7.Faults-Protection and Protective DevicesG
7.Faults-Protection and Protective DevicesG
The electric shock may be received by a direct contact or indirect contact with live parts.
1) Covering the live part or parts by insulation, which can only be removed by destruction, e.g. cable
insulation.
2) Placing the live part or parts behind a barrier or an enclosure locked with a key or screws.
3) Placing obstacles to prevent unintentional approach to/or contact with live parts. This method
must only be used where skilled persons are working.
4) Placing out of Arms’ reach: for example, the high level of the bare conductors of travelling cranes.
5) By using a Residual Current Device (RCD) or Earth Leakage (EL): this is not permitted as the sole
means of protection; also one of the other methods should be applied.
The RCD has a rated residual operating current (IΔn) 30mA, and an operating time not
exceeding 40ms at 150mA.
Note that Residual Current Circuit Breaker (RCCB), Residual Circuit Breaker (RCB), Residual
Current Device (RCD), or Earth Leakage (EL) are all names of the same device.
Page 1 of 16
I.b) Protection Against Indirect Contact
Indirect Contact: the contact of persons or livestock with exposed conductive part(s) made live by a
fault.
2) Non-Conducting Location
Is the area in which the floor, walls, and ceiling are insulated.
In such an area, there must be no earth conductors; also the socket outlets must not have
earth connection.
However, it must not be possible to touch two conductive parts, simultaneously.
3) Electrical Separation
This method relies on a supply from a safety source such as isolating transformer, which has
no earth connection on the secondary side, as shown in the Figure below.
However, no an inadvertent connection to earth or interconnection with other circuits must
be made.
Page 2 of 16
II) Protection Against Over-Current:
Over-current is any current greater than the rated current of a circuit. It may damage circuit
conductors or equipments. Over-current occurs either by:
Fuses, Circuit Breaker (CB), or Miniature Circuit Breaker (MCB) are used for protection against over
currents (overload or short-circuit currents).
2) Protective Devices
It is also known as Residual Current Circuit Breaker (RCCB) or Residual Current Breaker (RCB). A photo of a
single phase RCD is shown in the left Figure below, whilst the right Figure below shows a three-phase
RCD.
Page 3 of 16
The construction of a single–phase RCD is shown in the
next Figure. It has the phase and the neutral connected
directly to and out of it. It detects any leakage current by
comparing the current in the phase with that in the
neutral. Typically, it operates when the difference
between both currents (called residual operating current,
IΔn) exceeds 30mA. The RCD operates in not more than
40ms at a fault current of 150mA. It has a Test button [T]
to have the functionally of the device checked
periodically.
In some RCDs, out-of balance current as low as 5mA to 30mA will be detected.
The Test button creates an out-of-balance condition, which operates (trips) the RCD. It is used to
check whether the device is in working order or not.
Note that the phase to neutral fault appears as a load, and hence the RCD will not operate for
this fault.
The three-phase RCD has of four inputs and four outputs. The four inputs are the three phase lines
and the Neutral, whilst the four outputs are the three phase load terminals and the Neutral. It
Page 4 of 16
compares the current sum in the three lines (phases) with the value of the Neutral current. If the
sum of the currents in the three lines is equal to the neutral current, no fault is recorded. If there is a
difference between the current sum in the three lines and the Neutral current, this difference or
residual current will be detected using a magnetic field mechanism. Besides, when the difference
exceeds a threshold value (30mA, 100mA or 300mA …), the RCD will trip isolating the main source
from the load, and consequently preventing more damage to the system or Shock Risks.
Nuisance Tripping:
Certain appliances such as cookers, water heaters, and freezers tend to have, by the nature of their
construction and use, some leakage currents to earth. This may cause the operation of an RCD
protecting an entire installation. Sometimes this problem is also faced in particular factories.
2.2) Fuses:
A Fuse: is a device which carries a metal element, usually tinned Copper, that will melt and break the
circuit when an excessive current flows; it acts as a sacrificial device to provide over-current
protection. Thus, it forms the weakest link in a circuit and protects the circuit conductors from
damage. There are many different types, ratings and sizes of fuses.
Fuses Types:
A) Rewirable (Renewable) or semi-enclosed Fuse
B) Cartridge Fuse and Fuse link
C) High-Rupturing-Capacity Fuse
Page 5 of 16
2.2.A.) Rewirable (Renewable) Fuse:
It consists of a porcelain or glass tube with metal and caps to which the element is attached.
The Fuse is filled with Silica. The left Figure below shows the main components of a Cartridge Fuse,
whilst the right Figure shows samples of this type of Fuse.
Page 6 of 16
These Fuses are found in modern plug tops, some distribution boards, and equipments.
They are more expensive to replace!
The protective device (Fuse or MCB) is characterized a Fusing Factor, a Nominal Current Rating (In), and an
Operating Current (I2).
Nominal Current Rating (In): is the maximum current which a protective device (a Fuse or an MCB) can
sustain (carry indefinitely) without blowing (or tripping).
Operating Current (I2): is the minimum current causing a Fuse to blow or a Circuit Breaker to trip.
Page 8 of 16
Example # 1: A 5A fuse blows only when a 9A current flows, what is the Fusing Factor?
Solution:
When a short circuit occurs, the current may for a fraction of a second, reach hundreds or even thousands
of Amperes. The protective device must be able to break or make the high (short circuit) current without
damage to its surroundings by arcing, overheating or scattering of hot particles. According to IEC, the MCB
is assigned Icu (for industrial) or Icn (for domestic) to indicate the rated ultimate short circuit breaking
capacity, which is normally given in kArms. For example, according to British standards, the breaking
capacity of MCBs is indicated by an “M” number; i.e. M3-3KA, M6-6KA, M9-9KA; in other regulations it is
given by a number only, e.g. 6000.
In high current three-phase Circuit Breakers, the breaking capacity could reach hundreds of
thousands of amperes.
In some types of Fuses and Circuit Breakers, the breaking capacity is in the range of hundreds of
MVA, e.g. 750MVA, or even much higher.
Page 9 of 16
Fuse and Circuit Breaker Operation:
Recall the definition of:
The Nominal current rating (In): the value of current that can be carried indefinitely by the protective
device.
The Operating current ( ): the value of current that will cause operation of the protective device
( ).
Coordination:
IEE Regulations require coordination between conductors and protection when an over current (over load
or short circuit) occurs by taking into account the following points:
1. In is greater than or equal to design current of the circuit (Ib); (In > Ib)
2. In is less than or equal to the lowest current-carrying capacity (IZ) of any conductor ( )
3. The operating current of the device ( ) is less than or equal to 1.45 ( )
Example # 2: The nominal current (In) of a protective device is 10A, the Fusing Factor is 1.45 and the cable
current-carrying capacity ( ) is also 10A.
a) Does the design comply with IEE Regulations?
b) If a Rewirable Fuse was used with a Fusing Factor of 2, then what would be its Nominal Current to
make the design comply with IEE Regulations?
Solution:
a) Since In= 10A = , then Condition # 2 is satisfied.
Since the Fusing Factor is 1.45, then the Operating Current of the device is:
As no information is given about the circuit Design Current, the design complies with IEE
Regulations.
Page 10 of 16
b) To satisfy Condition # 3, the Operating current of the fuse should be less than or equal to
1.45Xcable rating;
But,
Where, k is a factor which depends on cable’s material, temperature and properties and can be
calculated or obtained from tables, whilst A is the cross sectional area of cable [mm2].
Discrimination:
Where several protective devices (Fuses or Circuit Breakers) are connected in series at the various levels
of a power distribution system, it is desirable to blow (clear) only the Fuse (or other protective device)
electrically closest to the fault; in the Figure below Fuse ‘C’ should blow not ‘B’ nor ‘A’.
Discrimination: is the arrangement of protective devices to protect the correct part of the circuit.
Discrimination between Fuses (or protective device) is achieved if the Total Let-through energy of the
minor Fuse (or protective device) does not exceed the Pre-arcing Let-through energy of the major Fuse (or
protective device). Table # 2 shows the If2t energy of Fuses.
Page 12 of 16
2
Table # 2: If t energy of Fuses
Page 13 of 16
Time-Current Characteristic of Fuses
Page 14 of 16
MCB Classifications:
According to IEC regulations, the MCB class determines the value of overload current compared to rated
current to operate instantaneously. The circuit breaker is labeled with the rated current in Amperes, but
without the unit symbol "A". Instead, the Ampere figure is preceded by a letter "B", "C" or "D" that
indicates the instantaneous (operating) tripping current, that is the minimum value of current that causes
the circuit breaker to trip without intentional time delay (i.e., in less than 100 ms), expressed in terms of
In. Table # 3 lists the classes of MCB against the value of the operating currents according to IEC, whilst
Table # 4 lists the classes of MCB against the value of the overload currents according to British Standards.
Table # 3: Classes of MCB against the value of the Operating current according to IEC Regulations
Class (Type) Operating (Instantaneous Tripping) current
1 4 times
2 7 times
3 10 times
B and C 5 times
Page 15 of 16
Application Categories of Fuses
According to IEC 60269, the application category of Fuses is a two-digit code (e.g. gG):
The first letter is a if the Fuse is for short-circuit protection only; an associated device must
provide overload protection.
The first letter is g if the Fuse is intended to operate even with currents as low as those that cause
it to blow in one hour. These are considered general-purpose Fuses for protection of wires.
Any Fuse built according IEC 60269 standard and carrying the same application category (for
example, gG or aM) will have similar electrical characteristics, time-current characteristics, power
dissipation as any other, even if the Fuses are made in the packages standardized to the earlier
national standards. Fuses of the same application category can be substituted for each other
provided the voltage rating of the circuit does not exceed the Fuse rating.
Page 16 of 16