Lighting Illumination Level calculations-REV - 0
Lighting Illumination Level calculations-REV - 0
Lighting Illumination Level calculations-REV - 0
Table of contents
Project 1
Table of contents 1
Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830
Luminaire Data Sheet 3
Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830
Luminaire Data Sheet 4
Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830
Luminaire Data Sheet 5
Philips Europa 2 FBS122 O 2xPL-C/2P13W/830
Luminaire Data Sheet 6
Philips TBS230 C6 4xTL-D18W/830
Luminaire Data Sheet 7
Philips TCW 079/179/279 TCW179 HS 2xTL-D36W/830
Luminaire Data Sheet 8
BED ROOM (TYP)
Summary 9
Photometric Results 10
CORRIDOR 1
Summary 11
Photometric Results 12
CORRIDOR 2
Summary 13
Photometric Results 14
LINEN ROOM
Summary 15
Photometric Results 16
STAIRCASE CORRIDOR
Summary 17
Photometric Results 18
PANTRY
Summary 19
Photometric Results 20
LOBBY
Summary 21
Photometric Results 22
AIR LOCK ROOM 1
Summary 23
Photometric Results 24
AIR LOCK ROOM - 2
Summary 25
Photometric Results 26
PUMP ROOM-1
Summary 27
Photometric Results 28
PUMP ROOM-2
Summary 29
Photometric Results 30
JANITOR ROOM
Summary 31
Photometric Results 32
TELECOM ROOM
Summary 33
Photometric Results 34
ELECTRICAL ROOM
Page 1
IPS Residential Building lighting illumination level calculations
Table of contents
Summary 35
Photometric Results 36
PAY PHONE ROOM
Summary 37
Photometric Results 38
FIRE EXIT
Summary 39
Photometric Results 40
Page 2
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
120
100
120° 120°
80
60
105° 40 105°
90° 90°
75° 75°
60° 60°
2H 2H 17.5 18.8 18.0 19.3 19.8 14.8 16.1 15.3 16.6 17.1
3H 20.3 21.5 20.8 22.0 22.6 16.2 17.3 16.7 17.8 18.4
4H 22.1 23.2 22.6 23.7 24.3 16.7 17.8 17.2 18.4 18.9
6H 24.1 25.1 24.6 25.7 26.3 17.2 18.2 17.7 18.7 19.3
8H 25.1 26.2 25.7 26.7 27.3 17.3 18.3 17.9 18.9 19.5
12H 26.3 27.2 26.8 27.8 28.4 17.5 18.5 18.1 19.0 19.6
4H 2H 18.1 19.2 18.6 19.7 20.3 16.1 17.2 16.7 17.8 18.3
3H 21.2 22.2 21.8 22.7 23.3 17.8 18.7 18.4 19.3 19.9
4H 23.1 24.0 23.7 24.6 25.3 18.5 19.4 19.1 20.0 20.6
6H 25.4 26.2 26.0 26.8 27.5 19.2 20.0 19.8 20.6 21.3
8H 26.6 27.3 27.2 27.9 28.7 19.5 20.2 20.1 20.8 21.5
12H 27.9 28.5 28.5 29.2 29.9 19.7 20.4 20.4 21.0 21.8
8H 4H 23.5 24.2 24.1 24.9 25.6 19.9 20.6 20.5 21.3 22.0
6H 26.1 26.7 26.8 27.4 28.1 21.0 21.6 21.6 22.2 23.0
8H 27.5 28.1 28.2 28.7 29.5 21.5 22.0 22.1 22.7 23.4
12H 29.0 29.5 29.7 30.2 31.0 21.9 22.4 22.6 23.1 23.9
12H 4H 23.5 24.2 24.2 24.8 25.6 20.5 21.2 21.1 21.8 22.5
6H 26.2 26.8 26.9 27.5 28.2 21.8 22.4 22.5 23.0 23.8
8H 27.8 28.2 28.4 28.9 29.7 22.5 23.0 23.2 23.6 24.4
Page 3
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
105° 105°
90° 90°
75° 75°
60° 60°
200
45° 45°
300
2H 2H 21.8 22.7 22.1 22.9 23.1 20.4 21.4 20.7 21.6 21.8
3H 21.7 22.5 22.0 22.8 23.0 20.3 21.1 20.6 21.4 21.6
4H 21.6 22.4 22.0 22.7 22.9 20.2 21.0 20.5 21.3 21.5
6H 21.6 22.3 21.9 22.6 22.9 20.1 20.9 20.5 21.1 21.4
8H 21.5 22.2 21.9 22.5 22.8 20.1 20.8 20.5 21.1 21.4
12H 21.5 22.1 21.9 22.5 22.8 20.1 20.7 20.4 21.0 21.3
4H 2H 21.7 22.5 22.0 22.7 23.0 20.4 21.2 20.7 21.5 21.7
3H 21.6 22.3 22.0 22.6 22.9 20.3 20.9 20.6 21.2 21.6
4H 21.6 22.1 21.9 22.5 22.8 20.2 20.8 20.6 21.1 21.5
6H 21.5 22.0 21.9 22.3 22.7 20.1 20.6 20.6 21.0 21.4
8H 21.5 21.9 21.9 22.3 22.7 20.1 20.5 20.5 20.9 21.3
12H 21.4 21.8 21.9 22.2 22.6 20.1 20.5 20.5 20.9 21.3
8H 4H 21.5 21.9 21.9 22.3 22.7 20.1 20.5 20.5 20.9 21.3
6H 21.4 21.7 21.8 22.1 22.6 20.0 20.4 20.5 20.8 21.2
8H 21.3 21.6 21.8 22.1 22.5 20.0 20.3 20.5 20.7 21.2
12H 21.3 21.5 21.8 22.0 22.5 19.9 20.2 20.4 20.7 21.1
12H 4H 21.4 21.8 21.9 22.2 22.6 20.1 20.5 20.5 20.9 21.3
6H 21.3 21.6 21.8 22.1 22.5 20.0 20.3 20.5 20.7 21.2
8H 21.3 21.5 21.8 22.0 22.5 19.9 20.2 20.4 20.7 21.1
Page 4
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
105° 105°
90° 90°
75° 75°
100
60° 60°
150
250
300
2H 2H 22.0 22.9 22.3 23.1 23.4 21.1 22.0 21.4 22.2 22.4
3H 21.9 22.7 22.2 23.0 23.2 21.0 21.8 21.3 22.0 22.3
4H 21.8 22.6 22.2 22.9 23.1 20.9 21.7 21.2 21.9 22.2
6H 21.8 22.5 22.1 22.8 23.0 20.8 21.5 21.2 21.8 22.1
8H 21.7 22.4 22.1 22.7 23.0 20.8 21.5 21.1 21.8 22.1
12H 21.7 22.3 22.0 22.6 23.0 20.7 21.4 21.1 21.7 22.0
4H 2H 21.9 22.7 22.2 23.0 23.2 21.1 21.8 21.4 22.1 22.4
3H 21.8 22.5 22.2 22.8 23.1 20.9 21.6 21.3 21.9 22.2
4H 21.8 22.3 22.1 22.7 23.0 20.9 21.4 21.2 21.8 22.1
6H 21.7 22.2 22.1 22.5 22.9 20.8 21.3 21.2 21.6 22.0
8H 21.6 22.1 22.1 22.5 22.9 20.8 21.2 21.2 21.6 22.0
12H 21.6 22.0 22.0 22.4 22.8 20.7 21.1 21.2 21.5 21.9
8H 4H 21.6 22.1 22.1 22.5 22.9 20.8 21.2 21.2 21.6 22.0
6H 21.6 21.9 22.0 22.3 22.8 20.7 21.0 21.1 21.4 21.9
8H 21.5 21.8 22.0 22.3 22.7 20.6 20.9 21.1 21.4 21.8
12H 21.5 21.7 22.0 22.2 22.7 20.6 20.8 21.1 21.3 21.8
12H 4H 21.6 22.0 22.0 22.4 22.8 20.7 21.1 21.2 21.5 21.9
6H 21.5 21.8 22.0 22.3 22.7 20.6 20.9 21.1 21.4 21.8
8H 21.5 21.7 22.0 22.2 22.7 20.6 20.8 21.1 21.3 21.8
Page 5
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
105° 105°
90° 90°
75° 75°
40
60° 60°
60
45° 80 45°
100
120
2H 2H 21.5 22.8 21.8 23.0 23.3 21.4 22.7 21.7 23.0 23.2
3H 23.0 24.2 23.3 24.4 24.7 22.9 24.1 23.3 24.4 24.7
4H 23.6 24.7 23.9 25.0 25.3 23.5 24.6 23.9 24.9 25.2
6H 23.9 25.0 24.3 25.3 25.6 23.9 24.9 24.3 25.2 25.6
8H 24.0 25.0 24.4 25.3 25.7 24.0 25.0 24.4 25.3 25.6
12H 24.1 25.0 24.5 25.4 25.7 24.0 25.0 24.4 25.3 25.7
4H 2H 22.1 23.3 22.5 23.5 23.8 22.1 23.2 22.5 23.5 23.8
3H 23.8 24.8 24.2 25.1 25.5 23.8 24.8 24.2 25.1 25.4
4H 24.5 25.4 24.9 25.7 26.1 24.5 25.4 24.9 25.7 26.1
6H 25.0 25.8 25.4 26.1 26.5 25.0 25.7 25.4 26.1 26.5
8H 25.2 25.8 25.6 26.2 26.6 25.1 25.8 25.6 26.2 26.6
12H 25.2 25.8 25.7 26.2 26.7 25.2 25.8 25.6 26.2 26.6
8H 4H 24.8 25.5 25.2 25.9 26.3 24.8 25.5 25.2 25.9 26.3
6H 25.4 26.0 25.9 26.4 26.8 25.4 25.9 25.8 26.4 26.8
8H 25.6 26.1 26.1 26.5 27.0 25.6 26.0 26.0 26.5 27.0
12H 25.7 26.1 26.2 26.6 27.1 25.7 26.1 26.2 26.6 27.1
12H 4H 24.8 25.4 25.3 25.8 26.3 24.8 25.4 25.2 25.8 26.3
6H 25.4 25.9 25.9 26.4 26.9 25.4 25.9 25.9 26.4 26.8
8H 25.7 26.1 26.1 26.5 27.0 25.6 26.0 26.1 26.5 27.0
Page 6
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
105° 105°
90° 90°
75° 75°
60° 60°
160
45° 45°
240
2H 2H 14.4 15.3 14.6 15.5 15.8 15.9 16.8 16.1 17.0 17.2
3H 14.2 15.1 14.5 15.3 15.6 15.7 16.6 16.0 16.8 17.1
4H 14.1 14.9 14.5 15.2 15.5 15.6 16.4 16.0 16.7 17.0
6H 14.1 14.8 14.4 15.1 15.4 15.6 16.3 15.9 16.6 16.9
8H 14.0 14.7 14.4 15.0 15.3 15.5 16.2 15.9 16.5 16.8
12H 14.0 14.7 14.4 15.0 15.3 15.5 16.2 15.9 16.5 16.8
4H 2H 14.3 15.1 14.6 15.4 15.6 15.7 16.5 16.0 16.7 17.0
3H 14.2 14.8 14.5 15.1 15.4 15.5 16.2 15.9 16.5 16.8
4H 14.1 14.7 14.5 15.0 15.3 15.5 16.0 15.8 16.4 16.7
6H 14.0 14.5 14.4 14.9 15.3 15.4 15.9 15.8 16.2 16.6
8H 14.0 14.4 14.4 14.8 15.2 15.4 15.8 15.8 16.2 16.6
12H 13.9 14.3 14.4 14.7 15.2 15.3 15.7 15.8 16.1 16.5
8H 4H 14.0 14.4 14.4 14.8 15.2 15.4 15.8 15.8 16.2 16.6
6H 13.9 14.2 14.3 14.7 15.1 15.3 15.6 15.7 16.1 16.5
8H 13.8 14.2 14.3 14.6 15.1 15.2 15.5 15.7 16.0 16.5
12H 13.8 14.1 14.3 14.5 15.0 15.2 15.4 15.7 15.9 16.4
12H 4H 13.9 14.3 14.4 14.7 15.2 15.3 15.7 15.8 16.1 16.5
6H 13.8 14.2 14.3 14.6 15.1 15.2 15.5 15.7 16.0 16.5
8H 13.8 14.1 14.3 14.5 15.0 15.2 15.4 15.7 15.9 16.4
Page 7
IPS Residential Building lighting illumination level calculations
Luminous emittance 1:
250
150
90° 90°
75° 75°
60° 60°
Luminaire classification according to CIE: 89 Due to missing symmetry properties, no UGR table
CIE flux code: 44 75 92 89 71 can be displayed for this luminaire.
Page 8
IPS Residential Building lighting illumination level calculations
160 6.00 m
240 240 80
80 320
320 240
400
160 320 320
400
320 320
240 80
80
240
160
320 160
320
240 400 80
80 320
320 400
320 160
240 240
0.00
0.00 4.00 m
Height of Room: 2.500 m, Mounting Height: 2.585 m, Light loss factor: Values in Lux, Scale 1:78
0.70
Specific connected load: 5.83 W/m² = 2.84 W/m²/100 lx (Ground area: 24.00 m²)
Page 9
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 189 17 205 / /
Floor 154 23 177 20 11
Ceiling 0.00 27 27 50 4.34
Wall 1 36 23 59 50 9.35
Wall 2 19 25 45 50 7.11
Wall 3 36 23 59 50 9.38
Wall 4 19 24 44 50 6.95
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.176, Ceiling / Working Plane: 0.133.
Specific connected load: 5.83 W/m² = 2.84 W/m²/100 lx (Ground area: 24.00 m²)
Page 10
IPS Residential Building lighting illumination level calculations
CORRIDOR 1 / Summary
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:219
0.70
Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.304, Ceiling / Working Plane: 0.151.
Specific connected load: 8.60 W/m² = 6.72 W/m²/100 lx (Ground area: 67.32 m²)
Page 11
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 112 16 128 / /
Floor 86 19 105 20 6.71
Ceiling 0.00 19 19 50 3.08
Wall 1 27 18 45 50 7.17
Wall 2 11 17 27 50 4.34
Wall 3 27 18 45 50 7.17
Wall 4 11 17 28 50 4.39
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.304, Ceiling / Working Plane: 0.151.
Specific connected load: 8.60 W/m² = 6.72 W/m²/100 lx (Ground area: 67.32 m²)
Page 12
IPS Residential Building lighting illumination level calculations
CORRIDOR 2 / Summary
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:122
0.70
Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.148.
Specific connected load: 7.74 W/m² = 6.74 W/m²/100 lx (Ground area: 37.40 m²)
Page 13
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 101 14 115 / /
Floor 77 17 94 20 5.99
Ceiling 0.00 17 17 50 2.71
Wall 1 24 16 40 50 6.41
Wall 2 7.54 15 23 50 3.62
Wall 3 24 16 40 50 6.41
Wall 4 7.54 15 22 50 3.54
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.148.
Specific connected load: 7.74 W/m² = 6.74 W/m²/100 lx (Ground area: 37.40 m²)
Page 14
IPS Residential Building lighting illumination level calculations
3.60 m
100
150 150
150
200 200
200
250
150 200 250 200
250 250
200
250 250
150
250 250
200
200 200
150
150
100
0.00
0.00 1.95 2.90 3.30 m
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:47
0.70
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.713, Ceiling / Working Plane: 0.506.
Specific connected load: 7.36 W/m² = 4.48 W/m²/100 lx (Ground area: 9.51 m²)
Page 15
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 111 53 164 / /
Floor 72 48 120 20 7.63
Ceiling 34 49 83 50 13
Wall 1 39 42 81 50 13
Wall 2 92 42 134 50 21
Wall 3 40 38 78 50 12
Wall 4 40 44 84 50 13
Wall 5 64 43 107 50 17
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.713, Ceiling / Working Plane: 0.506.
Specific connected load: 7.36 W/m² = 4.48 W/m²/100 lx (Ground area: 9.51 m²)
Page 16
IPS Residential Building lighting illumination level calculations
4.60 m
50 150 150
100
200
150 250 250
200 100
200
250 250
100
150 200
200
100
100 200
200
250 150
250
250
250 200 100
200
100
200 150
150
0.00
0.00 3.50 m
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:60
0.70
Specific connected load: 8.99 W/m² = 6.27 W/m²/100 lx (Ground area: 16.10 m²)
Page 17
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 129 14 143 / /
Floor 101 18 120 20 7.61
Ceiling 0.00 19 19 50 3.08
Wall 1 25 18 43 50 6.78
Wall 2 19 19 37 50 5.91
Wall 3 25 17 42 50 6.76
Wall 4 19 18 36 50 5.81
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.223, Ceiling / Working Plane: 0.135.
Specific connected load: 8.99 W/m² = 6.27 W/m²/100 lx (Ground area: 16.10 m²)
Page 18
IPS Residential Building lighting illumination level calculations
PANTRY / Summary
2.50 m
280
140 140
210 280
280
350 210
350 Residential Building lighting illumination level calculations
MPS
350 280
280 350
210 140
140 350
350 210
280
280 350
350
210
350 280 140
140 350 210
280
350
210 280
280
210
0.00
0.00 3.95 m
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:33
0.70
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.130.
Specific connected load: 7.09 W/m² = 3.28 W/m²/100 lx (Ground area: 9.87 m²)
Page 19
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 190 26 216 / /
Floor 126 34 160 20 10
Ceiling 0.00 28 28 50 4.46
Wall 1 46 28 74 50 12
Wall 2 28 28 55 50 8.80
Wall 3 46 28 74 50 12
Wall 4 28 28 56 50 8.84
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.130.
Specific connected load: 7.09 W/m² = 3.28 W/m²/100 lx (Ground area: 9.87 m²)
Page 20
IPS Residential Building lighting illumination level calculations
LOBBY / Summary
200 6.00 m
150 200
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:78
0.70
Specific connected load: 11.12 W/m² = 4.76 W/m²/100 lx (Ground area: 54.60 m²)
Page 21
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 208 26 234 / /
Floor 183 30 213 20 14
Ceiling 0.00 39 39 50 6.28
Wall 1 46 33 80 50 13
Wall 2 38 34 72 50 11
Wall 3 46 34 80 50 13
Wall 4 38 32 70 50 11
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.169.
Specific connected load: 11.12 W/m² = 4.76 W/m²/100 lx (Ground area: 54.60 m²)
Page 22
IPS Residential Building lighting illumination level calculations
2.10 m
250
250 200
200 250
300 300
300
250
350 300
250
300 350 350
350
350 300
350 250
250 300 350
350 350 300
300 250
300 300
250
250 250
200
0.00
0.00 2.70 m
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:27
0.70
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.374, Ceiling / Working Plane: 0.158.
Specific connected load: 17.85 W/m² = 6.69 W/m²/100 lx (Ground area: 5.67 m²)
Page 23
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 221 46 267 / /
Floor 145 48 193 20 12
Ceiling 0.00 42 42 50 6.69
Wall 1 56 43 99 50 16
Wall 2 60 42 102 50 16
Wall 3 56 43 99 50 16
Wall 4 60 42 102 50 16
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.374, Ceiling / Working Plane: 0.158.
Specific connected load: 17.85 W/m² = 6.69 W/m²/100 lx (Ground area: 5.67 m²)
Page 24
IPS Residential Building lighting illumination level calculations
160 2.10 m
200 160 160
160
200 240 240
240 200 240
240 240
160 240 240 240 240 200 240 240
200 240 240
200
200 160 160
160 160
0.00
0.00 9.10 m
Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:66
0.70
Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.324, Ceiling / Working Plane: 0.152.
Specific connected load: 10.59 W/m² = 5.64 W/m²/100 lx (Ground area: 19.11 m²)
Page 25
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 162 26 188 / /
Floor 119 30 149 20 9.51
Ceiling 0.00 29 29 50 4.54
Wall 1 40 28 68 50 11
Wall 2 30 27 56 50 8.94
Wall 3 40 28 68 50 11
Wall 4 30 27 56 50 8.95
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.324, Ceiling / Working Plane: 0.152.
Specific connected load: 10.59 W/m² = 5.64 W/m²/100 lx (Ground area: 19.11 m²)
Page 26
IPS Residential Building lighting illumination level calculations
12.00 m
Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.70
Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.589, Ceiling / Working Plane: 0.354.
Specific connected load: 6.73 W/m² = 2.58 W/m²/100 lx (Ground area: 124.80 m²)
Page 27
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 205 56 261 / /
Floor 180 58 238 20 15
Ceiling 34 59 92 50 15
Wall 1 87 54 141 50 22
Wall 2 166 57 223 50 35
Wall 3 87 54 141 50 22
Wall 4 47 48 95 50 15
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.589, Ceiling / Working Plane: 0.354.
Specific connected load: 6.73 W/m² = 2.58 W/m²/100 lx (Ground area: 124.80 m²)
Page 28
IPS Residential Building lighting illumination level calculations
180 12.00 m
240
240 240
120 240 300
240
240 240 240
300
300
300
240 240
120 240 300
300 300
240 240 300
240
300
180
240 240 240
120
240 300
300
240 180
240
0.00
0.00 8.00 m
Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.70
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.356.
Specific connected load: 5.83 W/m² = 2.64 W/m²/100 lx (Ground area: 96.00 m²)
Page 29
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 173 48 221 / /
Floor 148 50 198 20 13
Ceiling 29 50 79 50 13
Wall 1 72 46 117 50 19
Wall 2 131 48 179 50 28
Wall 3 72 46 118 50 19
Wall 4 38 42 80 50 13
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.356.
Specific connected load: 5.83 W/m² = 2.64 W/m²/100 lx (Ground area: 96.00 m²)
Page 30
IPS Residential Building lighting illumination level calculations
1.85 m
210 240 270
270 210
270 300
300 300 240
270
240
300 300
270
270 300
240 300
270
300
300 240
270 300
270
240 270
0.00
0.00 2.30 m
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:24
0.70
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.886, Ceiling / Working Plane: 0.664.
Specific connected load: 16.45 W/m² = 6.31 W/m²/100 lx (Ground area: 4.26 m²)
Page 31
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 159 101 261 / /
Floor 91 79 170 20 11
Ceiling 69 104 173 50 28
Wall 1 129 84 213 50 34
Wall 2 86 85 171 50 27
Wall 3 129 83 212 50 34
Wall 4 86 85 171 50 27
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.886, Ceiling / Working Plane: 0.664.
Specific connected load: 16.45 W/m² = 6.31 W/m²/100 lx (Ground area: 4.26 m²)
Page 32
IPS Residential Building lighting illumination level calculations
2.80 m
200 160
200
200
240 240
200 240 240
280 200
280
240
280
240 280
280
280 240
280
240
200 240 240
240
200
200 200
160
0.00
0.00 2.30 m
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:36
0.70
Specific connected load: 10.87 W/m² = 5.12 W/m²/100 lx (Ground area: 6.44 m²)
Page 33
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 139 74 212 / /
Floor 83 63 146 20 9.31
Ceiling 49 70 119 50 19
Wall 1 62 61 123 50 20
Wall 2 100 60 160 50 25
Wall 3 62 61 123 50 20
Wall 4 100 59 159 50 25
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.769, Ceiling / Working Plane: 0.559.
Specific connected load: 10.87 W/m² = 5.12 W/m²/100 lx (Ground area: 6.44 m²)
Page 34
IPS Residential Building lighting illumination level calculations
3.00 m
240 200
240 240
320
280
280 320
320
320 320 320
280
280 240
280 280
240
240 240 200
0.00
0.00 4.00 m
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:39
0.70
Specific connected load: 11.67 W/m² = 4.34 W/m²/100 lx (Ground area: 12.00 m²)
Page 35
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 182 87 269 / /
Floor 123 79 202 20 13
Ceiling 55 81 136 50 22
Wall 1 116 71 187 50 30
Wall 2 97 73 170 50 27
Wall 3 116 72 188 50 30
Wall 4 97 73 170 50 27
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.750, Ceiling / Working Plane: 0.505.
Specific connected load: 11.67 W/m² = 4.34 W/m²/100 lx (Ground area: 12.00 m²)
Page 36
IPS Residential Building lighting illumination level calculations
5.50 m
270 270
270 5.10
360 360
450
360 360
270 270
180
90
0.00
0.00 1.20 2.20 m
Height of Room: 2.500 m, Mounting Height: 2.585 m, Light loss factor: Values in Lux, Scale 1:71
0.70
Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.335, Ceiling / Working Plane: 0.158.
Specific connected load: 10.77 W/m² = 4.23 W/m²/100 lx (Ground area: 6.50 m²)
Page 37
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 206 48 255 / /
Floor 127 49 176 20 11
Ceiling 0.00 40 40 50 6.39
Wall 1 0.23 8.94 9.17 50 1.46
Wall 2 47 33 80 50 13
Wall 3 65 51 115 50 18
Wall 4 65 51 116 50 18
Wall 5 47 33 80 50 13
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.335, Ceiling / Working Plane: 0.158.
Specific connected load: 10.77 W/m² = 4.23 W/m²/100 lx (Ground area: 6.50 m²)
Page 38
IPS Residential Building lighting illumination level calculations
6.60 m
100
150
200 250
250
250 300
250
250 300
250 250
200
2.70
250 250 150
200 1.90
300
200
250 1.00
250
200 0.60
0.00
0.00 0.82 1.90 2.60 4.00 m
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:85
0.70
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.748, Ceiling / Working Plane: 0.514.
Specific connected load: 9.06 W/m² = 4.50 W/m²/100 lx (Ground area: 15.45 m²)
Page 39
IPS Residential Building lighting illumination level calculations
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 137 65 201 / /
Floor 93 59 152 20 9.70
Ceiling 42 62 104 50 16
Wall 1 90 64 154 50 25
Wall 2 113 66 179 50 28
Wall 3 125 69 194 50 31
Wall 4 37 51 88 50 14
Wall 5 91 51 142 50 23
Wall 6 31 45 76 50 12
Wall 7 83 53 136 50 22
Wall 8 85 62 148 50 23
Wall 9 91 60 151 50 24
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.748, Ceiling / Working Plane: 0.514.
Specific connected load: 9.06 W/m² = 4.50 W/m²/100 lx (Ground area: 15.45 m²)
Page 40