLC_SEL
2. Cassette Type Indoor Unit

DISPLAY R01L
GND
20 TEST (PWM/PDO)/P52 45 S_B1
SB0 Multi_TX 5 5 Multi_TX
10K
GND 1 1 NC 21 P21(XTIN) (INT4/TC4)/P51 44 S_B0
R02L 1K CC RX Multi_RX 6 6 Multi_RX
Vout 중앙_RX
2 2 REMO NC 22 P22(XTOUT) (INT3/TC3)/P50 43
R03L 1K CC TX
Vcc LED1 RESET 중앙_TX GND 1 1 GND
3 3 23 RESET (SO2)/P47 42
R04L 1K XIN
LED2
PRE AMP 4 4 R01B 24 XIN (SI2)/P46 41 유선_RX 5V 2 2 5V
TFMS-2380B
R05L 1K 1.0M XOUT
LED3
5 5 25 XOUT (SCK2)/P45 40 유선_TX 12V 3 3 12V
LED4 R06L 1K OSC01B SO1/PLC
Force VSS 4 4
SW
6 6 8.00MHZ 26 (SO1)/P44 39 SO1
LED1 SI1/MULTI TX
7 7 5V
27 P30 (SI1)/P43 38 5 5 SI1
LED2 SCK1/MULTI RX
CN-DISP P31 (SCK)/P42 6 6
28 37 SCK1
LED3
5V
29 P32 NC 36 7 7 CS0
CN-LOUVER R02F R01F LED4
30 P33 NC 35 8 8 CS1
1K 1K
LOUVER
1 1
31 P34 NC 34
3 3
FLOAT
NC
CN_ZONE
32 P35 33
CN-FLOAT
CSO
C02F C01F
1 1 103 103
2 2 CSI
3. Art Cool Type Indoor Unit

- 113 -
4. Convertible Type Indoor Unit

RY-OUTFAN
RY-4WAY

- 114 -
TSUP_B/A OUT PIPE
4 3 2 1 4 3 2 1
CN-TH5 CN-TH6
4 3 2 1 4 3 2 1
DISCHARGE SUCTION TSUP_D TSUP_C +5V +5V IC07K TLP627
1 4
R16H R14H R12H R10H R08H R06H R04H R02H R13K
6.2K,1% 12.1K,1% 6.2K,1% 6.2K,1% 6.2kK,1% 6.2K,1% 1K
6.2K,1% 18K,1% 2 3
R15H 1K D04K
CN-TH1 1 2 3 CN-TH2 1 2 3 CN-TH3 1 2 3 CN-TH4 1 2 3 C07K
R13H 1K 102 +5V 1SR139-600
1 2 3 1 2 3 1 2 3 1 2 3 4 1
R11H 1K 50V
R09H 1K R14K 1K D08K
R07H 1K 1K 1SR139-600
3 2
R05H 1K
R20K
R03H 1K C08K R15K IC08K R16K 82K,3W
R01H 1K 102 TLP621
50V 10K
C08H C07H C06H C05H C04H C03H C02H C01H +5V IC05K TLP627
104K 104K 104K 104K 104K 104K 104K 104K 1 4
R09K
1K
2 3
5V D03K
MICOM C05K
102 +5V
4 1
1SR139-600
50V
R05T, 270 1/8W +5V
TMP88CK49 R10K 1K D07K
1K 1SR139-600
1
1

3 2
LEV D_1 1 P70 VDD 64
R19K
AIN07 DISCHARGE C06K R11K IC06K R12K 82K,3W
R06T, 270 1/8W R02Z R04Z
LEV D_2 2 P71 63 102 TLP621
10K
2
2

12.1K 12.1K AIN06 SUCTION 50V


LEV D_3 3 P72 62
1% 1% TSUP_D
R07T, 270 1/8W +5V IC03K TLP627
LEV D_4 4 P73 AIN05 61
1 4
3
3

MODEL OP
5 P74 AIN04 60 TSUP_C R05K CN_DATA
R08T, 270 1/8W OP1
R01Z,1K
CURRENT OP P75 TSUP_B 1K
6 AIN03 59 2 3 DATA_D
4
4

R03Z,1K D02K 4 4 9
LOW P76 CT TSUP_A C03K
7 AIN02 58 102
+5V 1SR139-600
R09Z 4 1
R09T, 270 1/8W OUT_TH 50V DATA_C
12K DC_LINK 8 P77 DC_LINK_V 57
5
5

OP2 AIN01 3 3 8
HIGH MED OOT_PIPE R06K 1K R18K
9 W1 AIN00 56 1K DATA_B
R10T, 270 1/8W 3 2 82K,3W
+5V 2 2 7
6
6

10 V1 VAREF 55 R08K D06K


C04K IC04K 1SR139-600
11 U1 VASS 54 102 R07K TLP621 DATA_A
+5V 50V 10K 1 1 6
RX_D
7
7

12 W1 P54 53
TX_D +5V IC01K TLP627
13 V1 P53 52
R02T,10K 1 4
5
RX_C
8
8

R03T,1K +5V 14 U1 P52 51 R01K


R05Z TX_C 1K
15 EMG 4
P51 50 2 3
9
9

R01T +12V 10K RX_B D01K


C02T C03T +
16 P07 P50 49 C01K +5V
103 Q01T 10k C01M 104K 102 1SR139-600
CN-IPM TX_B 50V
4 1
16V 107M 17 P10 P47 48 +5V
+12V IC01M
1 2 3 4 5 6 7 RX_A Q01Z R02K 1K R17K
8 9 KID65004AP 9 8 MGT INT 18 P11 MGT ON INT P46 47 KRA107M 1K 82K,3W
3 2
1 2 3 4 5 6 7 8 9 RY-PWR 10 7 TX_A
19 P12 P45 46
IC01S IC02S IC03S IC04S IC05S IC06S IC07S R04T C02K IC02K R04K D05K
C01T RY-4WAY 11 6 102 R03K TLP621 1SR139-600 +12V
1K 20 P13 P44 45
CN-IPM 103 5 50V 10K
LED01T RY-FAN H 12 21 P14 P43 44 CN-LEV C
(GREEN) RY-FAN L 13 4
CN-GATE2

22 P15 P42 43 C03M 104K +12V 5 5


CN-GATE2 RY-SV 14 3
23 P16 P41 42 AR02Z
+
C03M 4 4

-115-
R03S R04S R05S R06S D10D S-TRANS +5V 9 330uF/25V
R01S R02S 1 1N4937x4 RY-START 15 2 10K,5% 10
560 560 560 560 560 24 P17 P40 41 3 3 LEV C
560 D08D D09D IC04D 1 18
3 2 1

7 6 5 4 3 2 1

RU2YX +12V 1SR139-600 16 1 +5V NC 2 2


+
C06D 25 P20 P37 40 2 17 IC03M
7805
220UF R08D R07Z 26 TEST P36 39 16 ULN2804 1 1
+5V 3
35V 1.2K 1 1 56K
CN-TEST2 CN-LEV B
C15D C16D 2 2 27 P21 P35 38
5 4

D11D 4 15
+ 104 103 R02A R01A 3 3 5 5
IC01A
R06Z 28 P22
+ +
4.7K P34 37 5 14
+ C03D C04D C05D 1 3 1K 4 4
10K 29 4 4
C07D KIA7036P P33 36
7 6

2200UF 470UF 470UF RESET 6 13


220UF 50V 1 3 3 LEV B
C04A 2 R03A +
35V R09D C01A 30 XIN P32 35 7
7 C14D INT1 102 100 102 2 12
1K 2 2
1 D12D 473 31 XOUT P31 34 8 11
C02A
3 2 1
4 3 2 1

1 1
+ IC03D,SE012N +5V 10 50V 32 VSS P30 33
C08D R03D R06V 3 R01B CN-LEV A
1K OSC01B +12V
220UF 46K 1M C02M 104K
3W C11D,473,630V 16MHz 5 5
35V R04V
D05D C04M 4 4
5 4

+
C01S C02S C03S D13D 10K R03V IC01V
EG01C C112D,100P,1KV AR01Z
10UF 10UF 10UF 33K TLP621-BL
D01V R01V 9 10 330uF/25V
7 6 5

C04S 1SR139-600 56K,3W 10K,5% 3 3 LEV A


R04D D06D Q01V
+

+
1 18
C09D
8 7 6

+
33UF 10,1/4W 1N4937 C3198 2 2
330UF FB01D R02V
FBA04HA900 C01V 2 17
R05V 1K
Vup1 Up Vupc Vvp1 Vp Vvpc Vwp1 Wp Vwpc Un Vn Vn1 Wn Vnc F0 25V + 102 1 1
3 2 1 6 5 4 9 8 7 12 13 11 14 10 15 C02D 10K 1/4W 3 16
47UF IC02D FUSE
8

2 25V TLP621-BL 250V,3A/3.15A CN-LEV D


4 15
CN-GATE1

1 IC01D
5 5
CN-GATE1 D07D 4 5 14
FB02D 1N4937 R05D LEV D_4 4 4
In GND In GND In GND 5.6K D01D~D04D NF01J
Vcc Vcc Vcc Vcc Fo Vcc Fo Vcc Fo 1/4W 6 13
In GND In GND In GND
G6551
1SR139-600 LEV D_3 3 3 LEV D
2 R01D ~
CT01N +5V 7 12
R06D,680 5 27,5W +
~ R02N D06N LEV D_2 2 2
Out Si GND Out Si GND Out Si GND Out Si GND Out Si GND Out Si GND 1/4W ZNR01J 1.65K,1% 1N4148 8 11
C13D + - + LEV D_1 1 1
R07D ZNR561D14
2.2,1/4W 680P C01D ~ ~
+
3 IC02M
D05N C01N
D01N~04N 1N4148 220 ULN2804
68UF R02D C02J C01J 1SR139-600 R01N
400V 82K,1W 104 104,250V 680,1% 16V(RN)
IPM 250V
P U V W N
1SR139-600 NTC01K
D09K 100D-9 RY-Start
R07Y,1K
DC LOW

RY-FAN_H

RY-Power
471,250V

RY-FAN_L
15uF,450V

1M,1W

RY-4WAY
R21K
C02X R01J

C09K
LED01Y(RED) C01Y~C03Y

C10K
+
ZNR01J,02J C01X FUSE

RY-SV
R05Y R03Y 1.0uF 1M,1/2W SVC561 NF01J 472M 1.0uF 250V/25A
R02Y 3 3

3
15K 82K 51K,3W 9mH
+5V 1/4W 1
Q02Y 1/4W CN-POWER WH
C3198 CN- TEST1 PTC OUTPUT CN-POWER
Q01Y DZ01Y
40 Ohm (WH) INPUT

2
COMP C3198 20V R01Y
RY-DISC CN- CN-PWR 2 2
1W 51K,3W (RDE)
+12V CN-SV1 4WAY CN-FAN CN-AC2 CN-AC1 CN-POWER
5. Outdoor Unit

BK

1
2 1 2 1 4 3 2 1 2 1 1 1 2
R06Y,10K IC01Y 3 2 1
TLP521 R04Y
2.2K R11Y,R12Y RY-DISC 2 1 3 2 1 4 3 2 1 1 1 1 1
1/4W 56K,3W
474/450V C01Y,222 3
Comp WH WH
OLP
CN-DC 4WAY
SURGE CN-GND GREEN

Magnet
FAN /YELLOW
2 1 DSA-362MA-05F25(UL)
~ MOTOR 1
DB02J,S50VB60 2 1 High BK
+ - G/Y Press
DB01J,S50VB60 Power
2200UF,400V 165UF,400V ~
Relay
~ REACTOR + -
+ +
~
Exploded View & Replacement Parts List
1. Room Type Indoor Unit (7K, 9K, 12K Btu Models)
135312

152313
135314

152302

131410 733010

359011

342800
159830

159901
668713

268712
35211B 346810
354212
135516

352150 263230
135311

146811-1 146811-2
264110

266090 268714-2
267110 268714-1

249951 W0CZZ
263232

- 116 -
Parts List (Indoor Unit)

LOCATION PART No.


DESCRIPTION REMARKS
No. 7K 9K 12K
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006A 3141A20005A R
135311 GRILLE ASSEMBLY,DISCHARGE 3531A10127B 3531A10127B 3531A10107A R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20100X 3531A20100X 3531A10117Y R
135316 GRILLE ASSEMBLY,FRONT 3531A20187F 3531A20187F 3531A10208F R
135516 COVER ASSEMBLY,MOTOR 3551A20050P 3551A20050P 3551A20099A R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A10005A 5230A10005A 5230A20014A R
152313 FILTER ASSEMBLY,DEODORIZER 5231AR2412T 5231AR2412T 5231AR2412T R
159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A20007A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20213U 4995A20213V 4995A20213W R
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A R
267110 REMOTE CONTROLLER 6711A20067G 6711A20067G 6711A20067G R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194A 6871A20194A 6871A20194A R
268715 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20267A 6871A20267A 6871A20267A R
268716 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20370A 6871A20370B 6871A20370C R
342800 BEARING 4280A20004A 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062D 4681A20062A 4681A20048A R
35211B TUBE ASSEMBLY,TUBING 5211AR7066P 5211AR7066P 5211AR7066N R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F R
354212 EVAPORATOR ASSEMBLY,FINAL 5421A10035A 5421A10035B 5421A20087M R
359011 FAN ASSEMBLY,CROSS FAN 5901A20007B 5901A20007B 5901A20007A R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 1H00843A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A R

- 117 -
2. Room Type Indoor Unit (18K, 24K Btu Models)

135316
267110-1

152313
135314

152302
135511
131410 733010

359011

342800

159830
135311

159901-1
159901-2
668713

268712
35211B 346810
354212
135516

352150 263230
268714-1
146811-1 146811-2

249951
268714-2

W0CZZ

- 118 -
Parts List (Indoor Unit)

LOCATION PART No.


DESCRIPTION REMARKS
No. 18K 24K
131410 CHASSIS ASSEMBLY 3141A10002A 3141A10002A R
135311 GRILLE ASSEMBLY,DISCHARGE 3531A10116A 3531A10116A R
135314 GRILLE ASSEMBLY,INLET SUB 3531A20107X 3531A20107X R
135316 GRILLE ASSEMBLY,FRONT 3531A20207B 3531A20207B R
135516 COVER ASSEMBLY,MOTOR 3551A20099C 3551A20099C R
146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A R
152302 FILTER(MECH),A/C 5230A20001A 5230A20001A R
152313 FILTER ASSEMBLY,DEODORIZER 5231AR2595G 5231AR2595G R
159901-1 VANE,HORIZONTAL 5990A20008A 5990A20008A R
159901-2 VANE,HORIZONTAL 5990A20009A 5990A20009A R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20213X 4995A20213Y R
263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A R
267110 REMOTE CONTROLLER 6711A20067G 6711A20067G R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20194B 6871A20194B R
268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20267A 6871A20267A R
268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20370D 6871A20370E R
342800 BEARING 4280A20004A 4280A20004A R
346810 MOTOR ASSEMBLY,INDOOR 4681A20003D 4681A20067A R
35211B TUBE ASSEMBLY,TUBING 5211A30439E 5211A30439J R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F R
354212 EVAPORATOR ASSEMBLY,FINAL 5421A20116Q 5421A20116R R
359011 FAN ASSEMBLY,CROSS FAN 5901A20008A 5901A20008A R
733010 PLATE ASSEMBLY,INSTALL 3301A10002A 3301A10002A R
W0CZZ CAPACITOR,DRAWING 3H01487G 3H01487G R

- 119 -
3. Cassette Type Indoor Unit (AMNN126EA0, AMNN186TEA0)

249951

268714

354212

352118 352114

263230

158591
266012

330870

- 120 -
130411

W0CZZ

346810

359011

146811 268712
140570

152312

135802

135312-2

137211

130911
352150

267110
352150

- 121 -
Parts List (AMNN126EA0, AMNN186TEA0)

Part No.
Location No. Description Remarks
AMNN126TEA0 AMNN186TEA0
354212 EVAPORATOR ASSY 5421A10007Q 5421A10007F
352114 TUBE ASSY, DISTRIBUTOR 5211A10225A 5211A10225A
352118 TUBE ASSY, MANIFOLD 5211A20241Q 5211A20241Q
158591 PUMP ASSY, WATER 5859A20001C 5859A20001C
266012 SWITCH ASSY, FLOAT 6601A20001F 6601A20001F
330870 DRAIN PAN ASSY 3087A10002A 3087A10002A
249951 CONTROL BOX ASSY, INDOOR 4995A10026L 4995A10026V
268714 PWB(PCB) ASSY, MAIN 6871A10040Z 6871A10038E
130411 BASE ASSY, WELD INDOOR 3041A10013A 3041A10013A
346810 MOTOR ASSY, SINGLE 4681AC2026E 4681AC2026D
359011 FAN TURBO 5900A10004A 5900A10004A
140570 LOCKER 4056A20001A 4056A20001A
130911 CABINET ASSY, INDOOR 3091A10023A/B 3091A10023A/B
352150 DRAIN ASSY, TUBE 5251A20002A 5251A20002A
137211 PANEL ASSY, FRONT(INDOOR) 3721A10021N 3721A10021N
146811 MOTOR ASSY, STEP 4681AP2968D 4681AP2968D
268712 PWB(PCB) ASSY, DISPLAY 6871A20096C 6871A20096C
152312 FILTER ASSY 5231A10005A 5231A10005A
135802 DOOR, LOCK 3580A20005A 3580A20005A
267110 REMOTE CONTROLLER 6711A20039H 6711A20039H
263230 THERMISTOR ASSY 6323AQ3226F 6323AQ3226F
W0CZZ CAPACITOR, DRAWING 3H00660N 3H00660N
352150 DRAIN TUBE ASSY 5251AP2954A 5251AP2954A
135312-2 INLET GRILLE 3530A10065A 3530A10065A
352111 TUBE ASSY, CONNECTOR 5211A20514C 5211A20514C

- 122 -
135515

249951

354210

268714

352115
267110
352111
352116
330870
144710-1
268717 35211B
146811 352150

135312
135500-3 263230
152312
144710-2
146811 352380 131410
147581

- 123 -
135311-2
135303
146811

135500-2
147581

135311-1
346810
349600
4. Art Cool Type Indoor Unit (AMNN096APA0, AMNN126APA0)

146811

135314
268712

135311-3 147581 146811


359012
135500-1
Parts List(AMNN096APA0)
LOCATION PART No.
DESCRIPTION REMARKS
No. Blue Wood Metal
131410 CHASSIS ASSEMBLY 3141A20004B
135311-1 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069E
135311-2 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069D
135311-3 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069F
135312 GRILL ASSEMBLY, FRONT(INDOOR) 3531A10161B 3531A10161C 3531A10161A
135303 GRILL INLET 3530A10071B 3530A10071C 3530A10071D
135314 GRILL ASSEMBLY, INLET 3531A20113B 3531A20113C 3531A20113A
135500-1 COVER 3550A20123A
135500-2 COVER 3550A20124A
135500-3 COVER 3550A20060A
135515 COVER ASSEMBLY, TOP(INDOOR) 3551A20031A
144710-1 GEAR ASSEMBLY 4471A20001C
144710-2 GEAR ASSEMBLY 4471A20001D
146811 MOTOR ASSEMBLY, STEP 4681A20055A
147581 LOUVER, HORIZONTAL 4758A20014B
152312 FILTER ASSEMBLY, AIR CLEANER 5231A20005A
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20246A
263230 THERMISTOR ASSEMBLY 6323A20004F
267110 REMOTE CONTROLLER ASSEMBLY 6711A20039P
268712 PWB (PCB) ASSEMBLY, DISPLAY 6871A20238A
268714 PWB (PCB) ASSEMBLY, MAIN 6871A10087E
268717 PWB (PCB) ASSEMBLY, SUB 6871A30027A
330870 DRAIN PAN ASSEMBLY 3087A30004A
346810 MOTOR ASSEMBLY, INDOOR 4681A20047B
352115 TUBE ASSEMBLY, EVAPORATOR IN 5211A20302D
352116 TUBE ASSEMBLY, EVAPORATOR OUT 5211A20301B
35211B TUBE ASSEMBLY, TUBING 5211AR7066D
352150 HOSE ASSEMBLY, DRAIN 5251AR1222Q
352380 AIR GUIDE 5238A10007A
354210 EVAPORATOR ASSEMBLY, FIRST 5421A20072A
359012 FAN, TURBO 5900400003A
352111 TUBE ASSEMBLY, CONECTOR 5211A20254B

- 124 -
Parts List(AMNN126APA0)
LOCATION PART No.
DESCRIPTION REMARKS
No. Blue Wood Metal
131410 CHASSIS ASSEMBLY 3141A20004B
135311-1 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069E
135311-2 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069D
135311-3 GRILL ASSEMBLY, DISCHARGE(INDOOR) 3531A20069F
135312 GRILL ASSEMBLY, FRONT(INDOOR) 3531A10161B 3531A10161C 3531A10161A
135303 GRILL INLET 3530A10071B 3530A10071C 3530A10071D
135314 GRILL ASSEMBLY, INLET 3531A20113B 3531A20113C 3531A20113A
135500-1 COVER 3550A20123A
135500-2 COVER 3550A20124A
135500-3 COVER 3550A20060A
135515 COVER ASSEMBLY, TOP(INDOOR) 3551A20031A
144710-1 GEAR ASSEMBLY 4471A20001C
144710-2 GEAR ASSEMBLY 4471A20001D
146811 MOTOR ASSEMBLY, STEP 4681A20055A
147581 LOUVER, HORIZONTAL 4758A20014B
152312 FILTER ASSEMBLY, AIR CLEANER 5231A20005A
249951 CONTROL BOX ASSEMBLY, INDOOR 4995A20246A
263230 THERMISTOR ASSEMBLY 6323A20004F
267110 REMOTE CONTROLLER ASSEMBLY 6711A20039P
268712 PWB (PCB) ASSEMBLY, DISPLAY 6871A20238A
268714 PWB (PCB) ASSEMBLY, MAIN 6871A10087F
268717 PWB (PCB) ASSEMBLY, SUB 6871A30027A
330870 DRAIN PAN ASSEMBLY 3087A30004A
346810 MOTOR ASSEMBLY, INDOOR 4681A20047B
352115 TUBE ASSEMBLY, EVAPORATOR IN 5211A20302D
352116 TUBE ASSEMBLY, EVAPORATOR OUT 5211A20301B
35211B TUBE ASSEMBLY, TUBING 5211AR7066D
352150 HOSE ASSEMBLY, DRAIN 5251AR1222Q
352380 AIR GUIDE 5238A10007A
354210 EVAPORATOR ASSEMBLY, FIRST 5421A20072A
359012 FAN, TURBO 5900400003A
352111 TUBE ASSEMBLY, CONECTOR 5211A20254B

- 125 -
146811

159911

130911
346811
159911 166000

352150
235450

237900 268712 W0CZZ

137213
261704
352115

267110

- 126 -
137213 354211
35211A

135314
352111
263230
5. Convertible Type Indoor Unit (AMNN186VBA0)

330870

359010

152302

342800
Parts List(AMNN186VBA0)

Location No. Description Part No. Remarks


130911 CABINET ASSY 3091AP2533A
135314 GRILLE ASSY, INLET SUB 5237AP2817B
137213 PANEL ASSY, SIDE 3720AP2767P
137213 PWB(PCB) ASSY, MAIN 6871A20042W
146811 MOTOR ASSY, STEP 4681AR2727G
152302 FILTER(MECH), A/C 5230AP7093A
159911 VANE ASSY, HORIZONTAL 5991AP2867B
159911 VANE ASSY 5991AP7334C
166000 SWITCH, PUSH 6600AP2059B
235450 DISPLAY ASSY (MECH) 3545AP7224A
237900 WINDOW, DISPLAY 3790AP7080A
261704 TRANSFORMER, POWER 6171AQ3198E
263230 THERMISTOR ASSY 6323AQ2333J
267110 REMOTE CONTROLLER ASSY 6711A20010K
268712 PWB(PCB) ASSY, DISPLAY 6871AQ3263A
330870 DRAIN PAN ASSY 3087AP7233A
342800 BEARING 3H02821A
346811 MOTOR ASSY, INDOOR 4681AP2306G
352115 TUBE ASSY, EVA-IN 5211AP2810C
35211A TUBE ASSY, SUCTION INDOOR 5211AP2813C
352150 HOSE ASSY, DRAIN 5251AP2460B
354211 EVAPORATOR ASSY 5421AP2812B
359010 FAN ASSY, CROSS FLOW 5901AR2351E
W0CZZ CAPACITOR 3H00671A
352111 TUBE ASSY, CONNECTOR 5211A20514B

- 127 -
554031 263230-4 137213-1

435300 137213-2

435512

546810 649950

559010
668713 W6200
W0CZZ-3
437210 W6640-1
W0CZZ-2
W0CZZ-1
349600
669200 W6640-2
447910

- 128 -
658740
6. Outdoor Unit (A2UN186FA0/A3UN216FA0)

668711 435511
552203-1
263230-1 561410

552117

554160
566000 552116
552115
552203-2
435301 349480
561411-1
263230-3
561411-2
263230-2 561411-3
430410

552113
Outdoor Unit Parts List (A2UN186FA0/A3UN216FA0)

LOCATION PART No.


DESCRIPTION REMARKS
No. A2UN186FA0 A3UN216FA0
137213-1 PANEL ASSEMBLY, SIDE 1A00201D 1A00201D R
137213-2 PANEL ASSEMBLY, SIDE 3A02284W 3A02284W R
263230-4 THERMISTOR ASSEMBLY 6323A20002Q 6323A20002Q R
263230-3 THERMISTOR ASSEMBLY 6323A20002R 6323A20002R R
263230-2 THERMISTOR ASSEMBLY - 6323AQ3226K R
269310-1 THERMISTOR ASSEMBLY 6323A20001A 6323A20001A R
349480 ORIFICE 4948AP2527A 4948AP2527A R
349600 MOUNT, MOTOR 4960AP1361A 4960AP1361A R
430410 BASE ASSEMBLY, WELD(OUTDOOR) 3041A20022B 3041A20022B R
435300 GRILLE, REAR 1A00207B 1A00207B R
435301 GRILLE, DISCHARGE 3530A20007B 3530A20007B R
435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 3551A10003Y 3551A10003Y R
435512 COVER ASSEMBLY, TOP(OUTDOOR) 3H03266L 3H03266L R
437210 PANEL ASSY, FRONT SUB 3721A20004L 3721A20004L R
447910 BARRIER ASSEMBLY, OUTDOOR 2H02110L 2H02110L R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20013Z 4681A20013Z R
552113 TUBE ASSEMBLY, CONDENSER OUT 5211A20954A 5211A20954A R
552115 TUBE ASSEMBLY, MENIFOLD(OUTDOOR) 5211A20419C 5211A20419A R
552116 TUBE ASSEMBLY, REVERSING 5211A20590A 5211A20949A R
552203-1 VALVE, SERVICE 5220A20035A 5220A20035A R
552203-2 VALVE, SERVICE 5220A20034A 5220A20034A R
554031 CONDENSER ASSEMBLY, BENT 5403A20072L 5403A20072L R
554160 COMPRESSOR 2520UTGV2AA 2520UTGV2AA R
559010 FAN ASSEMBLY, PROPELLER 1A00195B 1A00195B R
561410 COIL ASSY, REVERSING VALVE 6141AR3509A 6141AR3509A R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A10053J 4995A10053G R
561411-1 COIL ASSEMBLY, EXPANSION 6141A30003B 6141A30003B R
561411-2 COIL ASSEMBLY, EXPANSION 6140A30003C 6140A30003C R
561411-3 COIL ASSEMBLY, EXPANSION - 6141A30003D R
566000 SWITCH, PRESSURE 3A02524F 3A02524F R
658740 REACTOR 5874A90001E 5874A90001E R
668711 PWB(PCB) ASSEMBLY, MAIN(OUTDOOR) 6871A20204Q 6871A20204R R
W6200 FILTER(CIRC), EMC 6200JB8007Q 6200JB8007Q R
668713 PWB(PCB) ASSEMBLY, SUB 6871A20205A 6871A20205A R
669200 RELAY 6920AP3400A 6920AP3400A R
W0CZZ-1 CAPACITOR, DRAWING 0CZZA90001C 0CZZA90001C R
W0CZZ-2 CAPACITOR, DRAWING 0CZZA90001D 0CZZA90001D R
W0CZZ-3 CAPACITOR, DRAWING 2A00986D 2A00986D R
738281 MANUAL, SERVICE 3828A20097N 3828A20097N R
738290 MANUAL, OWNERS 3828A20331A 3828A20331A R
W6640-1 TERMINAL BLOCK 3A00093A 3A00093A R
W6640-2 TERMINAL BLOCK 4G00103C 4G00103C R

- 129 -
554031 137213-1 435300 137213-2
435512 263230-6

349600
Outdoor Unit (A4UN306FA0)

668713 W6200
546810
W0CZZ-3
W6640-1
437210
559010 W0CZZ-2
W0CZZ-1
669200 W6640-2

447910
435511
658740

- 130 -
668711 649950

552112
554160
561410-1
552116
556000 561410-2

263230-5 552115

263230-4 561411-1
263230-3
561411-2

561411-3
561410-3
435311

561411-4 552203-1
552203-2
430410
552113
Outdoor Unit Parts List (A4UN306FA0)

Location No. Description Part No. Remarks


137213-1 PANEL ASSEMBLY, SIDE 1A00202F R
137213-2 PANEL ASSEMBLY, SIDE 3A02284X R
263230-1 THERMISTOR ASSEMBLY 6323A20001A R
263230-3 THERMISTOR ASSEMBLY 6323A20002S R
263230-6 THERMISTOR ASSEMBLY 6323A20002Z R
263230-4 THERMISTOR ASSEMBLY 6323AQ3226L R
263230-5 THERMISTOR ASSEMBLY 6323AQ3226M R
263230-2 THERMISTOR ASSEMBLY 6323AQ3226X R
349600 MOUNT, MOTOR 1A00206B R
430410 BASE ASSEMBLY, WELD[OUTDOOR] 3041A20022D R
435300 GRILLE, REAR 1A00208D R
435311 GRILLE, DISCHARGE 3530A20007B R
435511 COVER ASSEMBLY, CONTROL(OUTDOOR) 3550AR2886C R
435512 COVER ASSEMBLY, TOP(OUTDOOR) 3H03266L R
437210 PANEL ASSY, FRONT SUB 1A00197C R
447910 BARRIER ASSEMBLY, OUTDOOR 2A01043T R
546810 MOTOR ASSEMBLY, OUTDOOR 4681A20013Z R
552112 TUBE ASSEMBLY, CONDENSER IN 5211A20899A R
552113 TUBE ASSEMBLY, CONDENSER OUT 5211A21035A R
552115 TUBE ASSEMBLY, MENIFOLD(OUTDOOR) 5211A20419B R
552116 TUBE ASSEMBLY, REVERSING(OUTDOOR) 5211A10271B R
552203-2 VALVE, SERVICE 5220A20035A R
552203-1 VALVE, SERVICE 5220A20034A R
554031 CONDENSER ASSEMBLY, BENT 5403A20141A R
554160 COMPRESSOR SET 2520UUBV2AA R
559010 FAN ASSEMBLY, PROPELLER 1A00195B R
561410-1 COIL ASSEMBLY, REVERSING VALVE 6141A20010C R
561410-2 COIL ASSEMBLY, SOLENOID 6141A20013H R
561410-3 COIL ASSEMBLY, SOLENOID 6141A20013J R
561411-1 COIL ASSEMBLY, EXPANSION 6141A30003B R
561411-2 COIL ASSEMBLY, EXPANSION 6141A30003C R
561411-3 COIL ASSEMBLY, EXPANSION 6141A30003D R
561411-4 COIL ASSEMBLY, EXPANSION 6141A30003E R
566000 SWITCH, PRESSURE 3A02524F R
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A10053H R
658740 REACTOR 5874A90001G R
668711 PWB(PCB) ASSEMBLY, MAIN(OUTDOOR) 6871A20204S R
W6200 FILTER(CIRC), EMC 6200JB8008L R
668713 PWB(PCB) ASSEMBLY, SUB 6871A20205A R
W0CZZ-2 CAPACITOR, DRAWING 0CZZA90001D R
W0CZZ-1 CAPACITOR, DRAWING 0CZZA90001G R
W0CZZ-3 CAPACITOR, DRAWING 2A00986D R
W6640-1 TERMINAL BLOCK 3A00093A R
W6640-2 TERMINAL BLOCK 4G00103C R
669200 RELAY 6920AP3400A R
738281 MANUAL, SERVICE 3828A20097N R
738290 MANUAL, OWNERS 3828A20331A R

- 131 -
August, 2003
Printed in Korea
P/No.: 3828A20097N

You might also like