Smart PV Controller: SUN2000-60KTL-M0

The document summarizes the key specifications of the SUN2000-60KTL-M0 Smart PV Controller. It has a maximum efficiency of 98.7% and supports 12 string intelligent monitoring. It features fuse free design and Type II surge arresters for both DC and AC circuits for safety. The controller has 6 maximum power point trackers and can support up to 2 input strings per tracker.

Uploaded by

Catalin Spalatu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views2 pages

Smart PV Controller: SUN2000-60KTL-M0

The document summarizes the key specifications of the SUN2000-60KTL-M0 Smart PV Controller. It has a maximum efficiency of 98.7% and supports 12 string intelligent monitoring. It features fuse free design and Type II surge arresters for both DC and AC circuits for safety. The controller has 6 maximum power point trackers and can support up to 2 input strings per tracker.

Uploaded by

Catalin Spalatu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SUN2000-60KTL-M0

Smart PV Controller

Smart Efficient Safe Reliable


12 strings intelligent monitoring Max. efficiency 98.7% Fuse free design Type II surge arresters for DC & AC

Efficiency Curve Circuit Diagram


+
MPPT1
Efficiency [%]
+
-

100%
-
L1
+
Output EMI L2
MPPT2
99%
+
Filter Filter L3
-
N
98% -
DC/AC Output
+ Inverter Isolation SPD PE
97% + MPPT3 Relay
- EMI
96% -
DC SPD Filter
Switch 1
95%
+
94% + MPPT4
-
93% -
+
92% + MPPT5

91%
-
-

90% +
+ MPPT6
0% 20% 40% 60% 80% 100% -
-
SPD
520V 600V 800V Current DC
Sensor Switch 2

Load [%] SUN2000-60KTL-M0

SOLAR.HUAWEI.COM/EU/
SUN2000-60KTL-M0
Technical Specification

Technical Specification SUN2000-60KTL-M0

Efficiency
Max. efficiency 98.9% @480 V; 98.7% @380 V / 400 V
European efficiency 98.7% @480 V; 98.5% @380 V / 400 V

Input
Max. Input Voltage 1 1,100 V
Max. Current per MPPT 22 A
Max. Short Circuit Current per MPPT 30 A
Start Voltage 200 V
MPPT Operating Voltage Range 2 200 V ~ 1,000 V
Rated Input Voltage 600 V @380 Vac / 400 Vac; 720 V @480 Vac
Number of MPP trackers 6
Max. input number per MPP tracker 2

Output
Rated AC Active Power 60,000 W
Max. AC Apparent Power 66,000 VA
Max. AC Active Power (cosφ=1) 66,000 W
Rated Output Voltage 220 V / 380 V, 230 V / 400 V, default 3W + N + PE; 3W + PE optional in settings; 277 V / 480 V, 3W + PE
Rated AC Grid Frequency 50 Hz / 60 Hz
Rated Output Current 91.2 A @380 V, 86.7 A @400 V, 72.2 A @480 V
Max. Output Current 100 A @380 V, 95.3 A @400 V, 79.4 A @480 V
Adjustable Power Factor Range 0.8 leading... 0.8 lagging
Max. Total Harmonic Distortion <3%

Protection
Input-side Disconnection Device Yes
Anti-islanding Protection Yes
AC Overcurrent Protection Yes
DC Reverse-polarity Protection Yes
PV-array String Fault Monitoring Yes
DC Surge Arrester Type II
AC Surge Arrester Type II
DC Insulation Resistance Detection Yes
Residual Current Monitoring Unit Yes

Communication
Display LED indicators; WLAN adaptor + FusionSolar APP
RS485 Yes
USB Yes
Monitoring BUS (MBUS) Yes (isolation transformer required)
Smart Dongle-4G Yes

General Data
Dimensions (W x H x D) 1,075 x 555 x 300 mm (42.3 x 21.9 x 11.8 inch)
Weight (with mounting plate) 74 kg (163.1 lb.)
Operating Temperature Range -25°C ~ 60°C (-13°F ~ 140°F)
Cooling Method Natural Convection
Max. Operating Altitude 4,000 m (13,123 ft.)
Relative Humidity 0 ~ 100%
DC Connector Amphenol Helios H4
AC Connector Waterproof PG Terminal + Terminal Clamp
Protection Degree IP65
Topology Transformerless
Nighttime Power Consumption <2W

Standard Compliance (more available upon request)


Certificate EN 62109-1/-2, IEC 62109-1/-2, EN 50530, IEC 62116, IEC 60068, IEC 61683
IEC 61727, VDE-AR-N4105, VDE 0126-1-1, BDEW, VDE 4120, UTE C 15-712-1, CEI 0-16, CEI 0-21, RD 661, RD 1699,
Grid Connection Standards
P.O. 12.3, RD 413, EN-50438-Turkey, EN-50438-Ireland, C10/11
*1 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.
*2 Any DC input voltage beyond the operating voltage range may result in inverter improper operating.

Version No.:04-(20201006) SOLAR.HUAWEI.COM/EU/