Internship Final Report
Internship Final Report
Internship Final Report
CHAPTER-1
INTRODUCTION
The present day electrical power system is ac i.e. electric power is generated,
transmitted and distributed in the form of Alternating current. The electric power is
produce at the power station, which are located at favorable places, generally quite
away from the consumers. It is delivered to the consumer through a large network
of transmission and distribution. At many place in the line of power system, it may
be desirable and necessary to change some characteristic (e.g. Voltage, ac to dc,
frequency power factor etc.) of electric supply. This is accomplished by suitable
apparatus called sub-station for example, generation voltage (11KV or 6.6KV) at
the power station is stepped up to high voltage (Say 220KV to 132KV) for
transmission of electric power. Similarly near the consumer’s localities, the voltage
may have to be stepped down to utilization level. This job is again accomplished
by suitable apparatus called sub-station.
CHAPTER 2
ABOUT THE ORGANIZATION
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
3. Current Scenario
Power Sector is one of the most important infrastructure sectors essential for
economic development, human welfare and higher standard of living. With an
objective as mandated in Electricity Act, 2003 to build, operate and maintain an
efficient Power Transmission System in the State of Karnataka, being the State
Transmission Utility (STU), KPTCL is one of the path to achieving global
standards in transmitting reliable and quality power in the State and is committed
to provide cost effective and quality services to its valued customers.
4. Vision Statement
5. Mission Statement
6. Overview
Government vide order No. 69 BSR 2001 Bangalore, dated 15/02/2002 has
unbundled KPTCL and formed four distribution companies. Consequent to this the
function of distribution of power has been totally separated from KPTCL. KPTCL
is now vested with the responsibility of transmitting power all over the State and
construction and maintenance of Stations and lines of 66KV and above. The four
newly formed independent distribution companies, which were registered on
30/04/2002, are Bangalore Electricity Supply Company, Mangalore Electricity
Supply Company, Hubli Electricity Supply Company and Gulbarga Electricity
CHAPTER 3
OVER VIEW ON
220/66/11KV NRS RECIVING SUBSTATION
I. Introduction
N.R.S, an abbreviation for New Receiving Station, is one of the oldest
Substations of KPTCL (Karnataka Power Transmission Corporation) functioning
from 1951. 220 KV two lines are coming from Vrushabavathi and Peenya
Presently NRS is one of the biggest station (But very compact) in Bangalore
handling about 3 million units per day, with a Peak load of the station at about 176
MW’s. Out of this about 100 mega watts are handled at 66KV side and the balance
70 megawatts are handled at 11KV side. As regards equipments of this station, one
can see equipments manufactured about 50 years back to latest.
Two 100 MVA transformers are connected to stepped down the 220 KV Voltage
to 66 KV Voltage. Transformer 1 made of NGEF and Transformer 2 is of ABB, to
match the impedance of the transformer they are operated within 2 to 7 numbers of
the taps. And 5 numbers of 66KV/ 11KV transformers are connected to feed local
feeder of 11 KV. Two numbers are single bus arrangement is available in this
substation 220 KV and 66 KV bus.
CHAPTER 4
SUBSTATION
1. What Is A Substation?
The word substation comes from the days before the distribution system became a
grid. As central generation stations became larger, smaller generating plants were
converted to distribution stations, receiving their energy supply from a larger plant
instead of using their own generators. The first substations were connected to only
one power station, where the generators were housed, and were subsidiaries of that
power station.
2. Types Of Substation
Substations may be described by their voltage class, their applications within the
power system, the method used to insulate most connections, and by the style and
materials of the structures used
Transmission substation
Distribution substation
Collector substation
Converter substations
Switching station
Mobile substation
3. Selection Of Site
Main points to be considered while selecting the site for Grid Sub-Station are as
follows:
i) The site chosen should be as near to the load center as possible.
ii) It should be easily approachable by road or rail for transportation of equipments.
iii) Land should be fairly leveled to minimize development cost.
iv) Source of water should be as near to the site as possible. This is because water
is required for various construction activities (especially civil works), earthing and
for drinking purposes etc.
v) The sub-station site should be as near to the town / city but should be clear of
Public places, aerodromes, and Military / police installations.
vi) The land should be have sufficient ground area to accommodate substation
Equipments, buildings, staff quarters, space for storage of material, such as store
yards and store sheds etc. with roads and space for future expansion.
vii) Set back distances from various roads such as National Highways, State
Highways should be observed as per the regulations in force.
viii) While selecting the land for the Substation preference to be given to the Govt.
Land over private land.
ix) The land should not have water logging problem.
x) Far away from obstructions, to permit easy and safe approach/termination of
high voltage overhead transmission lines.
4. Equipments In Substation
A. Power Transformers
Design
The skeleton of the power transformer is designed with metal which is laminated
by sheets. It is fixed into either a core type or shell type. The skeletons of the
transformer are wound and connected using conductors to make three 1-phase or
one 3-phase transformer. Three 1-phase transformers requires each bank isolated
from the additional and thus offer continuity of service when one bank flops. A
single 3-phase transformer, whether the shell or core type, will not function even
with one bank out of service. The 3-phase transformer is inexpensive to make and
it has a smaller footprint, and functions comparatively with higher efficiency.
The skeleton of the transformer is absorbed in fire retardant protecting oil inside a
tank. The conservatory on top of the oil tank lets for the increasing oil to fall into
it. The charger of the load taps to the side of the tank changes the no of turns on the
high voltage-low current winding for superior voltage regulation. The bushings of
the tank permit for conductors to carefully enter and exit the tank without
stimulating the outer shell. The power transformer can be worked beyond its small
rating as long as it stays within the 65ºC rise of the temperature. To allow the
above nominal operation, transformers are built-in with fans that cool the core of
the transformer to a point below the indicated temperature.
Specifications
Power transformers can be designed as either a single phase or a three phase
configuration. There are numerous important specifications to identify when
searching for power transformers. The specifications of power transformer include
a maximum power rating, maximum secondary current rating, maximum voltage
rating and o/p type. Power transformer specifications mainly include
Phase is 3Ø
Frequency if 60Hz,50Hz
Primary Voltage is 22.9 kV
Secondary Voltage is 6.6/3.3 kV
Tap Voltage 23.9-R22.9-21.9-20.9-19.9kV
Vector Dd0, Dyn11, etc.
B. Instrument Transformer
Primary of P.T. is having large no. of turns. Primary is connected across the line
(generally between on line and earth). Hence, sometimes it is also called the
parallel transformer. Secondary of P.T. is having few turns and connected directly
to a voltmeter. As the voltmeter is having large resistance. Hence the secondary of
a P.T. operates almost in open circuited condition. One terminal of secondary of
P.T. is earthed to maintain the secondary voltage with respect to earth. Which
assures the safety of operators?
Capacitor stack the capacitor stack is a voltage divider which provides a reduced
voltage at the intermediate voltage bushing for a given the voltage applied to the
primary terminal. The capacitor stack is a multi-capacitor unit assembly. Each unit
is housed in an individual insulator. A cast aluminum cover is on top of the upper
capacitor assembly and is fitted with an aluminum terminal. An adapter for
mounting a line trap on top of the CVT can be provided with an optional (and
removable) HV terminal. The capacitor units are mechanically coupled together by
means of stainless steel hardware passing through the corrosion resistant cast
aluminum housing. The mechanical connection also establishes the electrical
connection between capacitor units. This facilitates field assembly of the CVT.
C. Lightning Arrester
A lightning arrester is a device used on electric power systems
and telecommunication systems to protect the insulation and conductors of the
system from the damaging effects of lightning. The typical lightning arrester has
a high-voltage terminal and a ground terminal. When a lightning surge (or
switching surge, which is very similar) travels along the power line to the arrester,
the current from the surge is diverted through the arrester, in most cases to earth.
This is the first component in an electrical substation, and the main function of
these components is to protect the components of the substation from passing high
voltage as well as stops the amplitude and duration of the flow of current. The light
arrestor components are connected among the earth as well as a line which mean
parallel to the components under defense at the electrical substation. If protection
fails or is absent, lightning that strikes the electrical system introduces thousands of
kilovolts that may damage the transmission lines, and can also cause severe
damage to transformers and other electrical or electronic devices. Lightning-
produced extreme voltage spikes in incoming power lines can damage electrical
home appliances or even produce death.
D. Circuit Breaker
The circuit breaker must first detect a fault condition. In small mains and low
voltage circuit breakers, this is usually done within the device itself. Typically, the
heating or magnetic effects of electric current are employed. Circuit breakers for
large currents or high voltages are usually arranged with protective relay pilot
devices to sense a fault condition and to operate the opening mechanism. These
typically require a separate power source, such as a battery, although some high-
voltage circuit breakers are self-contained with current transformers, protective
relays, and an internal control power source.
Once a fault is detected, the circuit breaker contacts must open to interrupt the
circuit; this is commonly done using mechanically stored energy contained within
the breaker, such as a spring or compressed air to separate the contacts. Circuit
breakers may also use the higher current caused by the fault to separate the
The bus bar system consists the isolator and the circuit breaker. On the occurrence
of a fault, the circuit breaker is tripped off and the faulty section of the busbar is
easily disconnected from the circuit. The electrical bus bar is available in
rectangular, cross-sectional, round and many other shapes. The rectangular bus bar
is mostly used in the power system. The copper and aluminum are used for the
manufacturing of the electrical busbar. The various types of busbar arrangement
are used in the power system. The selection of the bus bar is depended on the
different factor likes reliability, flexibility, cost etc. The following are the electrical
considerations governing the selection of any one particular arrangement.
F. Protective Relays
A relay is automatic device which senses an abnormal condition of electrical
circuit and closes its contacts. These contacts in turns close and complete the
circuit breaker trip coil circuit hence make the circuit breaker tripped for
disconnecting the faulty portion of the electrical circuit from rest of the healthy
circuit.
Pickup Level of Actuating Signal: The value of actuating quantity (voltage or
current) which is on threshold above which the relay initiates to be operated. If the
value of actuating quantity is increased, the electromagnetic effect of the relay coil
is increased, and above a certain level of actuating quantity, the moving
mechanism of the relay just starts to move.
Reset Level: The value of current or voltage below which a relay opens its
contacts and comes in original position.
Operating Time of Relay: Just after exceeding pickup level of actuating quantity
the moving mechanism (for example rotating disc) of relay starts moving and it
ultimately closes the relay contacts at the end of its journey. The time which
elapses between the instant when actuating quantity exceeds the pickup value to
the instant when the relay contacts close.
Reset Time of Relay: The time which elapses between the instant when the
actuating quantity becomes less than the reset value to the instant when the relay
contacts return to its normal position.
Reach of Relay: A distance relay operates whenever the distance seen by the relay
is less than the pre-specified impedance. The actuating impedance in the relay is
the function of distance in a distance protection relay. This impedance or
corresponding distance is called the reach of relay.
Types of Relays
Types of protection relays are mainly based on their characteristic, logic, on
actuating parameter and operation mechanism.
G. Insulators
Electrical Insulator must be used in electrical system to prevent unwanted flow of
current to the earth from its supporting points. The insulator plays a vital role in
electrical system. Electrical Insulator is a very high resistive path through which
practically no current can flow. In transmission and distribution system, the
overhead conductors are generally supported by supporting towers or poles. The
towers and poles both are properly grounded. So there must be insulator between
tower or pole body and current carrying conductors to prevent the flow of current
from conductor to earth through the grounded supporting towers or poles.
Insulating Material
The main cause of failure of overhead line insulator, is flash over, occurs in
between line and earth during abnormal over voltage in the system. During this
flash over, the huge heat produced by arcing, causes puncher in insulator body.
Viewing this phenomenon the materials used for electrical insulator, has to posses
some specific properties.
Figure: - Insulators
Types of Insulators
There are 5 types of insulators used in transmission lines as overhead insulation:
1. Pin Insulator
2. Suspension Insulator
3. Strain Insulator
4. Stay Insulator
5. Shackle Insulator
Pin, Suspension, and Strain insulators are used in medium to high voltage systems.
While Stay and Shackle Insulators are mainly used in low voltage applications.
H. ISOLATOR
The isolator can be defined as; it is one type of mechanical switch used to isolate a
fraction of the electrical circuit when it is required. Isolator switches are used for
opening an electrical circuit in the no-load condition. It is not proposed to be
opened while current flows through the line. Generally, these are employed on
circuit breaker both the ends thus the circuit breaker repair can be done easily
without any risk.
Figure: Isolator
I. EARTHING SWITCH
J. BATTERIES
Figure: Batteries
The instrument used for measuring the physical and electrical quantities is known
as the measuring instrument. The term measurement means the comparison
between the two quantities of the same unit. The magnitude of one of the quantity
is unknown, and it is compared with the predefined value. The result of the
comparison obtained regarding numerical value. The measuring instrument
categorised into three types;
Electrical Instrument
Electronic Instrument
Mechanical Instrument
The mechanical instrument uses for measuring the physical quantities. This
instrument is suitable for measuring the static and stable condition because the
instrument is unable to give the response to the dynamic condition. The electronic
instrument has quick response time. The instrument provides the quick response as
compared to the electrical and mechanical instrument. The electrical instrument is
used for measuring electrical quantities likes current, voltage, power, etc.
The ammeter, voltmeter, wattmeter are the examples of the electrical measuring
instrument.
L. Conductor
covers.” The underground cables has several advantages over overhead line like
less effect or damage though lighting, less maintenance cost, less chance of fault,
smaller voltage drop, better general appearance & most reliable. In a modern
power system for power distribution, generally used underground cables. However
recent improvement in the design & manufacturing has leaded the development of
the cable suitable for used at high voltages. This has made it possible to employ
underground cables for transmission of electric power for short or moderate
distance. This review paper focuses on the various types of cables which are used
for the 11kv power transmission. The design and construction of underground
transmission lines differ from overhead lines because of two significant technical
challenges that need to be overcome.
These are:
1)Providing sufficient insulation so that cables can be within inches of grounded
material
2) Dissipating the heat produced during the operation of the electrical cables
b) Insulation
c) Metallic Sheath
d) Bedding
e) Armouring
f) Serving
Properties of Conductor:-
a) A conductor always allows free movement of electrons or ions.
b) The electric field inside a conductor must be zero to permit the electrons or ions
to move through the conductor.
c) Charge density inside a conductor is zero i.e. the positive and negative charges
cancel inside a conductor.
d) As no charge inside the conductor, only free charges can exist only on the surface
of a conductor.
M. Feeders
i. To supply the power at load/consumer end, substation has transformer (usually
step-down) to change the voltage level to a standard distribution level voltage.
ii. To connect the consumer/load end with the substation, we have feeders. There are
no tapping taken out of them. They just connect the consumer area with the
substation.
iv. Feeder is network of conductors which feeds power in different localities from
sub-station usually at 11kV. It makes power reach near the consumers where
11kV is stepped down to 440V for uses. According to purposes and requirements
feeders are divided into four groups
Figure: Feeders
a. And they are Radial feeder, Ring Feeder, Parallel feeder, Meshed System.
i. There are 36 feeders in NRS station and they are fed to various areas
ii. These 36 feeders is divided into two sections namely bank1, bank2, bank3 with
bus coupler for load management.
iii. Feeder panel consists of vacuum circuit breaker, bus-bar, earth fault relay, over
current relay, isolator switch, indicators, meters, UG cable etc,.
N. Wave Trap
Figure: Earthing
The substation grounding system comprises of a grid (earth mat) formed by a
horizontal buried conductors. The grounding system in substation is very
important.
The functions of grounding systems or earth mat in include:
To ensure safety to personnel in substations against electrical shocks.
To provide the ground connection for connecting the neutrals of star connected
transformer winding to earth (neutral earthing ).
To discharge the over voltages from overhead ground wires to earth. To provide
ground path for surge arresters. To provide a path for discharging the charge
between phase and ground by means of earthing switches.
To provide earth connections to structures and other non-current carrying
metallic objects in the sub-station (equipment earthing).
If the switchyards have a soil of low resistivity, earth resistance of the earthing
system would be low. If the soil resistivity is high, the mesh rods are laid at
closer spacing. More electrodes are inserted in the ground.
P. TRANSMISSION TOWER
Q. Control Room
Figure: CR Panels
Figure: CR Panels
R. SCADA
Supervisory Control and Data Acquisition (SCADA) is an automation control
system. The system has a centralized system that monitors and controls entire
Substations throughout the KPTCL network and is connected across the Karnataka
state. A SCADA system works by operating with signals that communicate via
channels to provide the user with remote controls of any equipment in a given
system. It also implements a distributed database or points throughout the
substation. These points represent a single input or output value that is monitored
or controlled by the SCADA system in the centralized control room. The points are
stored in the distributed database as value-timestamp pairs. While these systems
simplify a given infrastructure, their components are quite complex.
There are five essential composing parts of a SCADA system:
Human Machine Interface (HMI)
supervisory system
Remote Terminal Units (RTUs)
Programmable Logic Controllers (PLCs)
communication infrastructures
Figure: CR Panels
CHAPTER 5
REFLECTION NOTES
Work Experience
Started from 13th January 2020 for a period of 17 days till date 31th January
2020. Internship carried out at KPTCL is very good opportunity for an
Electrical Engineer because of core sector. Power system is vast network and
there are many things to learn.
Now, I am also aware of how load is managed during the variations of input
and output of substation. Here load is managed accordingly by load
monitoring and load shedding.
Also learnt about SCADA in receiving station which controls and monitors
the electrical equipments also collects the data from it and accordingly
maintenance is done.
And also performed the related work assigned by Maintenance Engineer during
my tenure.
Safety is the important factor. All the equipments in substation are properly
grounded and well maintained. Technicians who perform duty in substation
yard uses safety shoes, helmets, hand gloves and goggles etc.
Mainly KPTCL has the motto of providing uninterrupted quality power supply.
Conclusion
Now from this report i can conclude that electricity plays an important role in our
life. From the generation, the power is transmitted and distributed to consumer end
using various transmission and distribution stations at various scales throughout a
power system. In general, they represent an interface between different levels or
sections of the power system, with the capability to switch or reconfigure the
connections among various transmission and distribution lines. The major stations
include a control room from which operations are coordinated. Smaller distribution
substations follow the same principle of receiving power at higher voltage on one
side and sending out a number of distribution feeders at lower voltage on the other,
but they serve a more limited local area and are generally unstaffed. The central
component of the substation is the transformer, as it provides the effective interface
between the high- and low-voltage parts of the system. Other crucial components
are circuit breakers and switches. Circuit breakers serve as protective devices that
open automatically in the event of a fault, that is, when a protective relay indicates
excessive current due to some abnormal condition. Switches are control devices
that can be opened or closed deliberately to establish or break a connection. an
important difference between circuit breakers and switches is that breakers are
designed to interrupt abnormally high currents (as they occur only in those very
situations for which circuit protection is needed), whereas regular switches are
designed to be operable under normal currents. Breakers are placed on both the
high- and low-voltage side of transformers. Finally, substations may also include
capacitor banks to provide voltage support.
References
K. P. Krishnarajendra, Superintending Engineer, KPTCL, Bangalore
“Hand Book On Metering And Protection”
KPTCL Website
http://www.kptcl.com/Zones/kptclZones.php
http://www.kptcl.com/kptclhistroy.htm
Electrical4u.com
wikipedia.org