NCU Diagnostic Displays and Switches: Tatus
NCU Diagnostic Displays and Switches: Tatus
The NCU diagnostic features are found on the lower front face
and consists of a 7-segment display unit and 8 status-
LED Location
display.
The 7 segment display is found
beneath the light blue clip-on
cover.
Notes
The 7-Segment display is located behind the lower cover of 7-segment Meaning
the control unit. display
The display can output a single numeric value (0 to 9) or a
1 Not applicable.
single letter (A, C, E, F, P). A decimal point is present to the
lower right of the numeric value. 2 Not applicable.
It serves as a status display during commissioning and can 3 Debugger was initialised.
be used to display the following information:
4 NRK operating system was successfully acti-
IP address of the NCU vated.
5 NRK operating system has booted, init task is
Test and diagnosis information
being processed (The application boots)
Status during booting 6 Initialisation was successfully performed; the
6. control is in cyclic operation and the cycles are
During normal operation a "6." is displayed with the point active.
F Internal error.
An "8" indicates that the fan is defective or that the Control 1 or 2 CF card and SRAM data do not match. To re-
Unit is operating without a fan. solve this problem, a general reset is required by
booting with NCK- Switch position 1 or 2.
During the boot phase the display changes to indicate the
different stages of the boot process.
System Errors
7 segment Meaning
LED and the 7-segment display. display
Permanent error
C
Meaning found in the system log-file.
Flashing red Permanent error: System stopped P
@ 2Hz (See below for 7-segment display) Temporary error
Flashing red/ Temporary error: System may continue with
orange @ restricted functions.
Compact Flash Card (An additional point is dis-
2Hz (See below for 7-segment display) E
that the CF card is defective.
Notes
Two rotary switches, one for NCK functions and one for PLC Switch
Function
functions are also present. Certain tasks can be achieved Position
depending on the position of the switches.
0 Normal NCK boot up
1 NCK boot up with default values (Memory reset)
ton is conveniently located for this purpose.
7 Debug mode, NCK is not started.
8 IP address is displayed on 7 segment display
All others Not relevant.
RESET-button Switch
Function
Position
A036: END
Notes