NFS-320 Programming
NFS-320 Programming
NFS-320/E/C, NFS-320SYS/E
Programming Manual
This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for Class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options
must be limited to specific values or not used at all as indicated below.
Permitted in Permitted Settings
Program Feature or Settings Permitted
UL 864? in ULC 527- Possible Settings Permitted in ULC
Option in UL 864
(Y/N) 11? (Y/N) 527-11
IP downloads over a local No No Yes No No
area network (LAN) or the No
internet (WAN - WIde Area Timed
Network)
Releasing: Abort Switch Yes Yes NYC ULI ULI
AHJ IRI IRI
ULI
IRI
For Wireless Applications: Yes Yes 4 hours, 24 hours 4 hours 4 hours
Trouble Reannunciation
Alarm Reannunciation Yes Yes 4 Hours, 24 Hours 24 Hours 24 Hours
Supervisory Yes Yes 4 Hours, 24 Hours 24 Hours 24 Hours
Reannunciation
CO Reaannunciation Yes Y/N 4 Hours, 24 Hours 24 Hours Y/N
Detector Programming: Yes Yes SUP L(DUCTI) SUP L(DUCTI) SUP L(DUCTI)
Supervisory Type Codes SUP T(DUCTI) SUP T(DUCTI) SUP T(DUCTI)
SUP T(DUCTP) SUP L(DUCTP) SUP L(DUCTP)
SUP L(DUCTP) SUP T(DUCTP) SUP T(DUCTP)
SUP L(ION)
SUP T(ION)
SUP L(PHOTO)
SUP T(PHOTO)
SUP L(LASER)
SUP T(LASER)
PHOTO/CO (P SUP)
ALA.SCROLL (Scroll Yes Yes Y N N
Display) N
TBL.REMIND Yes Yes *, 1, 2, 3, 4, 5 2 2
Alarm Verification timer Yes Yes 0 to 240 seconds 0 to 60 seconds 0 to 60 seconds
REGION No No 0 (No special setting) 0 (No special 2 (Canada)
1 (China) setting)
2 (Canada)
DCC Enable Yes Yes Yes, No Yes or No Yes
Table 1.1 Programming Settings
CAUTION:
! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,
RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
WARNING:
! INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO
THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL
INJURY.
NOTE: Information that highlights an important part of the preceding or subsequent text or illustration.
NOTE: The term NFS-320 is used in this manual to refer to the NFS-320/C, the NFS-320E and the NFS-320C,
NFS-320SYS AND NFS-320SYSE unless otherwise noted.
1.4 Features
Programming features include the following:
• Ease-of-use – Field program the control panel without needing special software skills.
• Autoprogram option – Automatically detects newly installed, addressable devices, allowing quicker installation.
• Local programming – program directly from the control panel keypad to reduce installation time.
• PC programming – input long data entry programming information on a PC; transfer programming data between a PC and the
control panel using VeriFire™ Tools programming utility.
• Security – use passwords to control access to the control panel and protect memory.
• 80-Character (2x40) Liquid Crystal Display – view programming and device information on the control panel.
In Program Change or Status Change, the control panel does the following:
• Activates the System Trouble relay
• Shuts off the panel sounder
• Flashes the SYSTEM TROUBLE LED, which continues to flash while programming
For security purposes, passwords can be changed. To do so, follow the instructions in “How to Enter a Password” on page 11.
NOTE: The Read Status selection, which does not require a program password, is covered in the NFS-320
Operations Manual.
NOTE: The NFS-320 continues to monitor and report alarms in programming mode, except in
autoprogramming.
Section 2: Programming
2.1 Overview
Program Change is the programming level that lets you change the essential control panel functions, such as point programming,
changing passwords, changing system functions. Included are four options: Basic Program, Network, FlashScan Poll, and Utility
Program.
The structure of the Program Change option is shown below:
This section contains instructions and sample screens for using the Programming selections:
• Basic Program The Basic Program lets you program essential functions, such as clearing the program, Autoprogram-
ming the system, programming points, and setting system functions. Refer to “Basic Program” on page 14.
• Network Program The Network Program allows programming of network channel thresholds, network node number,
and wiring style.“The Network Program” on page 44.
• Utility Program The Utility Program screen provides selections for selecting a Trouble Reminder per NFPA, selecting a
Region setting, and enabling or disabling local control of the ACKNOWLEDGE/SCROLL DISPLAY, SIGNAL SILENCE, DRILL and
SYSTEM RESET keys. Refer to “The Utility Program” on page 44.
• FlashScan Poll The FlashScan Poll screen provides the option for selecting between CLIP (Classic Loop Interface Poll)
and FlashScan Poll. Refer to “FlashScan Poll” on page 46.
2. At the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen as shown below:
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT) _
3. Enter your Program Change password (See “Change a Password (3=PASSWD)” on page 25). The control panel displays the
“Program Change Selection” screen, as shown below:
1=BASIC PROGRAM 2=NETWORK
3-UTILITY 4=FLASHSCAN POLL
Press the number of any one of the nine (9) options as detailed below
Option 0=CLR - Clears all existing user programming. For details, refer to How to Clear Memory (0=CLR) on page page 15. Note:
The user is prompted to double-check that this is what is really wanted.
Option 1=AUTO - Add or remove addressable devices to the control panel program. For details, refer to How to Autoprogram the
Control Panel (1=AUTO) on page page 15.
Option 2=POINT - Modify or delete a point. For details, refer to “How to Modify or Delete a Point (2=POINT)” on page page 19.
Option 3=PASSWD - Change the Program Change or the Alter Status password. For details, refer to “How to Change a Password
(3=PASSWORD)” on page page 25.
Option 4=MESSAGE - Edit the 40-character message that displays on the first line. For details, refer to “How to Create a System
Message (4=MESSAGE)” on page page 26.
Option 5=ZONES - Edit the 20-character custom zone label for zones 01-99. For details, refer to “How to Create a Custom Zone
Label (5=ZONE)” on page page 27.
Option 6=SPL FUNCT - Program Releasing Zones and Special Zones. For details, refer to “How to Program Special Zones (6=SPL
FUNCT)” on page page 27.
Option 7=SYSTEM - Program Global System Functions. For details, refer to “How to Change Global System Functions
(7=SYSTEM)” on page page 31.
Option 8=CHECK PRG - Check the program for errors. For details, refer to “How to Check the Program for Errors (8=CHECK
PRG)” on page 43.
1.From the “Basic Program” screen, press the 0 (zero) key to display the Clear Program screen. The control
panel prompts for verification as shown below:
PRESS ENTER TO CLEAR ENTIRE PROGRAM
OR ESCAPE TO ABORT
2. Press the ENTER key to clear control panel memory or press the ESC key to exit the screen without clearing.
Create a new program for A new control panel or a control panel with no “Create a New Program for the
the control panel existing program in memory. Control Panel” on page 15
Add one or more A program exists in memory and you want to “Add a Device to the Program”
SLC-connected detectors add a detector or module to the existing on page 16
and modules to an program—without modifying information for
existing program existing detectors and modules.
Remove one or more A program exists in memory and you want to “Remove a Device from the
SLC-connected detectors remove an installed detector or module from Program” on page 17
and modules from an the existing program—without modifying
existing program information for existing detectors and
modules.
View system defaults A program exists in memory and you want to “Change Autoprogram Default
view system settings assigned during Values” on page 17
Autoprogram, such as custom labels,
passwords, and so on.
1. Use the Clear option to clear program information from memory. For instructions on clearing memory, refer to “How to Clear
Memory (0=CLR)” on page page 15.
NOTE: Once Step 1 is completed, Step 2 will cause the panel to assess whether a loop is
comprised of all FlashScan devices or not. If they are all FlashScan, autoprogramming will
change the loop setting to FlashScan if it was not already at that setting. If the devices are not all
FlashScan, autoprogramming will not make a change to the default setting of CLIP. (See
“FlashScan Poll” on page 46 for FlashScan settings.)
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. While the control panel scans the system to identify all
SLC devices and NACs, it displays the following screen:
AUTOPROGRAM PLEASE WAIT
When the autoprogram is finished identifying SLC devices and NACs, it displays a summary screen that gives a count of all the
devices it has located. Refer to the following screen for an example of this display.
L1:010Dets, 159Mods
SB L1:010 Bells: 04
3. Press ENTER. All devices are automatically accepted during initial autoprogramming. The following screen displays briefly,
followed by the SYSTEM NORMAL screen.
ACCEPT ALL DEVICES Please Wait!!!
To edit the autoprogramming default values for a point, refer to “How to Modify or Delete a Point (2=POINT)” on page page 19.
To edit the autoprogram default values assigned to all modules and detectors during autoprogramming, refer to “Change
Autoprogram Default Values” on page 17.
Add a Device to the Program
You can also use the Autoprogram option to add addressable devices to the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices. However, it will assess
whether a loop contains all FlashScan devices and change the loop setting to FlashScan if
necessary.
The following steps describe how to add a new detector at SLC address 1D147 with 10 detectors in the existing program:
1. Physically install the addressable detector to the SLC at address 147 (for instructions, refer to the NFS-320 Installation Manual
and the installation document that comes with the detector).
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram Prompt screen appears in the LCD
display as the control panel identifies addressable devices. When finished identifying addressable devices, the control panel
displays information for the new detector at SLC address 1D147 on the LCD display as shown below:
PROGRM SMOKE(PHOTO) DETECTOR ADDR 1D147
03 __ __ __ __A8P8** 1D147
3. Press the ENTER key to add detector 147 to the program with the default program information. If you want to change the default
information, use the programming keys to do so, then press the ENTER key to add detector 147 to the program.
The Autoprogram Summary screen appears. You can verify addition of the detector to the program by noting the new count of
detectors as shown below:
Note that the number of detectors increases (in this example
from 10 to 11) to show the addition of the detector to the SLC.
L1:011Dets, 159Mods
Panel Outputs: 64 Bells: 04
4. Press the ENTER key, then press the esc key to save the program in memory and return to the “Basic Program” screen).
Remove a Device from the Program
You can also use the Autoprogram option to remove addressable detectors and modules from the control panel program.
NOTE: When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices.
The following steps describe how to delete a detector at SLC address 1D133 with 11 detectors connected to the SLC in the existing
program:
1. Disconnect and remove the detector from the SLC at address 1D133.
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. The Autoprogram Prompt screen displays while the
control panel identifies addressable devices.
3. When finished identifying addressable devices, the control panel displays a screen, indicating a missing detector at SLC
address 1D133 as shown below:
Type Code
4. Press the ENTER key to delete detector 1D133 from the program.
The Autoprogram Summary screen appears. You can verify removal of the detector from the program by noting the new count
of detectors as shown below:
Note that the number of detectors decreases (from 11 to
10) to show the removal of the detector from the SLC.
L1:010Dets, 159Mods
SB L1:010 Bells: 04
5. Press the ENTER key, then press the ESC key to save the program in memory and return to the “Basic Program” screen.
Change Autoprogram Default Values
To assign system default values from the basic program screen, Press 0 (clear), then press 1 (autoprogram). Refer to the chart below
for default values and how to modify them.
Table 2.1 Autoprogram Defaults (1 of 2)
Function Default Values To Alter, refer to
Software Default custom label “Zone xx” where xx is the “How to Create a Custom Zone Label (5=ZONE)” on page 27
Zones number of the zone
01-99 Note: Zone 00 is reserved for a general alarm.
F5 and F6 PRG TIME FUNCTION TIME CONTROL “F5-F6 (Time Control Functions) The Time Control screen
ON=**:** OFF=**:** DAYS=******** provides fields for changing the start time, stop time, or days of
the week. For details on time selections, refer to “Time Control
Zones” on page 87. From the Special Function Change screen,
select F5 or F6 to display the Time Control screen:” on page 30
F7 PRG HOLIDAY FUNCTION **/** **/** **/** “F7 (Holiday) The Holiday screen provides fields for specifying up to
**/** **/** **/** **/** **/** **/** nine holiday dates. For details on holiday selections, refer to “Time
Control Zones” on page 87. From the Special Function Change
screen, press F7 to display the Holiday screen:” on page 30
F8 PRG CODING FUNCTION CODE TYPE “F8 (Coding Function) The Coding Function screen provides
MARCH TIME F08 fields for specifying one of the following coding functions: March
Time, Two-stage, California, Temporal, Two-Stage Canada (3
minutes), Two-Stage Canada (5 minutes), Two-Stage Canada
Manual, System Sensor Strobe, Gentex Strobe, and Wheelock
Strobe. For details on selecting coding functions, refer to
“Coding Functions for NACS” on page 87. From the Special
Function Change screen, press F8 to display the Coding
Function screen:” on page 30
F9 PRE-ALARM FUNCT ALERT “F9 (Pre-Alarm) The Pre-Alarm screen provides fields for
F09 programming the Alert or Action Pre-Alarm functions. For
details on Pre-Alarm selections, refer to “Pre-Alarm” on
page 93. From the Special Function Change screen, press F9
to display the Pre-Alarm screen.” on page 30
System SIL INH=0000 AUTO=0077 “How to Change Global System Functions (7=SYSTEM)” on
Parameters 0 VERIFY=30 USA TIME page 31
TERM=N AC_DLY=Y LocT BLINK=01 ST=4 ACS=N
Passwords Default programming passwords are: “How to Change a Password (3=PASSWD)” on page page 25
Program Change=00000
Status Change=11111
SYSTEM (YOUR CUSTOM SYSTEM MESSAGE HERE) Note: The second line, “SYSTEM NORMAL”, is a standard
NORMAL SYSTEM NORMAL 10:23A 011508 Tue system message that you cannot change
message A message, along with the current day, time, and
date, that displays on the second line of the LCD
display during normal operation.
System (YOUR CUSTOM SYSTEM MESSAGE HERE) “How to Create a System Message (4=MESSAGE)” on page
Message SYSTEM NORMAL 10:23A 0711508 Tue page 26
The first line of the LCD display contains 40 blank
characters for a custom message.
IP ACCESS Default setting is zero (0), IP Access not enabled. “The Utility Program” on page 44
DCC Mode Default setting is zero (0), no DCC participation. “The Utility Program” on page 44
To modify a point for a detector, module, or NAC: press the 1 key to display the “Modify Point” screen.
NOTE: When programming points, take the following into design consideration:
Each general zone must be dedicated to a single device type (i.e. Fire, MN, Security, etc.).
Map inputs only to general zones designed for the input’s event type. For example, map mass notification devices to general zones
designed for mass notification.
Outputs can be mapped to multiple general zones that are dedicated to different event types. For instance, a single output can be
mapped to an MN general zone and a Fire general zone.
To delete a point for a detector, module, or NAC: press the 2 key to display the “Delete Point” screen.
Press for detector point.
SLC number (always displays 1)
Modify Point Screen Three-digit address (001-159)
E - press the
POINT PROG. ENTER:DETECTOR=*,LDAAA,E ENTER key
MODULE=#,1MAAA,E OUTPUT CKT=&,A-A,E
The Modify Point and Delete Point screens let you edit or delete points for a detector, a monitor or control module, or NAC. To
select a point, follow these steps:
Press
Press
Press
Press
The next four sections describe how to program the points selected.
Modify an Addressable Detector Point
This section contains a sample detector programming screen, detector default selection, and instructions for modifying a detector
point. Autoprogram default values for a detector are shown:
20-character user-editable custom label (in
this example, autoprogramming has used
Blinking Type Code selection
the first 19 and left a space at the end.)
Type Code Detector function Press the NEXT or PREVIOUS Selection keys to scroll through valid detector
specification - Type Code selections. See F.4 on page 106 for lists and descriptions.
SMOKE(PHOTO) in example.
Custom 20 character custom label. Change by placing the cursor into the first space of the field using the arrow
Label keys, then typing the descriptor. DETECTOR ADDR 1D101 is the
autoprogram default custom label for the detector at address 101 on the SLC.
CBE List Five zones can be listed - one Zones can be changed or added to the CBE list by placing the cursor in the
zone, Z03, is shown in the zone field using arrow keys, then typing.
example. Up to 4 more could Defaults: Zone 01 (Heat detectors)
be added to this detector. Zone 02 (Ion detectors)
Zone 03 (Photo detectors, Beam detectors)
Zone 04 (Laser detectors)
Zone 05 (Multisensor)
Alarm The alarm sensitivity level, Refer to Table C.1 on page 95 for settings. Select by placing the cursor in the
Sensitivity with 9 the least sensitive field using the arrow keys, then either pressing the NEXT or PREVIOUS keys to
alarm level and 1 the most make the selection, or typing the value.
sensitive alarm level. Defaults: A8 (Photo)
A6 (Ion)
A6 (Laser)
A5 (Multisensor)
Pre-alarm Shows the Pre-Alarm level Refer to Table C.1 on page 95 for settings. Select by placing the cursor in the
level setting—a number between 0 field using the arrow keys, then either pressing the NEXT or PREVIOUS keys to
and 9—as follows: make the selection, or typing the value.
0 – no Pre-Alarm Defaults: P8 (Photo)
1 – self optimizing P6 (Ion)
2 – most sensitive Pre-Alarm P6 (Laser)
level P5 (Multisensor)
9 – least sensitive Pre-Alarm
level
Cooperative Indicates the cooperative Select by placing the cursor in the field using the arrow keys, then either
Multi- multi-detector mode (A in the pressing the NEXT or PREVIOUS keys to make the selection, or typing the value.
detector example). * = OFF (Default)
mode A combines the detector's alarm decision with the next address above
B combines the detector's alarm decision with the next address below
C combines the detector's alarm decision with the next address above and the
next address below
Alarm Indicates the alarm Indicates Alarm Verification (V=on, *=off). Select by placing the cursor in the
verification verification setting (V in the field using the arrow keys, then pressing the NEXT or PREVIOUS keys to make
example). the selection. Refer to “Interpreting a Detector Status Display or Maintenance
Report” on page 98 for more information on the alarm verification feature.
Note: Do not use this setting when an alarm activation requires activation of
two or more automatic detection devices.
Type Code Monitor Module function Press the NEXT or PREVIOUS Selection keys to scroll through
specification - MONITOR in example. valid monitor module Type Code selections. Lists and
descriptions are in See F.4 on page 106.
Custom Label 20 character custom label. Change by placing the cursor into the first space of the field
using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any space
necessary between the custom and extended label fields. An
80-column printout will run the two fields together.
CBE List Five zones can be listed - one zone, Zones can be changed or added to the CBE list by placing
Z09, is shown in the example. Up to the cursor in the zone field using arrow keys, then typing.
4 more could be added to this See Table 2.4 on page 22 for defaults.
module.
When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to select another point.
Monitor Module Default Zone Assignments
Listing of the monitor module address range and the default zone assignment for each range:
01 through 19 Z04
20 through 39 Z05
40 through 59 Z06
60 through 79 Z07
80 through 99 Z08
NOTE: On a control module, the default zone is always set to Zone 00 (general alarm).
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1. From the programming screen, use the arrow keys to move to a field that you want to modify. See below for descriptions and
settings.
Type Code Specifies the function of the control Press the NEXT or PREVIOUS Selection keys to scroll
module through valid control module Type Code selections (listed
in Table F.5.2 on page 110)
Custom Label 20 character custom label. Change by placing the cursor into the first space of the
field using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any
space necessary between the custom and extended label
fields. An 80-column printout will run the two fields
together.
CBE list Up to five software zones can be Type the number of up to five zones, including E0-E9, F0-
entered to define the output responses F9, L0-L9, R0-R9, and zones 00-99. The first zone default
of the control module based on is Z00 (general alarm).
various initiating conditions (events)
Switch Inhibit Specifies if an operator can manually Type one of the following entries.
activate an output I = Switch Inhibit enabled
* = no switch inhibit (default for all but releasing circuits)
Silenceable Specifies if an operator can manually Type one of the following entries.
silence an activated output * = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
C = silenceable, resound by CO detection
If the “Strobe” Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,“*” will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.
Walk Test Specifies if outputs sound during Walk Type one of the following entries.
Test W = devices sound (Basic Walk Test)
* = devices do not sound (Silent Walk Test) (default)
2. When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to select another point.
Modify NAC Points
Modifying NACs (four NACs on the NFS-320) is like modifying control modules—except for the Type Code and device address.
Type Code 20-character user-editable custom label
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1. From the programming screen, use the arrow keys to move to a field that you want to modify and refer to information below for
descriptions and settings.
Type Code Specifies the function of the NAC. Press the NEXT or PREVIOUS Selection keys to scroll
through the NAC Type Code selections (listed in
Table F.1 on page 111)
Custom Label 20 character custom label. Change by placing the cursor into the first space of the
field using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any
space necessary between the custom and extended label
fields. An 80-column printout will run the two fields
together.
CBE zones Specifies up to five software zones to Type the numbers of up to five zones, including E0-E9,
define the output responses of the F0-F9, L0-L9, R0-R9, and zones 00-99. The first zone
NAC based on various initiating default is 00 (general alarm)
conditions (events)
Switch Inhibit Specifies if an operator can manually Type in one of the following values.
activate an output I = Switch Inhibit enabled
* = Switch Inhibit disabled (default for all but releasing
circuits)
Silenceable Specifies if an operator can manually Type in one of the following values.
silence an activated output * = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
C = silenceable, resound by CO detection
If the “Strobe” Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,“*” will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.
Walk Test Specifies if outputs sound during Walk Type in one of the following values.
Test W = devices sound (Basic Walk Test) - default
* = devices do not sound (Silent Walk Test)
2. When finished modifying a point, press the ENTER key; then press the NEXT or PREVIOUS key to select another point.
To Press Then
Change the Status Change Enter the new Status Change password.
password Use five digits, no characters.
INCORRECT PASSWORD
PROGRAM: 9066-21F5-7D78-5FA4-6163
Code
From the “Basic Program” screen, press the 4 key to display the “System Message Change” screen:
SYSTEM NORMAL
To Do this
The zone number displays in the first line, characters 39 and 40. When changing a zone label, follow these guidelines.
• For single-digit numbers, enter a leading zero before the digit.
• Enter an alphanumeric zone label into line 2, characters 21–40.
To change a custom label for a zone, follow these instructions:
To Do this
Change a zone label Enter a new zone label from the keypad.
NOTE: Special Zones F0-F9 appear in the CBE list of a device as ZF0-ZF9. For example, if you
list F0 for a detector, one of the five zones in the CBE list of the detector will display as ZF0.
F0=PRESIG Select a Presignal Delay Timer and select PAS (Positive Alarm
Sequence)
F5-F6=TIME Specify Time Control functions such as the start time, stop time, or
days of the week
FB (ZF16)* Turn on if custom drill set to Y and the panel in Drill mode (Alarm
Signal Mode for Canadian applications)
FD (ZF20*) Turns on when a mass notification alarm occurs (Not applicable for
FireCommand applications)
ZF36* If the local control active LED is on, this special zone will
activate
ZF40* Auto Silence Activation. ZF40 will activate when the auto
silence timer has expired and silenceable outputs on the
fire panel have been silenced as a result. ZF40 will remain
active until a system reset, resound, or drill (alarm signal for
Canadian applications) is performed.
R0-R9 (Releasing Functions) The Releasing Function screen provides fields for changing releasing functions: Delay Timer, Abort
Switch, Cross Zone, and Soak Timer. For details on releasing applications, refer to “NFPA Releasing Applications” on page 58.
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the DELAY and
SOK (soak) times.
From the Special Function Change screen, select a function (R0-R9) to display the Releasing Function screen:
Releasing Zone programming status banner
F7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. For details on holiday selections, refer to
“Time Control Zones” on page 87. From the Special Function Change screen, press F7 to display the Holiday screen:
Holiday programming status banner
PRG HOLIDAY FUNC **/** **/** **/**
**/** **/** **/** **/** **/** **/**
F8 (Coding Function) The Coding Function screen provides fields for specifying one of the following coding functions: March
Time, Two-stage, California, Temporal, Two-Stage Canada (3 minutes), Two-Stage Canada (5 minutes), Two-Stage Canada
Manual, System Sensor Strobe, Gentex Strobe, and Wheelock Strobe. For details on selecting coding functions, refer to “Coding
Functions for NACS” on page 87. From the Special Function Change screen, press F8 to display the Coding Function screen:
Coding Function programming status banner
F9 (Pre-Alarm) The Pre-Alarm screen provides fields for programming the Alert or Action Pre-Alarm functions. For details on
Pre-Alarm selections, refer to “Pre-Alarm” on page 93. From the Special Function Change screen, press F9 to display the
Pre-Alarm screen.
FA (Verification) Turn on when detector in verification mode. This is a fixed point and is not programmable.
FB (Custom drill zone) Turn on if custom drill is set to Y and the panel is in Drill mode (Alarm Signal for Canadian mode).
FC (CO Alarm) Turn on in the event a CO alarm is present on an FCO-851 detector or a monitor module with a CO monitor type
code.
FA, FB and FC can map to output point only. It can be mapped to the output device as a CBE using either panel key pad or VeriFire
Tools. But the custom drill option (Yes or No) is only programmed by VeriFire Tools.
FD (MN Alarm) Turn on when an MN Alarm occurs on the fire panel. (Not applicable for FirstCommand applications)
FE (MN Supervisory) Turn on when an MN Supervisory occurs on the fire panel.
FF (MN Trouble) Turn on when an MN Trouble occurs on the fire panel.
Pre-Alarm programming
status banner
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC_DLY setting of Y (3 hours). The UDACT/UDACT-2 is set for
notification after 1 hour.
1:00 p.m. - AC Failure. Panel notifies the UDACT/UDACT-2. Panel and UDACT/UDACT-2 timers begin countdown to
report time.
2:00 p.m. - UDACT/UDACT-2 reports.
4:00 p.m. - TM-4 reports, TB4 trouble relay activates.
The ACPS-610, ACPS-2406, power supplies must be set to an AC Delay value of 0 (zero) when used with this panel.
NOTE: An ACM-24AT or AEM-24AT LED point must be programmed as a dedicated visual indicator for a mass notification or CO
event. This is not required for displayless systems.
Use Annunciator Selection screens to select information that will display on the ACS annunciators. (Table 2.13 on page 34 contains
the ACS display selections.) Setting ACS=Y from the “System Function” screen displays the Annunciator Selection 1 screen, address
A1 - A11. Press enter to display Annunciator Selection 2 screen, address A12 - A19:
ACS Address ACS Selection Group (A-M; 0-9)
A1-A11 or *=not selected
ACS Address
A12-A19
ANNUN SELECTION2 A12=* A13=* A14=*
A15=* A16=* A17=* A18=* A19=* UDACT=N
If UDACT=2: The UDACT is installed with Detector Maintenance Reporting. A24-A31 are
pre-programmed to send control panel status to the UDACT. Only the first 100 detectors on
Loop 1 participate in Detector Maintenance Reporting. For pre-programmed point
addressing, refer to associated table for Groups P through W on the following pages.
UDACT-2 does not support this option.
If UDACT=1: The UDACT or UDACT-2 is installed. Addresses A20-A32 are available to
send control panel status to the UDACT (software release #UDACT02.1 or higher) or the
UDACT-2
If UDACT=0: No UDACT or UDACT-2 installed: The control panel displays the Annunciator
Selection 3 & 4 screen addresses A20-A32.
Enter “N” (ACS Selection Group N) for a TM-4 module used for remote station communication.
Enter “O” (ACS Selection Group O) for a TM-4 used as a municipal box trip. This will provide a “Master Box” trouble message at
the panel.
Refer to page page 40 for further information on Group N and Group O.
ACS Selection Group Example
An example of a screen listing ACS Selection Groups (H, I and M):
ACS Address (A1) ACS Selection Group (H)
ANNUN SELECTION1 A1=H A2=* A3=* A4=*
A5=8 A6=* A7=* A8=* A9=* A10=* A11=*
NOTE: Refer to the VeriFire™ Tools programming utility for programming these annunciators.
NOTE: Point number to Zone number relationship is sequential. To determine Point to Zone
relationship subtract 8 from Point number to arrive at Zone number.
61 NAC Output NAC B01 Active NAC B01 Trouble Controls NAC B01
62 NAC Output NAC B02 Active NAC B02 Trouble Controls NAC B02
63 NAC Output NAC B03 Active NAC B03 Trouble Controls NAC B03
64 NAC Output NAC B04 Active NAC B04 Trouble Controls NAC B04
* Pressing the switch button when the Switch Function is “Not Used” will cause the associated LED to stop
blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE:
1. Point number to Zone number relationship is sequential. To determine Point to Zone
relationship, add 56 to Point number to arrive at Zone number.
2. Point number to Zone number relationship is sequential; therefore, point 48 is zone F5 and
point 57 is zone R4.
NOTE: Point number to Module number relationship is sequential. To determine Point to Module
relationship add 64 to Point number to arrive at Module number.
NOTE:
1. Point number to Module number relationship is sequential. To determine Point to Module
relationship add 128 to Point number to arrive at Module number.
2. Point number to Module number relationship is sequential. To determine Point to Module
relationship add 96 to Point number to arrive at Module number.
NOTE:
1. Point number to Detector number relationship is sequential. To determine Point to Detector
relationship add 128 to Point number to arrive at Detector number.
2. Point number to Detector number relationship is sequential. To determine Point to Detector
relationship add 96 to Point number to arrive at Detector number.
Panel Programming
If VeriFire Tools is not used and Group M is programmed at the panel, Zone 00 (general alarm) will be mapped to A1p11 and
A1p40. A general alarm will play message 1 and activate an all-call on the FireVoice. VeriFire Tools must be used for speaker and
circuit and message control.
ACS Selection Group N
This group is the same as Group A (See Table 2.14 on page 35), with the following exceptions:
• It should be selected only for TM-4s used for remote station communication.
• Selection Group N follows the alarm relay for annunciation (Selection Group A annunciates immediately).
• The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is for Signal Silenced).
ACS Selection Group O
This group is the same as Group A (See Table 2.14 on page 35), with the following exceptions:
• It should be selected for only for TM-4s used as Fire Municipal Box Trip outputs.
• Selection Group O provides a “Master Box” trouble displayed at the panel.
• Selection Group O follows the alarm relay for annunciation (Selection Group A annunciates immediately).
• The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is for Signal Silenced).
NOTE:
1. Point number to Module number relationship is sequential. To determine Point to Module relationship add 64 to Point number to
arrive at Module number.
2. Point number to Detector number relationship is sequential in groups of 2. Since each detector occupies 2 points, to determine
the Point to Detector relationship, count by 2 starting from point 37.
3. This group is only available when UDACT setting is programed as option 2 and will automatically be assigned to ACS address
24.
NOTE:
1. Point number to Detector number relationship is sequential in groups of 2. Since each detector occupies 2 points, to determine
the Point to Detector relationship, start with detector 15 and count by 2 starting from point 1.
2. This group is only available when UDACT setting is programmed as option 2 and will automatically be assigned to ACS address
26.
NOTE:
1. Point number to Detector number relationship is sequential in groups of 2. Since each detector occupies 2 points, to determine
the Point to Detector relationship, start with detector 47 and count by 2 starting from point 1.
2. This group is only available when UDACT setting is programmed as option 2 and will automatically be assigned to ACS address
28.
NOTE:
1. Point number to Detector number relationship is sequential in groups of 2. Since each detector occupies 2 points, to determine
the Point to Detector relationship, start with detector 79 and count by 2 starting from point 1.
2. This group is only available when UDACT setting is programmed as option 2 and will automatically be assigned to ACS address
30.
THRESHOLD CH.A: - Enter H or L, for high or low threshold setting for channel A on the NCM module.
THRESHOLD CH.B: - Enter H or L, for high or low threshold setting for channel B on the NCM module.
NODE: - Enter the panel’s network node number. The valid network node number range is 1-103. The number will be entered after
the decimal point; the spaces before the decimal point are for future use.
CLASS X: - Enter N for network style determination (either Class A or Class X) through autoprogramming. Enter Y to force a
Class X designation for network wiring.
NOTE: If network Class X wiring is determined by autoprogramming, a change in the wiring (for
example, a break in the network wiring) would cause the system to reassess the network wiring
class as A If network Class X wiring is forced, a break in the wiring will create a trouble message.
TBL.REMIND This option provides trouble reannunciation selections to meet the requirements of NFPA 72-
TBL Reminder* 2002, which you can select as follows:
• Select * if you don’t want a trouble reminder
*Use of a setting • Select 1 to sound a short trouble reminder tone every minute
other than “2” • Select 2 to resound a trouble tone every 24 hours at 11:00 AM, and to send a reminder
requires AHJ every sixty seconds for acknowledged events.
approval. • Select 3 to display a detector while in the alarm verification mode and no trouble reminder
• Select 4 for once a minute trouble reminder with alarm verification display
• Select 5 for trouble reminder resound every 24 hours at 11:00 AM with alarm verification
display, and to send a reminder every sixty seconds for acknowledged troubles
ALA.SCROLL This option allows the programmer to select how alarms are displayed.
Alarm Scroll* • Select Y if you want each alarm displayed for approximately two seconds, and to
acknowledge all alarms with a single acknowledgement. (default)
*Setting this field to • Select N if you want only the first alarm and the alarm count displayed, and to acknowledge
“Y” requires AHJ each alarm singly, point by point.
approval.
LOCAL This option allows the programmer to disable local control of the ACKNOWLEDGE/SCROLL
CONTROL DISPLAY key, SIGNAL SILENCE key SYSTEM RESET key, and DRILL key. Local control selections
are as follows:
• Select 0 to disable local control
• Select 1 to enable local control (default)
• Select 2 to enable partial local control. This setting allows control of the ACKNOWLEDGE and
SYSTEM RESET keys only (required in Chicago).
Note that if the panel is to be controlled exclusively by a Display and Control Center (DCC),
Local Control should be disabled.
DCC Mode This option allows the programmer to select whether this panel will participate in DCC (Display
and Control Center) functions. Select Y for participation, N for no participation.
NOTE: For Mass Notification applications, DCC participation should be disabled.
This menu allows the selection of CLIP (Classic Loop Interface Protocol) or FlashScan detectors and modules for the loop. Once
this screen is accessed, the cursor will be positioned underneath the L1DET detector selection, blinking the currently selected
protocol type. The default selections are shown in the above figure. This indicates that loop detectors and modules are selected to
use CLIP devices. If FlashScan devices are to be employed, change the blinking cursor by pressing the Y key or toggle it by using
the PREVIOUS or NEXT key. After the selections have been made to the detectors and modules of the loop, press the ENTER key, at
which time the panel will reset.
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Observe one of the following three options
when using FlashScan devices:
Option 1 Program all modules and detectors on an SLC as FlashScan.
(In the “FlashScan Poll” screen, enter Y for DET and Y for MOD. It is possible to have up to 159 FlashScan modules
and 159 FlashScan detectors on this SLC.)
Option 2 Program all modules and detectors on an SLC as CLIP.
(In the “FlashScan Poll” screen, enter N for DET and N for MOD. It is possible to have up to 99 CLIP modules and 99
CLIP detectors on this SLC.)
CAUTION:
! Do not program more than 99 CLIP addresses, as this will compromise the response time of the
panel to display off-normal events.
Option 3 Program all detectors as CLIP and all modules as FlashScan on an SLC.
(In the “FlashScan Poll” screen, enter N for DET and Y for MOD. It is possible to have up to 99 CLIP detectors and
159 FlashScan modules on this SLC.)
CAUTION:
! Do not program modules as CLIP and detectors as FlashScan on the same SLC. The following
combination is not an option: Y for DET, N for MOD in the “FlashScan Poll” screen.
NOTE: Autoprogramming following a Clear Program command will cause the panel to determine
the FlashScan capability of the loop based on whether all devices on it are FlashScan or not. It will
set the loop settings to FlashScan if necessary.
2. Press the 1 key. The control panel displays the Enter Password screen, as shown below:
ENTER PROG OR STAT PASSWORD, THEN ENTER.
_ (ESCAPE TO ABORT)
3. Enter 2400B and press . The five asterisks that appear when you type in the baud rate will disappear when you press
NOTE: The serial EIA-232 CRT port can only be enabled in standalone (non-networked)
applications. The only baud rate supported is 9600.
1. From the SYSTEM NORMAL screen, press the ENTER key to display the Program Entry screen, as shown below:
2. Press the 1 key. The control panel displays the Enter Password screen, as shown below:
ENTER PROG OR STAT PASSWORD, THEN ENTER.
_ (ESCAPE TO ABORT)
3. Enter CRT96 and press . The five asterisks that appear when you type in the code will disappear when you press
3.1 Overview
Status Change provides a second programming level - accessed by an assigned password - for changing operating parameters.
(These operating parameters do not affect control program settings.) For example, the Status Change password lets you change
settings such as detector sensitivity and system time and date.
NOTE: Assign the Status Change password to persons who do not have access to Level 1
programming options.
2. From the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen as shown below:
ENTER PROG OR STAT PASSWORD, THEN ENTER.
3. Enter your Status Change password (See “How to Enter a Password”, page 11). The control panel displays the “Status Change
Selection” screen, as shown below:
STATUS CHANGE PRESS: 1=DISABL 2=SENSITIV
3=CLR VER 4=CLR HIST 5=TIME 6=WALK TEST
NOTE: When an input or output point associated with releasing functions is disabled, a single
supervisory trouble will be generated.
The Disable/Enable option lets you disable programmed points for detectors, modules, zones, and NACs. The
program allows you to disable an initiating device in alarm: however, the disable will not take effect until
Status Change after the panel has been reset.
Password
1. From the “Status Change Selection” screen, press the 1 key to display the “Disable/Enable” screen.
2. Select the point type:
for detectors
for modules
for NACs
for zones
The cursor will blink the first SLC address digit in the detector, zone, module, or NAC field.
D
WARNING:
! Disabling a zone disables all input and output devices that use the zone as the first entry in the
CBE list.
3. Enter the address of the point, then press the ENTER key. A sample display follows:
Blinking status banner (ENABLE or DISABL)
ENABLE CONTROL CONTROL ADDRESS 1M101
00 __ __ __ __ ISW 1M101
When you disable a point and press the ESC key to return to the Disable/Enable screen, the control panel: a) turns on the POINT
DISABLEDLED; b) sounds the panel sounder; and c) changes the status banner to TROUBL for the point.
You can disable or enable a point by changing the status banner as follows:
Table 3.1 Changing the Status Banner (1 of 2)
To Press
Change the status Maneuver the cursor with the arrow keys until it is in the status field. Press
To Press
To select a detector, enter the SLC address (D101) of an installed detector in the “LDAAA” field (shown above). The control panel
displays the following screen:
Use the instructions below to set/change detector sensitivity, display additional detectors, and set Pre-alarm values.
NOTE: If not using Pre-Alarm, set PA=0. PA=1 is the self-optimizing mode. For details, refer to
“How to Select a Pre-Alarm Level” on page 94.
To Enter or Press
Set alarm sensitivity level. A value (1-9) or increase or decrease values by pressing
The first digit flashes until you change the value or press the ENTER key. To set the system time and date, follow
the instructions below:
To Do this
Change the time and date values Enter values from the numeric keys on the keypad.
WARNING:
! Walk Test mode deactivates fire protection. Always observe the following:
1. Prior to Walk Test, secure all protected buildings, and notify the building owner/operator, fire department, and other
pertinent personnel that testing is in progress.
2. Immediately after Walk Test is completed, notify the same people that testing is complete and is restored to normal
operation.
WARNING:
! Physically disconnect all releasing devices before starting Walk Test. It is not sufficient to
disable in any other manner.
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
For information on programming Walk Test field selections, refer to “Modify or Delete a Point (2=POINT)” on page 19 or “Modify
NAC Points” on page 24.
Program Silenceable
For Silenceable Outputs will
Outputs with
To Press
Stop a Walk Test and return to the “Status Change Selection” screen
NOTE: Some detectors, laser detectors for example, can be difficult to place in alarm using a magnet.
Advanced Walk Test facilitates magnet testing of these detectors.
NOTE: The control panel can not be put into Walk Test from an alarm condition.
To Press
Advanced Walk Test directs the control panel to do the same as it does for Basic Walk Test (see “3.8.1, "Basic Walk Test"” above)
with the following exceptions:
37 3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop,....
152 15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long
stop....
• an input device activated in Basic Walk Test latches on steady green for the duration of the test.
• an output device activated in Basic Walk Test will remain active and the LED will glow steady green for:
- approximately 4 seconds for alarms
- approximately 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow steady green until the reset
key is pressed.
CLIP mode - Once the test is started:
• intelligent addressable input and output devices continue to blink red as usual until activated.
• an input device activated in Basic Walk Test latches on steady red during activation. If the device is put in trouble (for
instance, the detector head is removed, then replaced), the LED will be latched on for the duration of the test.
• an output device activated during Basic Walk Test will remain active and the LED will glow steady green (if a FlashScan
module) or steady red (if a CLIP module) for:
- approximately 4 seconds for alarms
- approximately 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow steady green (if a FlashScan
module) or steady red (if a CLIP module) until the reset key is pressed.
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions.
A.1 Overview
A.1.1 Description of Releasing Zones
The control panel includes ten Releasing Zones (R0-R9) that can be used to control up to ten releasing operations. Each zone
operates independently, and is fully programmable..
NOTE: Releasing Zones R0-R9 appear in the CBE list of devices as ZR0-ZR9. For example, if
you list R5 for a detector, one of the five zones in the CBE list of the detector will display as ZR05.
From the “Special Function Change” screen (refer to “Program Special Zones (6=SPL FUNCT)” on page 27), select a Releasing Zone
(R0-R9) to display the “Releasing Function” screen:
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=30 ABORT=ULI CROSS=N SOK=0000 R05
Delay Program a 01 to 60-second Delay Timer (or 00, no delay). The Delay Timer equals the
time that must elapse between activating an initiating device and activating the releasing
zones mapped to the active initiating device. Refer to “Programming a Delay Timer” on
page 58.
Abort Select a 3-letter Abort switch Type Code (ULI, IRI, NYC, or AHJ) that adds a delay time
to a Releasing Zone, or prevents a release of a Releasing Zone. Refer to “Abort
Switches” on page 59.
Cross Select one of three Cross Zone types or “N” (not used). A Cross Zone requires tripping
two or more devices to activate the outputs mapped to one of the Releasing Zones.
Refer to “Using Cross Zones” on page 67.
Soak Select a Soak Timer (0001-9999 seconds) or “0000” (not used). Refer to “Programming a
Soak Timer” on page 69.
Standard Covers
Zone R1 activate.
activates.
30 30
To Program Do this
Delay Timer Enter a value (00-60) from the numeric keys on the keyboard.
Press at this point to save the Delay Timer value if no other fields on the screen are changing. To change another field on
the screen, move the cursor into position by pressing the arrow keys.
Manual Agent
Release lever
NBG12LRAface.wmf
NBG-12LRA station with Abort Switch
This section contains information for programming each type of Abort Switch for a Releasing Zone.
How an Abort Switch Works
The figure below contains an example for configuring an Abort Switch and shows the requirements for using an Abort Switch for
Releasing Zone R05, which are:
• A monitor module is wired to an abort station
• The monitor module is programmed with the Type Code, ABORT SWITCH
• All initiating devices and outputs are mapped to a common Releasing Zone (R05 shown)
• Releasing Zone R05 is programmed with the releasing functions: Delay, Abort, Cross, and Soak
NOTE: The abort switch can only be associated with one release zone.
When an initiating device activates, you must press and hold the Abort Switch or the control panel will send the command to dump
releasing agents when the Delay time (15 seconds shown) expires. The Abort selection (ULI, IRI, NYC, or AHJ) determines the
function of the Abort Switch.
SYSTEM SYSTEM
NORMAL ACTIVATED
Monitor
Module with
Detector Detector
ABORT SWITCH
Type Code
Abort station with Abort Switch
and Manual Release lever
R05
Description
Requires a standard UL-type delay timer that complies with UL Standard 864.
How to Program
1. Program the monitor module connected to the abort station with the Type Code ABORT SWITCH as detailed in “Modify an
Addressable Monitor Module Point” on page 21.
2. Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page 58).
To Program Do this
ULI Abort Switch Type ULI in the ABORT= field, or press the NEXT or PREVIOUS
3. Press at this point to save the Abort Switch value if no other fields on the screen are changing. To change another
field on the screen, move the cursor into position by pressing the arrow keys on the keypad.
How It Works
When an alarm initiates in the programmed Releasing Zone, you can press and hold the Abort Switch while the Delay Timer
continues to count down. (If the delay timer has expired, the abort switch has no effect.) When you release the Abort Switch, a 10-
second ULI timer counts down. At the end of the 10-second ULI timer, the control panel activates the Releasing Zone outputs.
Example
A ULI Abort Switch and a Delay Timer programmed to Releasing Zone R05:
5 sec.
15 sec.
Alarm
10 sec.
Press and hold the
Abort Switch for 15
seconds Release the Abort
Switch; the 10-second
ULI timer begins
IRI Abort Switch Type IRI in the ABORT= field, or press the next or previous keys,
3. Press at this point to save the Abort Switch value if no other fields on the screen are changing. To change another
field on the screen, move the cursor into position by pressing the arrow keys on the keypad.
How it Works
When the first alarm occurs in a releasing zone programmed with a cross-zone code, pressing the abort switch will prevent
activation of the releasing zone should a second alarm occur while the switch is held. When the abort switch is released, if a second
alarm has occurred while the switch was held, the ten-second IRI timer activates immediately, and the control panel activates the
releasing zone outputs at the end of the IRI timer countdown. When the abort switch is released and a second alarm has not occurred
while the switch was held, the panel waits for the cross-zone conditions to be met before activating the releasing zone.
WARNING:
! The IRI abort switch will only work if it is pushed before the second alarm occurs. If it is pushed after the
second alarm, the releasing zone will already have been activated, and the switch will have no effect.
Example
An IRI Abort Switch and a Delay Timer programmed to Releasing Zone R05:
PRG RELEASE FUNCT RELEASE CONTROL
DELAY=15 ABORT=IRI CROSS=Z SOK=0000 R05
Program selections for Releasing Zone R05
5 sec.
5 sec.
Alarm 1
10 sec.
Description
A standard NYC delay timer that adds 90 seconds to the programmed Delay Timer.
How to Program
1. Program the monitor module connected to the abort station with the Type Code ABORT SWITCH as detailed in “Modify an
Addressable Detector Point” on page 20.
2. Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page 58).)
To Program Do this
NYC Abort Switch Type NYC in the ABORT= field, or press the next or previous
3. Press at this point to save the Abort Switch value if no other fields on the screen are changing. To change another
field on the screen, move the cursor into position by pressing the arrow keys on the keypad.
How It Works
When an alarm initiates in the programmed Releasing Zone, pressing and holding the Abort switch stops the Delay Timer
countdown. The Delay Timer restarts at the beginning of its countdown when the Abort switch is released. When the Delay Timer
expires, the 90-second NYC timer starts counting down. When both timers expire, the control panel activates Releasing Zone
outputs.
NOTE: 120 seconds is the maximum delay after the Abort switch is released. If the Delay Timer
time plus the NYC delay time of 90 seconds exceeds 120 seconds, Releasing Zone outputs will
still be activated at 120 seconds after the Abort switch is released.
Select a Delay Timer value for R05 of 15 seconds. The Releasing Zone activates and the 15-second Delay Timer starts. Ten seconds
into the Delay Timer countdown, press and hold the Abort Switch for 30 seconds, then release the Abort Switch. The control panel
restarts the Delay Timer at 15 seconds and adds the NYC delay of 90 seconds. The delay timers will both expire at 105 seconds, and
Releasing Zone outputs will begin releasing at that time. Following is an example of a NYC Abort Switch and a Delay Timer
programmed to Releasing Zone R05:
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=15 ABORT=NYC CROSS=N SOK=0000 R05
Program selections for Releasing Zone R05
Total time from alarm initiation to release:
10 + 30 + 105 = 145 seconds
Delay=15 sec.
Delay=15 sec. NYC Delay=90 sec.
0 sec.
10 sec.
30 sec.
Alarm
Select a Delay Timer value for R05 of 60 seconds. The Releasing Zone activates and the 60-second Delay Timer starts. Ten seconds
into the Delay Timer countdown, press and hold the Abort Switch for 30 seconds, then release the Abort Switch. The control panel
restarts the Delay Timer at 60 seconds and adds the NYC delay of 90 seconds. The delay timers will both expire at 150 seconds:
however, this time exceeds the maximum of 120 seconds, so the Releasing Zone outputs will begin releasing at 120 seconds, not at
150. Following is an example of a NYC Abort Switch and a Delay Timer programmed to Releasing Zone R05:
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=60 ABORT=NYC CROSS=N SOK=0000 R05
Program selections for Releasing Zone R05
Delay=60 sec.
Pressing and releasing Abort switch Total time from alarm initiation to release:
restarts Delay=60 countdown after 10 + 30 + 60 + 60 = 160 seconds
40 seconds have elapsed.
Delay=60 sec. NYC Delay=90 sec.
10 sec.
30 sec.
Alarm
Press and hold
the Abort Switch
120 sec. to release
Description
An AHJ (Authority Having Jurisdiction) delay timer that restores the programmed Delay Timer.
How to Program
1. Program the monitor module connected to the abort station with the Type Code ABORT SWITCH as detailed in “Modify an
Addressable Monitor Module Point” on page 21.
2. Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page 58.
To Program Do this
AHJ Abort Switch Type AHJ in the ABORT= field, or press the NEXT or PREVIOUS
3. Press at this point to save the Abort Switch value if no other fields on the screen are changing. To change another
field on the screen, move the cursor into position by pressing the arrow keys on the keypad.
How It Works
When an alarm initiates, the programmed Delay Timer starts. Press and hold the Abort switch and the control panel suspends the
Delay Timer. When you release the Abort Switch, the control panel restores the value of the programmed Delay Timer and the
Delay Timer counts down. When the Delay Timer expires, the control panel activates Releasing Zone outputs.
Example
An AHJ Abort Switch and a Delay Timer programmed to Releasing Zone R05:
Delay=60 sec.
Total time from alarm initiation to release:
45 + 30 + 60 = 135 seconds
45 sec.
30 sec.
Alarm
60 sec.
NOTE: Only the first Software Zone (Z01-Z99) listed in the zone map is used to determine
Cross=Z.
A summary of the types of Cross Zones and the conditions for activating a Releasing Zone:
Y Two or more detectors or modules are alarmed that are mapped to one of the ten Releasing
Zones (R0-R9).
Z Two or more detectors or modules are alarmed that are mapped to two different software zones
and mapped to one of the ten Releasing Zones (R0-R9).
H At least one smoke detector or module mapped to one of the ten Releasing Zones (R0-R9) is
alarmed and at least one heat detector mapped to the same Releasing Zone (R0-R9) is alarmed.
NOTE: When in alarm, Special Zones R0-R9 appear in the CBE list as ZR00-ZR09. For
example, R5 appears in the CBE list as ZR05.
Releasing
Zone ZR1
REL
B03 CBE list = ZR1
A listing of each Cross Zone option and the conditions required to activate the Releasing Zone, according to the example shown
above.
Cross Zone
Selection Condition(s) Required to Activate the Releasing zone
(Cross=)
Cross=N An alarm from any detectors or modules activates the releasing circuit.
Cross=Y An alarm from any two detectors or modules activates the releasing
circuit.
Cross=H Activation of heat detector 2D104 and one smoke detector (2D101,
21D102, or 2D103).
Select a time for the Releasing Zone Delay Timer (refer to“Programming a Delay Timer” on page 58.)
To Program Do this
Cross Zones Type N, Y, Z, or H in the CROSS= field, or press the NEXT or PREVIOUS
To Program Do this
Soak Timer Type a seconds value of 0000 (no soak timer) to 9999 from the
numeric keys on the keypad in the SOK= field.
Press at this point to save the Soak Timer value if no other fields on the screen are changing. To change another field on the
screen, move the cursor into position by pressing the arrow keys on the keypad.
A Soak Timer value of 600 seconds is shown below:
ABORT SWITCH Provides an abort function through a “ABORT SWITCH Type Code” on page
(tracking) monitor module (connected to a UL-listed 70
abort station) for a Releasing Zone.
MAN. RELEASE Provides a manual release through a “MAN. RELEASE Type Code” on page
(latching) monitor module (connected to a UL-listed 72
pull station) for a Releasing Zone.
MAN REL DELAY Provides a manual release with a “MANREL DELAY Type Code” on
(latching) 30-second delay (dependent on the FACP page 73
Delay setting) through a monitor module
(connected to a UL-listed pull station) for a
Releasing Zone.
SECOND SHOT Provides a second manual release through “SECOND SHOT Type Code” on page
(latching) a monitor module (connected to a UL-listed 75
pull station) for a Releasing Zone.
REL END BELL Activates a NAC audio or visual device “RELEASE END BELL” on page 76
when releasing circuits shut off.
REL CKT ULC Directs outputs to perform a release “REL CKT ULC Type Code” on page
function as required by ULC. 77
RELEASE CKT Directs outputs to perform a releasing “RELEASE CKT Type Code” on page
function. 78
RELEA. FORM C Directs relay outputs to perform a “Relea. Form-C Type Code” on
releasing function. page 80
REL AUDIBLE Activates audio or visual devices steady “REL AUDIBLE Type Code” on page
when releasing starts. 81
INSTANT RELE Activates non-releasing output (panel NAC “INSTANT RELE Type Code” on page
or control modules) with no delay time. 82
REL CODE BELL Activates audio or visual devices to pulse “REL CODE BELL Type Code” on page
at 20 ppm (initial zone of a Cross Zone) or 83
120 ppm (Cross Zone satisfied).Steady on
release.
Description
A monitor module, connected to a UL-listed abort station (such as the Notifier NBG-12LRA), that you use as an abort switch for a
Releasing Zone. You can program multiple monitor modules with the ABORT SWITCH Type Code that work like multiple
conventional abort switches on a conventional zone.
Programming
1. Select a monitor module to use as an Abort Switch (refer to “Modify an Addressable Monitor Module Point” on page 21).
2. Select the ABORT SWITCH Type Code.
Type Code selection: ABORT SWITCH
A programming example of a monitor module programmed as an Abort Switch for Releasing Zone R5.
SYSTEM SYSTEM
NORMAL ACTIVATED
Monitor
Detector
Module
Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
R05
NBG12LRAface.wmf
Control
B01 Module
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-12LRA)—used to manually release agents.
A Manual Release switch overrides all timers, such as a Delay Timer or a Soak Timer. You can install multiple monitor modules
with a MAN. RELEASE Type Code that work like multiple conventional manual release switches on a conventional zone.
Programming
1. Select a monitor module (refer to “Modify an Addressable Detector Point” on page 20) to use for the manual release function.
2. Select the MAN. RELEASE Type Code.
Type Code selection: MAN RELEASE
Example
A programming example of a monitor module programmed as an manual release switch for Releasing Zone R5.
SYSTEM SYSTEM
NORMAL ACTIVATED
Monitor
Detector
Module
Type Code
MAN. RELEASE
R05
NBGLRAface.wmf
Control
B01 Module
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-12LRA)—used to initiate a manual release
with 30-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Timer in certain circumstances, but not the soak timer.
Override Circumstances:
When the Manual Release Delay Switch activates, the control panel replaces the Delay Time with 30 seconds if the Delay
Timer
• is set to more than 30 seconds
• is running, and
• has not counted down below 30 seconds.
NOTE: When the Delay Timer is set to less than 30 seconds, activation of the Manual Release
Delay Switch will invoke the FACP programmed Delay Time if the Delay Timer is not running, or
the FACP programmed Delay Timer countdown time if it is running. Refer to the examples 1
through 5 later in this section.
Multiple monitor modules can be programmed with a MANREL DELAY Type Code. They work like multiple conventional manual
release switches on a conventional zone.
How to program
1. Select a monitor module (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use for the manual release function.
2. Select the MANREL DELAY Type Code.
Type Code selection: MANREL_DELAY
PROGRM MANREL_DELAY MODULE ADDR 1M101
R5 __ __ __ __ 1M101
A programming example of a monitor module programmed for MANREL DELAY switch for Releasing Zone R5.
SYSTEM SYSTEM
NORMAL ACTIVATED
Monitor
Detector
Module
Manual Release
R05
Lever
NBGLRAface.wmr
Control
B01 Module
For examples 1, 2, and 3, program Releasing Zone R5 with a Manual Release Delay switch and the following releasing selections:
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=60 ABORT=ULI CROSS=N SOK=0030 R05
Example 1 - The FACP programmed Delay Timer begins its 60 second countdown. The Manual Release Delay switch is pulled
when the FACP Delay Timer has counted down to 48 seconds (elapsed time of 12 seconds). The 48 seconds remaining in the
countdown are overridden by the 30-second delay initiated by the Manual Release Delay switch. In this example, the total time
elapsing from FACP countdown initiation to agent release is 42 seconds (12 + 30), less than the original 60 second FACP Delay
Timer countdown.
Example 2 - The FACP programmed Delay Time begins its 60 second countdown. The Manual Release Delay switch is pulled
when the FACP Delay Timer has counted down to 8 seconds. The 8 seconds remaining in the countdown is not changed when the
switch is pulled. In this example, the total time elapsing from FACP countdown initiation to agent release is 60 seconds.
Example 3 - The FACP programmed Delay Time is not running (as would happen if the releasing station were pulled before an
alarm registered). The Manual Release Delay Switch is activated by the pull station. Agent release will occur in 30 seconds.
For examples 4 and 5, the delay is changed to DELAY=10.
Example 4 - The FACP programmed Delay Timer begins its 10 second countdown. The Manual Release Delay switch is pulled
when the FACP Delay timer has counted down to 8 seconds. The 8 seconds remaining in the countdown is not changed. In this
example, the total time elapsing from FACP countdown initiation to agent release is 10 seconds.
Example 5 - The FACP programmed Delay Timer is not running (as would happen if the releasing station were pulled before an
alarm registered). The Manual Release Delay switch is activated by the pull station. Agent release will occur in 10 seconds.
NOTE: The Second Shot switch can only be used with the MANREL DELAY Type Code.
The following contains information needed to program a Second Shot switch for a monitor module
Description
A monitor module—connected to a UL-listed manual station (such as the NBG-12LRA)—used as for a second release of agents. A
Second Shot switch overrides a Delay Timer, programmed to the same Releasing Zone.
Programming
1. Select a monitor module (refer to “Modify an Addressable Monitor Module Point” on page 21) to use for the manual release
function.
2. Select the SECOND SHOT Type Code.
Type Code selection: SECOND_SHOT
PROGRM SECOND_SHOT MODULE ADDR 1M101
R5 __ __ __ __ 1M101
Examples
A programming example of a monitor module programmed as a Manual Release Delay switch (Type Code MANREL DELAY) for the
first shot and a Second Shot switch (Type Code SECOND SHOT) for the second shot.
SYSTEM SYSTEM NBG-12LRA station with
Second
NORMAL ACTIVATED
B01 Control
Module
With two monitor modules configured as shown above, program Releasing Zone R5 with the following releasing selections.
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=15 ABORT=ULI CROSS=Y SOK=0030 RO5
R05 can be activated in one of two ways, as described in the examples given below.
Example 1: If the detector initiates the alarm, R05 activates. Releasing begins after the delay timer has expired (15 seconds).
Releasing will continue for the soak timer duration (30 seconds). Once the Soak Timer expires, the Second Shot Switch can then be
activated to initiate an additional soak cycle.
Example 2: If the NBG-12LRA (Type Code MANREL DELAY) lever is pulled, the delay timer begins its 15 second countdown.
Releasing will begin after the delay timer has expired, and will continue for the soak timer duration (30 seconds). Once the Soak
Timer expires, the Second Shot Switch can then be activated to initiate an additional soak cycle.
NOTE: A releasing circuit with this Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release End Bell circuit for a control module or a NAC.
Description
A control module or NAC to activate an audible or visual device when releasing devices shut off. You can also program multiple
outputs with the REL END BELL Type Code to the same Releasing Zone. When all the Releasing Zone functions are complete, all
outputs with the REL END BELL Type Code activate at the same time. A REL END BELL circuit remains on until you reset the system
Programming
1. Select a control module or NAC (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use as a Release End Bell
circuit.
2. Select the REL END BELL Type Code, as shown in the following example (control module shown).
Type Code selection: REL END BELL
Example
A programming example of a control module programmed as a Release End Bell for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Control Control
B01 B02
Module Module
NOTE: A ULC Release Circuit with this Type Code requires the following selections: A
Releasing Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch
Inhibit selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a ULC Release Circuit for a control module or a NAC.
Description
A control module or a NAC used to activate a releasing solenoid or other releasing device. You can also program multiple outputs
with the REL CKT ULC Type Code to the same Releasing Zone. When the Releasing Zone activates, all outputs with the REL CKT ULC
Type Code also activate at the same time. A ULC Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if using the Cross Zone option)
• The Delay Timer for R0-R9 (if used) expires
• No Abort Switch for R0-R9 (if used) is active
A ULC Release Circuit —and all wiring to the release device—is fully supervised and usable with power-limited energy cable.
Programming
1. Select a control module or a NAC (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use as a ULC Release Circuit.
2. Select the REL CKT ULC Type Code, as shown in the following example (control module shown).
Type Code selection: REL CKT ULC
Example
A programming example of a control module programmed as a ULC Release Circuit for Releasing Zone R5.
Monitor
Module Detector Detec Detector
R05
Control Control
B01 B02
Module Module
NOTE: A Release Circuit with this Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected; Non-Silenceable; No Walk Test.
NOTE: Do not use a Release Circuit for the following: An application requiring ULC Listing; An
application requiring power-limited energy cable.
The following contains information needed to program a Release Circuit for an output circuit (control module or NAC).
Description
A control module or a NAC used to activate a releasing solenoid or other releasing device. You can also program multiple outputs
with the RELEASE CKT Type Code to the same Releasing Zone. When the Releasing Zone activates, all outputs associated with the
releasing zone and with the RELEASE CKT Type Code also activate at the same time. A Release Circuit activates when:
• An initiating device programmed to the same Releasing Zone activates (two devices if using the Cross Zone option)
• The Delay Timer for R0-R9 (if used) expires
• The Abort Switch for R0-R9 (if used) is not active
Programming
1. Select a control module or a NAC (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use as a Release Circuit.
2. Select the RELEASE CKT Type Code, as shown in the following example (control module shown).
Type Code selection: RELEASE CKT
PROGRM RELEASE CKT MODULE ADDR 1M108
R5 __ __ __ __ I** 1M108
A programming example of a control module programmed as a Release Circuit for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Control Control
B01 B02
Module Module
NOTE: An output with a relea.form c Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release Form-C circuit for an output circuit.
Description
An output circuit, configured as a relay, programmed to activate an output by opening or closing a switch. Typical applications
include closing doors and air handlers.
Programming
1. Select a control module (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use as a Releasing Form-C Circuit.
2. Select the RELEA.FORM C Type Code, as shown in the following example (control module shown).
Type Code selection: RELEA.FORM C
Example
A programming example of a control module programmed as a Release Form-C circuit for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Control Control
B01 B02
Module Module
NOTE: An output with a REL AUDIBLE Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected.
The following contains information needed to program a Release Audible circuit for an output circuit (control module or NAC).
Description
An output circuit programmed to activate an audio or visual device when all releasing outputs, programmed to the same Releasing
Zone, turn on. You can also program multiple outputs with the REL AUDIBLE Type Code to the same Releasing Zone. When the
Releasing Zone activates, all outputs with the REL AUDIBLE Type Code activate at the same time.
Programming
1. Select a control module or NAC (refer to “Modify or Delete a Point (2=POINT)” on page 19) to use as a Releasing Circuit.
2. Select the REL AUDIBLE Type Code, as shown in the following example (control module shown).
Type Code selection: REL AUDIBLE
PROGRM REL AUDIBLE MODULE ADDR 1M108
R5 __ __ __ __ I** 1M108
Example
A programming example of a control module programmed as a Release Audible circuit for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Control Control
B01 B02
Module Module
NOTE: An output with an INSTANT RELE Type Code requires the following selections: a zone
selection (a releasing zone may be used, but is not required); an output circuit mapped to the
same zone; Switch Inhibit selected; Non-Silenceable; No Walk Test.
The following contains information needed to program an Instant Release circuit for an output circuit (control module or NAC).
Description
An output circuit programmed to activate non-releasing devices, such as door openers or warning sounders, without counting down
delay timers. A device programmed with the INSTANT RELE Type Code device is supervised for open circuits and ground faults.
Programming
1. Select a control module or a NAC (refer to“Modify or Delete a Point (2=POINT)” on page 19) to use as a Releasing Circuit.
2. Select the INSTANT RELE Type Code, as shown in the following example (control module shown).
Type Code selection: INSTANT REL
PROGRM INSTANT RELE MODULE ADDR 1M101
R5 __ __ __ __ I** 1M101
Example
A programming example of a control module programmed as an Instant Release circuit for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Control Control
B01 B02
Module Module
NOTE: An output with a REL CODE BELL Type Code requires the following selections: A
Releasing Zone selection (R0-R9); An input circuit mapped to the same Releasing Zone.
NOTE: For instructions on programming Switch Inhibit, Silenceable, and Walk Test, refer to
“Modify NAC Points” on page 24.
The following contains information needed to program a Release Code Bell circuit for a NAC.
Description
A NAC programmed to pulse an audio or visual device as follows:
• 20 ppm when a the initial zone of a cross-zone activates.
• 120 ppm when a Cross Zone is satisfied.
• Steady when a release occurs.
Programming
1. Select a NAC (refer to “Modify NAC Points” on page 24) to use as a Release Code Bell Circuit.
2. Select the REL CODE BELL Type Code, as shown in the following example (NAC shown).
Type Code selection: REL CODE BELL
PROGRM REL CODE BELL FRONT HALLWAY NO. 3
R5 __ __ __ __ I** B03
Example
A programming example of a NAC programmed as a Release Code Bell circuit for Releasing Zone R5.
Monitor
Module Detector Detector Detector
R05
Type Code
REL CODE BELL
A NAC programmed with the REL CODE BELL Type Code activates
simultaneously with other outputs programmed for R05 (B01 and B02).
When the Delay Timer starts, when the Map the control module or NAC to a releasing hazard zone
releasing device activates, or both (R0-R9).
Immediately when one of the initiating Map the control module or NAC to a separate zone (not R0-R9)
devices activate that is also mapped to all initiating devices of the hazard.
Function Do this
A releasing application Use control modules set for dry contact operation. Program the
requires control relays control relays for different functions by following the
instructions in “To activate a sounder” above.
Providing control functions Use an ACM-8R remote relay module mapped to the software
zones of the control panel.
To Annunciate Do this
Points of releasing functions Select ACS Selection Group B to annunciate any of the
software zones described previously, including zones R0-R9.
For instructions, refer to “Annunciation Points” on page 34.
PAS (15 s)
The control panel delays activation of outputs containing F0 in their Control-By-Event (CBE) list for all alarm initiating devices
that contain F0 in their CBE list. A subsequent alarm will abort the Presignal Delay Timer and execute CBE lists.
Notes on using F0
• NFPA 72 requires installation of a PAS Inhibit switch, that can be used to turn off the PAS delay timer when the control
panel is unattended. Do so by programming a monitor module with the Type Code, PAS INHIBIT. For details, refer to “Mod-
ify an Addressable Monitor Module Point” on page 21.
• The Presignal Delay timer countdown can be stopped by pressing the SYSTEM RESET key before the Presignal Delay Timer
expires.
• Program zone F0 to participating inputs and outputs that have appropriate CBE zone map entries.
• Outputs must be programmed for resound by fire.
Restrictions on using F0
• Do not include F0 in the CBE list for a releasing device.
• Do not include F0 in the CBE list for any monitor module that connects to a device other than an automatic fire detector.
All outputs with a CBE list containing F5 or F6 activate within the times specified for the days of the week listed in F5 or F6. All
smoke detectors with a CBE list containing F5 or F6 switch to their occupied level (lowest sensitivity, AL:9) within the times
specified for the days of the week listed in ZF5 or ZF6.Refer to “Intelligent Sensing Applications” on page 89 for details on setting
detector sensitivity.
Time Control is active for all days of the week listed in F5 or F6. Holidays listed in F7 are excluded unless you list Holidays (H) in
the day-of-week selection of F5 and F6. Enter the time in a 24-hour format with the OFF time later than the ON time. After
changing programming using Time Control, always reset the control panel.
NOTE: Do not include F8 in the CBE list of NACs used for releasing or zone coding applications.
Select Coding Functions on a global basis, through Special Zone F8. That is, all NACs selected for Coding Functions will sound the
same code when activated. Table B.1 contains descriptions of each Coding Function selection:
Coding Function
Signal
Selection
Temporal 0.5s on, 0.5s off, 0.5s on, 0.5s off, 0.5s on, 1.5s off, repeats
Coding Function
Signal
Selection
System Sensor Synchronizes System Sensor Horn/Strobes (Applies to NAC on NFS-320/E only)
Strobe Note: If the “Strobe” Type ID is used with System Sensor Strobe
synchronization,“*” will silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit. Refer to “Modify an
Addressable Control Module Point” on page 23 and “Modify NAC Points” on
page 24
C.1 Overview
“Intelligent Sensing” is a set of software algorithms that provide the NFS-320 with industry-leading smoke detection capability. You
can program Intelligent Sensing functions on a global or on a per-detector basis.
Intelligent Sensing topics covered in this appendix:
Topic Page
Intelligent Sensing Applications features – Descriptions of features, page 89
such as Drift Compensation, Sensitivity Adjust, programmable on a per-
detector basis.
Pre-Alarm – Alert and Action settings, programming (global settings). page 94
Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings page 95
for photo, ion, laser, and multisensor detectors programmable on a per-
detector basis.
Detector Maintenance Features – Instructions for viewing and printing page 97
detector maintenance information.
C.2 Features
Intelligent Sensing Applications features include the following:
• Drift Compensation and Smoothing
• Maintenance Warnings - Three Levels
• Self-optimizing Pre-Alarm
• Detector Sensitivity
• Cooperative Multi-Detector Sensing
A graphic representation of a detector analog reading using drift compensation and smoothing:
Alarm Level
without compensation
Awacs1a.wmf
Reading smoothing
Time
Maintenance Alert Dust accumulation that is near but below the allowed limit. The
Maintenance Alert level indicates the need for maintenance before
the performance of the detector is compromised.
DIRTY
Maintenance
Urgent
Maintenance
Alert
Acceptable
Range
Low Chamber
Reading
Low
Value
Prealarm Threshold
Analog
Reading
Awacs4a.wmf
Time (days)
For more information on setting Pre-Alarm levels, refer to “Changing Detector Sensitivity” on page 52
NOTE: For a list of all detector sensitivity levels, see Table C.1 on page 95.
• Alarm Sensitivity Levels - Select the sensitivity of a detector from 1-9 (1=highest sensitivity; 9=lowest sensitivity).
• Pre-Alarm Sensitivity Levels - Select one of nine levels from 1 to 9 (0=no Pre-Alarm, 1=self-optimizing, 2=highest sen-
sitivity, 9=lowest sensitivity). You can set Pre-Alarm operation to Action (latching) or Alert (non-latching) and to activate
Special Zones. For instructions on programming, refer to “How to Select a Pre-Alarm Level” on page 94.
Set the sensitivity levels as fixed or programmed for day and night operation. For details, refer to “Time Control Zones” on page 87.
A sample sensitivity window for a laser detector:
2.1%
OBSCURATION (% PER FOOT)
Combined
SMOKE OBSCURATION
Alarm
3 Sensors
Awacs5a.wmf
Time (minutes)
C.3 Pre-Alarm
C.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-time detector sensing values
above the programmed setting. Use the Pre-Alarm function if you want to get an early warning of incipient or potential fire
conditions. There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to “Action Level” on page 93)
Alert and Action Pre-Alarm settings are global. For instance, if you program Pre-Alarm for Alert, all intelligent detectors
programmed for Pre-Alarm are set to Alert (refer to “How to Select a Pre-Alarm Level” on page 94). You can, however, set unique
Pre-Alarm sensitivity levels (PA) for individual detectors (refer to “Detector Sensitivity Settings” on page 95).
• The Action message is sent to the History buffer and to any installed FDU-80s and printers. The message is sent (and time
stamped) only at the time that it first occurred. This historical data could provide valuable information about the progress
of a fire.
• The PRE-ALARM LED and panel sounder pulse until acknowledged.
• Zone F09 is activated—but Zone Z00 (general alarm or any other zone) and the System Trouble and System Alarm relays
do not activate.
• The fifth zone programmed (not the first four) for this detector activates. The fifth zone is the right-most entry on line two
of the detector CBE list in the Point Programming screen. (For more information, refer to “Modify an Addressable Detec-
tor Point” on page 20). You can use the fifth zone to control functions of a detector or group of detectors once the pre-alarm
level is reached. Fifth zone activations also allow ACS annunciation by a detector or group of detectors in Action
Pre-Alarm condition.
• The Pre-Alarm condition and the zone programmed will latch until system reset, even if the sensitivity drops below the
pre-alarm level.
• A subsequent alarm condition for this detector clears the Action indication from the LCD display alarm list.
6=SPL FUNCT
2. From the “Basic Program” screen, press the 6 key to display the “Special Function Zone Change” screen.
F9=PRE-ALARM
3. From the ‘Special Function Zone Change” screen, press F9 to display the “Pre-Alarm Function” screen, with Alert blinking.
ALERT blinking
* Detectors are suitable for open area protection within the listed air velocity range. Typically, this range is 0 - 4,000 ft/min for photoelectric
detectors and 0 - 1,200 ft/min for ionization detectors. Be sure to confirm this range before installing the detector by referring to the
manufacturer’s installation instructions.
† FSP-951, FSP-951-IV, FSP-951R, FSP-951R-IV, FSP-951T, FSP-951T-IV detectors must be programmed with sensitivity level 8 or 9 for
Open Area Protection, and Levels 1 through 7 for Special Applications to be compliant with UL 268 7th Edition requirements (Default = 8).
‡ Use only alarm sensitivity setting of AL=1, AL=2 or AL=3 for ION detectors installed in Canada.
** The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment for the detectors is
suitable for the higher sensitivity setting.
†† 1% maximum on CLIP. Higher figures may display.
‡‡ For Acclimate detectors installed in Canada: Use only the alarm settings of AL:1 or AL:2.
*** The FPTI-951, FPTI-951-IV must be programmed with sensitivity level 8 for Open Area Protection, and Level 2, 4, or 6 (Default=3) for
Special Applications to be compliant with UL 268 7th Edition requirements.
†††Refer to the beam detector manual to determine the alarm settings: they are a function of the distance between the detector and its reflector.
‡‡‡ In CLIP mode, any AL: settings over AL:5 will be set to AL:5 by the panel. Any PA: settings over PA:5 will be set to PA:5 by the
panel.
****Within the 10 minute fire signature confirmation delay period if there is a detection of another fire signature (Carbon Monoxide,
Infrared or Thermal) it overrides the 10 minute confirmation time.
†††† FCO-951, FCO-951-IV detectors must be programmed with sensitivity level 3, 4, or 5 for Open Area Protection, and Level 1 or 2 (Default
= 4) for Special Applications to be compliant with UL 268 7th Edition requirements.
C.4.2 How to Test Detectors Set Below 0.50% Obscuration per Foot
Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to ensure that the detector environment is suitable
for the higher sensitivity setting. To meet Notifier and Underwriters Laboratory requirements, test each detector planned to operate
below 0.50%/ft obscuration as follows:
1. Set the detector as follows:
Step Action
1 Initially set to the 0.50% obscuration per foot Alarm level.
2 Set the Pre-Alarm level to the desired final Alarm sensitivity.
3 Set the Pre-Alarm to Alert mode (non-latching).
2. Operate detectors continuously for 90 days with all environmental factors (such as, temperature, humidity, air flow, occupancy,
and so on) similar to the intended application for the detectors. Record all events for each tested detector with an electronic
History buffer or a printout.
3. At the end of the 90-day test: An authorized Notifier representative, or an end user trained by an authorized Notifier
representative must inspect the results of the test. If the test results show no alarms or pre-alarms for the tested detectors,
reprogram the fire alarm system to set the Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
2. At the Program Entry screen, press the M key. The control panel displays the Detector Maintenance Selection screen:
SLC Loop Three digit address
3. Specify the detector’s three digit address, then press the enter key; or to print a Detector Maintenance Report (Figure C.8 on
page 98): Press P; then, press the enter key.
Once you display information for a detector, you can use the (Next Selection) and (Previous Selection) keys to view
information for the next or previous detector on the SLC.
Refer to “Interpreting a Detector Status Display or Maintenance Report” on page 98 for descriptions of each item.
NORMAL SMOKE (PHOTO) DETECTOR ADDR 1D044 Comp:027% Pk:0001% 000% A8 8 C * 1D044
1 2 3 4 5 6 7 8 9 10 11
1. Device Status (NORMAL) The status of the detector: NORMAL, ALARM, DISABL OR TEST.
2. Type Code (SMOKE (PHOTO)) The software Type Code that identifies the type of detector. Refer to “Type Codes for
Intelligent Detectors” on page 106.
3. Custom Label (DETECTOR ADDR 1D044) The 19-character user-defined custom label.
4. Drift Compensation (COMP:027%) The relative cleanliness of a detector determined by sampling the amount of contaminants
in the detector, ambient air conditions, and the age of the detector. The Comp value also indicates if a detector requires
maintenance. Refer to “Maintenance Warnings – Three Levels” on page 90 for definitions of maintenance levels. The table
below contains a list of the maintenance level values for each type of detector:
Low Chamber
Type of Detector Normal Maint. Alert Maint. Urgent
Reading
5. Peak Value (PK:0001%) The highest analog value reached by the detector during the past week. The peak value slowly returns
to zero.
6. Alarm Reading (000%) The current alarm reading of the detector, as a percentage of the Alarm Sensitivity setting.
7. Alarm Sensitivity Setting (A8) The Alarm Sensitivity (x=1-9) entered in the Detector Sensitivity Screen.
8. Pre-Alarm Sensitivity Setting (8) The Pre-Alarm Sensitivity (1-9; 0 = Pre-Alarm not used) entered in the Detector Settings
Screen. Refer to “Detector Sensitivity Settings” on page 95 for more information on the Pre-Alarm sensitivity settings.
9. Multi-Detector Selection (*) A smoke detector programmed so that it evaluates readings from nearby detectors in making
Alarm or Pre-Alarm decisions. Cooperative Multi-Detector sensing also allows the combination of ionization with
photoelectric technology in reaching an alarm decision. See “Modify an Addressable Detector Point” on page 20 for
instructions on setting Cooperative Multi-Detector Settings.
* – Multi-not used.
A – combines the detector’s alarm decision with the next address above.
B – combines the detector’s alarm decision with the next address below.
C – combines the detector’s alarm decision with the next address above and the next address below.
10. Alarm Verification (*)
* – Alarm Verification not programmed for this detector.
V– Alarm Verification enabled.
xx – Alarm Verification programmed for the detector; xx equals the Verification Counter (00-99). See “Modify an Addressable
Detector Point” on page 20 for instructions on setting Alarm Verification.
11. Device SLC Address (1D044) The SLC address of the detector.
D.1 Description
CBE (Control-By-Event) is a software function that provides a means to program a variety of output responses based on various
initiating events. The control panel operates Control-By-Event (CBE) through 99 Software Zones with the following features:
• Each input point (detector, monitor module) can list up to five Software Zones
• Each output point (control module or NAC) can list up to five Software Zones
• Output points can list zone Z00 (general alarm). Non-Alarm or Supervisory points do not activate Software Zone Z00
(general alarm)
Inputs (detectors, monitor modules) When an input device activates, so do all Software
Zones listed to the input device.
Outputs (control modules and NACs) When a Software Zone activates, the output device(s)
in that zone turns on.
D.3 Equations
Space for up to twenty logic or time delay equations is included in the control panel. Each equation can be a logic equation or a time
delay function. A time delay function can have a logic equation as an internal equation, but not vice versa. The rules of the equations
are:
1. Equations can be entered, edited and viewed in the VeriFire™ Tools program, but can only be viewed on the control panel.
2. The twenty equations are designated in the panel as ZE0-ZE9 and ZL0-ZL9, and are evaluated in that order.
NOTE: In the VeriFire™ Tools program, ZL1 - ZL10 corresponds to ZE0-ZE9, and ZL11 - ZL20
corresponds to ZL0-ZL9.
for this part to be TRUE for this part to be TRUE for this part to be TRUE
Then all outputs programmed with this equation will be turned ON.
• If no duration is specified, then the device will not be deactivated until a reset occurs or the internal equation evaluates
false.
The “SDEL” Operator
A latched version of the DEL operator. Once the equation evaluates true, it remains activated until a reset, even if the internal
equation (ZE5) becomes false.
Example: SDEL(HH:MM:SS HH:MM:SS,ZE5)
• The first HH:MM:SS is the delay time, the second HH:MM:SS is the duration time.
• If delay of zero is entered (00.00.00), the equation will evaluate true as soon as the internal equation (ZE5) evaluates true
and will remain that way for the specified duration.
• If no duration is specified, then the device will not deactivate until reset.
The installer can enter the equations in any combination wanted as long as the format of the logic function or time delay is followed
from the lists above. Error checking will be performed after the user has entered the complete equation. Possible errors are too many
or too few parentheses, too many or too few arguments inside the parentheses, unknown function and unknown device type.
Monitor Control
Module Software Module
1M101 Zone Z05 1M108
When monitor module 1M101 activates, the following CBE takes place:
1. Software Zones Z04 and Z05 activate.
2. Since control module 1M108 has Z05 in its CBE list, all of its outputs would activate. All output devices with Z04 or Z05
would activate.
E.1 Overview
The control panel automatically performs a detector initialization routine when you add or change a detector, unless the control
panel is in Walk Test or Advanced Walk Test. If you change a detector with the control panel in Walk Test or Advanced Walk Test,
you must manually initialize the detector as detailed in “How to Manually Initialize a Detector” on page 105. The detector
initialization routine takes approximately 2.5 minutes, during which time the FACP remains in service. While initializing a detector,
follow these guidelines:
• Make sure the detector is free of residual smoke during detector initialization.
• Do not test a detector during detector initialization.
NOTE: The control panel only performs detector initialization if it senses that a detector was
removed for at least 15 seconds. This is what actually “turns on” the detector. It is an automatic
procedure but is specified here because of the delay between detector connection and full
function. The rest of the system remains in full service during this time.
A sample screen that appears on the LCD display during detector initialization.
Detector Initializing _ Please Wait
02:48P 012511 Tue
WARNING:
! If you replace any detector with a different type of detector (for example, replace a laser detector with
a photoelectric detector), you must immediately program the control panel with the new detector
Type Code. Failure to do so can cause incorrect control panel operation, including false alarms. For
instructions on replacing a detector, refer to “How to Replace a Detector” on page 104.
Step Action
1 Disable the point of the detector. (point 1D101)
2 Remove the photoelectric detector and replace with laser detector set to the same address.
3 Autoprogram the panel to recognize the new detector type.
4 Enable new detector.
2. Press the 1 key. The control panel displays the Enter Password screen:
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT)
3. Enter the password RESET, which starts detector initialization. The control panel displays the following screens, in the sequence
shown, while initializing a detector:
When the control panel completes the detector initialization, it displays system status as shown below:
Point Characteristics
Type Code Latching Device Function
Point Type Point Function
(Y/N)
SMOKE (ION) fire alarm Y lights fire alarm LED and activates CBE Ionization smoke detector
SMOKE(DUCTI) fire alarm Y lights fire alarm LED and activates CBE Duct Ionization smoke detector
SUP.T(DUCTI)3 supervisory N lights supervisory LED Ionization smoke detector used as a duct detector to report
supervisory condition rather than alarm. Tracking.
SUP.L(DUCTI) supervisory Y lights supervisory LED Ionization smoke detector used as a duct detector to report
supervisory condition rather than alarm. Latching.
SUP.T(ION)2,3 supervisory N lights supervisory LED Ionization smoke detector used to report supervisory
condition rather than alarm. Tracking.
SUP.L(ION)2 supervisory Y lights supervisory LED Ionization smoke detector used to report supervisory
condition rather than alarm. Latching.
SMOKE(PHOTO) fire alarm Y lights fire alarm LED and activates CBE Photoelectric smoke detector
SMOKE(DUCTP) fire alarm Y lights fire alarm LED and activates CBE Duct Photoelectric smoke detector
SUP.T(DUCTP)3 supervisory N lights supervisory LED Photoelectric smoke detector used as a duct detector to
report supervisory condition rather than alarm. Tracking.
SUP.L(DUCTP) supervisory Y lights supervisory LED Photoelectric smoke detector used as a duct detector to
report supervisory condition rather than alarm. Latching.
SUP.T(PHOTO)2,3 supervisory N lights supervisory LED Photoelectric smoke detector used to report supervisory
condition rather than alarm. Tracking.
SUP.L(PHOTO)2 supervisory Y lights supervisory LED Photoelectric smoke detector used to report supervisory
condition rather than alarm. Latching.
RF_PHOTO fire alarm Y lights fire alarm LED and activates CBE Wireless Photoelectric smoke detector
SMOKE(HARSH)1 fire alarm Y lights fire alarm LED and activates CBE HARSH smoke detector
FIRE/CO4 fire alarm Y lights fire alarm LED for photo and heat, Photoelectric, Carbon Monoxide, and Heat detector
no LED will light for a CO alarm, photo
and heat will activate CBE, CO alarm
activates special function zone FC and
sixth CBE zone only (sixth CBE zone
programmable via VeriFire Tools)
FIRE/CO (P SUP)2,4,5 fire alarm/ Y lights fire alarm LED for heat, no LED will Photoelectric, Carbon Monoxide, and Heat detector
supervisory light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone
only (sixth CBE zone programmable via
VeriFire Tools). Panel can be
FIRE/CO (C SUP)4 fire alarm/ Y lights fire alarm LED for heat and photo Photoelectric, Carbon Monoxide, and Heat detector
supervisory alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
NOTE: For FIRE/CO detectors:
Detectors programmed as FIRE/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will latch or track,
depending on the FIRE/CO (P SUP) setting. Detectors programmed as FIRE/CO (C SUP), the heat and Photo elements will latch and require a system reset to
clear. The CO element will latch or track depending on the FIRE/CO (C SUP) setting.
CO ALARM CO alarm Y CBE Position #5 Activates for CO Carbon Monoxide detector
Prealarm, all other CBEs activate for a
CO Alarm
CO SUP CO Y (see CBE Position #5 Activates for CO Carbon Monoxide detector
supervisory note on Prealarm, all other CBEs activate for a
page CO Supervisory
30)
PHOTO/CO4 fire Y CBE Position #4 activates for CO, CBE Photoelectric and Carbon Monoxide detector
Position #5 Activates for CO Prealarm, all
other CBEs activate when the Photo
element activates (i.e. fire alarm)
P/CO (P SUP)2,4,5 photo - Y (see CBE Position #4 activates for CO, CBE Photoelectric and Carbon Monoxide detector
supervisory note on Position #5 Activates for CO Prealarm, all
CO - Alarm page other CBEs activate when the Photo
30) element activates (i.e. Supervisory)
P/CO (C SUP)4 Photo - Fire Y CBE Position #4 activates for CO, CBE Photoelectric and Carbon Monoxide Detector
CO - Position #5 Activates for CO Prealarm, all
supervisory other CBEs activate when the Photo
element activates (i.e. fire alarm)
NOTE: For PHOTO/CO detectors:
Detectors programmed as PHOTO/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will latch or track,
depending on the PHOTO/CO (P SUP) setting. Detectors programmed as PHOTO/CO (C SUP), the heat and Photo elements will latch and require a system reset
to clear. The CO element will latch or track depending on the PHOTO/CO (C SUP) setting. For Photo/CO and CO Detectors programmed as Photo/CO (P SUP)
or CO (CO SUP) will either latch and track, depending on the setting.
SMOKE(BEAM) fire alarm Y lights fire alarm LED and activates CBE Beam smoke detector
SMOKE(LASER) fire alarm Y lights fire alarm LED and activates CBE Laser smoke detector
SUP.L(LASER)2 supervisory Y lights supervisory LED Laser smoke detector used to report supervisory condition
rather than alarm. Latching.
SUP.T(LASER)2,3 supervisory N lights supervisory LED Laser smoke detector used to report supervisory condition
rather than alarm. Tracking.
SMOKE(DUCTL) fire alarm Y lights fire alarm LED and activates CBE Duct Laser smoke detector
SUP T(DUCTL) supervisory N lights supervisory LED Laser smoke detector used as a duct detector to report
supervisory condition rather than alarm. Tracking.
SUP L(DUCTL) supervisory Y lights supervisory LED Laser smoke detector used as a duct detector to report
supervisory condition rather than alarm. Latching.
AIR REF fire alarm Y lights fire alarm LED and activates CBE Assign to one or more FSL-751 detectors used to monitor
the quality of air entering the protected area. The air quality
measurement allows the VIEW® system to compensate for
vehicle fumes, fog, or other particles brought into the
protected area through the ventilation system. Poor air
quality will lower the sensitivity of all FSL-751 detectors on
the SLC. The detector sensitivity, however, remains within
approved limits (always less than 1% obscuration per foot).
NOTE: A reference detector still functions as a smoke detector, but you should set the detector sensitivity level to the least sensitive level—AL:9 and PA:9
Change Alarm and Pre-Alarm sensitivity. Refer to “Detector Sensitivity (in percent obscuration per foot)” on page 95 for a complete list of detector
sensitivity settings.
HEAT fire alarm Y lights fire alarm LED and activates CBE 190oF intelligent thermal sensor
HEAT+ fire alarm Y lights fire alarm LED and activates CBE 190oF intelligent thermal sensor with low temperature
warning.
HEAT(FIXED) fire alarm Y lights fire alarm LED and activates CBE 135oF intelligent thermal sensor
HEAT (ROR) fire alarm Y lights fire alarm LED and activates CBE 15oF per minute rate-of-rise detector
SMOKE ACCLIM fire alarm Y lights fire alarm LED and activates CBE Combination Photoelectric/heat detector without freeze
warning (Acclimate Plus™)
SMOKE(ACCLI+) fire alarm Y lights fire alarm LED and activates CBE Combination Photoelectric/heat detector with freeze
warning (Acclimate Plus™, or IntelliQuad FSC-851
Photoelectric Multi-Criteria Smoke Sensor)
SMOKE(MULTI)1 fire alarm Y lights fire alarm LED and activates CBE Multisensor smoke detector
ASPIRATION fire alarm Y lights fire alarm LED and activates CBE Aspiration smoke detector
ASPIR (SUP) supervisory Y lights supervisory LED and activates CBE Aspiration detector supervision
ASPIR. (PRE) prealarm N lights prealarm LED and actives CBE Aspiration detector prealarm
ASPIR. (NON) non-fire N activates CBE Aspiration detector non-alarm
ASPIR. (REF) non-fire N activates CBE Used as a reference for other aspiration detectors on the
loop.
NOTE: Aspiration detector (FAAST) point programming requires 5 SLC addresses.
ACCL
ACCL (P SUP) fire Y (see activates CBE Combination Photoelectric/Heat detector. Photo element
note activation generates a supervisory condition
below)
ACCL+ (P SUP) fire Y (see activates CBE Combination Photoelectric/Heat detector with low
note temperature warning. Photo element activation generates a
below) supervisory condition.
Point Characteristics
Type Code Point Latching Device Function
Point Function
Type (Y/N)
MONITOR fire alarm Y Lights fire alarm LED and activates CBE Alarm-monitoring device
PULL STATION fire alarm Y Lights fire alarm LED and activates CBE Manual fire-alarm-activating device, such as a pull station
RF MON MODUL fire alarm Y Lights fire alarm LED and activates CBE Wireless alarm-monitoring device
RF PULL STA fire alarm Y Lights fire alarm LED and activates CBE Wireless manual fire-alarm-activating device, such as a pull
station
SMOKE CONVEN fire alarm Y Lights fire alarm LED and activates CBE Indicates activation of a conventional smoke detector
attached to an FZM-1
SMOKE DETECT fire alarm Y Lights fire alarm LED and activates CBE Indicates activation of a conventional smoke detector
attached to an FZM-1
WATERFLOW fire alarm Y Lights fire alarm LED and activates CBE Monitor for waterflow alarm switch
WATERFLOW S supervisory Y Lights supervisory LED and activates CBE Indicates supervisory condition for activated waterflow
switch
ACCESS MONTR non-alarm N Activates CBE Used for monitoring building access
AREA MONITOR security Y Lights security LED and activates CBE Monitors building access
AUDIO SYSTEM trouble N Lights trouble LED Not used
EQUIP MONITR security N Activates CBE Used for recording access to monitored equipment
RF SUPERVSRY supervisory N Lights Supervisory LED Monitors a radio frequency device
SECURITY security Y Lights security LED Indicates activation of security alarm
LATCH SUPERV supervisory Y Lights supervisory LED Indicates latching supervisory condition
TRACK SUPERV supervisory N Lights supervisory LED Monitors for waterflow tamper switches for alarm points
SYS MONITOR security Y Lights security LED and activates CBE Monitors equipment security
TAMPER supervisory Y Lights supervisory LED, activates CBE Indicates activation of tamper switch
ACK SWITCH non-alarm N Performs Acknowledge function, no CBE Silences panel sounder, gives an Acknowledge message on
the panel LCD
ALLCALL PAGE non-alarm N Activates all speaker circuits, no CBE Not used
DRILL SWITCH3 non-alarm N Performs Drill function Activates silenceable outputs
EVACUATE non-alarm N Performs Drill function Activates all silenceable outputs
SWITCH4
FIRE CONTROL non-alarm Y Activates CBE Used for non-fire activation of outputs
NON FIRE non-alarm N Activates CBE Used for building energy management
PAS INHIBIT non-alarm N Inhibits Positive Alarm Sequence Inhibits Positive Alarm Sequence
POWER MONITR trouble N Indicates trouble Monitors auxiliary power supplies
RESET SWITCH non-alarm N Performs Reset function Resets control panel
SIL SWITCH non alarm N Performs Signal Silence function Turns off all activated silenceable outputs
TELE PAGE non-alarm N Performs function of Page Button on FFT-7 Not used
DISABLE MON disable N When a point with this type code activates, Module can not be disabled via ACS, Alter Status, or over
it will create a disable on the panel for that the network.
point. No CBE generated.
TROUBLE MON trouble N Indicates Trouble Monitors trouble inputs
ABORT SWITCH non alarm N Indicates Active at the panel Aborts activation of a releasing zone.
Note: Abort switch can only be associated with one (1)
releasing zone.
MAN RELEASE fire alarm Y Lights Fire Alarm LED and activates CBE Indicates activation of a monitor module programmed to
releasing zone to perform a releasing function
MANREL DELAY fire alarm Y Lights Fire Alarm LED and activates CBE Indicates activation of a monitor module programmed for a
release output
SECOND SHOT fire alarm Y Indicates Active at the panel and activates Provides second activation of releasing zone after soak
CBE timer has expired.
Blank fire alarm Y Lights fire alarm LED and activates CBE Monitors for a device with no description
HEAT DETECT fire alarm Y Lights fire alarm LED and activates CBE Monitors for conventional heat detector
CO MON1 CO alarm Y Activates CBE, no LED will light for CO Monitors conventional CO detector
alarm
ECS/MN SUPT supervisory N Lights supervisory LED and activates CBE. Monitors mass notification devices.
ECS/MN SUPL supervisory Y Lights supervisory LED and activates CBE. Monitors mass notification devices
ESC/MN TROUBLE trouble N Indicates Trouble on a Mass Notification Monitors mass notification devices. Will generate a trouble
MON device condition for both open and short conditions.
ECS/MN MONITOR MNS alarm Y Does not light any LEDs, overrides existing Monitors mass notification devices
fire event2, shuts off silenceable outputs
and all fire activated strobes and activates
CBE.
RF GATEWAY non-alarm Y Activates CBE Provides communication between wireless device and the
fire panel.
1
LED representation of a CO alarm may be performed using an ACS annunciator.
2
IF ECS/MN Override is not selected in VeriFire Tools, fire events will take precedence over ECS/MN audio events.
3
The Drill Switch type code should not be used for Canadian applications.
4
For Canada, point type is alarm.
G.1 China
The REGION panel programming selection provides a setting for China. (Refer to “The Utility Program” on page 44.) This
selection activates the following features:
• POM-8A support
• Active output events displayed. A counter is displayed for active outputs.
• Municipal communication panel settings
• New special function zone for alarm verification
• Prealarm automatically cleared after five minutes
• Co-op detectors alarm functions
• Dual alarm window
• Points in trouble will not activate
• Ten minute limit for DEL and SDEL delay functions
• Disable events do not light LED or trip the trouble relay
• No system trouble generated upon entering program mode
• Low AC operation of FACP
• Power supply troubles
G.2 Canada
The REGION panel programming selection for Canada must meet the following requirements:
Zone Mapping The intelligent sounder base allows for up to 3 No zones mapped.
zones to be programmed for specific tone (When set as default, a fire alarm
generation. The tones available are: will generate a Temp-3 tone and a
• Continuous CO alarm will generate a Temp-4
• Temp-3 tone.)
• Temp-4
• March Tone
The first of the three zones has the highest
priority, the second zone has second priority,
and the third has third priority.
Silence and The intelligent sounder base may be Silenceable and Resound by Fire
Resound programmed for silenceable operation as well Event.
as signal resound. The silence and resound
options available are:
• No silence
• Silence and resound by Fire Alarm
• Silence and resound by Supervisory
• Silence and no resound
• Silence and resound by CO alarm
E L
Equations Labels 20
Argument Entries 102 note about spaces 20
Evaluating 102 Local Control 45
logic and time delay 100 LocM operating mode 32
Logic Functions 101 LocT operating mode 32
rules 100 Logic Functions 101
Time Delay Functions 102
M
F Maintenance Warnings 90
FAAST 10 Manual Release Delay Switch
FAAST XS 10 monitor module configuration example 74
FAAST XT 10 to program 73
FCM-1-REL 2 second delay 18, 29 Manual Release Switch
FireVoice 40 monitor module configuration example 72
FirstCommand NFS-50/100 39 to program 72
FlashScan Manually Initialization, detector 105
Devices, SLC options 46 March Time 28, 87
Poll 13, 46 Master Box trouble message 33
FSA-20000 10 Monitor
FSA-5000 10 default zones 22
FSA-8000 10 to disable programmed points 50
to program monitor 21
G
Gentex Strobes 28 N
Gentex Strobes, special zone 88 NAC
Global System Functions 14 to disable programmed points 50
defaults 31 NBG-12LRA 59, 70, 72, 73, 75
to change 31 Network node 44
as argument 102
H Network Program 13, 44
network node number range 44
History
NFPA Standards for Releasing Applications 58
Clear History 50, 53
NFS-320 keypad 11
Holiday 18, 30
NYC Abort Switch
Holiday, special zone 28
examples 64
programming 63
I
Initiating Devices, releasing zone 84 O
Instant Release Circuit
Operating parameters, to change. See Status
control module configuration example 82
Change
to program 82
Intelligent Sensing Applications 89–99
Drift Compensation 89 P
Maintenance Warnings, 3 levels 90 PAS Inhibit switch 86
Smoothing 89 Password
IP ACCESS 18, 45 Program Change (high level) 11
IRI Abort Switch Status Change (low level) 11, 50
example 62 to change 25
to program 62 to enter 11
Point, to disable/enable 51
K Poll, see FlashScan™ Poll, CLIP Poll
Pre-Alarm 93
keypad 11 Action Functions 93
Alert Level 93
to select a level 94 T
to select sensitivity 95
Temporal Code 28, 87
Pre-Alarm, special zone 18, 28, 30
Terminal mode supervision enable 31
Presignal Delay Timer/PAS 18, 28, 29, 86
Threshold Ch.A/B 44
Program Change 13–47
Time
Program Errors, check for 43
to set time/date for system clock 50, 53
USA or European 31
R Time control, special zones 18, 28, 30, 86
REGION 44 Time Delay Functions 102
Regional Settings 114 TM-4 33, 86
Release Audible Circuit Trouble reminder 45
control module configuration example 81 Two-Stage 28
to program 81 Two-Stage Canada code 87
Release Circuit Two-Stage Canada Manual 88
control module configuration example 79 Two-stage code 87
to program 78 Type Code
Release Code Bell Circuit for releasing zone inputs/outputs 69
NAC configuration example 83 Type Codes 106–111
to program 83 explanation 106
Release End Bell Circuit for Control Modules 110
control module configuration example 76 for Intelligent Detectors 106
Release End Bell Circuit, to program 76 for Monitor Modules 108
Release Form-C Circuit for NACs 111
control module configuration example 80 to select 106
to program 80
Releasing Applications 57–84 U
Releasing Zones (R0-R9) 14, 18, 27, 29, 57 UDACT 33
type codes for inputs/outputs 69 UDACT-2 33
RemT operating mode 32 ULC Release Circuit
control module configuration example 77
S to program 77
Second Shot Switch 75 ULI Abort Switch
monitor module configuration example example 61
Self-Optimizing Pre-Alarm 91 to program 61
Sensitivity level for detector 50, 52 Utility Program 13, 44
Silence Inhibit Timer 31
Smoothing 89 V
Soak Timer 28, 29, 57
VeriFire™ Tools 100
to program (NFPA 16 applications only)
69
Special Function, See Special Zones W
Special Zone Outputs 86–88 Walk Test 50
Special Zones Activation Indications 56
F0-F9 14, 27 Advanced 55
FA,FB 14, 27 Basic
Special Zone F0, notes and restrictions 86 audible 54
Status Change 50–56 silent 54
Options 50 trouble 54
Strobes, See System Sensor,Gentex,Wheelock WARNING
Strobes, special zone Definition 9
System clock 50 Disabling a zone disables all input and out-
System Message, custom 14, 18, 26 put devices.... 51
SYSTEM NORMAL message 18 Do not rely on disable/enable.....to lock out
System Sensor Strobes, special zone 28, 88 releasing devices. 51
If you replace any detector with a different
type... 104
Z
Zones
Custom label 14, 27
Software Zones 01-99 17
to disable programmed points 50
Z00 general alarm 17, 23, 43, 88, 94, 100
Warn-HL-08-2009.fm
www.notifier.com