Protection Automation Application Guide v1 - Compressed (201 300)
Protection Automation Application Guide v1 - Compressed (201 300)
ZR − ZF IB
x 100%
ZR
ZC
where:
∼ IA+IB
ZR = intended relay reach (relay reach setting) Source
xZC
A IA
ZF = effective reach F
ZA
The main cause of under-reaching is the effect of fault current
infeed at remote busbars. This is best illustrated by an Z<
example. Relaying point
Relay setting: ZA+ZC
In Figure 11.21, the relay at A will not measure the correct Relay actual reach due to parallel line infeed: ZA+xZC
impedance for a fault on line section ZC due to current infeed
Figure 11.21: Effect on distance relays of infeed at the remote busbar
IB.
Care should also be taken that large forward reach settings will
For a fault at point F, the relay is presented with an not result in operation of healthy phase relays for reverse earth
impedance: faults, see Section 11.10.5.
I A + IB
ZA + ZC 11.10.4 Over-Reach
IA
A distance relay is said to over-reach when the apparent
So, for relay balance: impedance presented to it is less than the impedance to the
fault.
Z A + ZC = Z A +
(I A + I B ) Z
IA
C Percentage over-reach is defined by the equation:
11-18
Chapter 11 ⋅ Distance Protection
11-19
Protection & Automation Application Guide
CB condition monitoring R1G Ground fault resistive reach value - Zone 1 104 Ω
CB control R2G Ground fault resistive reach value - Zone 2 104 Ω
Measurement of voltages, currents, etc. R3G Ground fault resistive reach value - Zone 3 104 Ω
Event recorder Table 11.2: Distance relay parameters for example
Disturbance recorder Calculations are carried out in terms of primary system
CB failure detection/logic impedances in ohms, rather than the traditional practice of
Directional/Non-directional phase fault overcurrent protection (backup to distance protection) using secondary impedances. With numerical relays, where
Directional/Non-directional earth fault overcurrent protection (backup to distance protection) the CT and VT ratios may be entered as parameters, the
Negative sequence protection
scaling between primary and secondary ohms can be
performed by the relay. This simplifies the example by
Under/overvoltage protection
allowing calculations to be carried out in primary quantities
Stub-bus protection
and eliminates considerations of VT/CT ratios.
Broken conductor detection
User-programmable scheme logic ABC XYZ PQR
1000/1A
100km 60km
Table 11.1: Listing of possible additional features in a numerical GS
distance relay
230kV 230kV 230kV
EXAMPLE
The system diagram shown in Figure 11.22 shows a simple Z<
230kV network. The following example shows the calculations
necessary to apply three-zone distance protection to the line Source Impedance: 5000MVA max
2000MVA min
interconnecting substations ABC and XYZ. All relevant data for
Line Impedance: Z = 0.089 + j0.476Ω/ km
this exercise are given in the diagram. The MiCOM P441 relay 1
= Z o 0. 4 2 6 + j 1 . 5 7 6 Ω / km
with quadrilateral characteristics is considered in this example.
Relay parameters used in the example are listed in Table 11.2. Figure 11.22: Example network for distance relay setting calculation
11-20
Chapter 11 ⋅ Distance Protection
(Z 0 − Z1 ) = 83.275∠79.41 Ω
K ZO =
3Z 1 Use a setting of 83.27∠80 Ω , nearest available setting.
11-21
Protection & Automation Application Guide
reach settings for each zone can be set independently of the R1G = 104Ω
impedance reach settings. The resistive reach setting
represents the maximum amount of additional fault resistance R2G = 104Ω
(in excess of the line impedance) for which a zone will trip,
regardless of the location of the fault within the zone. R3G = 104Ω
Two constraints are imposed upon the settings, as follows:
• it must be greater than the maximum expected phase- This completes the setting of the relay. Table 11.2 also shows
phase fault resistance (principally that of the fault arc) the settings calculated.
• it must be less than the apparent resistance measured
due to the heaviest load on the line, unless load 11.13 REFERENCE
blinding (load encroachment) is applied [11.1] Protective Relays – their Theory and Practice. A.R. van
The minimum fault current at Substation ABC is of the order of C. Warrington. Chapman and Hall, 1962
1.8kA, leading to a typical arc resistance Rarc using the van
Warrington formula (Equation 11.4) of 8Ω. Using the current
transformer ratio as a guide to the maximum expected load
current, the minimum load impedance Zlmin will be 130Ω.
Typically, the resistive reaches will be set to avoid the minimum
load impedance by a 40% margin for the phase elements,
leading to a maximum resistive reach setting of 78Ω.
Therefore, the resistive reach setting lies between 8Ω and 78Ω.
Allowance should be made for the effects of any remote fault
infeed, by using the maximum resistive reach possible. While
each zone can have its own resistive reach setting, for this
simple example they can all be set equal. This need not always Figure 11.23: Typical modern distance relay (Multilin D60 Distance
be the case, it depends on the particular distance protection Protection System)
scheme used and the need to include Power Swing Blocking.
Suitable settings are chosen to be 80% of the load resistance:
R1 ph = 78Ω
R2 ph = 78Ω
R3 ph = 78Ω
11-22
Chapter 11 ⋅ Distance Protection
11-23
DISTANCE PROTECTION
SCHEMES
Chapter 12
DISTANCE PROTECTION SCHEMES
Relay A
End Zone
Z3A
Time
Z2A
Z1A
A B C
F
0
Z1B
Z2B
Z3B
Relay B
End Zone
(a) Stepped time/distance characteristics
Z1
Z2 Z2T 0
≥1 Trip
Z3 Z3T 0
GEGridSolutions.com 12-1
Protection & Automation Application Guide
in the possibility that a transient fault will cause 12.2 ZONE 1 EXTENSION SCHEME (Z1X
permanent lockout of the circuit breakers at each end of SCHEME)
the line section
This scheme is intended for use with an auto-reclose facility, or
Even where instability does not occur, the increased duration where no communications channel is available, or the channel
of the disturbance may give rise to power quality problems, has failed. Thus it may be used on radial distribution feeders,
and may result in increased plant damage. or on interconnected lines as a fallback when no
Unit schemes of protection that compare the conditions at the communications channel is available, e.g. due to maintenance
two ends of the feeder simultaneously positively identify or temporary fault. The scheme is shown in Figure 12.2.
whether the fault is internal or external to the protected section The Zone 1 elements of the distance relay have two settings.
and provide high-speed protection for the whole feeder length. One is set to cover 80% of the protected line length as in the
This advantage is balanced by the fact that the unit scheme basic distance scheme. The other, known as 'Extended Zone
does not provide the back up protection for adjacent feeders 1’ or ‘Z1X’, is set to overreach the protected line, a setting of
given by a distance scheme. 120% of the protected line being common. The Zone 1 reach is
The most desirable scheme is obviously a combination of the normally controlled by the Z1X setting and is reset to the basic
best features of both arrangements, that is, instantaneous Zone 1 setting when a command from the auto-reclose relay is
tripping over the whole feeder length plus back-up protection received.
to adjacent feeders. This can be achieved by interconnecting On occurrence of a fault at any point within the Z1X reach, the
the distance protection relays at each end of the protected relay operates in Zone 1 time, trips the circuit breaker and
feeder by a communications channel. Communication initiates auto-reclosure. The Zone 1 reach of the distance relay
techniques are described in detail in Chapter 8. is also reset to the basic value of 80%, prior to the auto-reclose
The purpose of the communications channel is to transmit closing pulse being applied to the breaker. This should also
information about the system conditions from one end of the occur when the auto-reclose facility is out of service.
protected line to the other, including requests to initiate or Reversion to the Z1X reach setting occurs only at the end of
prevent tripping of the remote circuit breaker. The former the reclaim time. For interconnected lines, the Z1X scheme is
arrangement is generally known as a 'transfer tripping scheme' established (automatically or manually) upon loss of the
while the latter is generally known as a 'blocking scheme'. communications channel by selection of the appropriate relay
However, the terminology of the various schemes varies setting (setting group in a numerical relay). If the fault is
widely, according to local custom and practice. transient, the tripped circuit breakers will reclose successfully,
but otherwise further tripping during the reclaim time is
Z3A subject to the discrimination obtained with normal Zone 1 and
Z2A
Zone 2 settings.
Z1A Z1extA
The disadvantage of the Zone 1 extension scheme is that
A B C external faults within the Z1X reach of the relay result in
tripping of circuit breakers external to the faulted section,
Z1extB Z1B increasing the amount of breaker maintenance needed and
Z2B needless transient loss of supply to some consumers. This is
Z3B illustrated in Figure 12.3(a) for a single circuit line where three
(a) Distance/time
(a) Z1ext scheme characteristics
- zone reaches circuit breakers operate and in Figure 12.3(b) for a double
circuit line, where five circuit breakers operate.
Auto-reclose
Reset Zone 1ext
Zone 1ext &
≥1 Trip
Zone 1
12-2
Chapter 12 ⋅ Distance Protection Schemes
Z1A Z1ext A
Signal
A B C Z1
send
Z2 Z2T 0
(a) Fault within Zone 1 extension reach of distance relays Signal receive
(single circuit lines)
Figure 12.4: Logic for direct underreach transfer tripping scheme
Z1A Z1extA A fault F in the end zone at end B in Figure 12.1(a) results in
operation of the Zone 1 relay and tripping of the circuit breaker
A D
B C at end B. A request to trip is also sent to the relay at end A.
Z1extD Z1D The receipt of a signal at A initiates tripping immediately
Z1extB Z1B because the receive relay contact is connected directly to the
Z1C Z1extC
trip relay. The disadvantage of this scheme is the possibility of
undesired tripping by accidental operation or maloperation of
signalling equipment, or interference on the communications
Z1P Z1extP
channel. As a result, it is not commonly used.
P L
N M
12.3.2 Permissive Under-reach Transfer Tripping
Z1extN Z1N (PUP) Scheme
Z1M Z1extM The direct under-reach transfer tripping scheme described
Z1extL Z1L
above is made more secure by supervising the received signal
with the operation of the Zone 2 relay element before allowing
(b) Fault within Zone 1 extension reach of distance relays an instantaneous trip, as shown in Figure 12.5. The scheme is
(double circuit lines) then known as a 'permissive under-reach transfer tripping
Figure 12.3: Performance of Zone 1 extension scheme in conjunction scheme' (sometimes abbreviated as a PUTT, PUR or PUP Z2
with auto-reclose relays
scheme) or ‘permissive underreach distance protection’, as
both relays must detect a fault before the remote end relay is
12.3 TRANSFER TRIPPING SCHEMES
permitted to trip in Zone 1 time.
A number of these schemes are available, as described below.
Selection of an appropriate scheme depends on the
requirements of the system being protected.
12-3
Protection & Automation Application Guide
A B
Signal F
Z1
send
Z2T 0
∼
Z2
Z3 Z3T 0
≥1
Trip
A B
F
(a) Signal logic
Open
Distance relay
circuit circuit
send (f1) (f1) send
12-4
Chapter 12 ⋅ Distance Protection Schemes
Z3A
Signal
Z2A Z1
send
Z1A
A B C Z2 Z2T 0
Z1B
Z3 Z3T 0
≥1
Z2B Trip
Z3B
Z3T 0 ≥1 Trip
Z3
Signal Send f1 f2 Send Signal
Distance relay
Distance relay
circuit circuit
send (f1) (f2) send
Z2T 0
≥1 Range change signal Signal Receive Receive Signal
circuit circuit
Signal receive receive (f2) f2 f1 (f1) receive
(b) Signal logic Figure 12.8: Permissive over-reach transfer tripping scheme
Figure 12.7: Permissive under-reaching acceleration scheme
Since the signalling channel is keyed by over-reaching Zone 2
elements, the scheme requires duplex communication
12.3.4 Permissive Over-reach Transfer Tripping (POP)
channels - one frequency for each direction of signalling.
Scheme
If distance relays with mho characteristics are used, the
In this scheme, a distance relay element set to reach beyond
scheme may be more advantageous than the permissive
the remote end of the protected line is used to send an
under-reaching scheme for protecting short lines, because the
intertripping signal to the remote end. However, it is essential
resistive coverage of the Zone 2 unit may be greater than that
that the receive relay contact is monitored by a directional relay
of Zone 1.
contact to ensure that tripping does not take place unless the
fault is within the protected section; see Figure 12.8. The To prevent operation under current reversal conditions in a
instantaneous contacts of the Zone 2 unit are arranged to send parallel feeder circuit, it is necessary to use a current reversal
the signal, and the received signal, supervised by Zone 2 guard timer to inhibit the tripping of the forward Zone 2
operation, is used to energise the trip circuit. The scheme is elements. Otherwise maloperation of the scheme may occur
then known as a 'permissive over-reach transfer tripping under current reversal conditions, see Section 12.3.2 for more
scheme' (sometimes abbreviated to POTT, POR or POP), details. It is necessary only when the Zone 2 reach is set
'directional comparison scheme', or ‘permissive overreach greater than 150% of the protected line impedance.
distance protection scheme’. The timer is used to block the permissive trip and signal send
circuits as shown in Figure 12.9. The timer is energised if a
signal is received and there is no operation of Zone 2 elements.
An adjustable time delay on pick-up (tp) is usually set to allow
instantaneous tripping to take place for any internal faults,
taking into account a possible slower operation of Zone 2. The
timer will have operated and blocked the ‘permissive trip’ and
‘signal send’ circuits by the time the current reversal takes
place.
12-5
Protection & Automation Application Guide
Signal transmission can take place even after the remote end
&
Signal
breaker has tripped. This gives rise to the possibility of
Send continuous signal transmission due to lock-up of both signals.
Figure 12.9: Current reversal guard logic – permissive over-reach Timer T2 is used to prevent this. After this time delay, 'signal
scheme send' is blocked.
The timer is de-energised if the Zone 2 elements operate or the A variation on the Weak Infeed Echo feature is to allow
'signal received' element resets. The reset time delay (td) of tripping of the remote relay under the circumstances described
the timer is set to cover any overlap in time caused by Zone 2 above, providing that an undervoltage condition exists, due to
elements operating and the signal resetting at the remote end, the fault. This is known as the Weak Infeed Trip feature and
when the current in the healthy feeder reverses. Using a timer ensures that both ends are tripped if the conditions are
in this manner means that no extra time delay is added in the satisfied.
permissive trip circuit for an internal fault.
The above scheme using Zone 2 relay elements is often 12.4 BLOCKING OVERREACHING SCHEMES
referred to as a POP Z2 scheme. An alternative exists that The arrangements described so far have used the signalling
uses Zone 1 elements instead of Zone 2, and this is referred to channel(s) to transmit a tripping instruction. If the signalling
as the POP Z1 scheme. However POP Z1 is unusual as it channel fails or there is no Weak Infeed feature provided, end-
requires Zone 1 to be set overreaching, which is not usual zone faults may take longer to be cleared.
practice.
Blocking over-reaching schemes use an over-reaching distance
scheme and inverse logic. Signalling is initiated only for
12.3.5 Weak Infeed Conditions
external faults and signalling transmission takes place over
In the standard permissive over-reach scheme, as with the healthy line sections. Fast fault clearance occurs when no
permissive under-reach scheme, instantaneous clearance signal is received and the over-reaching Zone 2 distance
cannot be achieved for end-zone faults under weak infeed or measuring elements looking into the line operate. The
breaker open conditions. To overcome this disadvantage, two signalling channel is keyed by reverse-looking distance
possibilities exist. elements (Z3 in the diagram, though which zone is used
The Weak Infeed Echo feature available in some protection depends on the particular relay, with a dedicated reverse zone
relays allows the remote relay to echo the trip signal back to such as Zone 4 now commonly-used in numerical relays). An
the sending relay even if the appropriate remote relay element ideal blocking scheme is shown in Figure 12.11.
has not operated. This caters for conditions of the remote end
having a weak infeed or circuit breaker open condition, so that
the relevant remote relay element does not operate. Fast
clearance for these faults is now obtained at both ends of the
line. The logic is shown in Figure 12.10. A time delay (T1) is
required in the echo circuit to prevent tripping of the remote
end breaker when the local breaker is tripped by the busbar
protection or breaker fail protection associated with other
feeders connected to the busbar. The time delay ensures that
the remote end Zone 2 element will reset by the time the
echoed signal is received at that end.
12-6
Chapter 12 ⋅ Distance Protection Schemes
Z1A
‘blocking over-reach distance protection scheme’.
A B C Z1 Signal
F1 F2 F3
send
Z2T 0
Z1B Z2
Z2B
Z3B
Z3 Z3T 0
≥1
(a) Distance/time characteristics Trip
STL 0
Signal send
Z1 &
0 td
Z2T 0 Signal receive
Z2
Channel in service
Z3 Z3T 0 ≥1 Trip
Figure 12.12: Signal logic for BOP Z2 scheme
Distance relay
Signal
send
circuit
(f1)
circuit
(f1) send ends of the protected line. Signalling is controlled by the Z3
elements looking away from the protected section, so no
Receive Receive
Signal
circuit circuit
Signal
transmission takes place, thus giving fast tripping via the
receive (f1) (f1) receive
forward-looking Zone 1 elements.
Signalling equipment Signalling equipment
-End A -End B
A fault at F2 is seen by the forward-looking Zone 2 elements at
(c) Signalling arrangement ends A and B and by the Zone 1 elements at end B. No signal
Figure 12.11: Ideal distance protection blocking scheme transmission takes place, since the fault is internal and the
The single frequency signalling channel operates both local and fault is cleared in Zone 1 time at end B and after the short time
remote receive relays when a block signal is initiated at any lag (STL) at end A.
end of the protected section. A fault at F3 is seen by the reverse-looking Z3 elements at end
B and the forward looking Zone 2 elements at end A. The
12.4.1 Practical Blocking Schemes Zone 1 relay elements at end B associated with line section B-
A blocking instruction has to be sent by the reverse-looking C would normally clear the fault at F3. To prevent the Z2
relay elements to prevent instantaneous tripping of the remote elements at end A from tripping, the reverse-looking Zone 3
relay for Zone 2 faults external to the protected section. To elements at end B send a blocking signal to end A. If the fault
achieve this, the reverse-looking elements and the signalling is not cleared instantaneously by the protection on line section
channel must operate faster than the forward-looking B-C, the trip signal will be given at end B for section A-B after
elements. In practice, this is seldom the case and to ensure the Z3 time delay.
discrimination, a short time delay is generally introduced into The setting of the reverse-looking Zone 3 elements must be
the blocking mode trip circuit. Either the Zone 2 or Zone 1 greater than that of the Zone 2 elements at the remote end of
element can be used as the forward-looking element, giving the feeder, otherwise there is the possibility of Zone 2 elements
rise to two variants of the scheme. initiating tripping and the reverse looking Zone 3 elements
failing to see an external fault. This would result in
12.4.1.1 Blocking over-reaching protection scheme using instantaneous tripping for an external fault. When the
Zone 2 element signalling channel is used for a stabilising signal, as in the
This scheme (sometimes abbreviated to ‘BLOCKING’ or BOP above case, transmission takes place over a healthy line
Z2) is based on the ideal blocking scheme of Figure 12.11, but section if power line carrier is used. The signalling channel
has the signal logic illustrated in Figure 12.12. It is also should then be more reliable when used in the blocking mode
than in tripping mode.
12-7
Protection & Automation Application Guide
It is essential that the operating times of the various relays be 12.4.1.2 Blocking over-reaching protection scheme using
skilfully co-ordinated for all system conditions, so that Zone 1 element
sufficient time is always allowed for the receipt of a blocking This is similar to the BOP Z2 scheme described above, except
signal from the remote end of the feeder. If this is not done that an over-reaching Zone 1 element is used in the logic,
accurately, the scheme may trip for an external fault or instead of the Zone 2 element. It may also be known as the
alternatively, the end zone tripping times may be delayed BOP Z1 scheme, although it is rarely used.
longer than is necessary.
If the signalling channel fails, the scheme must be arranged to 12.4.2 Weak Infeed Conditions
revert to conventional basic distance protection. Normally, the The protection at the strong infeed terminal will operate for all
blocking mode trip circuit is supervised by a 'channel-in- internal faults, since a blocking signal is not received from the
service' contact so that the blocking mode trip circuit is weak infeed terminal end. In the case of external faults behind
isolated when the channel is out of service, as shown in Figure the weak infeed terminal, the reverse-looking elements at that
12.12. end will see the fault current fed from the strong infeed
In a practical application, the reverse-looking relay elements terminal and operate, initiating a block signal to the remote
may be set with a forward offset characteristic to provide back- end. The relay at the strong infeed end operates correctly
up protection for busbar faults after the zone time delay. It is without the need for any additional circuits. The relay at the
then necessary to stop the blocking signal being sent for weak infeed end cannot operate for internal faults, and so
internal faults. This is achieved by making the ‘signal send’ tripping of that breaker is possible only by means of direct
circuit conditional upon non-operation of the forward-looking intertripping from the strong source end.
Zone 2 elements, as shown in Figure 12.13.
12.5 DIRECTIONAL COMPARISON
Z3G
UNBLOCKING SCHEME
Z2G
Z1G The permissive over-reach scheme described in Section 12.3.4
can be arranged to operate on a directional comparison
G H
unblocking principle by providing additional circuitry in the
Z1H signalling equipment. In this scheme (also called a ’deblocking
Z2H overreach distance protection scheme’), a continuous block (or
Z3H
guard) signal is transmitted. When the over-reaching distance
elements operate, the frequency of the signal transmitted is
(a) Distance/time characteristics
shifted to an 'unblock' (trip) frequency. The receipt of the
unblock frequency signal and the operation of over-reaching
Z3
& Signal Send
distance elements allow fast tripping to occur for faults within
Z2
the protected zone. In principle, the scheme is similar to the
(b) Solid state logic of send circuit permissive over-reach scheme.
Figure 12.13: Blocking scheme using reverse-looking relays The scheme is made more dependable than the standard
Blocking schemes, like the permissive over-reach scheme, are permissive over-reach scheme by providing additional circuits
also affected by the current reversal in the healthy feeder due in the receiver equipment. These allow tripping to take place
to a fault in a double circuit line. If current reversal conditions for internal faults even if the transmitted unblock signal is
occur, as described in Section 12.3.2, it may be possible for the short-circuited by the fault. This is achieved by allowing aided
maloperation of a breaker on the healthy line to occur. To tripping for a short time interval, typically 100 to 150
avoid this, the resetting of the ‘signal received’ element milliseconds, after the loss of both the block and the unblock
provided in the blocking scheme is time delayed. frequency signals. After this time interval, aided tripping is
permitted only if the unblock frequency signal is received.
The timer with delayed resetting (td) is set to cover the time
difference between the maximum resetting time of reverse- This arrangement gives the scheme improved security over a
looking Zone 3 elements and the signalling channel. So, if blocking scheme, since tripping for external faults is possible
there is a momentary loss of the blocking signal during the only if the fault occurs within the above time interval of
current reversal, the timer does not have time to reset in the channel failure. Weak Infeed terminal conditions can be
blocking mode trip circuit and no false tripping takes place. catered for by the techniques detailed in 12.3.5 Weak Infeed
Conditions.
12-8
Chapter 12 ⋅ Distance Protection Schemes
12-9
PROTECTION OF
COMPLEX TRANSMISSION
CIRCUITS
Chapter 13
PROTECTION OF COMPLEX
TRANSMISSION CIRCUITS
Source Source
∼ ∼
Bus A Bus B
Figure 13.1: Parallel and Multi-ended feeders
GEGridSolutions.com 13-1
Protection & Automation Application Guide
13.2.2.1 Current Reversal on Double Circuit Lines (b) Fault current distribution
with circuit breaker D open
When a fault is cleared sequentially on one circuit of a double
Figure 13.2: Fault current distribution in double-circuit line
circuit line with generation sources at both ends of the circuit,
the current in the healthy line can reverse for a short time.
13.2.2.2 Under-Reach on Parallel Lines
Unwanted tripping of CBs on the healthy line can then occur if
a Permissive Overreach or Blocking distance scheme (see If a fault occurs on a line that lies beyond the remote terminal
Chapter 12) is used. Figure 13.2 shows how the situation can end of a parallel line circuit, the distance relay under-reaches
arise. The CB at D clears the fault at F faster than the CB at for those zones set to reach into the affected line. Analysis
shows that under these conditions, because the relay sees only
C. Before CB D opens, the Zone 2 elements at A may see the
50% (for two parallel circuits) of the total fault current for a
fault and operate, sending a permissive trip signal to the relay
fault in the adjacent line section, the relay sees the impedance
for CB B. The reverse looking element of the relay at CB B
of the affected section as twice the correct value. This may
also sees the fault and inhibits tripping of CBs A and B.
have to be allowed for in the settings of Zones 2 and 3 of
However, once CB D opens, the relay element at A starts to
conventionally set distance relays.
reset, while the forward looking elements at B pick up (due to
current reversal) and could initiate tripping. If the reset time of Since the requirement for the minimum reach of Zone 2 is to
the forward-looking elements of the relay at A is longer than the end of the protected line section and the under-reach effect
the operating time of the forward-looking elements at B, the only occurs for faults in the following line section(s), it is not
relays trip the healthy line. The solution is to incorporate a usually necessary to adjust Zone 2 impedance settings to
blocking time delay that prevents the tripping of the forward- compensate. However, Zone 3 elements are intended to
looking elements of the relays and is initiated by the reverse- provide backup protection to adjacent line sections and hence
looking element. This time delay must be longer than the reset the under-reaching effect must be allowed for in the
time of the relay elements at A. impedance calculations.
13-2
Chapter 13 ⋅ Protection of Complex Transmission Circuits
IB ZM 0
Z L1 Z LO
M =
Z S′ 1 ,Z SO
′
Line B
Z S′′1 ,Z SO
′′
Z L1
∼ Z MO ∼
IA The true impedance to the fault is nZL1where n is the per unit
Line A fault position measured from R and ZL1 is the positive
n sequence impedance of a single circuit. The 'error' in
Fault
measurement is determined from the fraction inside the
Relay R
Location bracket; this varies with the positive and zero sequence
(a) Single line diagram currents in circuit A and the zero sequence current in circuit B.
I B1 Z L1
These currents are expressed below in terms of the line and
Z S′ 1 Z S′′1 source parameters:
I A1 F1 I B0 nZ S'' 0 − (1 − n )Z S' 0
=
nZ L1 (1 − n ) Z L1 (
I A0 (2 − n )Z S'' 0 + (1 − n ) Z S' 0 + Z L 0 + Z M 0 )
R
I A1 =
( )
(b) Positive sequence network
1
2 Z S' 1 + Z S'' 1 + Z L1
I BO ( Z LO − Z M O )
′
Z SO nZ M O (1 − n ) Z M O ′′
Z SO
I A0 =
(2 − n )Z S'' 0 + (1 − n )(Z S' 0 + Z L 0 + Z M 0 ) I
I AO FO
( )
2 Z S' 0 + Z S'' 0 + Z L 0 + Z M 0
0
R
n ( ZLO − Z M O ) (1 − n ) ( Z LO − Z M O ) and
IO
ZM0 = zero sequence mutual impedance between two
(c) Zero sequence network circuits
Figure 13.3: General parallel circuit fed from both ends NOTE: For earth faults I1 = I0
As the current distribution in the two circuits is unaffected by
All symbols in the above expressions are either self-explanatory
the presence of mutual coupling, no similar variation in the
from Figure 13.3 or have been introduced in Chapter 11.
current applied to the relay element takes place and,
Using the above formulae, families of reach curves may be
consequently, the relay measures the impedance to the fault
constructed, of which Figure 13.4 is typical. In this figure, n’
incorrectly. Whether the apparent impedance to the fault is
is the effective per unit reach of a relay set to protect 80% of
greater or less than the actual impedance depends on the
the line. It has been assumed that an infinite busbar is located
direction of the current flow in the healthy circuit. For the
at each line end, that is, Z’S1 and Z”S1 are both zero. A family
common case of two circuits, A and B, connected at the local
of curves of constant n’ has been plotted for variations in the
and remote busbars, as shown in Figure 13.3, the impedance
source zero sequence impedances Z’S0 and Z”S0.
of Line A measured by a distance relay, with the normal zero
sequence current compensation from its own feeder, is given
by:
I B0
M
Z A = nZ L1 1 + I A0
I A1
2 + K
I A0
Equation 13.1
where:
13-3
Protection & Automation Application Guide
100 VR
Limit of n' =0.67 5 = Z L1
50 when y ∞ 0 .6
7
8
IR
x 0 n' = .6
=0
n'
0.
7 For a solid phase to earth fault at the theoretical reach of the
n' =
75
relay, the voltage and current in the faulty phase at the
10 0.
n' = .8 relaying point are given by:
=0 85
n' 0.
5
n'
= V A = I A1 Z L1 + I A 2 Z L 2 + I A0 Z L 0 + I B 0 Z M 0
1)
e
Z ′′
on
9
(Z
y = SO
.
n'
=0
Z LO I A = I A1 + I A 2 + I A0
gn
tti
se
95
al
1
Equation 13.2
.
in
=0
m
n'
No
0.5
The voltage and current fed into the relay are given by:
Limit of
n'=1
VR = V A
when y 0
0.1
x ∞ I R = I A + K R I A0 + K M I B 0
0.1 0.5 1 5 10 50 100
Z
x = SO
Equation 13.3
Z LO
where:
Figure 13.4: Typical reach curves showing the effect of mutual coupling
Figure 13.4 shows that relay R can under-reach or over-reach, K R = the residual compensation factor
according to the relative values of the zero sequence source to
K M = the mutual compensation factor
line impedance ratios; the extreme effective per unit reaches
for the relay are 0.67 and 1. Relay over-reach is not a Thus:
problem, as the condition being examined is a fault in the
protected feeder, for which relay operation is desirable. In
Z L 0 − Z L1
KR =
Figure 13.4, relay R tends to under-reach whereas the relay at Z L1
the opposite line end tends to over-reach. As a result, the
ZM 0
Zone 1 characteristic of the relays at both ends of the feeder KM =
overlap for an earth fault anywhere in the feeder – see Section Z L1
13.2.2.5 for more details.
13.2.2.4 Distance Relay Behaviour with Earth Faults on
Satisfactory protection can be obtained with a transfer trip, the Parallel Feeder
under-reach type distance scheme. Further, compensation for
Although distance relays with mutual compensation measure
the effect of zero sequence mutual impedance is not necessary
the correct distance to the fault, they may not operate correctly
unless a distance-to-fault facility is provided. Some
if the fault occurs in the adjacent feeder. Davison and Wright
manufacturers compensate for the effect of the mutual
[13.1] have shown that while distance relays without mutual
impedance in the distance relay elements, while others may
compensation do not over-reach for faults outside the
restrict the application of compensation to the distance-to-
protected feeder, the relays may see faults in the adjacent
fault function only. The latter is easy to implement in software
feeder if mutual compensation is provided. With reference to
for a digital/numerical relay but is impractical in relays using
Figure 13.3, the amount of over-reach is highest when
older technologies. Compensation is achieved by injecting a
proportion of the zero sequence current flowing in the parallel Z S'' 1 = Z S'' 2 = Z S'' 0 = ∞ .
Under these conditions, faults
feeder into the relay. However, some Utilities do not permit occurring in the first 43% of feeder A appear to the distance
this due to the potential hazards associated with feeding a relay in feeder B to be in its Zone 1 reach. The solution is to
relay protecting one circuit from a CT located in a different limit the mutual compensation applied to 150% of the zero
circuit. sequence compensation.
For the relay to measure the line impedance accurately, the
13.2.2.5 Distance Relay Behaviour with Single-Circuit
following condition must be met:
Operation
If only one of the parallel feeders is in service, the protection in
the remaining feeder measures the fault impedance correctly,
except when the feeder that is not in service is earthed at both
13-4
Chapter 13 ⋅ Protection of Complex Transmission Circuits
ends. In this case, the zero sequence impedance network is as out of service for maintenance. However, the probability of
shown in Figure 13.5. having a fault on the first section of the following line while
one line is out of service is very small, and many Utilities do
Humpage and Kandil [13.2] have shown that the apparent
not reduce the setting under this condition. It should be noted
impedance presented to the relay under these conditions is
that the use of mutual compensation would not overcome the
given by:
over-reaching effect since earthing clamps are normally placed
I A0 Z M2 0 on the line side of the current transformers.
Z R = Z L1 −
I R Z L0 Typical values of zero sequence line impedances for HV lines in
the United Kingdom are given in Table 13.1, where the
Equation 13.4
2
where: Z
maximum per unit over-reach error M 0 is also given.
I R is the current fed into the relay Z L0
The over-reach values quoted in this table are maxima, and
= I A + K R I A0 are found only in rare cases. In most cases, there is generation
at both ends of the feeder and the amount of over-reach is
FO therefore be reduced. In the calculations carried out by
Humpage and Kandil, with more realistic conditions, the
IO maximum error found in a 400kV double circuit line was
′
Z SO nZ LO (1 − n ) Z LO ′′
Z SO 18.6%.
I GO Zero sequence
Zero sequence line
Conductor size mutual Per unit
Relay mZ LO (1 − n ) Z M O impedance ZL0
Location Line impedance ZM0 over-reach
volts Metric error
I HO 2 Ohms Ohms Ohms Ohms (ZM0/ZL0)
2
Z LO (in ) equiv.
2 /mile /km /mile /km
(mm )
0.3 + 0.19+ 0.41+j 0.25+
132kV 0.4 258 0.264
j0.81 j0.5 1.61 j1.0
0.18+ 0.11+ 0.24+ 0.15+
NO 275kV 2 x 0.4 516 0.292
j0.69 j0.43 j1.3 j0.81
Figure 13.5: Zero sequence impedance network during single circuit 0.135+ 0.80+ 0.16+ 0.1+
400kV 4 x 0.4 1032 0.2666
operation j0.6 j0.37 j1.18 j0.73
Table 13.1: Maximum over-reach errors found during single circuit
I A0
The ratio varies with the system conditions, reaching a working
IR
maximum when the system is earthed behind the relay with 13.3 MULTI-ENDED FEEDERS – UNIT
I PROTECTION SCHEMES
no generation at that end. In this case, the ratio A0 is equal
IR A multi-ended feeder is defined as one having three or more
Z terminals, with either load or generation, or both, at any
to L1 , and the apparent impedance presented to the relay terminal. Those terminals with load only are usually known as
Z L0
’taps’.
is:
The simplest multi-terminal feeders are three-ended, and are
Z M2 0 generally known as tee’d feeders. This is the type most
Z R = Z L1 1 − 2
Z L0 commonly found in practice.
It is apparent from the above formulae that the relay has a The protection schemes described previously for the protection
tendency to over-reach. Care should be taken when Zone 1 of two-ended feeders can also be used for multi-ended feeders.
settings are selected for the distance protection of lines in However, the problems involved in the application of these
which this condition may be encountered. To overcome this schemes to multi-ended feeders are much more complex and
possible over-reaching effect, some Utilities reduce the reach require special attention.
of earth fault relays to around 0.65ZL1 when lines are taken The protection schemes that can be used with multi-ended
13-5
Protection & Automation Application Guide
feeders are unit protection and distance schemes. Each uses value, the ‘trip angle’, a trip signal is sent to the corresponding
some form of signalling channel, such as fibre-optic cable, circuit breakers. To prevent incorrect operation for external
power line carrier or pilot wires. The specific problems that faults, two different detectors, set at different levels, are used.
may be met when applying these protections to multi-ended The low-set detector starts the transmission of carrier signal,
feeders are discussed in the following sections. while the high-set detector is used to control the trip output.
Without this safeguard, the scheme could operate incorrectly
13.3.1 Balanced Voltage Schemes for Tee’d Circuits for external faults because of operating tolerances of the
Although pilot wire schemes are uncommon in the protection equipment and the capacitive current of the protected feeder.
of transmission circuits (as per the strict title of this chapter), This condition is worse with multi-terminal feeders, since the
they are discussed here for completeness. currents at the feeder terminals can be very dissimilar for an
external fault. In the case of the three-terminal feeder in
The balanced voltage scheme is a modification of the Figure 13.7, if incorrect operation is to be avoided, it is
MHOA04 / H0A4 scheme described in Section 10.7.1. Since necessary to make certain that the low-set detector at end A or
it is necessary to maintain linearity in the balancing circuit, end B is energised when the current at end C is high enough to
though not in the sending element, the voltage reference is operate the high-set detector at that end. As only one low-set
derived from separate quadrature transformers, as shown in starter, at end A or end B, needs to be energised for correct
Figure 13.6. These are auxiliary units with summation operation, the most unfavourable condition is when currents IA
windings energised by the main current transformers in series and IB are equal. To maintain stability under this condition,
with the upper electromagnets of the sensing elements. The the high-set to low-set setting ratio of the fault detectors needs
secondary windings of the quadrature current transformers at to be twice as large as that required when the scheme is
all ends are interconnected by the pilots in a series circuit that applied to a plain feeder. This results in a loss of sensitivity,
also includes the lower electromagnets of the relays. which may make the equipment unsuitable if the minimum
Secondary windings on the relay elements are not used, but fault level of the power system is low.
these elements are fitted with bias loops in the usual way.
A C
The plain feeder settings are increased in the tee'd scheme by IA T IC
50% for one tee and 75% for two.
End A End B
A
B IB Fault
C
Quadrature
CT
A C
IA T IC
End C
Relay
Pilots IB
Fault
Figure 13.6: Balanced voltage Tee’d feeder scheme
B
13.3.2 Power Line Carrier Phase Comparison
Figure 13.8: Internal fault with current flowing out at one line end
Schemes
A further unfavourable condition is that shown in Figure 13.8.
The operating principle of these protection schemes has
If an internal fault occurs near one of the ends of the feeder
already been covered in detail in Section 10.9. It involves
(end B in Figure 13.8) and there is little or no generation at
comparing the phase angles of signals derived from a
end C, the current at this end may be flowing outwards. The
combination of the sequence currents at each end of the
protection is then prevented from operating, since the fault
feeder. When the phase angle difference exceeds a pre-set
current distribution is similar to that for an external fault; see
13-6
Chapter 13 ⋅ Protection of Complex Transmission Circuits
A
IA IB
B I diff > K I bias
and
RC IC
I diff > I S
C where:
Figure 13.9: Current differential protection for tee’d feeders using
optical fibre signalling K = percentage bias setting
I S = minimum differential current setting
If the magnitudes of the differential currents indicate that a
fault has occurred, the relays trip their local circuit breaker.
The relays also continuously monitor the communication
channel performance and carry out self-testing and diagnostic
13-7
Protection & Automation Application Guide
operations. The system measures individual phase currents the currents IA and IC are in phase and their ratio is a real
and so single phase tripping can be used when required. number. The apparent impedance presented to the relay in
Relays are provided with software to re-configure the this case can be expressed in terms of the source impedances
protection between two and three terminal lines, so that as follows:
modification of the system from two terminals to three
terminals does not require relay replacement. Further, loss of
(Z SA + Z LA )
Z A = Z LA + Z LB + Z
a single communications link only degrades scheme (Z SC + Z LC ) LB
performance slightly. The relays can recognise this and use
The magnitude of the third term in this expression is a function
alternate communications paths. Only if all communication
of the total impedances of the branches A and B and can
paths from a relay fail does the scheme have to revert to
reach a relatively high value when the fault current
backup protection.
contribution of branch C is much larger than that of branch A.
Figure 13.12 shows how a distance relay with a mho
13.4 MULTI-ENDED FEEDERS - DISTANCE
characteristic located at A with a Zone 2 element set to 120%
RELAYS of the protected feeder AB, fails to see a fault at the remote
Distance protection is widely used at present for tee'd feeder busbar B. The ’tee’ point T in this example is halfway between
protection. However, its application is not straightforward, substations A and B (Z LA = Z LB ) and the fault currents IA
requiring careful consideration and systematic checking of all
and IC have been assumed to be identical in magnitude and
the conditions described later in this section.
phase angle. With these conditions, the fault appears to the
Most of the problems found when applying distance protection relay to be located at B' instead of at B so the relay under-
to tee’d feeders are common to all schemes. A preliminary reaches.
discussion of these problems will assist in the assessment of
A B
the performance of the different types of distance schemes. ZSA
IA IB
ZSB
T
∼ ∼
ZLA
13.4.1 Apparent Impedance Seen by Distance Relays ZLB
The impedance seen by the distance relays is affected by the ZLC Fault
current infeeds in the branches of the feeders. Referring to
IC
Figure 13.11, for a fault at the busbars of the substation B, the
voltage VA at busbar A is given by:
C
V A = I A Z LA + I B Z LB ∼ ZSC
VA I B'
ZA = = Z LA + B Z LB
IA IA
Or
B
IB
Z A = Z LA + Z LB
IA
Equation 13.5
or T
IC
Z A = Z LA + Z LB + Z LB
IA
R
The apparent impedance presented to the relay has been A
13-8
Chapter 13 ⋅ Protection of Complex Transmission Circuits
kind of fault. For the sake of simplicity, the equations and the reduction in zero sequence current. However, the solution
examples mentioned so far have been for balanced faults only. has two possible limitations:
For unbalanced faults, especially those involving earth, the
• over-reach occurs when the transformer is not
equations become somewhat more complicated, as the ratios
connected so operation for faults outside the protected
of the sequence fault current contributions at terminals A and
zone may occur
C may not be the same. An extreme example of this condition
is found when the third terminal is a tap with no generation • the inherent possibility of maloperation of the earth
but with the star point of the primary winding of the fault elements for earth faults behind the relay location
transformer connected directly to earth, as shown in Figure is increased
13.13. The corresponding sequence networks are shown in
Figure 13.14. 13.4.2 Effect of Pre-fault Load
In all the previous discussions it has been assumed that the
A B Z
ZSA IA T SB power transfer between terminals of the feeder immediately
∼ ZLA
∼ before the fault occurred was zero. If this is not the case, the
ZLB
fault currents IA and IC in Figure 13.11 may not be in phase,
ZLC
Phase A to
and the factor IC / IA in the equation for the impedance seen
ground fault by the relay at A, is a complex quantity with a positive or a
ZT negative phase angle according to whether the current IC
leads or lags the current IA. For the fault condition previously
considered in Figure 13.11 and Figure 13.12, the pre-fault
C load current may displace the impedance seen by the distance
M Load
relay to points such as B1' or B2' , shown in Figure 13.15,
Figure 13.13: Transformer tap with primary winding solidly earthed according to the phase angle and the magnitude of the pre-
fault load current. Humpage and Lewis [13.3] have analysed
Z SA1 Z LA1 T1 Z LB1 Z SH1 the effect of pre-fault load on the impedances seen by distance
A1 I A1
Z LJ1
B1 relays for typical cases. Their results and conclusions point out
some of the limitations of certain relay characteristics and
EA Z T1 EB
schemes.
Z M1
X
Z SA 2 Z LA 2 T2 Z LB2 Z SB2 B'2
G1 I A2 B2 B'1
Z LC2
ZT2
ZM2
B
Z SA O Z LA O TO Z LBO Z SBO
AO I AO BO
Z LCO
I CO
Z TO T
13-9
Protection & Automation Application Guide
B. Under some conditions, however, the current at one of 13.4.4 Maloperation with Reverse Faults
these terminals may flow outwards instead of inwards. A Earth fault distance relays with a directional characteristic tend
typical case is shown in Figure 13.16; that of a parallel tapped to lose their directional properties under reverse unbalanced
feeder with one of the ends of the parallel circuit open at fault conditions if the current flowing through the relay is high
terminal A. and the relay setting relatively large. These conditions arise
A B principally from earth faults. The relay setting and the reverse
IA IB
T fault current are now related, the first being a function of the
ZA ZB maximum line length and the second depending mainly on the
impedance of the shortest feeder and the fault level at that
∼ ∼
terminal. For instance, referring to Figure 13.18, the setting of
the relay at terminal A depends on the impedance ZA+ZB and
I'B
the fault current infeed IC, for a fault at B, while the fault
current IA for a reverse fault may be quite large if the T point is
IC I'C near the terminals A and C.
Fault
A B
C IA T IB
∼ ∼
ZA ZB
ZC
Fault
Figure 13.16: Internal Fault at busbar B with current flowing out at IC
terminal C
A IA B
T IB
C
∼
∼ Fault ∼ Figure 13.18: External fault behind the relay at terminal A
13-10
Chapter 13 ⋅ Protection of Complex Transmission Circuits
considerations when comparing these schemes are security, requirements mentioned later on, make transfer trip over-
that is, no operation for external faults, and dependability, that reach schemes unattractive for multi-ended feeder protection.
is, assured operation for internal faults.
13.5.3 Blocking Schemes
In addition, it should be borne in mind that transfer trip
schemes require fault current infeed at all the terminals to Blocking schemes are particularly suited to the protection of
achieve high-speed protection for any fault in the feeder. This multi-ended feeders, since high-speed operation can be
is not the case with blocking schemes. While it is rare to find obtained with no fault current infeed at one or more terminals.
a plain feeder in high voltage systems where there is current The only disadvantage is when there is fault current outfeed
infeed at one end only, it is not difficult to envisage a tee’d from a terminal, as shown in Figure 13.17. This is case 4 in
feeder with no current infeed at one end, for example when the Table 13.2. The protection units at that terminal may see the
tee’d feeder is operating as a plain feeder with the circuit fault as an external fault and send a blocking signal to the
breaker at one of the terminals open. Nevertheless, transfer remote terminals. Depending on the scheme logic either relay
trip schemes are also used for tee’d feeder protection, as they operation is blocked or clearance is in Zone 2 time.
offer some advantages under certain conditions. The directional unit should be set so that no maloperation can
occur for faults in the reverse direction; case 5 in Table 13.2.
13.5.1 Transfer Trip Under-Reach Schemes
The main requirement for transfer trip under-reach schemes is 13.5.4 Signalling Channel Considerations
that the Zone 1 of the protection, at one end at least, shall see The minimum number of signalling channels required depends
a fault in the feeder. To meet this requirement, the Zone 1 on the type of scheme used. With under-reach and blocking
characteristics of the relays at different ends must overlap, schemes, only one channel is required, whereas a permissive
either the three of them or in pairs. Cases 1, 2 and 3 in Table over-reach scheme requires as many channels as there are
13.2. should be checked when the settings for the Zone 1 feeder ends. The signalling channel equipment at each
characteristics are selected. If the conditions mentioned in terminal should include one transmitter and (N-1) receivers,
case 4 are found, direct transfer tripping may be used to clear where N is the total number of feeder ends. This may not be a
the fault; the alternative is to trip sequentially at end C when problem if fibre-optic cables are used, but could lead to
the fault current IC reverses after the circuit breaker at problems otherwise.
terminal B has opened; see Figure 13.17.
If frequency shift channels are used to improve the reliability of
Transfer trip schemes may be applied to feeders that have the protection schemes, mainly with transfer trip schemes, N
branches of similar length. If one or two of the branches are additional frequencies are required for the purpose. Problems
very short, and this is often the case in tee'd feeders, it may be of signal attenuation and impedance matching should also be
difficult or impossible to make the Zone 1 characteristics carefully considered when power line carrier frequency
overlap. Alternative schemes are then required. channels are used.
Another case for which under-reach schemes may be
advantageous is the protection of tapped feeders, mainly when 13.5.5 Directional Comparison Blocking Schemes
the tap is short and is not near one of the main terminals. The principle of operation of these schemes is the same as that
Overlap of the Zone 1 characteristics is then easily achieved, of the distance blocking schemes described in the previous
and the tap does not require protection applied to the terminal. section. The main advantage of directional comparison
schemes over distance schemes is their greater capability to
13.5.2 Transfer Trip Over-Reach Schemes detect high-resistance earth faults. The reliability of these
For correct operation when internal faults occur, the relays at schemes, in terms of stability for through faults, is lower than
the three ends should see a fault at any point in the feeder. that of distance blocking schemes. However, with the
This condition is often difficult to meet, since the impedance increasing reliability of modern signalling channels, directional
seen by the relays for faults at one of the remote ends of the comparison blocking schemes offer good solutions to the many
feeder may be too large, as in case 1 in Table 13.2, increasing difficult problems encountered in the protection of multi-ended
the possibility of maloperation for reverse faults, case 5 in feeders. For further information see Chapter 12 and specific
Table 13.2. In addition, the relay characteristic might relay manuals.
encroach on the load impedance.
These considerations, in addition to the signalling channel
13-11
Protection & Automation Application Guide
13-12
Chapter 13 ⋅ Protection of Complex Transmission Circuits
substations A and B, Line 1 being selected for this purpose. All KZO (ang)
Default residual compensation
7.8 deg
factor (phase angle)
relevant data for this exercise are given in the diagram. The
MiCOM P441 relay with quadrilateral characteristics is used to Zone 1 reach impedance setting
Z1 (mag) 17.56 Ω
(magnitude)
provide the relay data for the example. Relay quantities used
Zone 1 reach impedance setting
in the example are listed in Table 13.3, and calculations are Z1 (ang)
(phase angle)
66.3 deg
carried out in terms of actual system impedances in ohms,
Zone 2 reach impedance setting
rather than CT secondary quantities. This simplifies the Z2 (mag) 30.73 Ω
(magnitude)
calculations, and enables the example to be simplified by Zone 2 reach impedance setting
Z2 (ang) 66.3 deg
excluding considerations of CT ratios. Most modern distance (phase angle)
relays permit settings to be specified in system quantities Zone 3 reach impedance setting
Z3 (mag) 131.8 Ω
rather than CT secondary quantities, but older relays may (magnitude)
require the system quantities to be converted to impedances as Z3 (ang)
Zone 3 reach impedance setting
66.3 deg
seen by the relay. (phase angle)
Phase fault resistive reach value -
R1ph 84.8 Ω
Grid supply at 220kV Zone 1
Maximum fault level 7500MVA
Minimum fault level 2500MVA Phase fault resistive reach value -
R2ph 84.8 Ω
Zone 2
T3 T4
120MVA 220/110/11kV Transformers Phase fault resistive reach value -
XHL = 0.15; XHT = 0.35; XLT = 0.25 R3ph 84.8 Ω
XH = 0.125; XL = 0.025 Zone 3
XT = 0.225 on 120MVA
Zone 1 residual compensation
KZ1 (mag) 0.426 -
110kV Substation A factor (magnitude)
Zone 1 residual compensation
KZ1 (ang) 9.2 deg
factor (phase angle)
Current transformer ratio 600/1A
T5 Zone 2 residual compensation
Voltage transformer ratio KZ2 (mag) not used -
45 MVA 110kV/110V factor (magnitude)
Line 1 110/33kV Line 2
Transformer Zone 2 residual compensation
XT = 0.125
KZ2 (ang) not used deg
factor (phase angle)
110kV Substation B
TZ1 Time delay - Zone 1 0 s
TZ2 Time delay - Zone 2 0.25 s
13-13
Protection & Automation Application Guide
impedance, the impedance seen by the relay in the case of a ii. 21.95∠66.236 + 0.5 × 40 × 0.439∠66.236 Ω
fault involving earth is different to that seen for a phase fault.
Therefore the reach of the earth fault elements of the relay
It is clear that condition (ii) governs the setting, and therefore
needs to be different.
the initial Zone 2 reach setting is:
For the relay used, this adjustment is provided by the residual
(or neutral) compensation factor Kzo, set equal to: Z 2 = 30.73∠66.3 Ω
The effect of parallel Line 2 is to make relay 1 underreach for
KZ0 =
(Z 0 − Z1 ) faults on adjacent line sections, as discussed in Section 11.9.3.
3Z1 This is not a problem for the phase fault elements because Line
1 is always protected.
∠K Z 0 = ∠
(Z 0 − Z1 )
3Z1 13.7.1.5 Zone 3 Reach
For Lines 1 and 2, The function of Zone 3 is to provide backup protection for
uncleared faults in adjacent line sections. The criterion used is
Z L1 = 0.177 + j 0.402Ω that the relay should be set to cover 120% of the impedance
(
= 0.439∠66.236 Ω ) between the relay location and the end of the longest adjacent
line, taking account of any possible fault infeed from other
Z L 0 = 0.354 + j1.022Ω circuits or parallel paths. In this case, faults in Line 3 results in
(
= 1.082∠70.895 Ω ) the relay under-reaching due to the parallel Lines 1 and 2, so
the impedance of Line 3 should be doubled to take this effect
Hence, into account. Therefore,
K Z 0 = 0.490 (
Z 3 = 1.2 × 21.95∠66.3 + 100 × 2 × 0.439∠66.3 Ω )
∠K Z 0 = 7.8
= 131.8∠66.3 Ω
13.7.1.2 Zone Impedance Reach Settings – Phase 13.7.1.6 Zone Time Delay Settings
Faults Proper co-ordination of the distance relay settings with those
Firstly, the impedance reaches for the three relay zones are of other relays is required. Independent timers are available for
calculated. the three zones to ensure this.
For Zone 1, instantaneous tripping is normal. A time delay is
13.7.1.3 Zone 1 Reach used only in cases where large d.c. offsets occur and old circuit
Zone 1 impedance is set to 80% of the impedance of the breakers, incapable of breaking the instantaneous d.c.
protected line. Hence, component, are involved.
(
Z1 = 0.8 × 50 × 0.439∠66.236 Ω ) The Zone 2 element has to grade with the relays protecting
Lines 3 and 4 since the Zone 2 element covers part of these
= 0.8 × 21.95∠66.236 Ω lines. Assuming that Lines 3/4 have distance, unit or
instantaneous high-set overcurrent protection applied, the
= 17.56∠66.236 Ω time delay required is that to cover the total clearance time of
Use a value of 17.56∠66.3 Ω the downstream relays. To this must be added the reset time
for the Zone 2 elements following clearance of a fault on an
13.7.1.4 Zone 2 Reach adjacent line, and a suitable safety margin. A typical time
delay is 250ms, and the normal range is 200-300ms.
Zone 2 impedance reach is set to cover the maximum of:
The considerations for the Zone 3 element are the same as for
i. 120% of Line 1 length
the Zone 2 element, except that the downstream fault
ii. Line 1 + 50% of shortest line from Substation B clearance time is that for the Zone 2 element of a distance
i.e. 50% of Line 4 relay or IDMT overcurrent protection. Assuming distance
From the line impedances given, relays are used, a typical time is 450ms. In summary:
13-14
Chapter 13 ⋅ Protection of Complex Transmission Circuits
R2 ph = 84.8Ω
% Underreach = Underreach / Reach of Protected Zone, and
R1 ph = 84.8Ω hence:
% Underreach =14.3%
13.7.1.8 Earth Fault Reach Settings This amount of under-reach is not significant and no
By default, the residual compensation factor as calculated in adjustment need be made. If adjustment is required, this can
section 13.7.1.1 is used to adjust the phase fault reach setting be achieved by using the KZ2 relay setting, increasing it over
in the case of earth faults, and is applied to all zones. the KZ0 setting by the percentage under-reach. When this is
However, it is also possible to apply this compensation to done, care must also be taken that the percentage over-reach
zones individually. Two cases in particular require during single circuit operation is not excessive – if it is then use
consideration, and are covered in this example can be made of the alternative setting groups provided in most
modern distance relays to change the relay settings according
13-15
Protection & Automation Application Guide
R3G = 84.8Ω
R2G = 84.8Ω
R1G = 84.8Ω
This completes the setting of the relay. Table 13.3 also shows
the settings calculated.
13.8 REFERENCES
[13.1] Some factors affecting the accuracy of distance type
protective equipment under earth fault conditions.
Davison, E.B. and Wright, A. Proc. IEE Vol. 110, No. 9,
Sept. 1963, pp. 1678-1688.
[13.2] Distance protection performance under conditions of
single-circuit working in double-circuit transmission
lines. Humpage, W.D. and Kandil, M.S. Proc. IEE. Vol.
117. No. 4, April 1970, pp. 766-770.
[13.3] Distance protection of tee'd circuits. Humpage, W.A.
and Lewis, D.W. Proc. IEE, Vol. 114, No. 10, Oct.
1967, pp. 1483-1498.
13-16
Chapter 13 ⋅ Protection of Complex Transmission Circuits
13-17
AUTO-RECLOSING
Chapter 14
AUTO-RECLOSING
GEGridSolutions.com 14-1
Protection & Automation Application Guide
Instant
of fault
Operates Resets
Protection
Operating
time
Transient Trip coil Contacts Arc Contacts Closing circuit Contacts Contacts
fault energised separate extinguished fully open energised make fully closed
Circuit
breaker
Opening Arcing Closing
time time time
Auto-reclose
relay
Reclaim time
Time
Reclose
Operates Resets on to fault Operates Resets
Protection
Operating
time
Trip coil Contacts Arc Contacts Closing circuit Contacts Contacts Contacts Arc Contacts fully
Permanent energised separate extinguished fully open energised make fully closed separate Extinguished open
fault
Circuit
breaker
Opening Arcing Closing
time time time Trip coil
energised
Operating time Dead time
Relay locks out for protection
Reclose initiated re-operation before reclaim
by protection time has elapsed
Auto-reclose
relay
Time
14-2
Chapter 14 ⋅ Auto-Reclosing
14.2 APPLICATION OF AUTO-RECLOSING ensuing loss of supply to a number of healthy sections. Auto-
The most important parameters of an auto-reclose scheme reclosing allows these circuit breakers to be reclosed within a
are: few seconds. With transient faults, the overall effect would be
loss of supply for a very short time but affecting a larger
• dead time number of consumers. If only time-graded protection without
• reclaim time auto-reclose were used, a smaller number of consumers might
• single or multi-shot be affected, but for a longer time period.
These parameters are influenced by: When instantaneous protection is used with auto-reclosing,
the scheme is normally arranged to inhibit the instantaneous
• type of protection protection after the first trip. For a permanent fault, the time-
• type of switchgear graded protection will give discriminative tripping after
• possible stability problems reclosure, resulting in the isolation of the faulted section.
Some schemes allow a number of reclosures and time-graded
• effects on the various types of consumer loads trips after the first instantaneous trip, which may result in the
The weighting given to the above factors is different for HV burning out and clearance of semi-permanent faults. A further
distribution networks and EHV transmission systems and benefit of instantaneous tripping is a reduction in circuit
therefore it is convenient to discuss them under separate breaker maintenance by reducing pre-arc heating when
headings. Sections 14.3 and 14.4 cover the application of clearing transient faults.
auto-reclosing to HV distribution networks while Sections 14.5 When considering feeders that are partly overhead line and
to 14.9 cover EHV schemes. partly underground cable, any decision to install auto-reclosing
The rapid expansion in the use of auto-reclosing has led to the would be influenced by any data known on the frequency of
existence of a variety of different control schemes. The various transient faults. Where a significant proportion of faults are
features in common use are discussed in Section 14.10. The permanent, the advantages of auto-reclosing are small,
related subject of auto-closing, that is, the automatic closing of particularly since reclosing on to a faulty cable is likely to
normally open circuit breakers, is dealt with in Section 14.11. aggravate the damage.
• instantaneous fault clearance can be introduced, with • system stability and synchronism
the accompanying benefits of shorter fault duration, • type of load
less fault damage, and fewer permanent faults
• CB characteristics
As 80% of overhead line faults are transient, elimination of loss • fault path de-ionisation time
of supply from this cause by the introduction of auto-reclosing
• protection reset time
gives obvious benefits through:
These factors are discussed in the following sections.
• improved supply continuity
• reduction of substation visits 14.4.1.1 System stability and synchronism
Instantaneous tripping reduces the duration of the power arc To reclose without loss of synchronism after a fault on the
resulting from an overhead line fault to a minimum. The interconnecting feeder, the dead time must be kept to the
chance of permanent damage occurring to the line is reduced. minimum permissible consistent with de-ionisation of the fault
The application of instantaneous protection may result in non- arc. Other time delays that contribute to the total system
selective tripping of a number of circuit breakers and an disturbance time must also be kept as short as possible. The
14-3
Protection & Automation Application Guide
problem arises only on distribution networks with more than mechanism to reset before applying a closing impulse.
one power source, where power can be fed into both ends of Where high speed reclosing is required, a latch check
an inter-connecting line. A typical example is embedded interlock is desirable in the reclosing circuit
generation (see Chapter 17), or where a small centre of • Closing time: This is the time interval between the
population with a local diesel generating plant may be energisation of the closing mechanism and the making
connected to the rest of the supply system by a single tie-line. of the contacts. Owing to the time constant of the
The use of high-speed protection, such as unit protection or solenoid and the inertia of the plunger, a solenoid
distance schemes, with operating times of less than 0.05s is closing mechanism may take 0.3s to close. A spring-
essential. The circuit breakers must have very short operation operated breaker, on the other hand, can close in less
times and then be able to reclose the circuit after a dead time than 0.2s. Modern vacuum circuit breakers may have
of the order of 0.3s - 0.6s to allow for fault-arc de-ionisation. a closing time of less than 0.1s
It may be desirable in some cases to use synchronism check The circuit breaker mechanism imposes a minimum dead time
logic, so that auto-reclosing is prevented if the phase angle has made up from the sum of (a) and (b) above. Figure 14.3
moved outside specified limits. The matter is dealt with more shows the performance of modern HV/EHV circuit breakers in
fully in Section 14.9. this respect. Older circuit breakers may require longer times
than those shown.
14.4.1.2 Type of load
Arc Time (s)
extinguished
On HV systems, the main problem to be considered in relation Contacts Contacts
to dead time is the effect on various types of consumer load. separate make
Trip Breaker fully open:
Breaker
• Industrial consumers: Most industrial consumers initiation closing circuit energised
fully
closed
operate mixed loads comprising induction motors,
lighting, process control and static loads. Synchronous t1
t3 t4
motors may also be used. The dead time has to be long t2 t6
enough to allow motor circuits to trip out on loss of t5
supply. Once the supply is restored, restarting of drives
can then occur under direction of the process control Oil Vacuum Oil Air SF6 SF6
system in a safe and programmed manner, and can 11kV 15kV 132kV 380kV 132kV 380kV
t1 0.06 0.038 0.03 0.035 0.04 0.02
often be fast enough to ensure no significant loss of t2 0.1 0.053 0.06 0.045 0.07 0.05
production or product quality t3 0.08 0.023 0.2 0.235 0.03 0.01
t4 0.16 0.048 0.35 0.065 0.08 0.06
• Domestic consumers: It is improbable that expensive t5 0.24 0.28 0.55 0.3 0.11 0.07
processes or dangerous conditions will be involved with t6 0.02 0.07 0.01 0.02 0.12 0.04
domestic consumers and the main consideration is that Note: 380kV data applicable to 400kV also. All times in seconds
of inconvenience and compensation for supply Figure 14.3: Typical circuit breaker trip-close operation times
interruption. A dead time of seconds or a few minutes
is of little importance compared with the loss of cooking 14.4.1.4 De-ionisation of the fault path
facilities, central heating, light and audio/visual As mentioned above, successful high speed reclosure requires
entertainment resulting from a longer supply failure the interruption of the fault by the circuit breaker to be
that could occur without auto-reclosing followed by a time delay long enough to allow the ionised air to
disperse. This time is dependent on the system voltage, cause
14.4.1.3 Circuit breaker characteristics of fault, weather conditions and so on, but at voltages up to
The time delays imposed by the circuit breaker during a 66kV, 0.1s - 0.2s should be adequate. On HV systems,
tripping and reclosing operation must be taken into therefore, fault de-ionisation time is of less importance than
consideration, especially when assessing the possibility of circuit breaker time delays.
applying high speed auto-reclosing.
14.4.1.5 Protection reset time
• Mechanism resetting time: Most circuit breakers are
‘trip free’, which means that the breaker can be tripped If time delayed protection is used, it is essential that the timing
during the closing stroke. After tripping, a time of the device shall fully reset during the dead time, so that correct
order of 0.2s must be allowed for the trip-free time discrimination will be maintained after reclosure on to a
fault. The reset time of the electromechanical I.D.M.T. relay is
14-4
Chapter 14 ⋅ Auto-Reclosing
10 seconds or more when on maximum time setting, and dead are rarely used in practice, to relieve the duty on the circuit
times of at least this value may be required. breaker.
When short dead times are required, the protection relays
14.4.2.2 Spring winding time
must reset almost instantaneously, a requirement that is easily
met by the use of static, digital and numerical I.D.M.T. relays. The reclaim time of motor-wound spring-closed breakers must
be at least as long as the spring winding time, to ensure that
14.4.2 Reclaim Time the breaker is not subjected to a further reclosing operating
with a partly wound spring.
Factors affecting the setting of the reclaim time are discussed
in the following sections.
14.4.3 Number of Shots
14.4.2.1 Type of protection There are no definite rules for defining the number of shots for
any particular auto-reclose application, but a number of
The reclaim time must be long enough to allow the protection
factors must be taken into account.
relays to operate when the circuit breaker is reclosed on to a
permanent fault. The most common forms of protection
14.4.3.1 Circuit breaker limitations
applied to HV lines are I.D.M.T. or definite time over-current
and earth-fault relays. The maximum operating time for the Important considerations are the ability of the circuit breaker to
former with very low fault levels could be up to 30 seconds, perform several trip and close operations in quick succession
while for fault levels of several times rating the operating time and the effect of these operations on the maintenance period.
may be 10 seconds or less. Maintenance periods vary according to the type of circuit
breaker used and the fault current broken when clearing each
In the case of definite time protection, settings of 3 seconds or fault. Use of modern numerical relays can assist, as they often
less are common, with 10 seconds as an absolute maximum. have a CB condition-monitoring feature included that can be
It has been common practice to use reclaim times of 30 arranged to indicate to a Control Centre when maintenance is
seconds on HV auto-reclose schemes. However, there is a required. Auto-reclose may then be locked out until
danger with a setting of this length that during a maintenance has been carried out.
thunderstorm, when the incidence of transient faults is high,
the breaker may reclose successfully after one fault, and then 14.4.3.2 System conditions
trip and lock out for a second fault within this time. Use of a
If statistical information on a particular system shows a
shorter reclaim time of, say, 15 seconds may enable the
moderate percentage of semi-permanent faults that could be
second fault to be treated as a separate incident, with a further
burned out during 2 or 3 time-delayed trips, a multi-shot
successful reclosure.
scheme may be justified. This is often the case in forest areas.
Where fault levels are low, it may be difficult to select I.D.M.T. Multi-shot schemes may also be applicable where fused ‘tees’
time settings to give satisfactory grading with an operating are used and the fault level is low, since the fusing time may
time limit of 15 seconds, and the matter becomes a question not discriminate with the main I.D.M.T. relay. The use of
of selecting a reclaim time compatible with I.D.M.T. several shots will heat the fuse to such an extent that it would
requirements. eventually blow before the main protection operated.
It is common to fit sensitive earth-fault protection to
14.5 AUTO-RECLOSING ON EHV
supplement the normal protection to detect high resistance
earth faults. This protection is usually set to have an operating TRANSMISSION LINES
time longer than that of the main protection. This longer time The most important consideration in the application of auto-
may have to be taken into consideration when deciding on a reclosing to EHV transmission lines is the maintenance of
reclaim time. A broken overhead conductor in contact with dry system stability and synchronism. The problems involved are
ground or a wood fence may cause this type of fault. It is dependent on whether the transmission system is weak or
rarely if ever transient and may be a danger to the public. It is strong. With a weak system, loss of a transmission link may
therefore common practice to use a contact on the sensitive lead quickly to an excessive phase angle across the CB used for
earth fault relay to block auto-reclosing and lock out the circuit re-closure, thus preventing a successful re-closure. In a
breaker. relatively strong system, the rate of change of phase angle will
be slow, so that delayed auto-reclose can be successfully
Where high-speed protection is used, reclaim times of 1
applied.
second or less would be adequate. However, such short times
14-5
Protection & Automation Application Guide
An illustration is the interconnector between two power 14.6 HIGH SPEED AUTO-RECLOSING ON EHV
systems as shown in Figure 14.4. Under healthy conditions, SYSTEMS
the amount of synchronising power transmitted, P, crosses the
The first requirement for the application of high-speed auto-
power/angle curve OAB at point X, showing that the phase
reclosing is knowledge of the system disturbance time that can
displacement between the two systems is θ0. Under fault
be tolerated without loss of system stability. This will normally
conditions, the curve OCB is applicable, and the operating
require transient stability studies to be conducted for a defined
point changes to Y. Assuming constant power input to both
set of power system configurations and fault conditions. With
ends of the line, there is now an accelerating power XY. As a
knowledge of protection and circuit breaker operating
result, the operating point moves to Z, with an increased phase
characteristics and fault arc de-ionisation times, the feasibility
displacement, θ1, between the two systems. At this point the
of high-speed auto-reclosing can then be assessed. These
circuit breakers trip and break the connection. The phase
factors are now discussed.
displacement continues to increase at a rate dependent on the
inertia of the two power sources. To maintain synchronism,
14.6.1 Protection Characteristics
the circuit breaker must be reclosed in a time short enough to
prevent the phase angle exceeding θ2. This angle is such that The use of high-speed protection equipment, such as distance
the area (2) stays greater than the area (1), which is the or unit protection schemes, giving operating times of less than
condition for maintenance of synchronism. 40ms, is essential. In conjunction with fast operating circuit
breakers, high-speed protection reduces the duration of the
fault arc and thus the total system disturbance time.
∼ ∼
It is important that the circuit breakers at both ends of a fault
Fault line should be tripped as rapidly as possible. The time that the
line is still being fed from one end represents an effective
Loads Loads
reduction in the dead time, and may well jeopardise the
chances of a successful reclosure. When distance protection is
used, and the fault occurs near one end of the line, special
Normal system condition
A measures have to be adopted to ensure simultaneous tripping
Power
B
The de-ionisation time of an uncontrolled arc, in free air
O θ0 θ1 θ2
Phase displacement depends on the circuit voltage, conductor spacing, fault
Figure 14.4: Effect of high-speed three-phase auto-reclosing on system currents, fault duration, wind speed and capacitive coupling
stability for a weak system from adjacent conductors. Of these, the circuit voltage is the
This example, for a weak system, shows that the successful most important, and as a general rule, the higher the voltage
application of auto-reclosing in such a case needs high-speed the longer the time required for de-ionisation. Typical values
protection and circuit breakers, and a short dead time. On for three-phase faults are given in Table 14.1.
strong systems, synchronism is unlikely to be lost by the Line Voltage (kV) Minimum De-energisation Time (Seconds)
tripping out of a single line. For such systems, an alternative
66 0.2
policy of delayed auto-reclosing may be adopted. This enables
110 0.28
the power swings on the system resulting from the fault to
132 0.3
decay before reclosure is attempted.
220 0.35
The various factors to be considered when using EHV auto-
275 0.38
reclose schemes are now dealt with. High-speed and delayed
400 0.45
auto-reclose schemes are discussed separately.
525 0.55
Table 14.1: Fault-arc de-ionisation times
14-6
Chapter 14 ⋅ Auto-Reclosing
If single-phase tripping and auto-reclosing is used, capacitive 14.6.3.2 Air blast circuit breakers
coupling between the healthy phases and the faulty phase Air blast breakers have been developed for voltages up to the
tends to maintain the arc and hence extend the dead time highest at present in use on transmission lines. They fall into
required from the values given in the Table. This is a particular two categories:
problem on long distance EHV transmission lines. However
where shunt compensation is applied, a neutral reactor can • pressurised head circuit breakers
often be used to balance system inter-phase capacitance and • non-pressurised head circuit breakers
thus reduce the arcing time.
In pressurised head circuit breakers, compressed air is
maintained in the chamber surrounding the main contacts.
14.6.3 Circuit Breaker Characteristics
When a tripping signal is received, an auxiliary air system
The high fault levels involved in EHV systems impose a very separates the main contacts and allows compressed air to
severe duty on the circuit breakers used in high-speed auto- blast through the gap to the atmosphere, extinguishing the
reclose schemes. The accepted breaker cycle of break-make- arc. With the contacts fully open, compressed air is
break requires the circuit breaker to interrupt the fault current, maintained in the chamber.
reclose the circuit after a time delay of upwards of 0.2s and
then break the fault current again if the fault persists. The Loss of air pressure could result in the contacts reclosing, or, if
types of circuit breaker commonly used on EHV systems are a mechanical latch is employed, restriking of the arc in the de-
oil, air blast and SF6 types. pressurised chamber. For this reason, sequential series
isolators, which isolate the main contacts after tripping, are
14.6.3.1 Oil circuit breakers commonly used with air blast breakers. Since these are
comparatively slow in opening, their operation must be
Oil circuit breakers are used for transmission voltages up to
inhibited when auto-reclosing is required. A contact on the
300kV, and can be subdivided into the two types: ‘bulk oil’ and
auto-reclose relay is made available for this purpose.
‘small oil volume’. The latter is a design aimed at reducing the
fire hazard associated with the large volume of oil contained in Non-pressurised head circuit breakers are slower in operation
the bulk oil breaker. than the pressurised head type and are not usually applied in
high-speed reclosing schemes.
The operating mechanisms of oil circuit breakers are of two
types, ‘fixed trip’ and ‘trip free’, of which the latter is the most
14.6.3.3 SF6 circuit breakers
common. With trip-free types, the reclosing cycle must allow
time for the mechanism to reset after tripping before applying Most EHV circuit breaker designs now manufactured use SF6
the closing impulse. gas as an insulating and arc-quenching medium. The basic
design of such circuit breakers is in many ways similar to that
Special means have to be adopted to obtain the short dead of pressurised head air blast circuit breakers. Voltage
times required for high-speed auto-reclosing. Various types of withstand capability depends on a minimum gas pressure
tripping mechanism have been developed to meet this being available, and gas pressure monitors are fitted and
requirement. arranged to block CB operation in the event of low gas
The three types of closing mechanism fitted to oil circuit pressure occurring. Sequential series isolators are normally
breakers are: used, to prevent damage to the circuit breaker in the event of
voltage transients due to lightning strikes, etc. occurring when
• solenoid the CB is open. Provision should therefore be made to inhibit
• spring sequential series isolation during an auto-reclose cycle.
• pneumatic
14.6.4 Choice of Dead Time
CBs with solenoid closing are not suitable for high-speed auto-
At voltages of 220kV and above, the de-ionisation time will
reclose due to the long time constant involved. Spring,
probably dictate the minimum dead time, rather than any
hydraulic or pneumatic closing mechanisms are universal at
circuit breaker limitations. This can be deduced from Table
the upper end of the EHV range and give the fastest closing
14.1. The dead time setting on a high-speed auto-reclose
time. Figure 14.3 shows the operation times for various types
relay should be long enough to ensure complete de-ionisation
of EHV circuit breakers, including the dead time that can be
of the arc. On EHV systems, an unsuccessful reclosure is
attained.
more detrimental to the system than no reclosure at all.
14-7
Protection & Automation Application Guide
14.6.5 Choice of Reclaim Time • three-phase trip and lockout for phase-phase or 3-
Where EHV oil circuit breakers are concerned, the reclaim phase faults, or if either of the remaining phases should
time should take account of the time needed for the closing develop a fault during the dead time
mechanism to reset ready for the next reclosing operation. • use of a selector switch to give a choice of single or
three-phase reclosing
14.6.6 Number of Shots • combined single and three-phase auto-reclosing; single
High-speed auto-reclosing on EHV systems is invariably single phase to earth faults initiate single-phase tripping and
shot. Repeated reclosure attempts with high fault levels would reclosure, and phase-phase faults initiate three-phase
have serious effects on system stability, so the circuit breakers tripping and reclosure
are locked out after one unsuccessful attempt. Also, the
Modern numerical relays often incorporate the logic for all of
incidence of semi-permanent faults that can be cleared by
the above schemes for the user to select as required. Use can
repeated reclosures is less likely than on HV systems. Multi-
be made of any user-definable logic feature in a numerical
shot schemes have, however, occasionally been used on EHV
relay to implement other schemes that may be required.
systems, specifically to deal with bush fire faults prevalent in
Africa. The advantages of single-phase auto-reclosing are:
• the maintenance of system integrity
14.7 SINGLE-PHASE AUTO-RECLOSING
• on multiple earth systems, negligible interference with
Single phase to earth faults account for the majority of the transmission of load. This is because the current in
overhead line faults. When three-phase auto-reclosing is the unfaulted phases can continue to flow until the fault
applied to single circuit interconnectors between two power is cleared and the faulty phase restored
systems, the tripping of all three phases may cause the two
systems to drift apart in phase, as described in Section 14.5. The main disadvantage is the longer de-ionisation time
No interchange of synchronising power can take place during resulting from capacitive coupling between the faulty and
the dead time. If only the faulty phase is tripped, healthy lines. This leads to a longer dead time being required.
synchronising power can still be interchanged through the Maloperation of earth fault relays on double circuit lines owing
healthy phases. Any difference in phase between the two to the flow of zero sequence currents may also occur. These
systems will be correspondingly less, leading to a reduction in are induced by mutual induction between faulty and healthy
the disturbance on the system when the circuit breaker lines (see Chapter 13 for details).
recloses.
14.8 HIGH-SPEED AUTO-RECLOSING ON
For single-phase auto-reclosing each circuit breaker pole must
LINES EMPLOYING DISTANCE SCHEMES
be provided with its own closing and tripping mechanism; this
is normal with EHV air blast and SF6 breakers. The associated The importance of rapid tripping of the circuit breakers at each
tripping and reclosing circuitry is therefore more complicated, end of a faulted line where high-speed auto-reclosing is
as it must be inherently phase-selective. employed has already been covered in Section 14.6. Simple
distance protection presents some difficulties in this respect.
On the occurrence of a phase-earth fault, single-phase auto-
reclose schemes trip and reclose only the corresponding pole of Owing to the errors involved in determining the ohmic setting
the circuit breaker. The auto-reclose function in a relay of the distance relays, it is not possible to set Zone 1 of a
therefore has three separate elements, one for each phase. distance relay to cover 100% of the protected line – see
Operation of any element energises the corresponding dead Chapter 11 for more details. Zone 1 is set to cover 80-85% of
timer, which in turn initiates a closing pulse for the appropriate the line length, with the remainder of the line covered by time-
pole of the circuit breaker. A successful reclosure results in the delayed Zone 2 protection.
auto-reclose logic resetting at the end of the reclaim time,
ready to respond to a further fault incident. If the fault is
persistent and reclosure is unsuccessful, it is usual to trip and
lock out all three poles of the circuit breaker.
The above describes only one of many variants. Other
possibilities are:
14-8
Chapter 14 ⋅ Auto-Reclosing
Two methods are available for overcoming this difficulty. 14.9.1 Scheme Operation
Firstly, one of the transfer-trip or blocking schemes that
The sequence of operations of a delayed auto-reclose scheme
involves the use of an intertrip signal between the two ends of
can be best understood by reference to Figure 14.6. This
the line can be used. Alternatively, a Zone 1 extension scheme
shows a transmission line connecting two substations A and B,
may be used to give instantaneous tripping over the whole line
with the circuit beakers at A and B tripping out in the event of
length. Further details of these schemes are given in Chapter
a line fault. Synchronism is unlikely to be lost in a system that
12, but a brief description of how they are used in conjunction
employs delayed auto-reclose. However, the transfer of power
with an auto-reclose scheme is given below.
through the remaining tie-lines on the system could result in
the development of an excessive phase difference between the
14.8.1 Transfer-Trip or Blocking Schemes
voltages at points A and B. The result, if reclosure takes place,
This involves use of a signalling channel between the two ends is an unacceptable shock to the system. It is therefore usual
of the line. Tripping occurs rapidly at both ends of the faulty practice to incorporate a synchronism check relay into the
line, enabling the use of high-speed auto-reclose. Some reclosing system to determine whether auto-reclosing should
complication occurs if single-phase auto-reclose is used, as the take place.
signalling channel must identify which phase should be
tripped, but this problem does not exist if a modern numerical
relay is used.
Irrespective of the scheme used, it is customary to provide an
auto-reclose blocking relay to prevent the circuit breakers
auto-reclosing for faults seen by the distance relay in Zones 2
and 3.
14-9
Protection & Automation Application Guide
14-10
Chapter 14 ⋅ Auto-Reclosing
14.10.2 Type of Protection closed on to a fault and the closing pulse is longer than the
On HV distribution systems, advantage is often taken of auto- sum of protection relay and circuit breaker operating times.
reclosing to use instantaneous protection for the first trip, Circuit breakers with trip free mechanisms do not require this
followed by I.D.M.T. for subsequent trips in a single fault feature.
incident. In such cases, the auto-reclose relay must provide a
means of isolating the instantaneous relay after the first trip. 14.10.6 Reclaim Timer
In older schemes, this may be done with a normally closed Electromechanical, static or software-based timers are used to
contact on the auto-reclose starting element wired into the provide the reclaim time, depending on the relay technology
connection between the instantaneous relay contact and the used. If electromechanical timers are used, it is convenient to
circuit breaker trip coil. With digital or numerical relays with employ two independently adjustable timed contacts to obtain
in-built auto-reclose facilities, internal logic facilities will both the dead time and the reclaim time on one timer. With
normally be used. static and software-based timers, separate timer elements are
generally provided.
For certain utility companies, it is the rule to fit tripping relays
to every circuit breaker. If auto-reclosing is required, self or
14.10.7 CB Lockout
electrically reset tripping relays must be used. If the later is
used, a contact must be provided either in the auto-reclose If reclosure is unsuccessful the auto-reclose relay locks out the
logic or by separate trip relay resetting scheme to energise the circuit breaker. Some schemes provide a lockout relay with a
reset coil before reclosing can take place. flag, with provision of a contact for remote alarm. The circuit
breaker can then only be closed by hand; this action can be
14.10.3 Dead Timer arranged to reset the auto-reclose relay element automatically.
Alternatively, most modern relays can be configured such that
This will have a range of settings to cover the specified high-
a lockout condition can be reset only by operator action.
speed or delayed reclosing duty. Any interlocks that are
needed to hold up reclosing until conditions are suitable can be Circuit breaker manufacturers state the maximum number of
connected into the dead timer circuit. Section 14.12.1 operations allowed before maintenance is required. A number
provides an example of this applied to transformer feeders. of schemes provide a fault trip counting function and give a
warning when the total approaches the manufacturer's
14.10.4 Reclosing Impulse recommendation. These schemes will lock out when the total
The duration of the reclosing impulse must be related to the number of fault trips has reached the maximum value allowed.
requirements of the circuit breaker closing mechanism. On
auto-reclose schemes using spring-closed breakers, it is 14.10.8 Manual Closing
sufficient to operate a contact at the end of the dead time to It is undesirable to permit auto-reclosing if circuit breaker
energise the latch release coil on the spring-closing closing is manually initiated. Auto-reclose schemes include the
mechanism. A circuit breaker auxiliary switch can be used to facility to inhibit auto-reclose initiation for a set time following
cancel the closing pulse and reset the auto-reclose relay. With manual CB closure. The time is typically in the range of 2 - 5
solenoid operated breakers, it is usual to provide a closing seconds.
pulse of the order of 1 - 2 seconds, to hold the solenoid
energised for a short time after the main contacts have closed. 14.10.9 Multi-Shot Schemes
This ensures that the mechanism settles in the fully latched-in Schemes providing up to three or four shots use timing circuits
position. The pneumatic or hydraulic closing mechanisms are often included in an auto-reclose relay to provide different,
fitted to oil, air blast and SF6 circuit breakers use a circuit independently adjustable, dead times for each shot.
breaker auxiliary switch for terminating the closing pulse Instantaneous protection can be used for the first trip, since
applied by the auto-reclose relay. each scheme provides a signal to inhibit instantaneous tripping
after a set number of trips and selects I.D.M.T. protection for
14.10.5 Anti-Pumping Devices subsequent ones. The scheme resets if reclosure is successful
The function of an anti-pumping device is to prevent the circuit within the chosen number of shots, ready to respond to further
breaker closing and opening several times in quick succession. fault incidents.
This might be caused by the application of a closing pulse
while the circuit breaker is being tripped via the protection
relays. Alternatively, it may occur if the circuit breaker is
14-11
Protection & Automation Application Guide
14.11 AUTO-CLOSE SCHEMES scheme. The auto-close relay used in practice is a variant of
Auto-close schemes are employed to close automatically circuit one of the standard auto-reclose relays.
breakers that are normally open when the supply network is
healthy. This may occur for a variety of reasons, for instance 14.12 EXAMPLES OF AUTO-RECLOSE
the fault level may be excessive if the CBs were normally APPLICATIONS
closed. The circuits involved are very similar to those used for The following sections describe auto-reclose facilities in
auto-reclosing. Two typical applications are described in the common use for several standard substation configurations.
following sections.
14.12.1 Double Busbar Substation
14.11.1 Standby Transformers A typical double busbar station is shown in Figure 14.8. Each
Figure 14.7 shows a busbar station fed by three transformers, of the six EHV transmission lines brought into the station is
T1, T2 and T3. The loss of one transformer might cause under the control of a circuit breaker, CB1 to CB6 inclusive,
serious overloading of the remaining two. However, and each transmission line can be connected either to the
connection of a further transformer to overcome this may main or to the reserve busbars by manually operated isolators.
increase the fault level to an unacceptable value. Line 1 Line 2 Line 3 Line 4 Line 5 Line 6
L1 L2 L3 L4 L5 L6
T1
CB1A I T1
T1 T2 T3 T4 T2
(Standby)
CB2A I T2
Reserve
Figure 14.7: Standby transformer with auto-closing Figure 14.8: Double busbar substation
The solution is to have a standby transformer T4 permanently Bus section isolators enable sections of busbar to be isolated in
energised from the primary side and arranged to be switched the event of a fault and the bus coupler breaker BC permits
into service if one of the others trips on fault. sections of main and reserve bars to be interconnected.
The starting circuits for breaker CB4 monitor the operation of 14.12.1.1 Basic scheme – banked transformers omitted
transformer protection on any of the transformers T1, T2 and
Each line circuit breaker is provided with an auto-reclose relay
T3 together with the tripping of an associated circuit breaker
that recloses the appropriate circuit breakers in the event of a
CB1 - CB3. In the event of a fault, the auto-close circuit is
line fault. For a fault on Line 1, this would require opening of
initiated and circuit breaker CB4 closes, after a short time
CB1 and the corresponding CB at the remote end of the line.
delay, to switch in the standby transformer. Some schemes
The operation of either the busbar protection or a VT Buchholz
employ an auto-tripping relay, so that when the faulty
relay is arranged to lock out the auto-reclosing sequence. In
transformer is returned to service, the standby is automatically
the event of a persistent fault on Line 1, the line circuit
disconnected.
breakers trip and lock out after one attempt at reclosure.
14.11.2 Bus Coupler or Bus Section Breaker
14.12.1.2 Scheme with banked transformers
If all four power transformers are normally in service for the
Some utilities use a variation of the basic scheme in which
system of Figure 14.7, and the bus sections are interconnected
Transformers T1 and T2 are banked off Lines 1 and 2, as
by a normally-open bus section breaker instead of the isolator,
shown in Figure 14.8. This provides some economy in the
the bus section breaker should be auto-closed in the event of
number of circuit breakers required. The corresponding
the loss of one transformer, to spread the load over the
transformer circuits 1 and 2 are tee'd off Lines 1 and 2
remaining transformers. This, of course, is subject to the fault
respectively. The transformer secondaries are connected to a
level being acceptable with the bus-section breaker closed.
separate HV busbar system via circuit breakers CB1A and
Starting and auto-trip circuits are employed as in the stand-by CB2A.
14-12
Chapter 14 ⋅ Auto-Reclosing
Auto-reclose facilities can be extended to cover the circuits for recloses again, followed by B1, so that both transformers T1
banked transformers where these are used. For example, a and T2 are then supplied from Line 2.
fault on line 1 would cause the tripping of circuit breakers CB1,
A transformer fault causes the automatic opening of the
CB1A and the remote line circuit breaker. When Line 1 is re-
appropriate transformer isolator, lock-out of the transformer
energised, either by auto-reclosure of CB1 or by the remote
secondary circuit breaker and reclosure of circuit breaker 120.
circuit breaker, whichever is set to reclose first, transformer T1
Facilities for dead line charging or reclosure with synchronism
is also energised. CB1A will not reclose until the appearance
check are provided for each circuit breaker.
of transformer secondary voltage, as monitored by the
secondary VT; it then recloses on to the HV busbars after a
14.12.3 Four-Switch Mesh Substation
short time delay, with a synchronism check if required.
The mesh substation shown in Figure 14.10 is extensively used
In the event of a fault on transformer T1, the local and remote by some utilities, either in full or part. The basic mesh has a
line circuit breakers and breaker CB1A trip to isolate the fault. feeder at each corner, as shown at mesh corners MC2, MC3
Automatic opening of the motorised transformer isolator IT1 and MC4. One or two transformers may also be banked at a
follows this. The line circuit breakers then reclose in the mesh corner, as shown at MC1. Mesh corner protection is
normal manner and circuit breaker CB1A locks out. required if more than one circuit is fed from a mesh corner,
A shortcoming of this scheme is that this results in healthy irrespective of the CT locations – see Chapter 15 for more
transformer T1 being isolated from the system; also, isolator details.
L1 must be opened manually before circuit breakers CB1 and
CB1A, can be closed to re-establish supply to the HV busbars G1A G1B
and CB1A. The supply to Bus C is thereby restored without 103 403
Zone covered by
mesh corner
14.12.2 Single Switch Substation 120 protection 320
The arrangement shown in Figure 14.9 consists basically of 203 MC2 MC3 303
breaker 120. Each transformer therefore has an alternative Figure 14.10: Four-switch mesh substation
source of supply in the event of loss of one or other of the Considerable problems can are encountered in the application
feeders. of auto-reclosing to the mesh substation. For example, circuit
breakers 120 and 420 in Figure 14.10 are tripped out for a
variety of different types of fault associated with mesh corner 1
103 120 203
Bus A (MC1), and each requires different treatment as far as auto-
EHV Line 1 EHV Line 2 reclosing is concerned. Further variations occur if the faults
113 213
are persistent.
Following normal practice, circuit breakers must be reclosed in
T1 T2 sequence, so sequencing circuits are necessary for the four
mesh breakers. Closing priority may be in any order, but is
normally 120, 220, 320, and 420.
B1 B2
Bus B
A summary of facilities is now given, based on mesh corner
Figure 14.9: Single switch substation MC1 to show the inclusion of banked transformers; facilities at
For example, a transient fault on Line 1 causes tripping of other corners are similar but omit the operation of equipment
circuit breakers 120 and B1 followed by reclosure of CB 120. solely associated with the banked transformers.
If the reclosure is successful, Transformer T1 is re-energised
and circuit breaker B1 recloses after a short time delay. 14.12.3.1 Transient fault on Line 1
Tripping of circuit breakers 120, 420, G1A and G1B is followed
If the line fault is persistent, 120 trips again and the motorised
by reclosure of 120 to give dead line charging of Line 1.
line isolator 103 is automatically opened. Circuit breaker 120
14-13
Protection & Automation Application Guide
Breaker 420 recloses in sequence, with a synchronism check. be energised from each diameter, shown as Line 1 and Line 2.
Breakers G1A, G1B reclose with a synchronism check if It can therefore be seen that the ratio of circuit breakers to
necessary. lines is one-and-a-half, or breaker and a half. The advantage
of such a topology is that it reduces the number of costly
14.12.3.2 Persistent fault on Line 1 circuit breakers required, compared to a double-bus
Circuit breaker 120 trips again after the first reclosure and installation, but also it means that for any line fault, the
isolator 103 is automatically opened to isolate the faulted line. associated protection relay(s) must trip two circuit breakers to
Breakers 120, 420, G1A, and G1B then reclose in sequence as isolate it. Any autoreclose scheme will then need to manage
above. the closure of two breakers (e.g. CB1 and CB2 for reclosing
Line 1).
14.12.3.3 Transformer fault (local transformer 1A) Utilities usually select from one of three typical scheme
Automatic opening of isolator 113A to isolate the faulted philosophies in such a scenario:
transformer follows tripping of circuit breakers 120, 420, G1A
and G1B. Breakers 120, 420 and G1B then reclose in • Autoreclosure of an 'outer' (or 'diameter') breaker,
sequence, and breaker G1A is locked out. leaving the closing of the centre breaker for manual
remote control
14.12.3.4 Transformer fault (remote transformer) • A leader-follower autoreclosing scheme
For a remote transformer fault, an intertrip signal is received at • Autoreclosure of both breakers simultaneously
the local station to trip breakers 120, 420, G1A and G1B and
Bus 1
inhibit auto-reclosing until the faulted transformer has been VT
isolated at the remote station. If the intertrip persists for 60
seconds it is assumed that the fault cannot be isolated at the CB1 x
1
remote station. Isolator 103 is then automatically opened and
circuit breakers 120, 420, G1A and G1B are reclosed in Line 1
sequence. Line VT
CB2 x 3
14.12.3.5 Transient mesh corner fault A/R Relay
14-14
Chapter 14 ⋅ Auto-Reclosing
check is made. For this reason, the relay requires two bus
synchronising voltages as inputs, in addition to the three-
phase line VT input shown. CB1 can be permitted to close
only if the voltage checks between Bus 1 and the Line VT are
favourable, CB2 can be permitted to close only if the checks
between Bus 2 and the Line VT are favourable
If a utility opts for a scheme which closes two circuit breakers
simultaneously, the line voltage checks against both bus
voltages need to be satisfied before the relay issues
synchronised closing commands.
14-15
BUSBAR PROTECTION
Chapter 15
BUSBAR PROTECTION
GEGridSolutions.com 15-1
Protection & Automation Application Guide
stability, high-speed fault clearance is necessary. Unit busbar absolute, the degree of disturbance to which the power system
protection provides this, with the further advantage that if the is likely to be subjected may be increased by the installation of
busbars are sectionalised, one section only need be isolated to bus protection. The possibility of incorrect operation has, in
clear a fault. The case for unit busbar protection is in fact the past, led to hesitation in applying bus protection and has
strongest when there is sectionalisation. also resulted in application of some very complex systems.
Increased understanding of the response of differential systems
15.2 BUSBAR FAULTS to transient currents enables such systems to be applied with
The majority of bus faults involve one phase and earth, but confidence in their fundamental stability. The theory of
faults arise from many causes and a significant number are differential protection is given later in section 15.7.
interphase clear of earth. In fact, a large proportion of busbar Notwithstanding the complete stability of a correctly applied
faults result from human error rather than the failure of protection system, dangers exist in practice for a number of
switchgear components. reasons. These are:
With fully phase-segregated metalclad gear, only earth faults • interruption of the secondary circuit of a current
are possible, and a protection scheme need have earth fault transformer will produce an unbalance, which might
sensitivity only. In other cases, an ability to respond to phase cause tripping on load depending on the relative values
faults clear of earth is an advantage, although the phase fault of circuit load and effective setting. It would certainly
sensitivity need not be very high. do so during a through fault, producing substantial fault
current in the circuit in question
15.3 PROTECTION REQUIREMENTS
• a mechanical shock of sufficient severity may cause
Although not basically different from other circuit protection, operation, although the likelihood of this occurring with
the key position of the busbar intensifies the emphasis put on modern numerical schemes is reduced
the essential requirements of speed and stability. The special
• accidental interference with the relay, arising from a
features of busbar protection are discussed below.
mistake during maintenance testing, may lead to
operation
15.3.1 Speed
Busbar protection is primarily concerned with: In order to maintain the high order of integrity needed for
busbar protection, it is an almost invariable practice to make
• limitation of consequential damage tripping depend on two independent measurements of fault
• removal of busbar faults in less time than could be quantities. Moreover, if the tripping of all the breakers within a
achieved by back-up line protection, with the object of zone is derived from common measuring relays, two separate
maintaining system stability elements must be operated at each stage to complete a
tripping operation.
Some early busbar protection schemes used a low impedance
differential system having a relatively long operation time, of The two measurements may be made by two similar
up to 0.5 seconds. The basis of most modern schemes is a differential systems, or one differential system may be checked
differential system using either low impedance biased or high by a frame-earth system, by earth fault relays energised by
impedance unbiased relays capable of operating in a time of current transformers in the transformer neutral-earth
the order of one cycle at a very moderate multiple of fault conductors or by voltage or overcurrent relays. Alternatively, a
setting. To this must be added the operating time of any frame-earth system may be checked by earth fault relays.
tripping relays, but an overall tripping time of less than two
If two systems of the unit or other similar type are used, they
cycles can be achieved. With high-speed circuit breakers,
should be energised by separate current transformers in the
complete fault clearance may be obtained in approximately 0.1
case of high impedance unbiased differential schemes. The
seconds. When a frame-earth system is used, the operating
duplicate ring CT cores may be mounted on a common
speed is comparable.
primary conductor but independence must be maintained
throughout the secondary circuit.
15.3.2 Stability
In the case of low impedance, biased differential schemes that
The stability of bus protection is of paramount importance.
Bearing in mind the low rate of fault incidence, amounting to cater for unequal ratio CTs, the scheme can be energised from
either one or two separate sets of main current transformers.
no more than an average of one fault per busbar in twenty
The criteria of double feature operation before tripping can be
years, it is clear that unless the stability of the protection is
maintained by the provision of two sets of ratio matching
15-2
Chapter 15 ⋅ Busbar Protection
Security against maloperation is only achieved by increasing But in the 1980’s the advances in semiconductor technology,
the amount of equipment that is required to function to coupled with a more pressing need to be able to accommodate
complete an operation; and this inevitably increases the CTs of unequal ratio, led to the re-introduction of biased
statistical risk that a tripping operation due to a fault may fail. schemes, generally using static relay designs, particularly for
Such a failure, leaving aside the question of consequential the most extensive and onerous applications.
damage, may result in disruption of the power system to an Frame-earth protection systems have been in use for many
extent as great, or greater, than would be caused by an years, mainly associated with smaller busbar protection
unwanted trip. The relative risk of failure of this kind may be schemes at distribution voltages and for metalclad busbars
slight, but it has been thought worthwhile in some instances to (e.g. SF6 insulated busbars). However, it has often been quite
provide a guard in this respect as well. common for a unit protection scheme to be used in addition,
Security of both stability and operation is obtained by providing to provide two separate means of fault detection.
three independent channels (say X, Y and Z) whose outputs The different types of protection are described in the following
are arranged in a ‘two-out-of three’ voting arrangement, as sections.
shown in Figure 15.1.
15.5 SYSTEM PROTECTION SCHEMES
System protection that includes overcurrent or distance
systems will inherently give protection cover to the busbars.
Overcurrent protection will only be applied to relatively simple
15-3
Protection & Automation Application Guide
15-4
Chapter 15 ⋅ Busbar Protection
adequate rating and low resistance ensures sufficient current frame is also sub-divided, the sections mutually insulated, and
for scheme operation and limits the rise in frame potential. each provided with a separate earth conductor, current
When the system is resistance earthed, the earthing transformer and relay.
connection from the switchgear frame is made between the
Ideally, the section switch should be treated as a separate
bottom of the earthing resistor and the earthing electrode.
zone, as shown in Figure 15.4, and provided with either a
Figure 15.3 illustrates why a lower limit of 10 ohms insulation separate relay or two secondaries on the frame-leakage
resistance between frame and earth is necessary. current transformer, with an arrangement to trip both adjacent
zones. The individual zone relays trip their respective zone and
Outgoing
feeder Switchgear the section switch.
frame
Switchgear frame Insulation
Frame-leakage bonding bar barriers
current
IF=I1+I2 transformer
Zone G Zone H Zone J
Generator
L
K M
System I >
earthing
Earth resistor
Zone G
bar I >
frame leakage
I1+I2 relay
Zone H
I1 frame leakage
I1 I2 relay
Figure 15.3: Current distribution for external fault Trip K Trip L Trip M
Under external fault conditions, the current IF flows through Figure 15.4: Three zone frame-earth scheme
the frame-leakage current transformer. If the insulation If it is inconvenient to insulate the section switch frame on one
resistance is too low, sufficient current may flow to operate the side, this switch may be included in that zone. It is then
frame-leakage relay, and, as the check feature is unrestricted, necessary to intertrip the other zone after approximately 0.5
this will also operate to complete the trip circuit. The earth seconds if a fault persists after the zone including the section
resistance between the earthing electrode and true earth is switch has been tripped. This is illustrated in Figure 15.5.
seldom greater than 1Ω, so with 10Ω insulation resistance the
current I1 is limited to 10% of the total earth fault current I1
and I2. For this reason, the recommended minimum setting
for the scheme is about 30% of the minimum earth fault
current.
All cable glands must be insulated, to prevent the circulation of
spurious current through the frame and earthing system by
any voltages induced in the cable sheath. Preferably, the gland
insulation should be provided in two layers or stages, with an
interposing layer of metal, to facilitate the testing of the gland
insulation. A test level of 5kV from each side is suitable.
15-5
Protection & Automation Application Guide
Insulation barriers
Insulation
barrier
Zone J
M
Zone G Zone H
Zone G Zone H
K L
J L g1 j1 h1 j2
K N
Zone H
Zone G Zone H I >
relay
I > I >
Zone G I >
relay
+ _
g1
K
Trip
j1
J K1 K2 L M1
relays
M2
Trip J Trip K Trip L Tripping
relays
Figure 15.5: Frame-earth scheme: bus section breaker insulated on one L1
side only
L2
For the above schemes to function it is necessary to have a
h1
least one infeed or earthed source of supply, and in the latter N
case it is essential that this source of supply be connected to
j2
the side of the switchboard not containing the section switch. G HJ Busbar isolator
Further, if possible, it is preferable that an earthed source of D.C. zone auxiliary switches
supply be provided on both sides of the switchboard, in order bus wires
to ensure that any faults that may develop between the Figure 15.6: Frame-earth scheme for double busbar substation
insulating barrier and the section switch will continue to be fed
with fault current after the isolation of the first half of the 15.6.4 Frame-Earth Protection - Check System
switchboard, and thus allow the fault to be removed. Of the On all but the smallest equipments, a check system should be
two arrangements, the first is the one normally recommended, provided to guard against such contingencies as operation due
since it provides instantaneous clearance of busbar faults on all to mechanical shock or mistakes made by personnel. Faults in
sections of the switchboard. the low voltage auxiliary wiring must also be prevented from
causing operation by passing current to earth through the
15.6.3 Frame-Earth Scheme - Double Bus Substation switchgear frame. A useful check is provided by a relay
It is not generally feasible to separately insulate the metal energised by the system neutral current, or residual current. If
enclosures of the main and auxiliary busbars. Protection is the neutral check cannot be provided, the frame-earth relays
therefore generally provided as for single bus installations, but should have a short time delay.
with the additional feature that circuits connected to the When a check system is used, instantaneous relays can be
auxiliary bus are tripped for all faults, as shown in Figure 15.6. used, with a setting of 30% of the minimum earth fault current
and an operating time at five times setting of 15 milliseconds
or less.
Figure 15.7 shows a frame-leakage scheme for a metalclad
switchgear installation similar to that shown in Figure 15.4
and incorporating a neutral current check obtained from a
suitable zero sequence current source, such as that shown in
Figure 15.2.
15-6
Chapter 15 ⋅ Busbar Protection
+ Trip relays - isolating switches - one switch per zone - are provided in the
In Out 64A-1 GH 64CH-1 trip supply circuits and an alarm cancellation relay is used.
K
CSS-G 64B-1
15.7 DIFFERENTIAL PROTECTION PRINCIPLES
CSS-H L1
The Merz-Price principle is applicable to a multi-terminal zone
such as a busbar. The principle is a direct application of
L2
Kirchhoff's first law. Usually, the circulating current
arrangement is used, in which the current transformers and
M
interconnections form an analogue of the busbar and circuit
L5 connections. A relay connected across the CT bus wires
represents a fault path in the primary system in the analogue
64CH-2 64A-2
I > and hence is not energised until a fault occurs on the busbar; it
64B-2 then receives an input that, in principle at least, represents the
fault current.
74-1
The scheme may consist of a single relay connected to the bus
74-2
wires connecting all the current transformers in parallel, one
In Out L3 set per circuit, associated with a particular zone, as shown in
Figure 15.8(a). This will give earth fault protection for the
L4 busbar. This arrangement has often been thought to be
CSS-G
L3 adequate.
15-7
Protection & Automation Application Guide
scheme is recommended for its ease of application and good other and also the individual circuit protections. The overlap
performance. should occur across a circuit breaker, so that the latter lies in
both zones. For this arrangement it is necessary to install
15.7.1 Differential Protection for Sectionalised and current transformers on both sides of the circuit breakers,
Duplicate Busbars which is economically possible with many but not all types of
switchgear. With both the circuit and the bus protection
Each section of a divided bus is provided with a separate
circulating current system. The zones so formed are over- current transformers on the same side of the circuit breakers,
the zones may be overlapped at the current transformers, but
lapped across the section switches, so that a fault on the latter
a fault between the CT location and the circuit breaker will not
will trip the two adjacent zones. This is illustrated in Figure
be completely isolated. This matter is important in all
15.9.
switchgear to which these conditions apply, and is particularly
Tripping two zones for a section switch fault can be avoided by important in the case of outdoor switchgear where separately
using the time-delayed technique of section 15.6.2. However mounted, multi-secondary current transformers are generally
instantaneous operation is the preferred choice. used. The conditions are shown in Figure 15.10.
(a) (b)
Zone A Zone B
Bus protection
BS
Fault
BC BC
Zone C
Circuit
protection
15-8
Chapter 15 ⋅ Busbar Protection
has opened but that the fault current is still flowing. Under 15.8 HIGH IMPEDANCE DIFFERENTIAL
these conditions, the protection can initiate an intertrip to the PROTECTION
remote end of the circuit. This technique may be used,
This form of protection is still in common use. The
particularly when the circuit includes a generator. In this case
considerations that have to be taken into account are detailed
the intertrip proves that the fault is in the switchgear
in the following sections.
connections and not in the generator; the latter is therefore
tripped electrically but not shut down on the mechanical side
15.8.1 Stability
so as to be immediately ready for further service if the fault can
be cleared. The incidence of fault current with an initial unilateral transient
component causes an abnormal build-up of flux in a current
15.7.2.1 CT locations for mesh-connected substations transformer, as described in section 15.8.2. When through-
fault current traverses a zone protected by a differential
The protection of busbars in mesh connected substations gives
system, the transient flux produced in the current transformers
rise to additional considerations in respect of CT location. A
is not detrimental as long as it remains within the substantially
single mesh corner is shown in Figure 15.11(a). Where only
linear range of the magnetising characteristic. With fault
one connection to the mesh is made at a corner, CTs located
current of appreciable magnitude and long transient time
as shown will provide protection not only to the line but the
constant, the flux density will pass into the saturated region of
corner of the mesh included between them. However, this
the characteristic; this will not in itself produce a spill output
arrangement cannot be used where more than one connection
from a pair of balancing current transformers provided that
is made to a mesh corner. This is because a fault on any of the
these are identical and equally burdened. A group of current
connected circuits would result in disconnection of them all,
transformers, though they may be of the same design, will not
without any means of determining the faulted connection.
be completely identical, but a more important factor is
Protection CTs must therefore be located on each connection,
inequality of burden. In the case of a differential system for a
as shown in Figure 15.11(b). This leaves the corner of the
busbar, an external fault may be fed through a single circuit,
mesh unprotected, so additional CTs and a relay to provide
the current being supplied to the busbar through all other
mesh-corner protection are added, as also shown in Figure
circuits. The faulted circuit is many times more heavily loaded
15.11(b).
than the others and the corresponding current transformers
Mesh corner are likely to be heavily saturated, while those of the other
(Note 1)
circuits are not. Severe unbalance is therefore probable,
which, with a relay of normal burden, could exceed any
acceptable current setting. For this reason such systems were
Line protection at one time always provided with a time delay. This practice
relay
is, however, no longer acceptable.
Note 1: Only 1 connection to the mesh corner permitted It is not feasible to calculate the spill current that may occur,
(a) CT arrangements for protection including mesh corner
but, fortunately, this is not necessary; an alternative approach
provides both the necessary information and the technique
required to obtain a high performance.
An equivalent circuit, as in Figure 15.12, can represent a
Transformer circulating current system.
protection
Mesh corner
(Note 2)
Line
protection
Mesh corner
protection
15-9
Protection & Automation Application Guide
Vf I f ( RLH + RCTH )
IR = =
RR RR
Equation 15.3
or alternatively:
G H
I R RR = V f = I f (RLH + RCTH )
RCTG RLG RLH RCTH Equation 15.4
15-10
Chapter 15 ⋅ Busbar Protection
It remains to be shown that the setting chosen is suitable in • fault arc resistance and earth path resistance reduce
section 15.8.2. fault currents somewhat
• a reasonable margin should be allowed to ensure that
The current transformers will have an excitation curve which
relays operate quickly and decisively
has not so far been related to the relay setting voltage, the
latter being equal to the maximum nominal voltage drop It is desirable that the primary effective setting should not
across the lead loop and the CT secondary winding resistance, exceed 30% of the prospective minimum fault current.
with the maximum secondary fault current flowing through
In the case of a scheme exclusively for earth fault protection,
them. Under in-zone fault conditions it is necessary for the
the minimum earth fault current should be considered, taking
current transformers to produce sufficient output to operate
into account any earthing impedance that might be present as
the relay. This will be achieved provided the CT knee-point
well. Furthermore, in the event of a double phase to earth
voltage exceeds the relay setting. In order to cater for errors, it
fault, regardless of the inter-phase currents, only 50% of the
is usual to specify that the current transformers should have a
system e.m.f. is available in the earth path, causing a further
knee-point e.m.f. of at least twice the necessary setting
reduction in the earth fault current. The primary operating
voltage; a higher multiple is of advantage in ensuring a high
current must therefore be not greater than 30% of the
speed of operation.
minimum single-phase earth fault current.
15.8.2 Effective Setting or Primary Operating Current In order to achieve high-speed operation, it is desirable that
settings should be still lower, particularly in the case of the
The minimum primary operating current is a further criterion
solidly earthed power system. The transient component of the
of the design of a differential system. The secondary effective
setting is the sum of the relay minimum operating current and fault current in conjunction with unfavourable residual flux in
the CT can cause a high degree of saturation and loss of
the excitation losses in all parallel connected current
output, possibly leading to a delay of several cycles additional
transformers, whether carrying primary current or not. This
summation should strictly speaking be vectorial, but is usually to the natural operating time of the element. This will not
done arithmetically. It can be expressed as: happen to any large degree if the fault current is a larger
multiple of setting; for example, if the fault current is five times
I R = I S + nI eS the scheme primary operating current and the CT knee-point
e.m.f. is three times the relay setting voltage, the additional
Equation 15.6
delay is unlikely to exceed one cycle.
where:
The primary operating current is sometimes designed to
IR = effective setting exceed the maximum expected circuit load in order to reduce
IS = relay circuit setting current the possibility of false operation under load current as a result
of a broken CT lead. Desirable as this safeguard may be, it will
IeS = CT excitation current at relay voltage setting be seen that it is better not to increase the effective current
n = number of parallel connected CTs setting too much, as this will sacrifice some speed; the check
feature in any case, maintains stability.
Having established the relay setting voltage from stability
considerations, as shown in section 15.8.1, and knowing the An overall earth fault scheme for a large distribution board
excitation characteristic of the current transformers, the may be difficult to design because of the large number of
effective setting can be computed. The secondary setting is current transformers paralleled together, which may lead to an
15-11
Protection & Automation Application Guide
30R-1 74-2
system, applied to the switchboard as a whole, no subdivision 95M1X-1
95CHX-1
For phase fault schemes, the check will usually be a similar In Out L1
type of scheme applied to the switchboard as a single overall L2
interconnections will cause an unbalance in the system, Figure 15.13: D.C. circuits for high impedance circulating current
scheme
equivalent to the load being carried by the relevant primary
circuit. Even though this degree of spurious output is below
the effective setting the condition cannot be ignored, since it is
likely to lead to instability under any through fault condition.
Supervision can be carried out to detect such conditions by
connecting a sensitive alarm relay across the bus wires of each
zone. For a phase and earth fault scheme, an internal three-
phase rectifier can be used to effect a summation of the bus
wire voltages on to a single alarm element; see Figure 15.14
and Figure 15.13.
The alarm relay is set so that operation does not occur with the
protection system healthy under normal load. Subject to this
proviso, the alarm relay is made as sensitive as possible; the
desired effective setting is 125 primary amperes or 10% of the
lowest circuit rating, whichever is the greater.
Since a relay of this order of sensitivity is likely to operate
during through faults, a time delay, typically of three seconds,
is applied to avoid unnecessary alarm signals.
15-12
Chapter 15 ⋅ Busbar Protection
Zone R
c1 c2
D H
Zone M1 Zone M2
a1 b1
E F G
c1 c2
a1 b1
Zone M1 A
Bus wires B
C
A
B Zone M2
C Bus wires
Zone R A
B
Bus wires C
N
A
Check zone B
Bus wires C
N
95 CHX-2
95 CHX-3
15-13
Protection & Automation Application Guide
where: where:
IeS = CT excitation current at relay voltage setting Iek = exciting current at knee-point voltage
It is clear from Equation 15.4 and Equation 15.6 that it is These formulae are therefore to be regarded only as a guide to
15-14
Chapter 15 ⋅ Busbar Protection
the possible peak voltage. With large current transformers, through current bias feature alone, but is enhanced by the
particularly those with a low secondary current rating, the addition of a stabilising resistor, having a value which may be
voltage may be very high, above a suitable insulation voltage. calculated as follows.
The voltage can be limited without detriment to the scheme by
The through current will increase the effective relay minimum
connecting a ceramic non-linear resistor in parallel with the
operating current for a biased relay as follows:
relay having a characteristic given by:
I R = I S + BI F
V = CI β
where:
where C is a constant depending on dimensions and β is a
constant in the range 0.2 - 0.25. IR = effective minimum operating current
The current passed by the non-linear resistor at the relay IS = relay setting current
voltage setting depends on the value of C; in order to keep the IF = through fault current
shunting effect to a minimum it is recommended to use a non-
linear resistor with a value of C of 450 for relay voltages up to B = percentage restraint
175V and one with a value of C of 900 for setting voltages up As IF is generally much greater than IS, the relay effective
to 325V. current, IR = BIF approximately.
15.8.6.8 High impedance relay From Equation 15.4, the value of stabilising resistor is given
by:
Instantaneous attracted armature relays or numeric relays that
mimic the high impedance function are used. Simple fast- I F (RLH + RCTH ) (RLH + RCTH )
operating relays would have a low safety factor constant in the RR = =
IR B
stability equation, Equation 15.5, as discussed in section
15.8.1. The performance is improved by series-tuning the It is interesting to note that the value of the stabilising
relay coil, thereby making the circuit resistive in effect. resistance is independent of current level, and that there would
Inductive reactance would tend to reduce stability, whereas appear to be no limit to the through fault stability level. This
the action of capacitance is to block the unidirectional has been identified [15.1] as ‘The Principle of Infinite Stability’.
transient component of fault current and so raise the stability
The stabilising resistor still constitutes a significant burden on
constant.
the current transformers during internal faults.
An alternative technique used in some relays is to apply the
An alternative technique, used by biased differential schemes
limited spill voltage principle shown in Equation 15.4. A tuned
such as the MBCZ system described in section 15.9.6, is to
element is connected via a plug bridge to a chain of resistors;
block the differential measurement during the portion of the
and the relay is calibrated in terms of voltage.
cycle that a current transformer is saturated. If this is achieved
by momentarily short-circuiting the differential path, a very
15.9 LOW IMPEDANCE BIASED DIFFERENTIAL
low burden is placed on the current transformers. In this way
PROTECTION the differential circuit of the relay is prevented from responding
The principles of low impedance differential protection have to the spill current.
been described in section 10.4.2, including the principle
It must be recognised though that the use of any technique for
advantages to be gained by the use of a bias technique. Most
inhibiting operation, to improve stability performance for
modern busbar protection schemes use this technique.
through faults, must not be allowed to diminish the ability of
The principles of a check zone, zone selection, and tripping the relay to respond to internal faults.
arrangements can still be applied. Current transformer
secondary circuits are not switched directly by isolator contacts 15.9.2 Effective Setting or Primary Operating Current
but instead by isolator repeat relays after a secondary stage of For an internal fault, and with no through fault current flowing,
current transformation. These switching relays form a replica the effective setting IR is raised above the basic relay setting IS
of the busbar within the protection and provide the complete by whatever biasing effect is produced by the sum of the CT
selection logic. magnetising currents flowing through the bias circuit. With low
impedance biased differential schemes particularly where the
15.9.1 Stability busbar installation has relatively few circuits, these magnetising
With some biased relays, the stability is not assured by the
15-15
Protection & Automation Application Guide
currents may be negligible, depending on the value of IS. current that is just greater than the maximum load current, to
prevent the busbar protection from operating spuriously from
The basic relay setting current was formerly defined as the
load current should a secondary circuit wiring fault develop.
minimum current required solely in the differential circuit to
This consideration is particularly important where the check
cause operation – Figure 15.15(a). This approach simplified
feature is either not used or is fed from common main CTs.
analysis of performance, but was considered to be unrealistic,
as in practice any current flowing in the differential circuit
15.9.3 Check Feature
must flow in at least one half of the relay bias circuit causing
the practical minimum operating current always to be higher For some low impedance schemes, only one set of main CTs is
than the nominal basic setting current. As a result, a later required. This seems to contradict the general principle of all
definition, as shown in Figure 15.15(b) was developed. busbar protection systems with a check feature that complete
duplication of all equipment is required, but it is claimed that
Conversely, it needs to be appreciated that applying the later the spirit of the checking principle is met by making operation
definition of relay setting current, which flows through at least of the protection dependent on two different criteria such as
half the bias circuit, the notional minimum operation current in directional and differential measurements.
the differential circuit alone is somewhat less, as shown in
Figure 15.15(b). In the MBCZ scheme, described in section 15.9.6, the
provision of auxiliary CTs as standard for ratio matching also
Using the definition presently applicable, the effective provides a ready means for introducing the check feature
minimum primary operating current duplication at the auxiliary CTs and onwards to the relays.
[
= N I s + B ∑ I es ] This may be an attractive compromise when only one set of
main CTs is available.
Where N = CT ratio
Iop Iop
15.9.4 Supervision of CT Secondary Circuits
In low impedance schemes the integrity of the CT secondary
circuits can also be monitored. A current operated auxiliary
) IS ) relay, or element of the main protection equipment, may be
(B% (B%
e e
IS s Lin I’S s Lin applied to detect any unbalanced secondary currents and give
Bia Bia
an alarm after a time delay. For optimum discrimination, the
IB IB
current setting of this supervision relay must be less than that
IB IS of the main differential protection.
In modern busbar protection schemes, the supervision of the
IS
secondary circuits typically forms only a part of a
comprehensive supervision facility.
15-16
Chapter 15 ⋅ Busbar Protection
multiple busbar systems where the isolators switch the Zone 1 Zone 2
auxiliary current transformer secondary circuits via auxiliary
relays within the protection. These relays form a replica of the Zone 3b
Zone 3a
busbar and perform the necessary logic. It is therefore
necessary to route all the current transformer secondary
circuits to the relay to enable them to be connected into this
busbar replica.
Check
Z3b Feeder 4 zone Bus coupler 2
Some installations have only one set of current transformers Bus coupler 1 Feeder 1 Z1 Z3a Feeder 2 Bus section Feeder 3 Z2
15-17
Protection & Automation Application Guide
Selection CT Fault
Alarm
Serious damage may result, and even danger to life, if a circuit
Links
c
Supervision OR
Trip
breaker fails to open when called upon to do so. To reduce this
Differential
m Enable
≥1 Buswire risk breaker fail protection schemes were developed some
r Selection
t Biased
Protection
fault
Links
Trip
years ago.
Differential c
Enable m These schemes are generally based on the assumption that if
Bias =1 ≥1
r current is still flowing through the circuit breaker a set time
Biased
Differential Trip
t
after the trip command has been issued, then it has failed to
function. The circuit breakers in the next stage back in the
Out of service system are then automatically tripped.
Figure 15.18: Block diagram of measuring unit
For a bus coupler or section breaker this would involve tripping
This arrangement provides supervision of CT secondary circuits all the infeeds to the adjacent zone, a facility that is included in
for both open circuit conditions and any impairment of the the busbar protection scheme.
element to operate for an internal fault, without waiting for an
actual system fault condition to show this up. For a zone to 15.10 NUMERICAL BUSBAR PROTECTION
operate it is necessary for both the differential supervision SCHEMES
element and the biased differential element to operate. For a
The application of numeric relay technology to busbar
circuit breaker to be tripped it requires the associated main
protection has become the preferred solution, overtaking the
zone to be operated and also the overall check zone, as shown
use of static. The very latest developments in the technology
in Figure 15.19.
can be included, such as extensive use of a data bus to link the
various units involved, and fault tolerance against loss of a
15-18
Chapter 15 ⋅ Busbar Protection
particular link by providing multiple communications paths. The feeder units have responsibility for collecting the required
The development process has been very rigorous, because the data, such as voltages and currents, and processing it into
requirements for busbar protection in respect of immunity to digital form for onwards transmission to the central processing
maloperation are very high. unit. Modelling of the CT response is included, to eliminate
errors caused by effects such as CT saturation. Disturbance
A philosophy that can be adopted is one of distributed
recording for the monitored feeder is implemented, for later
processing of the measured values, as shown in Figure 15.20.
download as required. Because each feeder unit is concerned
Feeders each have their own processing unit, which collects
only with an individual feeder, the differential protection
together information on the state of the feeder (currents,
algorithms must reside in the central processing unit.
voltages, CB and isolator status, etc.) and communicates it
over high-speed fibre-optic data links to a central processing The differential protection algorithm can be much more
unit. For large substations, more than one central processing sophisticated than with earlier technology, due to
unit may be used, while in the case of small installations, all of improvements in processing power. In addition to calculating
the units can be co-located, leading to the appearance of a the sum of the measured currents, the algorithm can also
traditional centralised architecture. evaluate differences between successive current samples, since
a large change above a threshold may indicate a fault – the
Feeder 1 Feeder 2
threshold being chosen such that normal load changes, apart
CT CT CT CT from inrush conditions do not exceed the threshold. The same
DFU CB DFU CB DFU CB CB considerations can also be applied to the phase angles of
currents, and incremental changes in them.
Fibre optic link
Personal CFU
One advantage gained from the use of numerical technology is
Computer
Central Processing Unit the ability to easily re-configure the protection to cater for
CU
System Communication Network changes in configuration of the substation. For example,
addition of an extra feeder involves the addition of an extra
DFU: Distributed Feeder Unit
CFU: Central Feeder Unit feeder unit, the fibre-optic connection to the central unit and
Figure 15.20: Architecture for numerical protection scheme entry via the HMI of the new configuration into the central
processor unit. Figure 15.21 illustrates the latest numerical
For simple feeders, interface units at a bay may be used with
technology employed.
the data transmitted to a single centrally located feeder
processing unit. The central processing unit performs the
calculations required for the protection functions. Available
protection functions are:
• protection
• backup overcurrent protection
• breaker failure
• dead zone protection (alternatively referred to as ‘short
zone’ protection - see section 15.7.2)
In addition, monitoring functions such as CB and isolator
monitoring, disturbance recording and transformer supervision
are provided.
Because of the distributed topology used, synchronisation of
the measurements taken by the Feeder Units is of vital
importance. A high stability numerically-controlled oscillator is
fitted in each of the central and feeder units, with time
synchronisation between them. In the event of loss of the
synchronisation signal, the high stability of the oscillator in the
affected feeder unit(s) enables processing of the incoming data
to continue without significant errors until synchronisation can
be restored.
15-19
Protection & Automation Application Guide
15-20
Chapter 15 ⋅ Busbar Protection
15-21
TRANSFORMER AND
TRANSFORMER FEEDER
PROTECTION
Chapter 16
TRANSFORMER AND TRANSFORMER
FEEDER PROTECTION
16.6 Transformer Overcurrent Protection The considerations for a transformer protection package
vary with the application and importance of the trans-
16.7 Restricted Earth Fault Protection former. To reduce the effects of thermal stress and electro-
16.8 Differential Protection dynamic forces, it is advisable to ensure that the protection
package used minimises the time for disconnection in the
16.9 Differential Protection Stabilisation During event of a fault occurring within the transformer. Small distri-
Magnetising Inrush Conditions bution transformers can be protected satisfactorily, from both
16.10 Combined Differential and Restricted technical and economic considerations, by the use of fuses or
overcurrent relays. This results in time-delayed protection due
Earth Fault Schemes
to downstream co-ordination requirements. However, time-de-
16.11 Earthing Transformer Protection layed fault clearance is unacceptable on larger power trans-
16.12 Autotransformer Protection formers used in distribution, transmission and generator appli-
cations, due to system operation/stability and cost of repair/
16.13 Overfluxing Protection length of outage considerations.
16.14 Tank-Earth Protection Transformer faults are generally classified into five categories:
16.15 Oil and Gas Devices .. winding and terminal faults
16.16 Transformer-Feeder Protection .. core faults
16.17 Intertripping .. tank and transformer accessory faults
16.18 Examples of Transformer Protection .. on–load tap changer faults
16.19 Transformer Asset Management .. abnormal operating conditions
.. sustained or uncleared external faults
For faults originating in the transformer itself, the approximate
proportion of faults due to each of the causes listed above is
shown in Figure 16.1.
Winding and
Terminal
Core
Tank and
Accessories
OLTC
GEGridSolutions.com 16-1
Protection & Automation Application Guide
(percentage of winding)
90
Single-Phase Earth fault current
Fault current
80 (IF)
70 For secondary winding faults, the primary winding fault
60
current is determined by the variable transformation ratio; as
the secondary fault current magnitude stays high throughout
50
the winding, the primary fault current is large for most points
40
along the winding.
30
20
Primary Current 16.2.3 Delta-Connected Winding
10 (Ip)
No part of a delta-connected winding operates with a voltage
0 10 20 30 40 50 60 70 80 90 100 to earth of less than 50% of the phase voltage. The range of
Distance of fault from Neutral fault current magnitude is therefore less than for a star
(percentage of winding) winding. The actual value of fault current will still depend on
the method of system earthing; it should also be remembered
that the impedance of a delta winding is particularly high to
fault currents flowing to a centrally placed fault on one leg.
The impedance can be expected to be between 25% and 50%,
based on the transformer rating, regardless of the normal
Ip
balanced through-current impedance. As the prefault voltage
to earth at this point is half the normal phase voltage, the
IF earth fault current may be no more than the rated current, or
even less than this value if the source or system earthing
impedance is appreciable. The current will flow to the fault
from each side through the two half windings, and will be
16-2
Chapter 16 Transformer and Transformer Feeder Protection
Section 16.2.2. 40 4
16-3
Protection & Automation Application Guide
The thermal time constant of naturally cooled transformers lies 16.2.8.4 Reduced system frequency
between 2.5-5 hours. Shorter time constants apply in the case Reduction of system frequency has an effect with regard to flux
of force-cooled transformers. density, similar to that of overvoltage.
16.2.8.2 System faults It follows that a transformer can operate with some degree of
overvoltage with a corresponding increase in frequency, but
System short circuits produce a relatively intense rate of
operation must not be continued with a high voltage input at a
heating of the feeding transformers, the copper loss increasing
low frequency. Operation cannot be sustained when the ratio
in proportion to the square of the per unit fault current. The
of voltage to frequency, with these quantities given values in
typical duration of external short circuits that a transformer
per unit of their rated values, exceeds unity by more than a
can sustain without damage if the current is limited only by
small amount, for instance if V/f >1.1. If a substantial rise in
the self-reactance is shown in Table 16.1. IEC 60076 provides
system voltage has been catered for in the design, the base of
further guidance on short-circuit withstand levels.
'unit voltage' should be taken as the highest voltage for which
Transformer Reactance Fault Current Permitted Fault the transformer is designed.
(%) (Multiple of Rating) Duration (seconds)
4 25 2 16.3 MAGNETISING INRUSH
5 20 2 The phenomenon of magnetising inrush is a transient
6 16.6 2 condition that occurs primarily when a transformer is
7 14.2 2 energised. It is not a fault condition, and therefore transformer
protection must remain stable during the inrush transient.
Maximum mechanical stress on windings occurs during the Figure 16.5(a) shows a transformer magnetising
first cycle of the fault. Avoidance of damage is a matter of characteristic. To minimise material costs, weight and size,
transformer design. transformers are generally operated near to the ‘knee point’ of
the magnetising characteristic. Consequently, only a small
16.2.8.3 Overvoltages increase in core flux above normal operating levels will result in
Overvoltage conditions are of two kinds: a high magnetising current.
transient surge voltages Under normal steady-state conditions, the magnetising current
associated with the operating flux level is relatively small
power frequency overvoltage
(Figure 16.5(b)). However, if a transformer winding is
Transient overvoltages arise from faults, switching, and energised at a voltage zero, with no remanent flux, the flux
lightning disturbances and are liable to cause interturn faults, level during the first voltage cycle (2 x normal flux) will result
as described in Section 16.2.5. These overvoltages are usually in core saturation and a high non-sinusoidal magnetising
limited by shunting the high voltage terminals to earth either current waveform – see Figure 16.5(c). This current is
with a plain rod gap or by surge diverters, which comprise a referred to as magnetising inrush current and may persist for
stack of short gaps in series with a non-linear resistor. The several cycles.
surge diverter, in contrast to the rod gap, has the advantage of
Several factors affect the magnitude and duration of the
extinguishing the flow of power current after discharging a
magnetising current inrush:
surge, in this way avoiding subsequent isolation of the
transformer. residual flux – worst-case conditions result in the flux
peak value attaining 280% of normal value
Power frequency overvoltage causes both an increase in stress
on the insulation and a proportionate increase in the working point on wave switching
flux. The latter effect causes an increase in the iron loss and a number of banked transformers
disproportionately large increase in magnetising current. In transformer design and rating
addition, flux is diverted from the laminated core into
structural steel parts. The core bolts, which normally carry system fault level
little flux, may be subjected to a large flux diverted from the
highly saturated region of core alongside. This leads to a rapid
temperature rise in the bolts, destroying their insulation and
damaging coil insulation if the condition continues.
16-4
Chapter 16 Transformer and Transformer Feeder Protection
three-phase transformers.
at switching
The very high flux densities quoted above are so far beyond the 16.4 TRANSFORMER OVERHEATING
normal working range that the incremental relative
The rating of a transformer is based on the temperature rise
permeability of the core approximates to unity and the
above an assumed maximum ambient temperature; under this
inductance of the winding falls to a value near that of the 'air-
condition no sustained overload is usually permissible. At a
cored' inductance. The current wave, starting from zero,
lower ambient temperature some degree of sustained overload
increases slowly at first, the flux having a value just above the
can be safely applied. Short-term overloads are also
residual value and the permeability of the core being
permissible to an extent dependent on the previous loading
moderately high. As the flux passes the normal working value
conditions. IEC 60354 provides guidance in this respect.
and enters the highly saturated portion of the magnetising
characteristic, the inductance falls and the current rises rapidly The only certain statement is that the winding must not
to a peak that may be 500% of the steady state magnetising overheat; a temperature of about 95°C is considered to be the
current. When the peak is passed at the next voltage zero, the normal maximum working value beyond which a further rise of
16-5
Protection & Automation Application Guide
8°- 10°C, if sustained, will halve the insulation life of the unit. The fuse must have a rating well above the maximum
transformer load current to withstand the short duration
Protection against overload is therefore based on winding
overloads that may occur. Also, the fuses must withstand the
temperature, which is usually measured by a thermal
magnetising inrush currents drawn when power transformers
modelling technique. Protection is arranged to trip the
are energised. High Rupturing Capacity (HRC) fuses, although
transformer if excessive temperature is reached. The trip
very fast in operation with large fault currents, are extremely
signal is usually routed via a digital input of a protection relay
slow with currents of less than three times their rated value. It
on one side of the transformer, with both alarm and trip
follows that such fuses will do little to protect the transformer,
facilities made available through programmable logic in the
serving only to protect the system by disconnecting a faulty
relay. Intertripping between the relays on the two sides of the
transformer after the fault has reached an advanced stage.
transformer is usually applied to ensure total disconnection of
the transformer. Table 16.3 shows typical ratings of fuses for use with 11kV
transformers
Winding temperature protection may be included as a part of a
complete monitoring package. See Section 16.18 for more details. Transformer Rating Fuse
Full Load Current Rated Current Operating Time at 3 x
16.5 TRANSFORMER PROTECTION – kVA
(A) (A) Rating (s)
OVERVIEW 100 5.25 16 3.0
The problems relating to transformers described in Section 200 10.5 25 3.0
16.4 require some means of protection. Table 16.2 315 15.8 36 10.0
summarises the problems and the possible forms of protection 500 26.2 50 20.0
that may be used. The following sections provide more detail 1000 52.5 90 30.0
on the individual protection methods. It is normal for a
modern relay to provide all of the required protection functions
This table should be taken only as a typical example;
in a single package, in contrast to electromechanical types that
considerable differences exist in the time characteristics of
would require several relays complete with interconnections
different types of HRC fuses. Furthermore grading with
and higher overall CT burdens.
protection on the secondary side has not been considered.
Fault Type Protection Used
Primary winding Phase-phase fault Differential; Overcurrent 16.6.2 Overcurrent Relays
Primary winding Phase-earth fault Differential; Overcurrent With the advent of ring main units incorporating SF6 circuit
Secondary winding Phase-phase fault Differential breakers and isolators, protection of distribution transformers
Secondary winding Phase-earth fault Differential; Restricted Earth Fault can now be provided by overcurrent trips (e.g. tripping
Interturn Fault Differential, Buchholz controlled by time limit fuses connected across the secondary
Core Fault Differential, Buchholz windings of in-built current transformers) or by relays
Tank Fault Differential, Buchholz; Tank-Earth
connected to current transformers located on the transformer
primary side. Overcurrent relays are also used on larger
Overfluxing Overfluxing
transformers provided with standard circuit breaker control.
Overheating Thermal
Improvement in protection is obtained in two ways; the
excessive delays of the HRC fuse for lower fault currents are
avoided and an earth-fault tripping element is provided in
16.6 TRANSFORMER OVERCURRENT
addition to the overcurrent feature.
PROTECTION
Fuses may adequately protect small transformers, but larger The time delay characteristic should be chosen to discriminate
ones require overcurrent protection using a relay and CB, as with circuit protection on the secondary side. A high-set
instantaneous relay element is often provided, the current
fuses do not have the required fault breaking capacity.
setting being chosen to avoid operation for a secondary short
16.6.1 Fuses circuit. This enables high-speed clearance of primary terminal
short circuits.
Fuses commonly protect small distribution transformers
typically up to ratings of 1MVA at distribution voltages. In
many cases no circuit breaker is provided, making fuse
protection the only available means of automatic isolation.
16-6
Chapter 16 Transformer and Transformer Feeder Protection
16.7 RESTRICTED EARTH FAULT PROTECTION Earth fault protection applied to a delta-connected or
Conventional earth fault protection using overcurrent elements unearthed star winding is inherently restricted, since no zero
fails to provide adequate protection for transformer windings. sequence components can be transmitted through the
This applies particularly to a star-connected winding with an transformer to the other windings.
impedance-earthed neutral, as discussed in Section 16.2.1. Both windings of a transformer can be protected separately
The degree of protection is very much improved by the with restricted earth fault protection, thereby providing high-
application of restricted earth fault protection (or REF speed protection against earth faults for the whole transformer
protection). This is a unit protection scheme for one winding with relatively simple equipment. A high impedance relay is
of the transformer. It can be a high impedance type as shown used, giving fast operation and phase fault stability.
in Figure 16.6 or a biased low-impedance type. For the high-
impedance type, the residual current of three line current 16.8 DIFFERENTIAL PROTECTION
transformers is balanced against the output of a current The restricted earth fault schemes described above in Section
transformer in the neutral conductor. In the biased low- 16.7 depend entirely on the Kirchhoff principle that the sum of
impedance version, the three phase currents and the neutral the currents flowing into a conducting network is zero. A
current become the bias inputs to a differential element. differential system can be arranged to cover the complete
transformer; this is possible because of the high efficiency of
The system is operative for faults within the region between
transformer operation, and the close equivalence of ampere-
current transformers, that is, for faults on the star winding in
turns developed on the primary and secondary windings.
question. The system remains stable for all faults outside this
Figure 16.7 shows the principle. Current transformers on the
zone.
primary and secondary sides are connected to form a
circulating current system.
Id >
I >
16-7
Protection & Automation Application Guide
requirements for ratio and vector correction were met by the primary and secondary line CTs may not have the same
application of external interposing current transformers (ICTs), winding configuration. Phase compensation and associated
as a secondary replica of the main winding connections, or by relay data entry requires more detailed consideration in such
a delta connection of the main CTs to provide phase correction circumstances. Rarely, the available phase compensation
only. Digital/numerical relays implement ratio and correction facilities cannot accommodate the transformer winding
in the relay software instead, thus enabling most combinations connection, and in such cases interposing CTs must be used.
of transformer winding arrangements to be catered for,
irrespective of the winding connections of the primary CTs. 16.8.4 Filtering of Zero Sequence Currents
This avoids the additional space and cost requirements of As described in Chapter 10.8, it is essential to provide some
hardware interposing CTs. form of zero sequence filtering where a transformer winding
can pass zero sequence current to an external earth fault. This
16.8.2 Line Current Transformer Primary Ratings is to ensure that out-of-zone earth faults are not seen by the
Line current transformers have primary ratings selected to be transformer protection as an in-zone fault. This is achieved by
approximately equal to the rated currents of the transformer use of delta-connected line CTs or interposing CTs for older
windings to which they are applied. Primary ratings will relays, and hence the winding connection of the line and/or
usually be limited to those of available standard ratio CTs. interposing CTs must take this into account, in addition to any
phase compensation necessary. For digital/numerical relays,
16.8.3 Phase Correction the required filtering is applied in the relay software. Table
Correct operation of transformer differential protection requires 16.4 summarises the phase compensation and zero sequence
that the transformer primary and secondary currents, as filtering requirements. An example of an incorrect choice of
measured by the relay, are in phase. If the transformer is ICT connection is given in Section 16.19.1.
connected delta/star, as shown in Figure 16.8, balanced three- Clock Phase HV Zero LV Zero
phase through current suffers a phase change of 30°. If left Transformer Transformer
Face Compensation Sequence Sequence
Connection Phase Shift
uncorrected, this phase difference would lead to the relay Vector Required Filtering Filtering
seeing through current as an unbalanced fault current, and Yy0 Yes Yes
result in relay operation. Vector or phase correction must be Zd0 Yes
implemented. 0° 0 0°
Dz0 Yes
A Dd0
B Yz1 Zy1 Yes Yes
C
Yd1 -30° 1 30° Yes
Dy1 Yes
Yy6 Yes Yes
Zd6 Yes
-180° 1 180°
Dz6 Yes
Dd6
Id > Id > Id >
Yz11 Zy11 Yes Yes
Yd11 30° 11 -30° Yes
Dy11 Yes
Electromechanical and static relays use appropriate CT/ICT YyH YzH Yes Yes
connections to ensure that the primary and secondary currents YdH ZdH Yes
(H / 12) x 360° Hour ‘H’ -(H / 12) x 360°
applied to the relay are in phase. DzH DyH Yes
16-8
Chapter 16 Transformer and Transformer Feeder Protection
2
Operate Id >
70%
slope
1 (c) Three winding transformer with unloaded delta tertiary
Setting range 30%
(0.1 - 0.5Id ) Restrain slope
0 1 2 3 4 5 6
Effective bias (x In)
16-9
Protection & Automation Application Guide
16-10
Chapter 16 Transformer and Transformer Feeder Protection
100
(percentage of rated current)
n
tio
Primary operating current
80
ec
ot
pr
u lt
fa
60
rth
n
ea
ctio
ed
o te
ct
40
pr
tri
l
tia
es
n
R
re
ffe
20 Di
0
100 80 60 40 20 0
Percentage of winding protected
16-11
Protection & Automation Application Guide
1/0.333
Earthing
transformer
16-12
Chapter 16 Transformer and Transformer Feeder Protection
is used, this and all the line current transformers can be 16.13 OVERFLUXING PROTECTION
connected in parallel to a single element relay, providing a The effects of excessive flux density are described in Section
scheme responsive to earth faults only; see Figure 16.19(a). 16.2.8. Overfluxing arises principally from the following system
conditions:
A
B high system voltage
C
low system frequency
geomagnetic disturbances
High The latter results in low frequency earth currents circulating
Id > impedance
relay through a transmission system.
Since momentary system disturbances can cause transient
(a) Earth fault scheme
overfluxing that is not dangerous, time delayed tripping is
required. The normal protection is an IDMT or definite time
A
characteristic, initiated if a defined V/f threshold is exceeded.
B
C
Often separate alarm and trip elements are provided. The
alarm function would be definite time-delayed and the trip
a
function would be an IDMT characteristic. A typical
b characteristic is shown in Figure 16.20.
c
Geomagnetic disturbances may result in overfluxing without
Id > Id > Id > the V/f threshold being exceeded. Some relays provide a 5th
n harmonic detection feature, which can be used to detect such
(b) Phase and earth fault scheme a condition, as levels of this harmonic rise under overfluxing
conditions.
Operating 0.80.18K
t
If current transformers are fitted in each phase at the neutral time (s) M12
end of the windings and a three-element relay is used, a 1000
differential system can be provided, giving full protection
against phase and earth faults; see Figure 16.19(b). This
provides high-speed sensitive protection. It is unaffected by 100
ratio changes on the transformer due to tap-changing and is K=63
immune to the effects of magnetising inrush current. K=40
damage to the transformer will have occurred. 1 1.1 1.2 1.3 1.4 1.5 1.6
V f
In addition, this scheme does not respond to any fault in a M
Set t i ng
tertiary winding. Unloaded delta-connected tertiary windings
are often not protected; alternatively, the delta winding can be
earthed at one point through a current transformer that
16.14 TANK-EARTH PROTECTION
energises an instantaneous relay. This system should be
separate from the main winding protection. If the tertiary This is also known as Howard protection. If the transformer
winding earthing lead is connected to the main winding tank is nominally insulated from earth (an insulation resistance
neutral above the neutral current transformer in an attempt to of 10 ohms being sufficient) earth fault protection can be
make a combined system, there may be ‘blind spots’ which the provided by connecting a relay to the secondary of a current
protection cannot cover. transformer the primary of which is connected between the
tank and earth. This scheme is similar to the frame-earth fault
busbar protection described in Chapter 15.
16-13
Protection & Automation Application Guide
16.15 OIL AND GAS DEVICES device may have to be slowed deliberately to avoid spurious
All faults below oil in an oil-immersed transformer result in tripping during circulation pump starts. Alternatively, sudden
localised heating and breakdown of the oil; some degree of pressure rise relays may have their output supervised by
arcing will always take place in a winding fault and the resulting instantaneous high-set overcurrent elements.
decomposition of the oil will release gases. When the fault is of
a very minor type, such as a hot joint, gas is released slowly, but 16.15.3 Buchholz Protection
a major fault involving severe arcing causes a very rapid release Buchholz protection is normally provided on all transformers
of large volumes of gas as well as oil vapour. The action is so fitted with a conservator. The Buchholz relay is contained in a
violent that the gas and vapour do not have time to escape but cast housing which is connected in the pipe to the conservator,
instead build up pressure and bodily displace the oil. as in Figure 16.21.
When such faults occur in transformers having oil conservators, 3 x internal pipe
the fault causes a blast of oil to pass up the relief pipe to the diameter (min) Conservator
conservator. A Buchholz relay is used to protect against such 5 x internal pipe
conditions. Devices responding to abnormally high oil pressure diameter (min)
or rate-of-rise of oil pressure are also available and may be used
in conjunction with a Buchholz relay.
16-14
Chapter 16 Transformer and Transformer Feeder Protection
valve is provided on the top of the housing for the gas to be moreover, the transformer-feeder can be protected as a single
released or collected for analysis. Transformers with forced oil zone or be provided with separate protections for the feeder
circulation may experience oil flow to/from the conservator on and the transformer. In the latter case, the separate
starting/stopping of the pumps. The Buchholz relay must not protections can both be unit type systems. An adequate
operate in this circumstance. alternative is the combination of unit transformer protection
with an unrestricted system of feeder protection, plus an
Cleaning operations may cause aeration of the oil. Under such
intertripping feature.
conditions, tripping of the transformer due to Buchholz
operation should be inhibited for a suitable period.
16.16.1 Non-Unit Schemes
Because of its universal response to faults within the The following sections describe how non-unit schemes are applied
transformer, some of which are difficult to detect by other to protect transformer-feeders against various types of fault.
means, the Buchholz relay is invaluable, whether regarded as
a main protection or as a supplement to other protection 16.16.1.1 Feeder phase and earth faults
schemes. Tests carried out by striking a high voltage arc in a
High-speed protection against phase and earth faults can be
transformer tank filled with oil, have shown that operation
provided by distance relays located at the end of the feeder
times of 0.05s-0.1s are possible. Electrical protection is
remote from the transformer. The transformer constitutes an
generally used as well, either to obtain faster operation for
appreciable lumped impedance. It is therefore possible to set a
heavy faults, or because Buchholz relays have to be prevented
distance relay zone to cover the whole feeder and reach part
from tripping during oil maintenance periods. Conservators
way into the transformer impedance. With a normal tolerance
are fitted to oil-cooled transformers above 1000kVA rating,
on setting thus allowed for, it is possible for fast Zone 1
except those to North American design practice that use a
protection to cover the whole of the feeder with certainty
different technique.
without risk of over-reaching to a fault on the low voltage side.
16.16 TRANSFORMER-FEEDER PROTECTION Although the distance zone is described as being set ’half way
A transformer-feeder comprises a transformer directly into the transformer’, it must not be thought that half the
connected to a transmission circuit without the intervention of transformer winding will be protected. The effects of auto-
switchgear. Examples are shown in Figure 16.22. transformer action and variations in the effective impedance of
the winding with fault position prevent this, making the
HV LV amount of winding beyond the terminals which is protected
very small. The value of the system is confined to the feeder,
which, as stated above, receives high-speed protection
throughout.
IS IF
100%
IF
The saving in switchgear so achieved is offset by increased
complication in the necessary protection. The primary where:
requirement is intertripping, since the feeder protection remote Is = setting current
from the transformer will not respond to the low current fault
IF = steady state r.m.s value of the fault current, which when
conditions that can be detected by restricted earth fault and
fully offset, just operates the relay.
Buchholz protections.
The instantaneous overcurrent relays must be set without risk
Either unrestricted or restricted protection can be applied;
16-15
Protection & Automation Application Guide
I s 1.2 1 t I F 2
IF1 IF2
16-16
Chapter 16 Transformer and Transformer Feeder Protection
in Section 16.7 is not applicable because of the remoteness of appreciable capacitance between each conductor and earth.
the transformer neutral. During an external earth fault the neutral will be displaced,
and the resulting zero sequence component of voltage will
Restricted protection can be applied using a directional earth
produce a corresponding component of zero sequence
fault relay. A simple sensitive and high-speed directional
capacitance current. In the limiting case of full neutral
element can be used, but attention must be paid to the
displacement, this zero sequence current will be equal in value
transient stability of the element. Alternatively, a directional
to the normal positive sequence current.
IDMT relay may be used, the time multiplier being set low.
The slight inverse time delay in operation will ensure that The resulting residual current is equal to three times the zero
unwanted transient operation is avoided. sequence current and hence to three times the normal line
charging current. The value of this component of in-zone
When the supply source is on the high voltage star side, an
current should be considered when establishing the effective
alternative scheme that does not require a voltage transformer
setting of earth fault relays.
can be used. The scheme is shown in Figure 16.24. For the
circuit breaker to trip, both relays A and B must operate, which
16.16.2 Unit Schemes
will occur for earth faults on the feeder or transformer winding.
The basic differences between the requirements of feeder and
External earth faults cause the transformer to deliver zero transformer protections lie in the limitation imposed on the
sequence current only, which will circulate in the closed delta transfer of earth fault current by the transformer and the need
connection of the secondary windings of the three auxiliary for high sensitivity in the transformer protection, suggesting
current transformers. No output is available to relay B. that the two components of a transformer-feeder should be
Through phase faults will operate relay B, but not the residual protected separately. This involves mounting current
relay A. Relay B must have a setting above the maximum transformers adjacent to, or on, the high voltage terminals of
load. As the earthing of the neutral at a receiving point is likely the transformer. Separate current transformers are desirable
to be solid and the earth fault current will therefore be for the feeder and transformer protections so that these can be
comparable with the phase fault current, high settings are not arranged in two separate overlapping zones. The use of
a serious limitation. common current transformers is possible, but may involve the
use of auxiliary current transformers, or special winding and
A
connection arrangements of the relays. Intertripping of the
B
remote circuit breaker from the transformer protection will be
C necessary, but this can be done using the communication
facilities of the feeder protection relays.
Relay A I >>
16-17
Protection & Automation Application Guide
16.25(b). Feeder A
Relay electromagnets
(bias inherent)
(b) Balanced voltage system
16-18
Chapter 16 Transformer and Transformer Feeder Protection
16-19
Protection & Automation Application Guide
600/1
16.18.2.3 Restricted earth fault protection
The KBCH relay implements high-impedance Restricted Earth
R=1000A Rstab
Fault (REF) protection. Operation is required for a primary
earth fault current of 25% rated earth fault current (i.e. 250A).
The prime task in calculating settings is to calculate the value
of the stabilising resistor Rstab and stability factor K.
Id >
A stabilising resistor is required to ensure through fault stability
Primary ICT's Unit Secondary ICT's
Yy0 protection Yd1 when one of the secondary CTs saturates while the others do
relay not. The requirements can be expressed as:
VS I S Rstab
16.18.2.1 Ratio correction
And
Transformer HV full load current on secondary of main CTs is:
VS KI f Rct 2Rl
175
0.7 where:
250
16-20
Chapter 16 Transformer and Transformer Feeder Protection
Rstab = stabilising resistor. Thus from Figure 16.30, with K = 0.5, the protection is
unstable.
For this example:
By adopting an iterative procedure for values of VK/VS and K,
VK = 97V
VK
RCT = 3.7Ω a final acceptable result of 4.55, K 0.6 is obtained.
VS
R1 = 0.057Ω This results in an operating time faster than 40ms.
For the relay used, the various factors are related by the graph The required earth fault setting current Iop is 250A. The
of Figure 16.30. chosen E/F CT has an exciting current Ie of 1%, and hence
using the equation:
70 0.1
I op CTratio I S nI e
Overall operation time - milliseconds
60
where:
50
0.2 n = no of CTs in parallel (=4)
40 Is = 0.377, use 0.38 nearest settable value.
K Factor
Overall Op 0.3
30 Time
The stabilising resistance Rstab can be calculated as 60.21.
0.4
Unstable The relay can only withstand a maximum of 3kV peak under
20 0.5
fault conditions. A check is required to see if this voltage is
Stable K Factor 0.6 exceeded – if it is, a non-linear resistor, known as a Metrosil,
10 0.7
0.8 must be connected across the relay and stabilising resistor.
0.9
0 1 The peak voltage is estimated using the formula:
1 2 3 4 5 6 7 8 9 10
Vk/Vs VP 2 2VK V f VK
where:
V
Starting with the desired operating time, the K ratio and K
VS V f I f RCT 2Rl Rstab
factor can be found. And
An operating of 40ms (2 cycles at 50Hz) is usually acceptable, If = fault current in secondary of CT circuit and substituting
and hence, from Figure 16.30, values, VP = 544V. Thus a Metrosil is not required.
VK
4, K 0.5 16.18.3 Unit Protection for On-Load Tap Changing
VS Transformer
The maximum earth fault current is limited by the earthing The previous example deals with a transformer having no taps.
resistor to 1000A (primary). The maximum phase fault In practice, most transformers have a range of taps to cater for
current can be estimated by assuming the source impedance different loading conditions. While most transformers have an
to be zero, so it is limited only by transformer impedance to off-load tap-changer, transformers used for voltage control in
5250A, or 10A secondary after taking account of the ratio a network are fitted with an on-load tap-changer. The
compensation. Hence the stability voltage can be calculated protection settings must then take the variation of tap-change
16-21
Protection & Automation Application Guide
position into account to avoid the possibility of spurious trips at reconditioning at a time of the asset-owner’s choosing is far
extreme tap positions. For this example, the same transformer more preferable than a forced unplanned outage due to failure.
as in Section 16.19.2 will be used, but with an on-load tapping
This section provides an overview of techniques commonly
range of +5% to -15%. The tap-changer is located on the
available in modern numerical transformer protection relays,
primary winding, while the tap-step usually does not matter.
which can extend to asset management of the protected
transformer.
16.18.3.1 Ratio correction
In accordance with Section 16.8.4 the mid-tap position is used 16.19.1 Loss of life monitoring
to calculate the ratio correction factors. The mid tap position is
Ageing of transformer insulation is a time-dependent function
–5%, and at this tap position:
of temperature, moisture, and oxygen content. The moisture
Primary voltage to give rated secondary voltage: and oxygen contributions to insulation deterioration are
= 33 x 0.95 = 31.35kV and Rated Primary Current = 184A minimised due to the preservation systems employed in the
design of most modern transformers. Therefore, temperature
Transformer HV full load current on secondary of main CTs is: is the key parameter in insulation ageing. Frequent excesses
184 of overloading will shorten the life-expectancy of the
0.737 transformer, due to the elevated winding temperatures.
250
Insulation deterioration is not uniform, and will be more
1
Ratio compensation = 1.36 pronounced at hot-spots within the transformer tank.
0.737 Therefore, any asset management system intended to model
525 the rate of deterioration and current estimated state of the
LV secondary current = 0.875 insulation must do so based on simulated real-time hot spot
600 temperature algorithms. These models may take ambient
1 temperature, top-oil temperature, load current flowing, the
Ratio compensation = 1.14 status of oil pumps (pumping or not), and the status of
0.875
radiator fans (forced cooling or not) as inputs.
Both of the above values can be set in the relay.
The MiCOM P640 provides such a loss of life monitoring
16.18.3.2 Bias slope setting facility, according to the thermal model defined in IEEE
Standard C57.91. The protection algorithm determines the
The on-load tapping range of +5% to -15% gives rise to a
current rate of losing life, and uses that to indicate the
maximum excursion of 10% from the -5% mid-tap position.
remaining years or hours until critical insulation health
As the differential scheme notionally balances at this mid-tap,
statuses are likely to be reached. Such criticalities will relate
this means that as an approximation, the maximum
typically to known percentage degradations in the tensile
differential current that can flow when at top or bottom tap is
strength of the insulation, degradation in the degree of
10% of the load (or fault current which may flow to an external
polymerisation, and other life-loss factors. The asset owner
fault). Those relays having an adjustable k1 bias slope setting
can be alerted in advance that an outage will be required for
should ensure that it is at least 10% higher than the percentage
reconditioning or rewinding, such that investment budgeting
excursion.
can be made years and months ahead of time.
16.19 TRANSFORMER ASSET MANAGEMENT
16.19.2 Through-fault monitoring
Due to the high capital cost of transformers, and the need for
Loss of life monitoring serves to track the deterioration caused
their in-service availability to be as high as possible to avoid
by long term, repeated overloading. However, it is not the
constraining load flows demanded on the network, protection
right technique to monitor short-term heavy fault currents
is no-longer the only concern. As cities expand, consumers’
which flow through the transformer, out to an external fault on
lifestyle expectations raise, and electric vehicle recharging
the downstream power system (e.g. fault IF2 in Figure 16.23).
loads become more prevalent, these combine to increase the
Through faults are a major cause of transformer damage and
demand on the network - and it is through the transformers,
failure, as they stress the insulation and mechanical integrity -
between the different voltage levels on the system, that the
such as the bracing of the windings.
demand is traditionally supplied. This increases the focus on
knowing the health of transformers, real-time, to be able to A specific through-fault monitor is recommended to monitor
schedule condition-based maintenance. Maintenance or currents which are due to external faults passing through, and
16-22
Chapter 16 Transformer and Transformer Feeder Protection
so may range from 3.5 times up to tens of times the rated Monitored Equipment Measured Quantity Health Information
current of the transformer. The MiCOM P640 performs an I2t Voltage
calculation when the through current exceeds a user-set Partial discharge measurement Insulation quality
threshold, such that the heating effect of the square of the (wideband voltage)
maximum phase current, and the duration of the fault event Bushings Loading
are calculated. Calculation results are added to cumulative Load current Permissible overload rating
values, and monitored so that utilities can schedule Hot-spot temperature
transformer maintenance or identify a need for system
Oil pressure Insulation quality
reinforcement.
Hot-spot temperature
Oil temperature
Permissible overload rating
16.19.3 CONDITION MONITORING OF
Oil quality
TRANSFORMERS Tank Gas-in-oil content
Winding insulation condition
It is possible to provide transformers with measuring devices to
Moisture-in-oil content Oil quality
detect early signs of degradation in various components and
Buchholz gas content Winding insulation condition
provide warning to the operator to avoid a lengthy and
Frequency of use of each tap
expensive outage due to failure. The technique, which can be Position
position
applied to other plant as well as transformers, is called
Tap changer Drive power consumption OLTC health
condition monitoring, as the intent is to provide the operator
Total switched load current OLTC contact wear
with regular information on the condition of the transformer.
By reviewing the trends in the information provided, the OLTC oil temperature OLTC health
operator can make a better judgement as to the frequency of Oil temperature difference
maintenance, and detect early signs of deterioration that, if Cooling air temperature Cooler efficiency
Coolers
ignored, would lead to an internal fault occurring. Such Ambient temperature
techniques are an enhancement to, but are not a replacement Pump status Cooling plant health
for, the protection applied to a transformer. Conservator Oil level Tank integrity
16-23
GENERATOR
AND GENERATOR
TRANSFORMER
PROTECTION
Chapter 17
GENERATOR AND GENERATOR
TRANSFORMER PROTECTION
Auxiliary
supplies switchboard
Figure 17.1: Generator-transformer unit
GEGridSolutions.com 17-1
Protection & Automation Application Guide
17-2
Chapter 17 ⋅ Generator and Generator Transformer Protection
17-3